SPACE HEATING DESIGN OPTIONS FOR ANHEUSER BUSCH’S STORAGE FACILITY Manuel A. Leija B.S., California State University, Sacramento, 2007 PROJECT Submitted in partial satisfaction of the requirements for the degree of MASTER OF SCIENCE in MECHANICAL ENGINEERING at CALIFORNIA STATE UNIVERSITY, SACRAMENTO FALL 2009 SPACE HEATING DESIGN OPTIONS FOR ANHEUSER BUSCH’S STORAGE FACILITY A Project By Manuel A. Leija Approved by: ______________________________, Committee Chair Professor Timothy Marbach _____________________________ Date ii Student: Manuel A. Leija I certify that this student has met the requirements for format contained in the University format manual, and that this Project is suitable for shelving in the Library and credit is to be awarded for the Project. ____________________________________, Department Chair Professor Susan Holl Department of Mechanical Engineering iii ___________________ Date Abstract of SPACE HEATING DESIGN OPTIONS FOR ANHEUSER BUSCH’S STORAGE FACILITY by Manuel A. Leija Statement of the Problem This project investigates the use to solar energy to heat Anheuser Busch’s storage facility in Fairfield, California, specifically using solar (Trombe) wall and an evacuated tube collector design considerations. This warehouse is currently using 25 steam heated air units that constantly malfunction. Anheuser Busch demands a solution to this problem by finding an alternative system that will meet the heat load requirements while at the same time utilize renewable energy sources. Using preexisting solar radiation data, as well as the facility constraints, an optimal solution will be presented. Sources of Data The hourly solar radiation data was collected from the National Solar Radiation Data Base for the Travis Field Air Force Base in Fairfield, California for 2005. The hourly temperature and wind velocities were taken from Weather Underground, a website that has historical data for various locations from 2006 to present. Microsoft Excel was used to perform the calculations necessary to present the solution. iv Conclusions The most optimal solution for this project was the Trombe wall design. The October 4th heat load demand is 35 MW and the wall capacity is 7 MW. This only meets 20% of the heat demand and the other two selected days were even less, therefore auxiliary heat must be supplied. The evacuated tube collector’s smallest storage tank is 859 m3 (227,000 gallons), which is an impractical and costly design. ________________________________, Committee Chair Professor Timothy Marbach _______________________ Date v ACKNOWLEDGMENT I would like to acknowledge the faculty at California State University, Sacramento for providing me with the proper tools and education for allowing me to finish this project. I would especially like to acknowledge Professor Marbach for instilling in me a passion for renewable energy and alternative technology. This desire allowed me to explore new heights with energy design that was not only challenging but exciting as well. I also would like to acknowledge William Bennett and Anheuser Busch for allowing me to help them with a project that may be a major influence to other companies. vi TABLE OF CONTENTS Acknowledgment ............................................................................................................... vi List of Tables ..................................................................................................................... ix List of figures ...................................................................................................................... x Nomenclature .................................................................................................................... xii Chapter 1. BACKGROUND AND INTRODUCTION .................................................................. 1 1.1 History of Solar Energy ........................................................................................... 2 1.2 Solar Contribution to Other Renewable Energy Sources ........................................ 4 1.3 Solar Applications .................................................................................................... 5 2. SOLAR COLLECTORS ................................................................................................ 7 2.1 Unglazed Solar Collectors ....................................................................................... 7 2.2 Glazed Collectors ..................................................................................................... 9 2.3 Evacuated Tube Collectors .................................................................................... 11 2.4 Concentrating Collectors ....................................................................................... 12 3. COMPUTATIONAL SETUP AND PROCEDURE ................................................... 15 3.1 Assumptions........................................................................................................... 15 3.2 Trombe Wall Analysis ........................................................................................... 16 3.3 Evacuated Tube Collector Analysis ....................................................................... 23 4. ANALYSIS OF THE DATA ....................................................................................... 28 4.1 Trombe Wall Data.................................................................................................. 29 vii 4.2 Evacuated Tube Collector Data ............................................................................. 30 5. FINDINGS AND INTERPRETATIONS .................................................................... 33 5.1 Further Research .................................................................................................... 33 5.2 Conclusions ............................................................................................................ 34 Appendix A: Solar Radiation Data for the Three Selected Days..................................... 36 Appendix B: Calculation Tables ...................................................................................... 37 Appendix C: Miscellaneous Charts ................................................................................. 52 Appendix D: Charts Used for Determing Specific Data for Trombe Wall Analysis....... 66 Bibliography ..................................................................................................................... 69 viii LIST OF TABLES Table 1: Assumed Values for Trombe Wall Analysis ..................................................... 16 Table 2: Assumed Values for Evacuated Tube Collector Analysis ................................. 16 Table 3: Solar Wall Data Calculated for Selected Days .................................................. 29 Table 4: Evacuated Tube Data Calculated for Selected Days ......................................... 31 Table 5: Yes or No Comparison Table of Both Design Methods .................................... 33 Table 6: Hourly Solar Radiation Data and Temperature for Three Selected Days ......... 36 Table 7: Evacuated Tube Collector Analysis for October 4, 2005 .................................. 37 Table 8: Evacuated Tube Collector Analysis for November 2, 2005 .............................. 39 Table 9: Evacuated Tube Collector Analysis for December 16, 2005 ............................ 41 Table 10: Trombe Wall Analysis for October 4, 2005 .................................................... 43 Table 11: Trombe Wall Analysis for November 2, 2005 ................................................ 46 Table 12: Trombe Wall Analysis for December 16, 2005 ............................................... 49 ix LIST OF FIGURES Figure 1: Unglazed Solar Collector Used for Pool Heating ............................................... 8 Figure 2: Glazed Flat-Plate Solar Water Collector ............................................................. 9 Figure 3: Glazed Flat Plate Solar Air Collector ............................................................... 10 Figure 4: Solar Wall (Trombe Wall) With Opening for Circulation ............................... 11 Figure 5: Evacuated Tube Collector ................................................................................ 12 Figure 6: Line Focus (Parabolic Trough) Collectors ....................................................... 13 Figure 7: Point Focus Line Collectors ............................................................................. 14 Figure 8: CM6B Pyranometer Measuring Device ........................................................... 22 Figure 9: Direct Applied Solar Storage System ............................................................... 23 Figure 10: Indirect Applied Storage System .................................................................... 24 Figure 11: Evacuated Tube Collector Area v. Useful Collector Gain for October 4, 2005 ........................................................................................................................................... 52 Figure 12: Collector Efficiency v. Useful Collector Gain for October 4, 2005............... 53 Figure 13: Useful Collector Gain v. Heat Used by Load for October 4, 2005 ................ 54 Figure 14: Useful Collector Gain v. Heat Used by Load for November 2, 2005 ............ 55 Figure 15: Useful Collector Gain v. Heat Used by Load for December 16, 2005........... 56 Figure 16: Isotropic Model v. Anisotropic Model for October 4, 2005 .......................... 57 Figure 17: Isotropic Model v. Anisotropic Model for November 2, 2005 ...................... 58 Figure 18: Isotropic Model v. Anisotropic Model for December 16, 2005 ..................... 59 Figure 19: Total, Beam, and Diffuse Hourly Radiation Components for October 4, 2005 ........................................................................................................................................... 60 x Figure 20: Total, Beam, and Diffuse Hourly Radiation Components for November 2, 2005................................................................................................................................... 61 Figure 21: Total, Beam, and Diffuse Hourly Radiation Components for December 16, 2005................................................................................................................................... 62 Figure 22: Hourly Heat Loss from Building for October 4, 2005 ................................... 63 Figure 23: Hourly Heat Loss from Building for November 2, 2005 ............................... 64 Figure 24: Hourly Heat Loss from Building for December 16, 2005 .............................. 65 Figure 25: Transmittance of One, Two, Three, and Four Covers for Three Types of Glass ........................................................................................................................................... 66 Figure 26: Effective Incidence Angle of Isotropic Diffuse Radiation and Isotropic Ground-Reflected Radiation on Sloped Surfaces ............................................................. 67 Figure 27: Typical (τα)/(τα)n Curves for One to Four Covers ......................................... 68 xi NOMENCLATURE Symbols Ab Ac Ai f GT I Ib Id Io kT K L Rb S Ta Ti Ts Ts+ U Qu VT Building Surface Area (m2) Solar Collector Receiving Area (m2) Anisotropy Index Modulating Factor Total Irradiance (Wh/m2) Total Hourly Irradiance (J/m2) Hourly Beam Irradiance (J/m2) Hourly Diffuse Irradiance (J/m2) Extraterrestrial Hourly Radiation (J/m2) Hourly Clearness Index Glass Extinction Coefficient (m-1) Glass thickness (m) Ratio of Beam Radiation on a Tilted Plane to that on the Plane of Measurement Absorbed Solar Radiation (J/m2 or W/m2) Ambient Temperature (°C or °F) Inside Temperature (°C or °F) Storage Temperature at the Beginning of the Hour (°C or °F) Storage Temperature at the End of the Hour (°C or °F) Overall Heat Loss Coefficient (W/m2K) Useful Energy Gain for the Solar Collector (J/m2 or W/m2) Tank Volume (m3 or gallons) Greek Symbols αn Absorptance of a Plate at Normal Incidence β Tilt Angle of Solar Collector (Degrees) η Efficiency of Solar Collector θ Angle of Incidence (Degrees) θe Effective Angle of Incidence (Degrees) ρg Ground Reflectance τ Transmittance (τα)b Beam Transmittance-Absorptance Product (τα)d Diffuse Transmittance-Absorptance Product (τα)g Ground Transmittance-Absorptance Product (τα)n Transmittance-Absorptance Product of a Plate at Normal Incidence xii 1 Chapter 1 BACKGROUND AND INTRODUCTION With the increase in human population during the last few decades there has been a large increase in energy consumption. This energy is used in almost every aspect of a person’s life and therefore must be supplied when demanded. Today approximately three quarters of the energy supplied comes from fossil fuels, i.e., coal, oil and natural gas (Boyle 6). Allowing this to continue in this manner may seem sufficient for the time being; however concern begins to arise when the longevity of this supply comes into question. At current consumption rates, proven world coal reserves should last for about 200 years, oil for approximately 40 years and natural gas for around 60 years (BP, 2003). The sustainability of fossil fuels and nuclear fuels, or lack thereof, is what brought about the development of renewable energy technology. An energy source is said to be sustainable if it is not substantially depleted by continuous use, does not emit pollutants or other environmental hazards, and does not produce health hazards or social injustices. There are a few renewable sources that are more sustainable than the previous mentioned fossil and nuclear fuels. Solar power, hydropower, wind power, wave power, tidal power, bioenergy and geothermal energy all fall under the category of renewable energy and although they are not 100 percent sustainable they essentially cannot be depleted, their use produces significantly less greenhouse gases, as well as fewer health hazards. Solar energy and its applications are the premise of this paper and therefore will be discussed more so than any other renewable energy source. 2 The sun is a sphere of intensely hot gaseous matter with a diameter of 1.39 x 109 meters and is approximately 1.5 x 1011 meters from the earth (Duffie, 3). This sphere can be thought of as a fusion reactor with its gases held together by gravitational attraction and it is the fusion of hydrogen into helium that produces the energy radiating from the sun. Basically, as four protons combine to form a helium nucleus mass is lost during the reaction and converted to energy. This energy at the sun’s center has a temperature of many millions of degrees and the radiative and convective processes this energy goes through to get to the surface causes the temperature to drop to about 6000 K. This thermal radiation emitted from the sun is what promotes life and growth for all the organisms on the earth. Thermal radiation can be considered as consisting of electromagnetic waves and much like all waves have specific characteristics such as wavelength and frequency that follow them. Although the electromagnetic spectrum has wavelengths that run from 10-5 to 104, thermal radiation covers wavelengths from about 10-1 to 102 with frequencies of 1012 to 1016. These wave characteristics can be used to accurately predict other properties that are used for solar design such as emissivity, absorptivity, and reflectivity. Emissivity is the amount of heat flux that is allowed to be emitted by an object and is usually a property of the material. Absorptivity is the amount that can be absorbed and reflectivity is the amount that can be reflected. All these properties limit the amount of solar energy the collector can actually use. 1.1 History of Solar Energy Ancient Greeks and Romans would use their architectural talents to design their buildings in order utilize the energy from the sun to heat and light indoor spaces. They 3 would face the house towards the south and later realized that installing glass would help entrap the heat inside the building for longer periods of time. This passive design would offset the need to burn wood which was often in short supply. To this day many people use this same technique in their homes or business for space heating and lighting. Since then many designs have been made to use solar for various processes and as technology improved so did the efficiencies and equipment used to collect and store this energy. In the 1760s a Swiss naturalist by the name of Horace de Saussure said, “It is a known fact, and a fact that has probably been known for a long time, that a room, a carriage, or any other place is hotter when the rays of the sun pass through glass.”(Perlin) In order to show the effectiveness of trapping heat with glass, Horace built a box out of pine, insulated the inside and covered the top with glass. He also put two smaller boxes inside the larger one. After exposing this apparatus to the sun for awhile, Horace noticed that the boxes inside were heated to 109° C (228° F). Unsure of the phenomenon behind this he still proclaimed that this “hot box” could have practical applications and later was the stepping stone to solar collector design. The first water heaters available were simply tanks of water placed behind a normal window. In 1891 Clarence Kemp combined the “hot box” method with the old method of exposing metal tanks to the sun to patent his own solar water heater he called The Climax. Combining the two methods increased the tanks ability to collect and retain solar heat. The only disadvantage to The Climax was that the heat collector and the storage tank were all one unit and exposed to the environment. This meant that during the night the heat would leave the tank and there would not be hot water in the mornings for bathing. In 1909, William J. Bailey of 4 California designed and patented a thermosyphon solar water heater (Boyle, 36). This new system was broken into two parts, a heating element that was exposed to the sun and an insulated storage tank that was tucked away in the house. This allowed water to remain hot overnight due to the reduction in heat loss. Using the sun to heat water started to become more widespread around the globe, however as natural gas prices dropped and fossil fuels became cheaper everywhere, solar heating decreased because it started to become less cost effective. It wasn’t until the oil crisis in the 1970s when solar started to make its way back into the homes of many residences. Now more people are turning to solar for their water and space heating needs and are either installing new systems on their preexisting homes or incorporating them into newly built houses. 1.2 Solar Contribution to Other Renewable Energy Sources Solar energy can be either directly used or indirectly used. Direct use involves solar energy to be absorbed through solar collectors for hot water or spacing heating, passively through walls and windows for heating and lighting, concentrated by mirrors to produce high temperatures or through photovoltaic cells to produce electricity. Solar radiation can be converted to useful energy indirectly, via other energy forms (Boyle, 12). When solar radiation reaches the earth part of that radiation is absorbed by the oceans warming them. This creates water vapor in the air which later condenses and forms rain. This rain is fed into rivers, where this water flow can be used to turn turbines and create electricity. This is known as hydropower and it currently provides about a sixth of the world’s electricity. Due to the tilt of the earth, solar radiation falls more perpendicular in the tropical regions than the polar regions, hence heating the tropics much more than the 5 poles. This heat imbalance causes heat to flow from the tropics to the poles creating wind. Wind power uses turbines to harness the energy potential from the wind converting it into electricity. When winds roll across the ocean, waves are created. These oceanic waves can be used to generate electricity similar to that of wind power. One last indirect form is bioenergy. Through photosynthesis in plants, solar radiation converts water and atmospheric carbon dioxide into carbohydrates which form the basis of more complex molecules (Boyle, 13). Biomass in the form of wood or other biofuels is usually burned and the steam created turns a steam turbine to create electricity. Solar plays an important role in energy generation, not only directly but indirectly as well. 1.3 Solar Applications Since this project involved direct use of solar energy, more emphasis will be put on the types of direct uses instead of indirect uses. When discussing solar energy and its applications, it is customary to distinguish between the different types of systems. The types of systems are active solar heating, solar thermal engines, passive solar heating and day lighting. An active system always involves solar collectors to gather the solar energy and is often used to heat water or small spaces. Solar thermal engines are essentially an extension of active solar heating. They use carefully designed collectors to get temperatures high enough to drive steam turbines for electricity generation. Passive systems generally are systems that absorb the solar energy directly into the building to heat a space and reduce the dependence of mechanical heating systems. Usually the collector is an integral part of the building. Day lighting is exactly what the name suggests. Windows or openings are used to bring in the suns natural light in order to cut 6 electrical costs. Although active and passive systems are stated here as two different solar collection systems, in practice however, these two are not clear cut but rather blend into each other with a range of possibilities in between. This project studied the effects of both active and passive systems and therefore will discuss the technology for those types of systems. 7 Chapter 2 SOLAR COLLECTORS There are different types of solar collectors and depending on the application the collector will need to be sized accordingly. Solar energy collectors absorbs solar radiation, converts it into heat and then transfers this heat to a collector fluid which is usually air, water, or oil. The fluid that receives the heat can then be delivered to the desired location to either be used instantly such as heating a room or water, or it can be stored in a tank for later use when no solar radiation is available. They are essentially specialized heat exchangers. Collectors can be unglazed, glazed, evacuated, and of the concentrating type. Unglazed and glazed collectors are generally used for low temperature collection while evacuated and concentration collectors are for high temperature situations. Some of these collectors are stationary while others are non-stationary. Stationary collectors generally have the same area for collecting radiation and absorbing radiation. Non-stationary collectors generally track the sun and have concave surfaces that allow the radiation to be concentrated to a smaller absorbing area. Stationary collectors were used for the analysis of this project, specifically evacuated tube collectors and vertical flat plate collectors, i.e., a Trombe wall. 2.1 Unglazed Solar Collectors Unglazed solar collectors are simply an absorber plate with tubes running through it for the fluid. They do not have a glass cover and there cannot block the reradiated energy 8 from the absorber plate. Without a glass cover the absorber plate is exposed to the environment and therefore is subject to convection and radiation losses. This is why they are low temperature collectors. The most common type of unglazed collectors are those used for swimming pool heating. Since the pool should be maintained around 70-80 degrees Fahrenheit it is not necessary and often considered overkill to use a glazed collector. Figure 1: Unglazed Solar Collector Used for Pool Heating 9 2.2 Glazed Collectors Glazed collectors are those with glass coverings and are often referred to as flat plate collectors. This glass can be single sheets or multiple sheets. Putting a glass cover over the absorber plate allows visible light and short wave radiation to be transmitted but blocks long wave radiation. The energy being reradiated by the absorber plate has long wavelengths and cannot be transmitted through the glass therefore becoming trapped between the glass and absorber plate allowing for more absorptivity. These collectors are also subject to radiation losses and convection losses. However, the convective losses in flat plate collectors are significantly less compared to unglazed type because the type of convection between the plate and glass is natural convection and not forced convection like the unglazed collectors. Flat plate collectors can have water flowing through tubes or the gap can be filled with air. Either way the fluid is heated and then transferred to perform its desired task. Figure 2: Glazed Flat-Plate Solar Water Collector 10 Figure 3: Glazed Flat Plate Solar Air Collector Another type of glazed collector that is often overlooked is a solar wall, or Trombe wall. Named after French inventor Felix Trombe in the late 1950s, the Trombe wall is essentially a vertical flat plate collector that uses air as its transfer medium. It has a glass covering and the wall of the building is converted to an absorber plate by adding to it a selective material that has a high absorptivity property and a low emissivity property. The air inside the wall can transfer heat by natural convection or by forced convection. If the wall has no gaps in it, then the heat inside the wall rises due to buoyancy effects. After some time the entire air space will be heated with the hotter temperatures towards the top of the wall. This heat is then conducted through the wall and then convectively warms the room on the other end of the wall. Another way to heat a room with a Trombe wall is to allow gaps in the upper and lower part of the absorber wall. This creates a 11 forced convection effect. This forces the warm air to flow out the upper gap into the room warming it and replacing the air in the wall with cooler air from the room. This continuous circulation will warm the room quicker than the just by natural convection alone. Glazed solar collectors are continuously being improved to increase efficiencies and reduce size and cost. Figure 4: Solar Wall (Trombe Wall) With Opening for Circulation 2.3 Evacuated Tube Collectors Evacuated tube collectors are used for high temperature applications because of their design and are therefore more costly. They consist of a tube with a metal strip running along the center of the tube as the absorber plate. Inside the tube air is evacuated and a vacuum exists. This vacuum suppresses all convective losses and the only heat loss is due to radiation. This device uses a heat pipe to carry the collected energy to the water 12 that circulates along a header pipe at the top of the array of tubes. A heat pipe is a device that takes advantage of a boiling fluid to carry large amounts of heat. A hollow tube is filled with a liquid at a pressure chosen so that it can be made to boil at the hot end but the vapor will condense at the cold end (Boyle, 37). This carefully designed tube has a thermal conductivity many times greater than if it was just made of a solid tube and are therefore able to transfer large amounts of heat. Figure 5: Evacuated Tube Collector 2.4 Concentrating Collectors Concentrating collectors are mostly used to generate steam in order to produce electricity. There are parabolic trough collectors, or line focus collectors, and point focus collectors. Both types of collectors focus the radiation directly onto a specific area in order to maximize the amount of absorbed energy. The line focus collectors are a parabolic 13 trough made of a highly reflective material that is designed to focus all the suns energy on to a pipe that runs along the focal center of the trough. The concentrators can remain still or be allowed to move in order to track the sun throughout the day. Figure 6: Line Focus (Parabolic Trough) Collectors Point focus collectors operate on the same principle as the line focus collectors except these focus all energy on a point instead of a tube along the center. They look like satellite dishes with a tip in the middle where water runs in and out. These collectors are 14 also allowed to track the sun except these are able to do it in two dimensions as opposed to one dimension like the parabolic trough collector. Figure 7: Point Focus Line Collectors 15 Chapter 3 COMPUTATIONAL SETUP AND PROCEDURE When sizing equipment for solar applications there are many different variables that need to be considered. Solar analysis can be done using thermal simulation software such as Transys or Fluent, or it can be done analytically using design equations and a numerical program such as Microsoft Excel. The analysis done for this project was done using the latter method. The equations used for this analysis were provided by John A. Duffie and William A. Beckman in their textbook “Solar Engineering of Thermal Processes.” Although this project involved separate analysis of a Trombe wall and an Evacuated Tube Collector, some of the equations used for one method may be used for the other. 3.1 Assumptions Before starting any of the analysis, several assumptions needed to be made. The absorptance of the plate at normal incidence (αn), the ground reflectance (ρg), and the glass extinction coefficient and thickness factor (KL). Due to the complexity of their numeric values, these variables had to be assumed but were made from previous design problems. Table 1 has the assumed values for the Trombe wall analysis. 16 Absorptance, αn Reflectivity, ρg Glass Factor, KL 0.90 0.3 0.0125 Table 1: Assumed Values for Trombe Wall Analysis The collector analysis also had to have some assumed values. The desired inside room temperature, the collector efficiency (η), and the heat loss from the tank all needed to be assumed also because of the difficulty of the calculations. Below is a table of these assumptions and their values. Desired Room Temp. Collector Efficiency Tank losses 21° C (70° F) 0.5 0 Table 2: Assumed Values for Evacuated Tube Collector Analysis Similar to the Trombe wall analysis, these assumed values were based off of previous design considerations for real world systems. 3.2 Trombe Wall Analysis As mentioned before a Trombe wall is essentially a flat plate collector attached to the south side of a building wall. The sun gives off radiation which is transmitted through the glass and abosorbed onto the absorbed plate heating it to temperatures higher than the ambient. As more radiation is emitted more heat is produced making the space a heat 17 source with a heat flux on the wall. Since the adjacent room to the wall is at a lower temperature than the air space in the wall, heat will flow into the room warming it up. One of the first things necessary for the analysis is to find how much heat is absorbed onto the absorber plate. This is denoted by S and is the sum of the beam, diffuse and ground radiation. 1 cos 1 cos S I b Rb b I d d g I g 2 2 (3.1.1) There are many different variables in this equation but each one is necessary and has its own way of being determined. The first term is the beam radiation contribution. Ib is the hourly beam radiation and can be found by subtracting the diffuse component from the total component. Rb is the ratio of beam radiation on a tilted surface to that on a horizontal surface and the equation is given by: Rb cos cos z (3.1.2) where, cos sin sin cos sin cos sin cos cos cos cos cos cos sin sin cos cos cos sin sin sin (3.1.2a) and, cos z cos cos cos sin sin (3.1.2b) 18 The variables presented in equations 2a and 2b are the angles that describe the geometric relationships between a plane of any particular orientation relative to the earth at any time and the incoming beam solar radiation (Duffie, 12). ϕ is the latitude which runs north or south of the equator, north being positive. δ is the declination which is the angular position of the sun at solar noon with respect to the plane of the equator and can be calculated as: 23.45 sin 360 284 n 365 (3.1.2c) where n is a specific day out of the year based on a 365 day cycle. β is the slope, γ is the surface azimuth angle, ω is the hour angle and can be calculated as 15° per hour with the morning being negative and the afternoon being positive. θ is the angle of incidence and θz is the zenith angle. The last component of the beam contribution is the transmittanceabsorptance product and is a property of the glass. The transmittance is found using figure 25 in the appendix. This figure gives the transmittance for one, two, three, or four glass covers. Knowing the angle of incidence, the glass extinction coefficient and the glass thickness, the transmittance can be determined. The absorptance of the plate at normal incidence was a given variable and did not need to be found. The transmittanceabsorption product can now be found and is given by: n 1.01 n n (3.1.3) 19 Figure 27 in the appendix is the graph for determining the transmittance-absorption product for beam, diffuse and ground radiation. This graph is of typical / n curves for one to four glass covers. However, in order to use this graph the incidence angle for each component must be determined. Figure 26 gives the effective incidence angle for diffuse and ground radiation knowing the slope of the collector. It can be seen that vertical collectors have a slope of 90° and therefore the diffuse and ground incidence angles are the same. The beam incidence angle can be found using equation 2a and rearranging to solve for θ. Looking back at equation 3.1.1, it can be seen that all components have been found or given and the only two remaining components are the diffuse hourly radiation and the total hourly radiation. The ground reflectance also still remains to be solved but there is not an equation available to determine this value. This is found either by testing methods or the same value can be used for a similar location. The diffuse radiation can be found by using this set of equations: Id I 1.0 .09 kT for k T 0.22 .9511.1604kT 4.388kT2 16.638kT3 12.336kT4 for 0.22 kT 0.80 (3.1.4) where kT is known as the hourly clearness index and is found by this equation: 20 I Io kT (3.1.4a) and I is the total incident hourly solar radiation and Io is the extraterrestrial hourly radiation and is found by: Io 12 3600 360n Gsc1 0.033 cos 365 2 1 cos cos sin 2 sin 1 sin sin 180 (3.1.4b) where n is the day of the year and Gsc is the solar constant of 1367 W/m2. All variables in equation 1 have been found and can now be used to determine the total amount of energy absorbed for each hour of the day. Summing up the total absorbed radiation for the 24 hours gives the total heat capacity for the Trombe wall for that specific day. This analysis was performed based on the isotropic sky model. This model states that it can be assumed that the combination of diffuse and ground-reflected radiation is isotropic. With this assumption, the sum of the diffuse from the sky and the groundreflected radiation on a tilted surface is the same regardless of orientation, and the total radiation on a tilted surface is the sum of the beam contribution and the diffuse on a horizontal surface (Duffie, 90). However, an improvement was made to this model by Liu and Jordan (1963), to where the radiation on a tilted surface was the sum of the beam, diffuse and ground-reflected radiation. This model was used in this analysis because it is 21 easier to calculate the radiation on a tilted surface. Other models do exist and one of them is the anisotropic sky model. This model accounts for horizon-brightening and the circumsolar diffuse radiation on a tilted surface. Hay and Davies (1980) account for the circumsolar diffuse radiation but not the horizon-brightening. It was Reindl (1990) who account for the horizon-brightening proposed by Klucher (1979) and is referred to as the HDKR model. This model gives the absorbed radiation as: 1 cos 3 S I b I d Ai Rb b I d 1 Ai d 1 f sin 2 2 1 cos I g g 2 (3.1.5) Most of these variables were used in the isotropic model and do not need further explanation. However, there are two new variables that appear and they are the anisotropy index, Ai, and the modulating factor, f and are given as: Ai f Ib Io Ib I (3.1.5a) (3.1.5b) 22 It is said that these new equations when used in conjunction with equation 5 will give better results. Both models were used in the Trombe wall analysis just to confirm to accuracy of the results with each other. The “I” component in the last part of equation 1 is the total radiation that was given by the sun for that hour before it gets absorbed by object. This value cannot be calculated by any equation but can only determined through testing measurements. Usually an instrument such as a pyranometer is used to measure the radiation given off by the sun. The detectors for these instruments must have a response independent of wavelength of radiation over the solar spectrum. In addition, they should have a response independent of the angle of incidence of the solar radiation (Duffie, 48). Figure 8: CM6B Pyranometer Measuring Device Most solar data is measured with these types of instruments. The data that was used for this project was provided by the National Renewable Energy Laboratory. The data by 23 NREL is the hourly radiation data for the entire 12 month period of 2005. This hourly data has units of W-h/m2, but in order to use this for our purpose this value must be multiplied by 3600 seconds (3600 seconds per hour) to get J/m2. Once the total absorbed radiation for the day is calculated, then this value is multiplied by the total wall area to get the total amount of heat the wall will provide for that day in J. 3.3 Evacuated Tube Collector Analysis The second analysis done for this project is that of an evacuated tube collector. It is important to investigate other means of supplying space heating other than a Trombe wall. An evacuated tube collector was chosen to be the device that would supply this heat requirement. Most collectors are used as direct systems. These are systems where the tube fluid transfers heat directly to the working fluid. The working fluid is generally stored in a tank a used whenever hot water is demanded. Figure 9: Direct Applied Solar Storage System 24 Indirect systems do not use the working fluid directly. The heated water is stored in a tank and then when heating is required, the working fluid removes the heat and uses it for another purpose. Most indirect systems are used for space heating where the storage fluid is water and the working fluid is air. Figure 10: Indirect Applied Storage System 25 Both systems involve a storage tank and this tank limits the amount of heat that can be utilized. The solar collector will absorb a fraction of the incoming radiation in itself, but the tank will have to store that heat so it can be used at times when solar energy is not readily available. This meant that it was not necessary to design the evacuated tube collector, but instead use the collector efficiency. When sizing a storage tank it is necessary to decide whether or not to go with the unstratified tank or the stratified tank model. The unstratified model seemed satisfactory for this project since once in equilibrium the tank would be large enough that stratification would have little effect. The heat capacity of water, or any liquid for that matter, operating over a finite temperature difference is given by: Qs (mC p ) s Ts (3.2.1) where Q is the total heat capacity, m is the mass of the water, Cp is the specific heat and ΔTs is the temperature difference. Now including all parts of the system, the collector, the tank, and the load, the energy balance on this unstratified tank is: mC p s dTs Qu Ls UAs Ts Ta' dt (3.2.2) where Qu is the useful energy from the collector, Ls is heat removal from the load, and U is the overall heat loss coefficient from the tank to the ambient. The variables above are 26 either properties of the fluid or the ambient and can be determined fairly easily. The useful energy from the collector and the heat removal from the load are also easily calculated but may take on different forms. For this project they were stated as such respectively: Qu Ac I T (3.2.3) And Ls hw A Tdesired Ta (3.2.4) Equation 3.2.2 can be integrated over a time to determine the performance of the collector-storage system. However this integration can be quite complex and rigorous due the time dependence of some of the variables, therefore it is often necessary to use numerical integration methods. Euler integration is a simple enough method to solve this time dependent system and this is done by rewriting the temperature derivative as T s Ts / t and solving for the tank temperature at the end of each time increment. Rearranging equation 3.2.2 and incorporating Euler integration will give a useful energy equation that can used to find the temperature of the tank at the end of each hour. Ts Ts t Qu Ls UAs Ts Ta' mC p s (3.2.5) 27 This equation is often used on a 1-hour time basis and Ts for one hour becomes the Ts for the next. Further analysis can be done to determine the size of the heat pipe, mass flow rate of the water, and the velocity of the air passing over the heat exchanger. More importantly, however, is the sizing of storage tank. The size of the tank will determine the amount of heat that can be stored, considering all losses, and therefore a tradeoff between tanks size and cost will ultimately determine the feasibility of the project. 28 Chapter 4 ANALYSIS OF THE DATA As mentioned earlier, the data was given by NREL as hourly data radiation for the entire year of 2005 for the Travis Airforce Base in Fairfield, California. Attempting to analyze all the data given would be impractical and cumbersome, therefore three days of that year were taken into consideration. First the data was broken down into five of the coldest months for that location and year: Janurary, February, October, November and December. Next, out of these five months, the three days that were considered were the warmest day, an average temperature day, and the coldest day: October 04, 2005, November 02, 2005 and December 16, 2005. Table 6 in the appendix gives the solar radiation in Wh/m2 for each hour of those days. 29 4.1 Trombe Wall Data Dates 10/4/05 11/2/05 12/16/05 Heat Load Desired 35 MW 42 MW 92 MW S/day (Isotropic) 7.88 MJ/m2 4.81 MJ/m2 811 kJ/m2 Total S for wall 7 MW 4.3 MW 720 kW % of Load Met 20% 10.2% .78% S/day (Anisotropic) 8.63 MJ/m2 5.30 MJ/m2 838kJ/m2 Total S for wall 7.7 MW 4.7 MW 744 kW % of Load Met 22% 11.2% .8% Table 3: Solar Wall Data Calculated for Selected Days Using the equations in section 3.1, the total absorbed energy for the wall was calculated for each hour. These values were then summed up and multiplied by the wall area to get a total amount of absorbed energy for the entire south facing wall of the facility. The total surface area of the south wall, subtracting the surface area for 21 loading dock doors, is 3196 m2. This data alone gives the total heat capacity of the wall, however it is still meaningless unless it is compared to the heating demand for the Anheuser Busch facility. To calculate this heat demand, the heat loss for this warehouse had to be determined. Normally, heat losses from buildings involve convection losses to the outside and conduction losses through the walls. Conduction through the walls was 30 ignored because convection losses generally are larger than conduction losses. The building heat loss are just the convection losses in this situation and is defined as: Qh hw AT (4.1.1) where hw is the heat transfer coefficient and is determined that for forced convection conditions over buildings this coefficient is expressed as: 8.6V 0.6 hw max 5, 0.4 L (4.1.1a) The variable V is the wind velocity in meters per second and L is the cube root of the building volume in meters. For this project, the average wind velocity for the three days was less than one. Therefore, the determining coefficient to use in equation 4.1.1 is 5 W/m2K. Using this information and the total surface area of the building, the total heat loss for each hour was found and then summed up to give a daily heat loss of 35 MW, 42 MW, 92 MW for October, November and December respectively. It can be seen from table 3 that the solar wall cannot meet the heat demands required by this facility for any of the selected days, furthermore, it would only have 11 hours of sunlight to do so. 4.2 Evacuated Tube Collector Data 31 Date 10/4/05 11/2/05 12/16/05 Qu for Collector 38.8 MW 46.7 MW 102 MW Heat Load Desired 38.7 MW 46.6 MW 102 MW Collector Area 15100 m2 31200 m2 380000 m2 % Roof Covered 33% 68% > 100% 900 m3 1279 m3 4542.5 m3 (238,000 gallons) (338,000 gallons) (1,200,000 gallons) Tank Volume Table 4: Evacuated Tube Data Calculated for Selected Days The data for the evacuated tube system was calculated using equation 3.2.3. Before this set could be generated, a start temperature had to be assumed otherwise there would not be any starting data to put into the equation. The ambient temperature at 1:00 am was used as the tank temperature for that hour. Simply putting this, as well as the other variables in table 4, into the equation yielded the final temperature after each hour for that day. The two variables that can be changed in order to validate this option for this project are the collector area and the tank volume. The area was increased until the useful energy for the collector was equal to the heat loss from the building. This was the minimum collector area allowed that ensured that the heating load for the building was satisfied for that day. The tank volume was increased so that way the temperature in the tank at the end of any hour was not lower than its freezing point. Temperatures below this point will not flow and there would be no heat transfer allowed until the fluid’s 32 temperature increased. Looking at table 4 it can be seen that for each of the three days the useful energy gain was either greater or equal to the building heat loss. If it is to be assumed that this is precisely what is supposed to occur, then the data shows that the equivalent collector area and tank volume necessary to produce this are also correct, except for the day in December. On this day the collector area exceeds the size of the roof and therefore the heat load cannot be met. The main concern, however, is the volume of the tank necessary for each day. These volumes are extremely large and it may be difficult for the design engineer to find a company with the capabilities to make a tank of such extreme proportions and even if there is a company out there willing to take on such a feat, the question of cost and space arises. Is it really economically beneficial to install a system such as this with a tank this size and if so, is there room on site for such an eyesore? This is just the beginning of concerns that the design engineer and the customer might have 33 Chapter 5 FINDINGS AND INTERPRETATIONS The appendix contains the excel sheets used to generate the data for the analysis and any other information that may have been briefly mentioned. The final table below briefly compares the two design methods and shows the options for heating the warehouse. This table is expressed as a yes or no evaluation as opposed to a numerical comparison which is shown in table 4 and table 3 in the above section. Trombe Wall Evacuated Tube Collector Dates 10/4/05 11/2/05 12/16/05 10/4/05 11/2/05 12/16/05 Was the heat load met? No No No Yes Yes Yes Is the design feasible? Yes Yes Yes Yes Yes No Is this method Yes Yes Yes No No No recommendable? Table 5: Yes or No Comparison Table of Both Design Methods 5.1 Further Research Although the analysis for this project included some lengthy and detailed equations, there is still more that can be done in order to determine the most optimal solution to the problem. First and foremost, a cost analysis should be done. Due to the specifications of the problem, cost was ignored because most companies that design these 34 types of systems need to be on site in order to obtain accurate sizes and in turn give accurate costs. Unfortunately, most companies cannot afford to waste time on a project that will not guarantee them the contract. Second, instead of just using a numerical analysis program such as excel to determine the necessary data; another type of program should be used to compare the results. A simulation program such as Fluent or Transys should be used in order to handle the more complicated issues such as variable heat fluxes and infiltration. Third, the assumed variables should be varied and possibly measured so that way the analysis is as accurate as possible. Projects similar to this one are tedious and time consuming and usually require the work of several engineers. Since there is a lot of money invested into these types of systems a very thorough analysis must be done, however, what has been done here is good first step in determining the feasibility and complexity. 5.2 Conclusions The information obtained from this report and the data presented here has paved the way for future analysis and further research into the design of space heating for Anheuser Busch’s Fairfield facility. Based off the obtained information the most optimal solution would have to be the solar wall. Even though the heat load was not met by this method, it appears to be more realistic than the alternative. Large tanks are too difficult and expensive to manufacture. To accommodate for the extra heat loss, an auxiliary heater system will have to be used. If there is a necessity to be completely sustainable, then another renewable system, such as geothermal, might be able to be incorporated to cover the excess heat loss. 35 APPENDICES 36 APPENDIX A Solar Radiation Data for the Three Selected Days 10/4/2005 11/2/2005 12/16/2005 Hours Gt (Wh/m2) Ta (°F) Gt (Wh/m2) Ta (°F) Gt (Wh/m2) Ta (°F) 1:00 AM 0 56.9 0 54.8 0 45.4 2:00 AM 0 57 0 54.1 0 41.7 3:00 AM 0 57.1 0 53.7 0 39.2 4:00 AM 0 57.3 0 53.6 0 37.3 5:00 AM 0 56.9 0 53.6 0 36 6:00 AM 0 57.2 0 53.9 0 35.3 7:00 AM 33 56.8 4 54 0 36 8:00 AM 193 58.1 82 54.3 6 36.2 9:00 AM 390 59.3 237 55 38 39.8 10:00 AM 563 61 315 55.8 60 42.1 11:00 AM 687 64.3 417 57.5 76 46.2 12:00 PM 749 66.8 422 60.3 85 50.7 1:00 PM 744 65.5 529 62.1 86 51.4 2:00 PM 675 65.8 423 61.8 77 51.9 3:00 PM 545 64.6 318 62.1 62 50.8 4:00 PM 367 62.2 198 61.5 41 49.9 5:00 PM 169 60.3 51 60.9 9 46.8 6:00 PM 21 59.8 0 61 0 46.1 7:00 PM 0 59 0 60.5 0 44.4 8:00 PM 0 57.8 0 60.4 0 43.4 9:00 PM 0 57.8 0 60.3 0 41.3 10:00 PM 0 58.7 0 58.6 0 40.8 11:00 PM 0 57.3 0 56.5 0 40.9 12:00 AM 0 56.7 0 58.6 0 46.6 Table 6: Hourly Solar Radiation Data and Temperature for Three Selected Days 37 APPENDIX B Calculation Tables VT (gallons) 238000 VT (m3) 900.9280036 AC (m2) 15100 AB (m2) 57791.8 U (W/m2K) 5 T inside (°C) 21 Hour 1:00 AM 2:00 AM 3:00 AM 4:00 AM 5:00 AM 6:00 AM 7:00 AM 8:00 AM 9:00 AM 10:00 AM 11:00 AM 12:00 PM 1:00 PM 2:00 PM 3:00 PM 4:00 PM 5:00 PM 6:00 PM 7:00 PM 8:00 PM 9:00 PM 10:00 PM 11:00 PM 12:00 AM Gt (Wh/m2) 0 0 0 0 0 0 33 193 390 563 687 749 744 675 545 367 169 21 0 0 0 0 0 0 I (J/m2) 0 0 0 0 0 0 118800 694800 1404000 2026800 2473200 2696400 2678400 2430000 1962000 1321200 608400 75600 0 0 0 0 0 0 Qu for the day 38776800 Ta (F) 56.9 57 57.1 57.3 56.9 57.2 56.8 58.1 59.3 61 64.3 66.8 65.5 65.8 64.6 62.2 60.3 59.8 59 57.8 57.8 58.7 57.3 56.7 Ta (C) 13.8 13.9 13.9 14.1 13.8 14.0 13.8 14.5 15.2 16.1 17.9 19.3 18.6 18.8 18.1 16.8 15.7 15.4 15.0 14.3 14.3 14.8 14.1 13.7 Heat used for the day 38688399.44 Ts 13.8 11.8 9.9 7.9 6.0 4.1 2.1 0.4 0.0 1.2 3.9 8.0 12.9 17.6 21.8 24.9 26.4 26.2 24.8 23.2 21.3 19.5 17.8 15.9 Table 7: Evacuated Tube Collector Analysis for October 4, 2005 38 Hour 1:00 AM 2:00 AM 3:00 AM 4:00 AM 5:00 AM 6:00 AM 7:00 AM 8:00 AM 9:00 AM 10:00 AM 11:00 AM 12:00 PM 1:00 PM 2:00 PM 3:00 PM 4:00 PM 5:00 PM 6:00 PM 7:00 PM 8:00 PM 9:00 PM 10:00 PM 11:00 PM 12:00 AM Total Ts+ 11.8 9.9 7.9 6.0 4.1 2.1 0.4 0.0 1.2 3.9 8.0 12.9 17.6 21.8 24.9 26.4 26.2 24.8 23.2 21.3 19.5 17.8 15.9 13.9 efficiency 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 Qu (J/hr) 0 0 0 0 0 0 896940000 5245740000 1.06E+10 1.5302E+10 1.8673E+10 2.0358E+10 2.0222E+10 1.8347E+10 1.4813E+10 9975060000 4593420000 570780000 0 0 0 0 0 0 1.396E+11 Heat used (J/hr) 7455142200 7397350400 7339558600 7223975000 7455142200 7281766800 7512934000 6761640600 6068139000 5085678400 3178549000 1733754000 2485047400 2311672000 3005173600 4392176800 5490221000 5779180000 6241514400 6935016000 6935016000 6414889800 7223975000 7570725800 1.39278E+11 Heat loss (J/hr) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Table 7: Evacuated Tube Collector Analysis for October 4, 2005 (Continued) 39 VT (gallons) 338000 VT (m3) 1279.469182 AC (m2) 31200 AB (m2) 57791.8 U (W/m2K) 5 T inside (°C) 21 Hour 1:00 AM 2:00 AM 3:00 AM 4:00 AM 5:00 AM 6:00 AM 7:00 AM 8:00 AM 9:00 AM 10:00 AM 11:00 AM 12:00 PM 1:00 PM 2:00 PM 3:00 PM 4:00 PM 5:00 PM 6:00 PM 7:00 PM 8:00 PM 9:00 PM 10:00 PM 11:00 PM 12:00 AM Gt (Wh/m2) 0 0 0 0 0 0 4 82 237 315 417 422 529 423 318 198 51 0 0 0 0 0 0 0 I (J/m2) 0 0 0 0 0 0 14400 295200 853200 1134000 1501200 1519200 1904400 1522800 1144800 712800 183600 0 0 0 0 0 0 0 Qu for the day 46737600 Ta (F) 54.8 54.1 53.7 53.6 53.6 53.9 54 54.3 55 55.8 57.5 60.3 62.1 61.8 62.1 61.5 60.9 61 60.5 60.4 60.3 58.6 56.5 58.6 Ta (C) 12.7 12.3 12.1 12.0 12.0 12.2 12.2 12.4 12.8 13.2 14.2 15.7 16.7 16.6 16.7 16.4 16.1 16.1 15.8 15.8 15.7 14.8 13.6 14.8 Heat Used for the day 46602665.39 Ts 12.7 11.1 9.4 7.7 5.9 4.2 2.5 0.8 0.0 0.9 2.7 5.7 9.1 13.8 17.4 19.9 21.0 20.6 19.7 18.7 17.7 16.6 15.4 14.0 Table 8: Evacuated Tube Collector Analysis for November 2, 2005 40 Hour 1:00 AM 2:00 AM 3:00 AM 4:00 AM 5:00 AM 6:00 AM 7:00 AM 8:00 AM 9:00 AM 10:00 AM 11:00 AM 12:00 PM 1:00 PM 2:00 PM 3:00 PM 4:00 PM 5:00 PM 6:00 PM 7:00 PM 8:00 PM 9:00 PM 10:00 PM 11:00 PM 12:00 AM Total Ts+ 11.1 9.4 7.7 5.9 4.2 2.5 0.8 0.0 0.9 2.7 5.7 9.1 13.8 17.4 19.9 21.0 20.6 19.7 18.7 17.7 16.6 15.4 14.0 12.8 efficiency 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 Qu (J/hr) 0 0 0 0 0 0 224640000 4605120000 1.331E+10 1.769E+10 2.3419E+10 2.37E+10 2.9709E+10 2.3756E+10 1.7859E+10 1.112E+10 2864160000 0 0 0 0 0 0 0 1.6826E+11 Heat used (J/hr) 8668770000 9073312600 9304479800 9362271600 9362271600 9188896200 9131104400 8957729000 8553186400 8090852000 7108391400 5490221000 4449968600 4623344000 4449968600 4796719400 5143470200 5085678400 5374637400 5432429200 5490221000 6472681600 7686309400 6472681600 1.6777E+11 Heat loss (J/hr) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Table 8: Evacuated Tube Collector Analysis for November 2, 2005 (Continued) 41 VT (gallons) 1200000 VT (m3) 4542.494136 AC (m2) 380000 AB (m2) 57791.8 U (W/m2K) 5 T inside (°C) 21 Hour 1:00 AM 2:00 AM 3:00 AM 4:00 AM 5:00 AM 6:00 AM 7:00 AM 8:00 AM 9:00 AM 10:00 AM 11:00 AM 12:00 PM 1:00 PM 2:00 PM 3:00 PM 4:00 PM 5:00 PM 6:00 PM 7:00 PM 8:00 PM 9:00 PM 10:00 PM 11:00 PM 12:00 AM Gt (Wh/m2) 0 0 0 0 0 0 0 6 38 60 76 85 86 77 62 41 9 0 0 0 0 0 0 0 I (J/m2) 0 0 0 0 0 0 0 21600 136800 216000 273600 306000 309600 277200 223200 147600 32400 0 0 0 0 0 0 0 Qu for the day 102600000 Ta (F) 45.4 41.7 39.2 37.3 36 35.3 36 36.2 39.8 42.1 46.2 50.7 51.4 51.9 50.8 49.9 46.8 46.1 44.4 43.4 41.3 40.8 40.9 46.6 Ta (C) 7.4 5.4 4.0 2.9 2.2 1.8 2.2 2.3 4.3 5.6 7.9 10.4 10.8 11.1 10.4 9.9 8.2 7.8 6.9 6.3 5.2 4.9 4.9 8.1 Heat Used for the day 101938313.9 Ts 7.4 6.7 5.8 4.9 3.9 2.9 1.8 0.8 0.0 0.5 1.8 3.8 6.2 8.8 11.0 12.6 13.5 13.1 12.4 11.6 10.8 10.0 9.1 8.2 Table 9: Evacuated Tube Collector Analysis for December 16, 2005 42 Hour 1:00 AM 2:00 AM 3:00 AM 4:00 AM 5:00 AM 6:00 AM 7:00 AM 8:00 AM 9:00 AM 10:00 AM 11:00 AM 12:00 PM 1:00 PM 2:00 PM 3:00 PM 4:00 PM 5:00 PM 6:00 PM 7:00 PM 8:00 PM 9:00 PM 10:00 PM 11:00 PM 12:00 AM Total Ts+ 6.7 5.8 4.9 3.9 2.9 1.8 0.8 0.0 0.5 1.8 3.8 6.2 8.8 11.0 12.6 13.5 13.1 12.4 11.6 10.8 10.0 9.1 8.2 7.5 efficiency 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 Qu (J/hr) 0 0 0 0 0 0 0 4104000000 2.5992E+10 4.104E+10 5.1984E+10 5.814E+10 5.8824E+10 5.2668E+10 4.2408E+10 2.8044E+10 6156000000 0 0 0 0 0 0 0 3.6936E+11 Heat used (J/hr) 14101199200 16239495800 17684290800 18782335000 19533628400 19938171000 19533628400 19418044800 17337540000 16008328600 13638864800 11038233800 10633691200 10344732200 10980442000 11500568200 13292114000 13696656600 14679117200 15257035200 16470663000 16759622000 16701830200 13407697600 366977930000.00 Heat loss (J/hr) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Table 9: Evacuated Tube Collector Analysis for December 16, 2005 (Continued) 43 Latitude 38.249 Τ 0.82 (τα)d=(τα)g 0.6186654 αn 0.9 (τα)n 0.74538 ρg 0.3 θe 59 KL 0.0125 (τα)/(τα)n 0.83 Hour 1:00 AM 2:00 AM 3:00 AM 4:00 AM 5:00 AM 6:00 AM 7:00 AM 8:00 AM 9:00 AM 10:00 AM 11:00 AM 12:00 PM 1:00 PM 2:00 PM 3:00 PM 4:00 PM 5:00 PM 6:00 PM 7:00 PM 8:00 PM 9:00 PM 10:00 PM 11:00 PM 12:00 AM Hour Angle -165.0 -150.0 -135.0 -120.0 -105.0 -90.0 -75.0 -60.0 -45.0 -30.0 -15.0 0.0 15.0 30.0 45.0 60.0 75.0 90.0 105.0 120.0 135.0 150.0 165.0 180.0 Gt (Wh/m2) 0 0 0 0 0 0 33 193 390 563 687 749 744 675 545 367 169 21 0 0 0 0 0 0 I (J/m2) 0 0 0 0 0 0 118800 694800 1404000 2026800 2473200 2696400 2678400 2430000 1962000 1321200 608400 75600 0 0 0 0 0 0 I0 (J/m2) 0 0 0 0 0 0 214427 1183644 2052620 2762135 3263839 3523540 3523540 3263839 2762135 2052620 1183644 214427 0 0 0 0 0 0 Date n-value declination Wall Area 10/4/2005 277 -5.400668 3186.723 kT 0 0 0 0 0 0 0.55403 0.58700 0.68400 0.73378 0.75776 0.76525 0.76014 0.74452 0.71032 0.64367 0.51401 0.35257 0 0 0 0 0 0 Id (J/m2) 0 0 0 0 0 0 112876.3 658093.7 1317569.3 1892949.7 2304532.2 2510691.4 2495162.6 2267173.0 1836571.7 1244663.0 384319.2 73201.1 0 0 0 0 0 0 Table 10: Trombe Wall Analysis for October 4, 2005 44 Hour 1:00 AM 2:00 AM 3:00 AM 4:00 AM 5:00 AM 6:00 AM 7:00 AM 8:00 AM 9:00 AM 10:00 AM 11:00 AM 12:00 PM 1:00 PM 2:00 PM 3:00 PM 4:00 PM 5:00 PM 6:00 PM 7:00 PM 8:00 PM 9:00 PM 10:00 PM 11:00 PM 12:00 AM Total Ib (J/m2) 0 0 0 0 0 0 5923.7 36706.3 86430.7 133850.3 168667.8 185708.6 183237.4 162827.0 125428.3 76537.0 224080.8 2398.9 0 0 0 0 0 0 Rb 0.64098 0.62533 0.59219 0.52150 0.32846 -1.26854 1.62008 1.14859 1.03063 0.98198 0.96027 0.95394 0.96027 0.98198 1.03063 1.14859 1.62008 -1.26854 0.32846 0.52150 0.59219 0.62533 0.64098 0.64565 θ 121.4 117.4 111.2 103.5 94.9 85.8 76.5 67.5 59.4 52.6 48.0 46.4 48.0 52.6 59.4 67.5 76.5 85.8 94.9 103.5 111.2 117.4 121.4 122.8 (τα)/(τα)n 0 0 0 0 0 0.06 0.38 0.66 0.86 0.92 0.95 0.95 0.95 0.92 0.86 0.66 0.38 0.06 0 0 0 0 0 0 (τα)b 0 0 0 0 0 0.04472 0.28324 0.49195 0.64103 0.68575 0.70811 0.70811 0.70811 0.68575 0.64103 0.49195 0.28324 0.04472 0 0 0 0 0 0 Table 10: Trombe Wall Analysis for October 4, 2005 (Continued) S (J/m2) 0 0 0 0 0 0 48659.2 288788.1 594959.8 863771.5 1057070.4 1152309.9 1144988.1 1036460.5 833050.7 550869.2 278167.7 29523.1 0 0 0 0 0 0 7878618 45 Hour 1:00 AM 2:00 AM 3:00 AM 4:00 AM 5:00 AM 6:00 AM 7:00 AM 8:00 AM 9:00 AM 10:00 AM 11:00 AM 12:00 PM 1:00 PM 2:00 PM 3:00 PM 4:00 PM 5:00 PM 6:00 PM 7:00 PM 8:00 PM 9:00 PM 10:00 PM 11:00 PM 12:00 AM Total Ta (C) 13.8 13.9 13.9 14.1 13.8 14.0 13.8 14.5 15.2 16.1 17.9 19.3 18.6 18.8 18.1 16.8 15.7 15.4 15.0 14.3 14.3 14.8 14.1 13.7 Heat loss (W) 1862150.8 1847715.6 1833280.3 1804409.7 1862150.8 1818845.0 1876586.1 1688927.5 1515704.2 1270304.4 793940.3 433058.3 620716.9 577411.1 750634.4 1097081.1 1371351.4 1443527.8 1559010.0 1732233.3 1732233.3 1602315.8 1804409.7 1891021.4 34789019.4 Ai 0 0 0 0 0 0 0.027626 0.031011 0.042108 0.048459 0.051678 0.052705 0.052004 0.049888 0.04541 0.037287 0.189314 0.011187 0 0 0 0 0 0 f 0 0 0 0 0 0 0.223301 0.229848 0.248114 0.256983 0.261148 0.262436 0.261559 0.258857 0.252841 0.240686 0.606887 0 0 0 0 0 0 0 Total S for the wall for 10/4/05 6996044.27 7 MW (Isotropic) 7667171.839 7.7 MW (Anisotropic) Table 10: Trombe Wall Analysis for October 4, 2005 (Continued) S (J/m2) 0 0 0 0 0 0 51805.984 310036.59 648698.33 947790.11 1163629.3 1269025.6 1260746.2 1138619.1 910830.15 594278.4 309727.4 29223.294 0 0 0 0 0 0 8634410.5 46 Latitude 38.249 τ 0.82 (τα)d=(τα)g 0.6186654 αn 0.9 (τα)n 0.74538 ρg 0.3 θe 59 KL 0.0125 (τα)/(τα)n 0.83 Hour 1:00 AM 2:00 AM 3:00 AM 4:00 AM 5:00 AM 6:00 AM 7:00 AM 8:00 AM 9:00 AM 10:00 AM 11:00 AM 12:00 PM 1:00 PM 2:00 PM 3:00 PM 4:00 PM 5:00 PM 6:00 PM 7:00 PM 8:00 PM 9:00 PM 10:00 PM 11:00 PM 12:00 AM Hour Angle -165.0 -150.0 -135.0 -120.0 -105.0 -90.0 -75.0 -60.0 -45.0 -30.0 -15.0 0.0 15.0 30.0 45.0 60.0 75.0 90.0 105.0 120.0 135.0 150.0 165.0 180.0 Gt 0 0 0 0 0 0 4 82 237 315 417 422 529 423 318 198 51 0 0 0 0 0 0 0 I 0 0 0 0 0 0 14400 295200 853200 1134000 1501200 1519200 1904400 1522800 1144800 712800 183600 0 0 0 0 0 0 0 I0 0 0 0 0 0 0 344239.4 607681.4 1461150.3 2158004.6 2650755.1 2905821.5 2905821.5 2650755.1 2158004.6 1461150.3 607681.4 0 0 0 0 0 0 0 Date n-value declination Wall Area 11/2/2005 306 -15.666098 3186.723 kT 0 0 0 0 0 0 0.041831 0.485781 0.583924 0.525485 0.566329 0.522813 0.655374 0.574478 0.530490 0.487835 0.302132 0 0 0 0 0 0 0 Id 0 0 0 0 0 0 14345.8 282293.8 808361.7 1080369.0 1424684.4 1447716.9 1792071.5 1444066.7 1090142.5 681504.4 173935.6 0 0 0 0 0 0 0 Table 11: Trombe Wall Analysis for November 2, 2005 47 Hour 1:00 AM 2:00 AM 3:00 AM 4:00 AM 5:00 AM 6:00 AM 7:00 AM 8:00 AM 9:00 AM 10:00 AM 11:00 AM 12:00 PM 1:00 PM 2:00 PM 3:00 PM 4:00 PM 5:00 PM 6:00 PM 7:00 PM 8:00 PM 9:00 PM 10:00 PM 11:00 PM 12:00 AM Total Ib 0 0 0 0 0 0 54.21 12906.23 44838.32 53631.04 76515.60 71483.12 112328.49 78733.33 54657.45 31295.58 9664.37 0 0 0 0 0 0 0 Rb 0.405220 0.370015 0.298398 0.157687 -0.159241 -1.268539 12.837653 2.418627 1.723912 1.493373 1.398808 1.372102 1.398808 1.493373 1.723912 2.418627 12.837653 -1.268539 -0.159241 0.157687 0.298398 0.370015 0.405220 0.415910 θ 111.33 107.71 102.09 94.93 86.69 77.76 68.51 59.33 50.69 43.26 38.02 36.08 38.02 43.26 50.69 59.33 68.51 77.76 86.69 94.93 102.09 107.71 111.33 112.58 (τα)/(τα)n 0 0 0 0 0.04 0.34 0.65 0.86 0.94 0.96 0.96 0.97 0.96 0.96 0.94 0.86 0.65 0.34 0.04 0 0 0 0 0 (τα)b 0 0 0 0 0.029815 0.253429 0.484497 0.641027 0.700657 0.715565 0.715565 0.723019 0.715565 0.715565 0.700657 0.641027 0.484497 0.253429 0.029815 0 0 0 0 0 Table 11: Trombe Wall Analysis for November 2, 2005 (Continued) S 0 0 0 0 0 0 6111.14 134727.08 383388.42 496738.85 656599.91 659722.83 843508.12 672147.45 509473.13 325480.13 130952.51 0 0 0 0 0 0 0 4818849.5 48 Hour 1:00 AM 2:00 AM 3:00 AM 4:00 AM 5:00 AM 6:00 AM 7:00 AM 8:00 AM 9:00 AM 10:00 AM 11:00 AM 12:00 PM 1:00 PM 2:00 PM 3:00 PM 4:00 PM 5:00 PM 6:00 PM 7:00 PM 8:00 PM 9:00 PM 10:00 PM 11:00 PM 12:00 AM Total Ta (C) 12.7 12.3 12.1 12.0 12.0 12.2 12.2 12.4 12.8 13.2 14.2 15.7 16.7 16.6 16.7 16.4 16.1 16.1 15.8 15.8 15.7 14.8 13.6 14.8 14.3 Heat loss 2165291.7 2266338.6 2324079.7 2338515.0 2338515.0 2295209.2 2280773.9 2237468.1 2136421.1 2020938.9 1775539.2 1371351.4 1111516.4 1154822.2 1111516.4 1198128.1 1284739.7 1270304.4 1342480.8 1356916.1 1371351.4 1616751.1 1919891.9 1616751.1 41905611.4 Ai 0 0 0 0 0 0 0.00015749 0.02123847 0.030687 0.02485214 0.02886559 0.02459997 0.03865636 0.02970223 0.02532777 0.02141845 0.01590368 0 0 0 0 0 0 0 f 0 0 0 0 0 0 0.06135814 0.20909394 0.22924467 0.21747112 0.22576454 0.21691734 0.24286553 0.22738294 0.21850424 0.20953552 0.22943012 0 0 0 0 0 0 0 S 0 0 0 0 0 0 6220.74038 148486.214 425322.642 542181.688 719203.045 717536.899 937178.487 739558.403 559673.733 358878.622 151597.097 0 0 0 0 0 0 0 5305837.57 Total S for the wall for 11/2/05 4279035.327 4.3 MW (Isotropic) 4711470.276 4.7 MW (Anisotropic) Table 11: Trombe Wall Analysis for November 2, 2005 (Continued) 49 Latitude 38.249 Τ 0.82 (τα)d=(τα)g 0.6186654 αn 0.9 (τα)n 0.74538 ρg 0.3 θe 59 KL 0.0125 (τα)/(τα)n 0.83 Hour 1:00 AM 2:00 AM 3:00 AM 4:00 AM 5:00 AM 6:00 AM 7:00 AM 8:00 AM 9:00 AM 10:00 AM 11:00 AM 12:00 PM 1:00 PM 2:00 PM 3:00 PM 4:00 PM 5:00 PM 6:00 PM 7:00 PM 8:00 PM 9:00 PM 10:00 PM 11:00 PM 12:00 AM Hour Angle -165.0 -150.0 -135.0 -120.0 -105.0 -90.0 -75.0 -60.0 -45.0 -30.0 -15.0 0.0 15.0 30.0 45.0 60.0 75.0 90.0 105.0 120.0 135.0 150.0 165.0 180.0 Gt 0 0 0 0 0 0 0 6 38 60 76 85 86 77 62 41 9 0 0 0 0 0 0 0 I 0 0 0 0 0 0 0 21600 136800 216000 273600 306000 309600 277200 223200 147600 32400 0 0 0 0 0 0 0 I0 0 0 0 0 0 0 0 149813.2 975088.6 1648923.2 2125396.2 2372036.8 2372036.8 2125396.2 1648923.2 975088.6 149813.2 0 0 0 0 0 0 0 Date n-value declination Wall Area 12/16/2005 350 -23.3716512 3186.723 kT 0 0 0 0 0 0 0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0 0 0 0 0 0 0 Id 0 0 0 0 0 0 0 21319.7 135072.7 213453.5 270430.2 302447.3 305963.2 273946.2 220480.9 145589.2 31764.9 0 0 0 0 0 0 0 Table 12: Trombe Wall Analysis for December 16, 2005 50 Hour 1:00 AM 2:00 AM 3:00 AM 4:00 AM 5:00 AM 6:00 AM 7:00 AM 8:00 AM 9:00 AM 10:00 AM 11:00 AM 12:00 PM 1:00 PM 2:00 PM 3:00 PM 4:00 PM 5:00 PM 6:00 PM 7:00 PM 8:00 PM 9:00 PM 10:00 PM 11:00 PM 12:00 AM Total Ib 0 0 0 0 0 0 0 280.29 1727.31 2546.53 3169.82 3552.74 3636.83 3253.79 2719.13 2010.81 635.05 0 0 0 0 0 0 0 Rb 0.252026 0.207628 0.119555 -0.045199 -0.380529 -1.268539 -7.772577 5.186074 2.700507 2.122074 1.908971 1.851056 1.908971 2.122074 2.700507 5.186074 -7.772577 -1.268539 -0.380529 -0.045199 0.119555 0.207628 0.252026 0.265656 θ 103.73 100.41 95.18 88.43 80.53 71.85 62.70 53.44 44.49 36.52 30.63 28.38 30.63 36.52 44.49 53.44 62.70 71.85 80.53 88.43 95.18 100.41 103.73 104.88 (τα)/(τα)n 0 0 0 0.02 0.22 0.56 0.8 0.91 0.95 0.97 0.98 0.98 0.98 0.97 0.95 0.91 0.8 0.56 0.22 0.02 0 0 0 0 (τα)b 0 0 0 0.014908 0.163984 0.417413 0.596304 0.678296 0.708111 0.723019 0.730472 0.730472 0.730472 0.723019 0.708111 0.678296 0.596304 0.417413 0.163984 0.014908 0 0 0 0 S 0 0 0 0 0 0 0 9585.32 57780.48 89980.04 113463.09 126757.39 128446.62 115456.91 94114.55 65806.16 9889.31 0 0 0 0 0 0 0 811279.86 Table 12: Trombe Wall Analysis for December 16, 2005 (Continued) 51 Hour 1:00 AM 2:00 AM 3:00 AM 4:00 AM 5:00 AM 6:00 AM 7:00 AM 8:00 AM 9:00 AM 10:00 AM 11:00 AM 12:00 PM 1:00 PM 2:00 PM 3:00 PM 4:00 PM 5:00 PM 6:00 PM 7:00 PM 8:00 PM 9:00 PM 10:00 PM 11:00 PM 12:00 AM Total Ta (C) 7.4 5.4 4.0 2.9 2.2 1.8 2.2 2.3 4.3 5.6 7.9 10.4 10.8 11.1 10.4 9.9 8.2 7.8 6.9 6.3 5.2 4.9 4.9 8.1 6.3 Heat loss 3522207.8 4056313.1 4417195.0 4691465.3 4879123.9 4980170.8 4879123.9 4850253.3 4330583.3 3998571.9 3406725.6 2757138.1 2656091.1 2583914.7 2742702.8 2872620.3 3320113.9 3421160.8 3666560.6 3810913.3 4114054.2 4186230.6 4171795.3 3348984.4 91664013.9 Ai 0 0 0 0 0 0 0 0.0018709 0.00177144 0.00154436 0.0014914 0.00149776 0.00153321 0.00153091 0.00164904 0.00206218 0.00423895 0 0 0 0 0 0 0 f 0 0 0 0 0 0 0 0.11391295 0.1123679 0.10857952 0.10763645 0.10775099 0.10838296 0.10834227 0.11037434 0.11671922 0.14000112 0 0 0 0 0 0 0 S 0 0 0 0 0 0 0 9978.39688 59821.0096 92914.6668 117079.418 130788.558 132576.785 119211.641 97354.4092 68624.0356 9707.88102 0 0 0 0 0 0 0 838056.802 Total S for the wall for 12/16/05 720399.1618 744176.5154 720 kW (Isotropic) 744 kW (anisotropic) Table 12: Trombe Wall Analysis for December 16, 2005 (Continued) 52 APPENDIX C Miscellaneous Charts Figure 11: Evacuated Tube Collector Area v. Useful Collector Gain for October 4, 2005 53 Figure 12: Collector Efficiency v. Useful Collector Gain for October 4, 2005 54 Figure 13: Useful Collector Gain v. Heat Used by Load for October 4, 2005 55 Figure 14: Useful Collector Gain v. Heat Used by Load for November 2, 2005 56 Figure 15: Useful Collector Gain v. Heat Used by Load for December 16, 2005 57 Figure 16: Isotropic Model v. Anisotropic Model for October 4, 2005 58 Figure 17: Isotropic Model v. Anisotropic Model for November 2, 2005 59 Figure 18: Isotropic Model v. Anisotropic Model for December 16, 2005 60 Figure 19: Total, Beam, and Diffuse Hourly Radiation Components for October 4, 2005 61 Figure 20: Total, Beam, and Diffuse Radiation Components for November 2, 2005 62 Figure 21: Total, Beam, and Diffuse Radiation Components for December 16, 2005 63 Figure 22: Hourly Heat Loss from Building for October 4, 2005 64 Figure 23: Hourly Heat Loss from Building for November 2, 2005 65 Figure 24: Hourly Heat Loss from Building for December 16, 2005 66 APPENDIX D Charts Used for Determing Specific Data for Trombe Wall Analysis Figure 25: Transmittance of One, Two, Three, and Four Covers for Three Types of Glass 67 Figure 26: Effective Incidence Angle of Isotropic Diffuse Radiation and Isotropic Ground-Reflected Radiation on Sloped Surfaces 68 Figure 27: Typical (τα)/(τα)n Curves for One to Four Covers 69 BIBLIOGRAPHY Books: Boyle, Godfrey, 2004: Renewable Energy, Power for a Sustainable Future, Oxford University Press Inc., New York. Duffie, John A. & Beckman, William A., 2006: Solar Engineering of Thermal Processes, John Wiley & Sons, Inc., Hoboken, New Jersey. Modest, Michael F., 2003: Radiative Heat Transfer, Academic Press, San Diego, Ca. Internet Sites: National Solar Radiation Data Base, “USAF #745160-Travis Field AFB, CA (CLASS II)” <http://rredc.nrel.gov/solar/old_data/nsrdb/1991-2005/hourly/siteonthefly> Wunderground.com, Temperature Historical Data <http://www.wunderground.com/weatherstation/WXDailyHistory> BP Statistical Review of World Energy, BP. <http://www.bp.com/centres/energy2002/index.asp> Perlin, John, “Solar Evolution: The History of Solar Energy” <http://www.californiasolarcenter.org/history_solarthermal.html> Journal Articles: Kalogirou, Soteris A., 2004: “Solar Thermal Collectors and Applications”, Progress in Energy and Combustion Science