Corporate Services 24 March 2003 PART 1

advertisement
24th March 2003
Corporate Services
PART 1
(OPEN TO THE PUBLIC)
SUBJECT:
ENERGY MANAGEMENT ACTIVITY
DURING THE PERIOD DECEMBER 2002
TO FEBRUARY 2003.
REPORT OF: DIRECTOR OF CORPORATE SERVICES
FOR INFORMATION
A. REPORT SUMMARY
1.
PURPOSE OF REPORT:
To update members on matters arising since the January 2003 meeting of the Scrutiny Committee
and to report significant activities in the Energy Audit Group.
2.
RECOMMENDATIONS
Members are asked to note the level of savings being achieved and identified by the Group.
3.
ROUTING
Direct to council.
4.
IMPLICATIONS
4.1
Resources (Finance/Staffing):
The operation of an efficient Energy
Management Group contributes to considerable
Cost savings to the City Council. Competitive
Tendering for energy supply will minimise the
Strain on limited budgets.
4.2
Performance Review:
Not Applicable.
4.3
Environmental:
4.4
Equal Opportunities:
Reduction in the use of fuels, energy and water
will minimise harmful effects on the
environment.
Not Applicable.
4.5
Community Strategy:
Not Applicable.
4.6
Anti-Poverty Strategy:
Not Applicable
IF YOU HAVE ANY QUERIES
PLEASE CONTACT
Jim Gosney
793 3472
QUALITY CONTROL
BACKGROUND DOCUMENTS
Report Prepared by Jim Gosney 793 3472
Checked by
Donald Simpson 793 3290
Corporate Services (Finance), Salford Civic Centre, Chorley Road, Swinton. M27 5AW
REPORT DETAILS
5.
ENERGY MANAGEMENT
Activities undertaken during the period December 2002 to March 2003 include the
following: Progress of the energy audit plan
The levels of energy savings achieved.
Recently published White Paper on Energy
6.
PURCHASE OF PUBLIC LIGHTING ELECTRICITY
We are pleased to report that savings of £38,856 (9%) have been achieved for a two-year
period, through the competitive tendering of the public lighting electricity contract. This
contract also includes provision for 10% of the electricity to be supplied via “Green”
energy resources.
7.
ELECTRICITY PURCHASING TO COUNCIL PREMISES
The competitive tendering for 15 of the council’s large sites has now been completed.
Savings of approximately £8,353 will be achieved across these sites, for a one-year period.
We are also pleased to advise that three of these sites, Civic Centre, Turnpike House and
Clarendon Recreation Centre will be supplied on a “Green” energy contract.
We are also pleased to report that another 30 sites have been included on our small site
contract with Scottish Power. Savings across the sites will amount to £11,393.88.
8.
ENERGY SAVINGS ACHIEVED
Implemented Energy Savings, through purchasing, tariff analysis and water audits amount
to £151,287.41 for the year to date. Refunds for the amount of £183,168.65 have also been
achieved and cheques from the various suppliers received.
A number of energy audits at the following premises have also been conducted. The
summaries are attached in Appendix A.
Premise Name
Potential Savings (Annual)
St Philip’s R C Primary
Clarendon Recreation Centre
Pendlebury Recreation Centre
Broughton Pool
Eccles Recreation Centre
Worsley Pool
Irlam Pool
Total
£1,107
£5,500
£4,130
£9,785
£5,645
£13,870
£ 3,995
£44,032
CO2
83.1
62.1
101.7
83.9
210.6
56.1
597.5
9.
ENVIRONMENTAL BENEFITS OF ENERGY AUDIT ACTIVITIES
Premises
Seedley Primary School
Langworthy Rd Primary School
St Pauls C E Primary School
St Marks R C Primary School
Monton Green Primary School
Libraries
Christ The King RC Primary
St Gilberts RC Primary
Lower Kersal PS
Lark Hill Primary
St Lukes Primary
St Boniface RC Primary
Civic Centre
Canon Williamson High School
St Ambrose Barlow High School
Irlam Primary School
Broughton Resource Centre
Worsley Courthouse
Ingleside
St Philip’s RC Primary
Clarendon Recreation Centre
Pendlebury Recreation Centre
Broughton Pool
Eccles Recreation Centre
Worsley Pool
Irlam Pool
Date Potential
Report Savings
Issued (Annual)
01/03/01 £4,646
26/03/01 £2,940
01/06/01 £3,350
18/06/01 £3,395
27/06/01 £2,480
03/08/01 £23,629
10/08/01 £3,608
27/03/02 £1,843
22/05/02 £9,512
23/05/02 £5,365
23/05/02 £2,040
23/05/02 £1,360
14/08/02 £4,870
11/07/02 £3,665
11/07/02 £4,955
18/07/02 £1,905
09/09/02 £4,217
21/10/02 £11,104
09/12/02 £1,880
06/02/03 £1,107
07/02/03 £5,500
07/02/03 £4,130
07/02/03 £9,785
07/02/03 £5,645
19/02/03 £13,870
19/02/03 £3,995
£140,796
10
CO2 Reduction (Tonnes)
9.29
5.88
6.70
6.8
4.96
47.3
7.2
36.9
11.9
10.73
4.08
2.72
61.0
52.0
52.0
32.8
83.1
62.1
101.7
83.9
210.6
56.1
949.76
ENERGY WHITE PAPER
The energy white paper and what Government expects in future from local authorities, a
brief synopsis:
On the 24th February 2003 the DTI published the energy white paper “Our energy future creating a low carbon economy”. This addressed three challenges of energy policy:
environmental protection, to reduce climate change and emissions of greenhouse gases,
the decline of the UK's indigenous energy supplies and the future dependence on imported
energy also the need to update and adapt much of the UK's energy infrastructure to
accommodate more renewables and small-scale de-centralised power generation.
To address these challenges the new energy policy has four goals:
To put the UK on a path to cut carbon dioxide emissions by some 60% by about 2050, with
real progress by 2020; to maintain the reliability of energy supplies; to promote competitive
markets in the UK and beyond, helping to raise the rate of sustainable economic growth
and improve the UK's productivity; to ensure that every home is adequately and affordably
heated.
Government expect the delivery of the energy policy to be achieved through partnership
with stakeholders, including local authorities, regional chambers and regional development
agencies who make decisions that are vital for energy policy (for example on planning,
regeneration and development, procurement, housing, transport and sustainable
development). The future energy system will also require greater involvement from local
communities. From 2002/2003 local authorities will be required to benchmark their energy
use in operational properties and street lighting and will have to set local improvement
targets from 2003/2004.
Local authorities will have a growing role as community leaders: There will be a greater
emphasis on developing and implementing both local and regional strategic approaches to
delivering the Government's energy objectives. Regional targets for renewable and energy
efficiency will be negotiated and an action plan will be set out showing how regional
bodies and local authorities intend to help deliver objectives on energy through their
various roles and functions
The Government will consult shortly on detailed proposals for developing this strategic
approach. Regional assemblies will take responsibility for leading the work where they are
established. RDA's will be strongly encouraged to play a key role in delivery of initiatives
at regional level.
In the longer term the Government want to see local authorities and regional bodies take a
pro-active role. The Sustainable Energy Policy Network will have a remit to develop the
partnership with local and regional bodies on energy issues. In addition the Government
will: establish a new beacon councils theme on sustainable energy to promote innovative
local approaches on generation and demand-side measures; promote energy efficiency and
the roll-out of new technologies as areas in which local authorities can consider Local
Public Service Agreements; urge local authorities to give energy issues priority at a
strategic level through their Community Plans and Housing Strategies, consistent with the
new strategic approach to be developed at regional level; encourage local authorities to
take the lead, acting as catalysts for change, developing and facilitating cross-sectoral
partnerships and providing advice and encouragement; review existing guidance to
Energy Conservation Authorities on complying with the requirements of the Home Energy
Conservation Act; consider with the Local Government Association (LGA) whether at the
next review to include energy as a shared central-local priority; and consult on arrangement
to collect and make available data on the pattern of energy usage in local areas, to enable
local authorities and regional bodies to target activity more effectively. '
APPENDIX A
RECREATION CENTRE ENERGY AUDITS
At the request of the Education and Leisure Directorate, energy audits have been conducted at the recreation
centres/pools.
CLARENDON RECREATION CENTRE
Recommendation
£ Saving
KWh
or m3
CO2
Pay back
Years
£
Cost
tonne
1.
Pool lights – switch off on no occupancy
£120
3,200
1.4
0
Immediate
2.
Pool Water – increase evaporative loss claim
from 4% to 12%
£120
n/a
0
0
Immediate
3.
Fluorescent Lights – use T8 tubes in place of
T12 (when stock runs out)
£70
1,860
0.8
0
Immediate
4.
Coke and Lucozade canned drink machines –
time control
75
1,400
1.2
80
1.1
5.
Café Lighting – convert from tungsten spot to
compact fluorescent spot lamps
85
2,320
1.0
180
2.1
6.
Sunbed Room lights – add switch plate
presence sensors to both rooms
45
1,200
0.5
100
2.2
7.
Pool ventilation plant – replacement with
desiccant wheel plant to recover 90% of the
extract air heat.
4,985
280,000
78.2
55,000
11.0
Summary
1,400
£ Saving
of savings
CO2
Pay back
Years
£
Cost
tonne
No Cost - Immediate payback
£310
2.2
£0
0
Low Cost - Rapid payback investment
£205
2.7
£360
1.8
High Cost - Longer payback investment
£4,985
78.2
£55,000
11.0
Totals
£5,500
83.1
£55,360
10.1
Source for CO2 saving calculations:
Environmental reporting Guidelines for Company Reporting on Greenhouse Gas Emissions - DEFRA August 2001
PENDLEBURY RECREATION CENTRE
Recommendation
£ Saving
Main boiler and Pool ventilation plant – reset
operating times to save 11.5 hours per week
£465
9.
Pool Water – evaporative loss claim
£150
10.
1 off Canned drink vending machines – time
control
11.
12.
8.
KWh
or m3
CO2
Pay back
Years
£
Cost
tonne
7.1
0
Immediate
n/a
0
0
Immediate
£45
700
0.6
£40
0.9
Sports dry change and administration area
boiler plant – BMS control
£530
28,000
8.3
£2,200
4.2
Replacement boiler plant
£2,940
165,000
46.1
£65,000
22.1
Summary
1,200
23,400
£ Saving
CO2
of savings
Pay back
Years
£
Cost
tonne
No Cost - Immediate payback
£615
0
£0
0
Low Cost - Rapid payback investment
£575
8.9
£2,240
3.9
High Cost - Longer payback investment
£2,940
46.1
£65,000
22.1
Totals
£4,130
62.1
£67,240
16.3
Source for CO2 saving calculations:
Environmental reporting Guidelines for Company Reporting on Greenhouse Gas Emissions - DEFRA August 2001
BROUGHTON POOL
Recommendation
£ Saving
KWh
or m3
CO2
£
Cost
tonne
Pay back
Years
13.
Pool Water – evaporative loss claim
£195
n/a
0
0
Immediate
14.
2 off Canned drink vending machines – time
control
£90
1,400
31,400
1.2
£80
0.9
15.
Boiler plant – BMS control – reset of flow
temperature during quiescent periods
£2,720
160,000
42.8
£8,000
2.9
16.
Pool Hall – lighting replacement
£320
8,000
3.4
£4,000
12.5
17.
Pool hall extract air desiccant wheel heat
recovery plant
£6,460
380,000
102
£55,000
8.5
Summary
£ Saving
CO2
of savings
£
Cost
tonne
Pay back
Years
No Cost - Immediate payback
£195
0
£0
0
Low Cost - Rapid payback investment
£3,130
47.4
£12,080
3.9
High Cost - Longer payback investment
£6,460
101.7
£55,000
10.1
Totals
£9,785
101.7
£67,080
6.9
Source for CO2 saving calculations:
Environmental reporting Guidelines for Company Reporting on Greenhouse Gas Emissions - DEFRA August 2001
ECCLES RECREATION CENTRE
Recommendation
£ Saving
KWh
or m3
CO2
£
Cost
tonne
Pay back
Years
18.
Sports Hall – reduce the temperature setting
from 18°C to 16°C
£460
28,900
7.1
0
Immediate
19.
Sports Hall – reset the time control for weekend
use saving 4 hours per week
£185
9,600
2.7
0
Immediate
20.
Pool Water – evaporative loss claim
£150
n/a
0
0
Immediate
21.
5 off Canned drink vending machines – time
control
£220
3,500
3.0
£200
0.9
22.
Boilers – BMS control
£510
32,100
7.9
£1,200
2.4
23.
Sports Hall – lighting control – reinstate
£190
4,800
2.1
£600
3.2
24.
Male change – lighting control
£60
1,450
0.6
£220
3.7
25.
Pool hall extract air desiccant wheel heat
recovery plant
£3,870
245,000
60.5
£49,600
12.8
Summary
£ Saving
of savings
CO2
£
Cost
tonne
Pay back
Years
No Cost - Immediate payback
£795
9.8
£0
0
Low Cost - Rapid payback investment
£980
13.6
£2,220
2.3
High Cost - Longer payback investment
£3,870
60.5
£49,600
12.8
Totals
£5,645
83.9
£51,820
9.2
Source for CO2 saving calculations:
Environmental reporting Guidelines for Company Reporting on Greenhouse Gas Emissions - DEFRA August 2001
WORSLEY POOL
Recommendation
£ Saving
KWh
or m3
CO2
£
Cost
tonne
Pay back
Years
26.
Water – claim for pool surface evaporative
loses from 4% to 12%
£300
0
0
0
Immediate
27.
Fitness Suite – use the fresh air ventilation fans
instead of the air conditioners
£415
3,600
5.2
0
Immediate
28.
Vending machines – time control canned drink
machines
£90
1,400
1.2
£80
0.9
29.
Main entrance doors – adjust closers, fit and
draught strip
£130
7,200
2.0
£350
2.7
30.
Male and Female main pool change – lighting
presence sensors
£190
4,800
2.1
£700
3.7
31.
Main pool ventilation plant replacement with a
desiccant wheel plant
£6,765
380,000
17.7
£80,000
11.8
32.
Boiler No. 2 – replacement plus controls
£3,845
216,000
105
£68,000
17.7
33.
Learner pool ventilation – new plant
£2,135
120,000
33.5
£75,000
35.1
Summary
£ Saving
of savings
CO2
£
Cost
tonne
Pay back
Years
No Cost - Immediate payback
£715
5.2
0
0
Low Cost - Rapid payback investment
£410
5.3
£1,130
2.8
High Cost - Longer payback investment
£12,475
200.1
£223,000
17.5
Totals
£13,870
210.6
£224,130
16.2
Source for CO2 saving calculations:
Environmental reporting Guidelines for Company Reporting on Greenhouse Gas Emissions - DEFRA August 2001
IRLAM POOL
Recommendation
£ Saving
KWh
or m3
CO2
Pay back
Years
£
Cost
tonne
34.
Change AHU – adjust times for early weekend
closing at 15:30.
£365
22,000
5.7
0
immediate
35.
Water – claim for pool surface evaporative
loses from 4% to 12%
£120
0
0
0
Immediate
36.
Vending machines – time control canned drink
machines
£90
1,400
1.2
£80
0.9
37.
Main entrance doors – adjust closers inner and
outer
£140
8,400
2.3
£350
2.5
38.
Main pool – recovery of heat from 50% of the
main pool air
£2,425
146,000
38.0
£9,000
3.7
39.
Main pool lighting – change to SONT
£855
21,500
9.2
£8,000
9.4
Summary
£ Saving
CO2
of savings
Pay back
Years
£
Cost
tonne
No Cost - Immediate payback
£485
0
0
0
Low Cost - Rapid payback investment
£230
3.4
£430
1.9
High Cost - Longer payback investment
£3,280
47.0
£17,000
5.2
Totals
£3,995
56.1
£17,430
4.4
Source for CO2 saving calculations:
Environmental reporting Guidelines for Company Reporting on Greenhouse Gas Emissions - DEFRA August 2001
ST. PHILIP’S R C PRIMARY SCHOOL
RECOMMENDATION
Saving
Saving
M3
£
Installation
Cost
Payback Period
1.
Installation of push taps (retro
fit)
553m3
£713
£684
11 months
2.
Cistern Dams
92m3
£118
£116
11 months
3.
Urinal Control
214m3
£276
£145
6 months
Total
859m3
£1,107
£945
Download