University of Manitoba PICTOGRAM EXIT SIGN Section 16519 Req. # 1.1 Page 1 RELATED WORK .1 Basic Electrical Materials and Methods .2 Fastenings and Supports .3 Outlet Boxes Section 16050 Section 16126 Section 16134 1.2 SYSTEM DESCRIPTION .1 Pictogram Exit sign shall identify exits and means of egress. 1.3 SUBMITTALS .1 Submit shop drawings in accordance with Section 16050. 2.1 PICTOGRAM EXIT SIGNS .1 Housing: steel frame and solid back plate .3 Illumination: white light emitting diodes (LED), maximum consumption of 2.5W. .4 Emergency: connection for DC emergency power. .5 Mounting: suitable for recessed, wall, end-to-wall, or ceiling mounting, as indicated. .6 Face plates: single or double face, as indicated. .7 Supplied standard with two (2) pictogram films per face, for direction selection. .7 Equipment shall operate with AC input voltage of 120V or 347V. .8 Manufacturers: .1 Lumacell: LA Series 3.1 INSTALLATION .1 Pictogram exit sign shall be NBC2010 compliant. .2 Install pictogram exit signs as indicated, shall meet or exceed the C22.2 #141-10 standard. .3 Connect pictogram exit signs to pictogram exit sign circuits as indicated. .4 Connect emergency connection to emergency circuits as indicated. .5 Ensure that pictogram exit sign circuit breaker is locked in on position. .6 Wiring for pictogram exit sign circuits shall be installed in a separate conduit system. Date revised November 30, 2012