Carry out routine inspection and servicing on 11kV and 33kV... mounted re-closer circuit breakers

advertisement
14339 version 3
Page 1 of 6
Carry out routine inspection and servicing on 11kV and 33kV pole
mounted re-closer circuit breakers
Level
3
Credits
3
Purpose
People credited with this unit standard are able to: prepare for inspection,
testing and servicing on 11 kV and 33kV pole mounted re-closer circuit
breakers; make the re-closer circuit breakers safe for work; carry out routine
inspections and diagnostic tests; carry out servicing; perform function tests
and pre-service checks; and complete documentation.
Subfield
Electricity Supply
Domain
Electricity Supply - Power System Maintenance
Status
Registered
Status date
27 April 1998
Date version published
20 June 2008
Planned review date
31 December 2009
Entry information
Prerequisites: Unit 14287, Use and maintain test
instruments used in the high voltage electrical industry;
Unit 14700, Apply and remove safety measures in an
electricity supply environment; Unit 12296 Apply earths
to and remove earths from electricity conductors, plant
and equipment in electrical switch yards and
substations; or demonstrate equivalent knowledge and
skills.
Core electrical theory is essential knowledge
underpinning the performances required by this unit
standard.
Accreditation
Evaluation of documentation and visit by NZQA and
industry.
Standard setting body (SSB)
Electricity Supply Industry Training Organisation
Accreditation and Moderation Action Plan (AMAP) reference
0120
This AMAP can be accessed at http://www.nzqa.govt.nz/framework/search/index.do.
 New Zealand Qualifications Authority 2016
14339 version 3
Page 2 of 6
Special notes
1
This unit standard can be assessed against in a workplace environment, or in a
training or educational environment if simulated equipment response and examples
are able to be provided, or in a combination of both environments.
2
Performance and work practices in relation to the elements and performance criteria
must comply with all current legislation, especially the Electricity Act 1992, and any
regulations and codes of practice recognised under that statute; the Health and
Safety in Employment Act 1992; and the Resource Management Act 1991.
Electricity supply industry codes of practice and documented industry procedures
include the Safety Manual – Electricity Industry (SM-EI) (2004) Wellington: Electricity
Engineers’ Association. A full list of current legislation and industry codes is
available from the Electricity Supply Industry Training Organisation, PO Box 1245,
Hamilton.
3
The phrase in accordance with industry requirements is implicit in all elements and
performance criteria in this unit standard.
4
‘Industry requirements’ include all industry and workplace documented policies,
procedures, specifications, business and quality management relevant to the
workplace where assessment is carried out.
5
All work practices shall meet documented enterprise maintenance standards,
including the quality management requirements, and the documentation of activities,
events, and decisions.
6
The range of this unit standard is limited to carrying out diagnostic testing and
applying preventative maintenance and replacement repairs, where necessary, on
high voltage pole mounted re-closer circuit breakers, and is normally done at field
locations.
7
The following terms and abbreviations relate to this unit standard:
SF6 = Sulphur hexafloride gas.
Elements and performance criteria
Element 1
Prepare for inspection, testing and servicing on 11kV and 33kV pole mounted re-closer
circuit breakers.
Performance criteria
1.1
The scope of work and equipment to be serviced is identified from client
requirements.
Range
may include but is not limited to associated ‘check and/or
inspection lists’, procedures and client required diagnostic tests
and servicing for – pole mounted re-closer circuit breakers,
vacuum break type, SF6 bottle type, oil breaker type, with high
voltage source powered mechanisms.
 New Zealand Qualifications Authority 2016
14339 version 3
Page 3 of 6
1.2
Personnel and equipment are resourced for the required work.
Range
1.3
may include but is not limited to – tools, spares, materials,
‘inspection sheets’, procedure sheets.
The inspection diagnostic testing and servicing requirements are interpreted
and analysed for determining the performance and quality standards required.
Range
may include but is not limited to – manufacturer’s guidelines, client
maintenance standards or enterprise guidelines.
Element 2
Make the re-closer circuit breakers safe for work.
Performance criteria
2.1
The required access permit, or approved equivalent, is received, checked, and
signed.
Range
2.2
Additional isolation from other energy sources on the circuit breaker is applied.
Range
2.3
may include but is not limited releasing or spragging spring closing
energy systems, isolating actuating trip coils.
The work party is fully briefed on the equipment to be worked on, work to be
done, safe working zone and safety features in place, and has signed the
access permit or its approved equivalent. All communication with the work
party is clear and unambiguous.
Range
2.4
includes a careful check of the isolations to ensure the access
permit or recognised equivalent provides a safe work environment.
may include but is not limited to the ability to resolve any concerns
the work party may have over the isolations and the delineation of
the safe work area.
Safety measures are available and prepared to protect the environment and
personnel.
Range
may include but is not limited to – oil spill clean up, protective
clothing.
 New Zealand Qualifications Authority 2016
14339 version 3
Page 4 of 6
Element 3
Carry out routine inspections and diagnostic tests.
Performance criteria
3.1
The re-closer circuit breaker defect history and operational records are
scrutinised and incidents indicating service needs noted for attention during the
routine servicing.
Range
3.2
The inspections are carried out and identify any damage or defects.
Range
3.3
may include but is not limited to – oil leaks, signs of overheating.
The diagnostic tests are carried out and the results analysed for interpreting the
servicing required.
Range
3.4
may include but is not limited to – serious fault interruptions,
malfunctions, reported problems.
may include but is not limited to – oil break down test, insulation
resistance test, contact resistance tests.
The results of the diagnostic tests are recorded to meet the client requirements.
Range
may include but is not limited to – completing enterprise check
lists, electronic data records, client reports.
Element 4
Carry out servicing.
Performance criteria
4.1
Oil replacement is completed consistent with enterprise or client requirements.
Range
4.2
The major or minor invasive servicing is carried out following enterprise or client
procedures.
Range
4.3
may include but is not limited to – testing of removed oil, tests on
replaced oil.
may include but is not limited to – repair or replacement of worn
parts, contact tip replacement, cleaning, lubrication, SF6 gas
bottles or vacuum interrupters replacement.
The re-assembly of the circuit breaker is carried out in the approved manner
provided by the maker.
Range
may include but is not limited to – all components being
assembled in the correct order, with proper fit and secured in the
specified way, oil replaced into circuit breaker to correct level.
 New Zealand Qualifications Authority 2016
14339 version 3
Page 5 of 6
Element 5
Perform function tests and pre-service checks.
Performance criteria
5.1
Work party is advised of a trial operation about to start.
5.2
All services and necessary control features are reinstated and approval
obtained for function tests.
Range
5.3
All the function tests required are completed without malfunction and to
standard.
Range
5.4
may include but is not limited to – checking all tools removed, all
connections tight re-closer returned to service.
All equipment worked on is inspected and set for return to service.
Range
5.6
may include but is not limited to – oil break down tests, insulation
resistance test, contact resistance tests.
All the maintenance tools and facilities have been removed and the circuit
breaker is left in the ‘ready-for-service’ condition.
Range
5.5
may include but is not limited to – control circuits, mechanism,
power and indication.
may include but is not limited to – confirming all equipment and the
work party are clear, all operational equipment which has been
worked on is now set ready for service.
Return of access permit, or its equivalent, is confirmed.
Range
may include but is not limited to – confirming all members of the
work party have signed off, the equipment is returned to service
without incident.
Element 6
Complete documentation.
Performance criteria
6.1
The ‘as found’ and ‘as left’ conditions are recorded in the plant history.
Range
may include but is not limited to – analysis and reporting of any
defects, correct completion of the plant and defect history
including replacement spare fitted.
 New Zealand Qualifications Authority 2016
14339 version 3
Page 6 of 6
6.2
The equipment condition status is recorded.
Range
6.3
may include but is not limited to – operation counter noted,
number of trial operations noted, pressures and auxiliary service
quantified.
The routine and inspection service records are completed to meet the client
requirements.
Range
may include but is not limited to written records or electronic data
reporting.
Please note
Providers must be accredited by NZQA, or an inter-institutional body with delegated
authority for quality assurance, before they can report credits from assessment against
unit standards or deliver courses of study leading to that assessment.
Industry Training Organisations must be accredited by NZQA before they can register
credits from assessment against unit standards.
Accredited providers and Industry Training Organisations assessing against unit standards
must engage with the moderation system that applies to those standards.
Accreditation requirements and an outline of the moderation system that applies to this
standard are outlined in the Accreditation and Moderation Action Plan (AMAP). The
AMAP also includes useful information about special requirements for organisations
wishing to develop education and training programmes, such as minimum qualifications for
tutors and assessors, and special resource requirements.
Comments on this unit standard
Please contact the Electricity Supply Industry Training Organisation info@esito.org.nz if
you wish to suggest changes to the content of this unit standard.
 New Zealand Qualifications Authority 2016