IGS-M-RS-401(1) July 2014 Approved IGS 10 000 !" - . /$ /$ % &'( )* + , . 012 Specification for Measuring/ Reducing and Measuring Cabinet Type Stations with Max. Capacity up to 10,000 SCM/H . Fax:(9821)-8131-5679 3345 67894: ;<3=9>?;@A9 BC;A=3 D>E4F@G: 6HI? JC4KL 6M NOP ;<3=9>?;@A9Q9 D3;R@A9 S94M http://igs.nigc.ir igs@nigc.ir N.I.G.C. July 2014 IGS-M-RS-401(1) FOREWORD This standard is intended to be mainly used by NIGC and contractors, and has been prepared based on interpretation of recognized standards, technical documents, knowledge, backgrounds and experiences in natural gas industry at national and international levels. Iranian Gas Standards (IGS) are prepared, reviewed and amended by technical standard committees within NIGC Standardization division and submitted to the NIGC's "STANDARDS COUNCIL" for approval. IGS Standards are subject to revision, amendment or withdrawal, if required. Thus the latest edition of IGS shall be checked/inquired by NIGC employees and contractors. This standard must not be modified or altered by NIGC employees or its contractors. Any deviation from normative references and / or well-known manufacturer’s specifications must be reported to Standardization division. The technical standard committee welcomes comments and feedbacks about this standard, and may revise this document accordingly based on the received feedbacks. GENERAL DEFINITIONS: Throughout this standard the following definitions, where applicable, should be followed: 1- "STANDARDIZATION DIV." is organized to deal with all aspects of industry standards in NIGC. Therefore, all enquiries for clarification or amendments are requested to be directed to mentioned division. 2- "COMPANY": refers to National Iranian Gas Company (NIGC). 3- "SUPPLIER": refers to a firm who will supply the service, equipment or material to NIGC whether as the prime producer or manufacturer or a trading firm. 4- "SHALL ": is used where a provision is mandatory. 5- "SHOULD": is used where a provision is advised only. 6- "MAY": is used where a provision is completely discretionary. ------------------------------------Website: http://igs.nigc.ir E-mail: igs@nigc.ir I July 2014 )IGS-M-RS-401(1 N.I.G.C. اﻣﻮر ﺗﺪوﻳﻦ اﺳﺘﺎﻧﺪاردﻫﺎ ﭘﻴﺸﮕﻔﺘﺎر -1اﻳﻦ اﺳﺘﺎﻧﺪارد /دﺳﺘﻮراﻟﻌﻤﻞ ﺑﻪ ﻣﻨﻈﻮر اﺳﺘﻔﺎده ﺧﺼﻮﺻﻲ در ﺷﺮﻛﺖ ﻣﻠﻲ ﮔﺎز اﻳﺮان و ﺷﺮﻛﺘﻬﺎي ﻓﺮﻋﻲ واﺑﺴﺘﻪ ﺗﻬﻴﻪ ﺷﺪه اﺳﺖ . -2ﺷﺮﻛﺖ ﻣﻠﻲ ﮔﺎز اﻳﺮان در ﻣﻮرد ﻧﻴﺎزﻫﺎي ﻋﻤﻮﻣﻲ از اﺳﺘﺎﻧﺪاردﻫﺎي وزارت ﻧﻔﺖ ) (IPSو در ﻣﻮرد ﻧﻴﺎزﻫﺎي اﺧﺘﺼﺎﺻﻲ از اﺳﺘﺎﻧﺪاردﻫﺎي اﺧﺘﺼﺎﺻﻲ ﺧﻮد ) (IGSاﺳﺘﻔﺎده ﻣﻲ ﻧﻤﺎﻳﺪ. -3اﺳــــﺘﺎﻧﺪاردﻫﺎي ﺷــــﺮﻛﺖ ﻣﻠــــﻲ ﮔــــﺎزاﻳﺮان ) (IGSﺗﻮﺳــــﻂ ﻛﻤﻴﺘــــﻪﻫــــﺎي ﺗﺨﺼﺼــــﻲ اﺳــــﺘﺎﻧﺪارد ﻣﺘﺸــــﻜﻞ از ﻛﺎرﺷﻨﺎﺳــــﺎن ﺑﺨﺶ ﻫﺎي ﻣﺨﺘﻠﻒ و ﻳﺎ ﻣﺸﺎور ﺗﻬﻴﻪ ﻣﻲ ﺷﻮد و ﺗﻮﺳﻂ ﺷﻮراي اﺳﺘﺎﻧﺪارد ) ﻣﻨﺘﺨﺐ ﻫﻴﺌﺖ ﻣﺪﻳﺮه ﺷﺮﻛﺖ ﻣﻠﻲ ﮔـﺎز اﻳـﺮان ( ﺑـﻪ ﺗﺼـﻮﻳﺐ ﻣﻲ رﺳﻨﺪ. -4در ﺗﻨﻈﻴﻢ ﻣﺘﻦ اﺳﺘﺎﻧﺪاردﻫﺎي ) (IGSاز ﻛﻠﻴﻪ ﻣﻨﺎﺑﻊ ﺷﻨﺎﺧﺘﻪ ﺷﺪه اﺳﺘﺎﻧﺪاردي ،اﻃﻼﻋﺎت ﻓﻨﻲ – ﺗﺨﺼﺼﻲ ﻣﺮﺑﻮط ﺑـﻪ ﺻـﻨﺎﻳﻊ ﮔـﺎز دﻧﻴـﺎ، ﻣﺸﺨﺼﺎت ﻓﻨﻲ ﺗﻮﻟﻴﺪات ﺳﺎزﻧﺪﮔﺎن ﻣﻌﺘﺒﺮ ﺟﻬﺎﻧﻲ و ﻧﻴﺰ از ﻧﺘﻴﺠﻪ ﺗﺤﻘﻴﻘﺎت و ﺗﺠﺮﺑﻴﺎت ﻛﺎرﺷﻨﺎﺳﺎن و ﻣﺘﺨﺼﺼﺎن داﺧﻠﻲ ﺑﺮﺣﺴﺐ ﻣـﻮرد اﺳﺘﻔﺎده ﻣﻲ ﺷﻮد .ﻫﻤﭽﻨﻴﻦ ﺑﻪ ﻣﻨﻈﻮر اﺳﺘﻔﺎده ازﻫﺮ ﭼﻪ ﺑﻴﺸﺘﺮ از ﺗﻮﻟﻴﺪات داﺧﻠﻲ ﻗﺎﺑﻠﻴﺖ ﻫﺎي ﺳﺎزﻧﺪﮔﺎن داﺧﻠﻲ ﻧﻴﺰ ﻣـﻮرد ﺗﻮﺟـﻪ ﻗـﺮار ﻣﻲ ﮔﻴﺮد. -5اﺳـــﺘﺎﻧﺪاردﻫﺎ از ﻃﺮﻳـــﻖ ﭘﺎﻳﮕـــﺎه اﻳﻨﺘﺮﻧﺘـــﻲ ﺷـــﺮﻛﺖ * و ﻳـــﺎ ﻟـــﻮح ﻓﺸـــﺮده ) (CDدر اﺧﺘﻴـــﺎر واﺣـــﺪﻫﺎ و ﻛـــﺎرﺑﺮان ﻗـــﺮار ﻣﻲ ﮔﻴﺮد. -6اﺳﺘﺎﻧﺪاردﻫﺎ ﺑﻪ ﻃﻮر ﻣﺘﻮﺳﻂ ﻫﺮ 5ﺳﺎل ﻳﻜﺒﺎر و ﻳﺎ در ﺻﻮرت ﺿﺮورت زودﺗﺮ ،ﻣﻮرد ﺑﺎزﻧﮕﺮي و ﺑﺮوز رﺳﺎﻧﻲ ﻗﺮار ﻣﻴﮕﻴﺮﻧـﺪ .ﺑﻨـﺎﺑﺮاﻳﻦ ﻛﺎرﺑﺮان ﺑﺎﻳﺪ ﻫﻤﻴﺸﻪ آﺧﺮﻳﻦ ﻧﮕﺎرش را ﻣﻮرد اﺳﺘﻔﺎده ﻗﺮار دﻫﻨﺪ. -7ﻫﺮ ﮔﻮﻧﻪ ﻧﻈﺮ و ﻳﺎ ﭘﻴﺸﻨﻬﺎد اﺻﻼح در ﻣﻮرد اﺳﺘﺎﻧﺪاردﻫﺎ ﻣﻮرد اﺳﺘﻘﺒﺎل و ﺑﺮرﺳﻲ ﻗﺮار ﺧﻮاﻫـﺪ ﮔﺮﻓـﺖ و در ﺻـﻮرت ﺗﺎﺋﻴـﺪ ،اﺳـﺘﺎﻧﺪارد ﻣﺮوﺑﻮﻃﻪ ﻧﻴﺰ ﻣﻮرد ﺗﺠﺪﻳﺪ ﻧﻈﺮ ﻗﺮار ﺧﻮاﻫﺪ ﮔﺮﻓﺖ. ﺗﻌﺎرﻳﻒ ﻋﻤﻮﻣﻲ در ﻣﺘﻦ اﺳﺘﺎﻧﺪاردﻫﺎي ) (IGSاز ﺗﻌﺎرﻳﻒ و اﺻﻄﻼﺣﺎت زﻳﺮ اﺳﺘﻔﺎده ﻣﻲ ﺷﻮد . " -1ﺷﺮﻛﺖ" ) : (COMPANYﻣﻨﻈﻮر از ﺷﺮﻛﺖ " ﺷﺮﻛﺖ ﻣﻠﻲ ﮔﺎز اﻳﺮان " و ﻳﺎ ﺷﺮﻛﺘﻬﺎي ﻓﺮﻋﻲ واﺑﺴﺘﻪ ﻣﻲ ﺑﺎﺷﺪ. " -2ﻓﺮوﺷﻨﺪه " ) : (PUPPLIER / VENDORﺑﻪ ﻓﺮد ﻳﺎ ﻣﻮﺳﺴﻪ اي اﻃﻼق ﻣﻲ ﮔﺮدد ﻛﻪ ﺗﻌﻬﺪي را ﻧﺴـﺒﺖ ﺑـﻪ ﺷـﺮﻛﺖ ﺗﻘﺒـﻞ ﻧﻤـﻮده اﺳﺖ . " -3ﺧﺮﻳـــﺪار" ) : (PURCHASERﻣﻨﻈـــﻮر از ﺧﺮﻳـــﺪار " ﺷـــﺮﻛﺖ ﻣﻠـــﻲ ﮔـــﺎز اﻳـــﺮان" و ﻳـــﺎ ﺷـــﺮﻛﺘﻬﺎي ﻓﺮﻋـــﻲ واﺑﺴـــﺘﻪ ﻣﻲ ﺑﺎﺷﺪ. : "SHALL" -4در ﻣﻮاردي ﺑﻜﺎرﺑﺮده ﻣﻲ ﺷﻮد ﻛﻪ اﻧﺠﺎم ﺧﻮاﺳﺘﻪ ﻣﻮرد ﻧﻈﺮ اﺟﺒﺎري اﺳﺖ. : "SHOULD" -5در ﻣﻮاردي ﺑﻜﺎرﺑﺮده ﻣﻲ ﺷﻮد ﻛﻪ اﻧﺠﺎم ﺧﻮاﺳﺘﻪ ﻣﻮرد ﻧﻈﺮ ﺗﺮﺟﻴﺤﻲ و در ﻋﻴﻦ ﺣﺎل اﺧﺘﻴﺎري اﺳﺖ . : "MAY" -6در ﻣﻮاردي ﺑﻜﺎر ﺑﺮده ﻣﻲﺷﻮد ﻛﻪ اﻧﺠﺎم ﻛﺎر ﺑﻪ ﺷﻜﻞ ﻣﻮرد ﺑﺤﺚ ﻧﻴﺰ ﻗﺎﺑﻞ ﻗﺒﻮل ﻣﻲ ﺑﺎﺷﺪ. ) ،(nigcigs@nigc.irآدرس اﻟﻜﺘﺮوﻧﻴﻜﻲ) *(http://igs.nigc.irآدرس اﻳﻨﺘﺮﻧﺘﻲ II N.I.G.C. July 2014 IGS-M-RS-401(1) CONTENTS PAGE 1. SCOPE 2 2. REFERENCES 2 3. DEFINITIONS 4 4. REQUIREMENTS 9 4.1 Design and Service Conditions 9 4.2 Materials 15 5. INSPECTION, TESTS AND CERTIFICATIONS 15 5.1 Prior to Fabrication 15 5.2 Inspection Documents 16 5.3 Tests 16 5.4 Inspection and Certificates 17 6. PAINTING 17 7. MARKING 18 8. PACKING AND PACKAGING 18 9. DOCUMENTATION 18 9.1 With Technical Quotation 18 9.2 After Receipt of Order 19 10.GUARANTEE 19 APPENDIXES APPENDIX A – ﻣﺼﻮﺑﻪ ﺷﻮراي ﻋﺎﻟﻲ ﻣﺤﻴﻂ زﻳﺴﺖ 21 APPENDIX B – Data Sheet 22 APPENDIX C – Typical Arrangement of Cabinet Type Station 37 1 N.I.G.C. July 2014 IGS-M-RS-401(1) 1. SCOPE This specification together with the Appendices there to covers the minimum requirements for design, material, construction, testing, inspection, painting, marking, packing and packaging of cabinet type stations to be used for measuring, pressure reducing and measuring of natural gas (as per composition in (IGS-M-CH-033)) with inlet working pressure of (10-17.2) bar (150-250) psig and maximum capacity of 10,000 scm/h. For specific requirements see Appendix B (data sheet). In case of any exception to this specification, it shall be clearly stated on the technical quotation submitted by supplier. In this specification, cabinet type station will be referred as station. 2. REFERENCES Throughout this standard specification the following standards, codes and reports are referred to. The editions of these standards and codes that are in effect at the time of publication of this standard specification shall, to the extent specified herein, form a part of this standard specification. The applicability of changes in standards and codes that occur after the date of this standard specification shall be mutually agreed upon by the purchaser and supplier and/or manufacturer. 2.1 Normative References ANSI/ASME B1.20.1 "Pipe Threads, General Purpose (inch)" API 5L "Standard Specification for Line Pipe" API RP 500 "Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I , Division 1 and Division 2 First Edition" API 1104 "Welding of Pipelines and Related Facilities" ASTM A 53 "Standard Specification for Pipe, Steel, Block and Hot-Dipped, Zinc-Coated, Welded and Seamless" ASTM A 105/A 105M "Standard Specification for Carbon Steel Forgings for Piping Applications" ASTM A 106/A 106 M "Standard Specification for Seamless Carbon Steel Pipe for HighTemperature Service" ASTM A 193 "Standard Specification for Alloy-Steel and Stainless Steel Bolting Materials for High-Temperature Service" ASTM A 144 "Standard Specification for Carbon and Alloy Steel Nuts for Bolts for High Pressure or High Temperature Service, or both" ASTM A 216/ A126 M "Standard Specification for Steel Casting, Carbon, Suitable for Fusion Welding, for High Temperature Service" 2 N.I.G.C. July 2014 IGS-M-RS-401(1) ASTM A 283 "Standard Specification for Low and Intermediate Tensile Strength Carbon Steel Plates" ASTM A 403 "Standard Specification for Wrought Austenitic Stainless Steel Piping, Fittings" ASTM B 117 "Standard Practice for Operating Salt Spray (FOG) Apparatus" ANSI B16.5 "Pipe Flanges and Flanged Fittings NPS l/2 Through NPS 24" ANSI B31.8 "Gas Transmission and Distribution Piping Systems" BS 381 C " Specification for Colures for Identification, Coding and Special Purposes" BS 4368 "Metallic Tube Connectors for Fluid Power and General Use Split Collect Compression Fittings" BS 4800 "Paint Colures for Building Purpose" BS EN 1776 "Gas Supply – Natural Gas Measuring Stations - Functional Requirements" BS EN 12186 " Gas Supply Systems – Gas Pressure Regulating Stations for Transmission and Distribution - Functional Requirements" EN 837-1 "Pressure Gauges - Bourdon Tube, Pressure Gauge - Dimensions, Metrology, Requirements and Testing" IGS-M-CH-033(0) "Specification for pipeline quality natural gas" IGS-CH-041(0) "Specification for Painting Procedure for Gas Pressure Reducing Stations" IGS-0-CH- 042 (2006) “Painting-procedure for Gas Industry Installation” IGS-IN-302(0) "Specification for Relief Valves" IGS-M-1N-102 "Specification for Turbine Meters" IGS-M-IN-202(0) "Specification for Gas Pressure Regulators for Nominal Inlet Pressure.5 to 100 bar (72-1450 psig)" IGS-M-PL-002-1(2) "Specification for Plug Valves Size 2" to 24" Part (1)" IGS-M-PL-010-1(1) "Specification for Ball Valves Class Rating: 150 Part (1)" IGS-PL-003(2) "Specification for Needle and Gauge Valves" IGS-PL-005 (1) "Specification for Sensing Tube Lines" 3 N.I.G.C. July 2014 IGS-M-RS-401(1) IGS- PL-006(1) "Specification for Insulating Joints" IGS-PL-005(1) "Specification for Gaskets" IGS-PL-018(0) "Specification for Welding Consumables" IGS-PL-022-1(0) "Specification for Butt Welding Ends, Carbon Steel Fitting Size: 1/2 in. to 12 in. Part (1)" IGS-PM-105(0) "Specification for Dry Gas Filter" ISO 9000 (2005) "Quality Management and Quality Assurance Standards Guidelines for Selection and Use" ASTM A 193 grade B7 (Bolts) and ASTM A194 grade2H (Nuts) pr EN 50154 "Electrical Installations in Explosive Gas Atmospheres (other than Mines)” EN 60079-10 “Electrical Apparatus for Explosive Gas Atmospheres - Part10 : Classification of Hazardous Areas.(IEC 60079-10 :1995) " IPS-G-GN-210 ”Packing and Packaging” IGS-M-PM-111 "Dry Gas Filter Cartridge" 3. DEFINITIONS For the purpose of this standard, the following definitions apply: 3.1 Measuring Station An installation comprising all the equipment including the inlet and outlet pipework as far as the isolating valves and any structure within which the equipment is housed, used for gas measurement in custody transfer. 3.2 Pressure Reducing Station The station consists of equipment installed for the purpose of automatically reducing and regulating the pressure in the downstream pipeline or main to which it is connected. Included are piping and auxiliary devices such as valves, control instruments, control lines, the enclosure, and ventilation equipment. 3.3 Pressure Reducing and Measuring Station The combination of a pressure reducing station and measuring station. It consists of equipment installed for the purpose of automatically reducing and regulating the pressure in the downstream pipeline or main to which it is connected and also measuring it. 3.4 Pressure The gauge pressure of the fluid inside the system, measured in static conditions. 4 N.I.G.C. July 2014 IGS-M-RS-401(1) 3.5 Design Pressure (DP) Design pressure is the maximum pressure permitted by code, as determined by the design procedures applicable to the material and locations involved. 3.6 Operating Pressure (OP) The pressure which occurs within a system under normal operating conditions. 3.7 Maximum Operating Pressure (MOP) The maximum pressure at which a system can be operated continuously under normal operating conditions. Note: Normal operating conditions are: no fault in any device or stream. 3.8 Maximum Incidental Pressure (MIP) The maximum pressure which a system can experience during a short time, limited by the safety devices. 3.9 Temporary Operating Pressure (TOP) The pressure at which a system can be operated temporarily under control of regulating devices. 3.10 Maximum Operating Temperature (Tmax ) The maximum temperature at which a system can be operated continuously under normal conditions. Note: Normal conditions are: no fault in any device or stream. 3.11 Minimum Operating Temperature (Tmin ) The minimum temperature at which a system can be operated. 3.12 Measuring System Complete set of measuring instruments and other equipment assembled to carry out specified measurements. 3.13 Measuring Instrument Device intended to be used for measurements, alone or in conjunction with supplementary device(s). Measuring instruments are e.g. gas meter, pressure sensor, density sensor. 3.14 Instrumentation Any system or combination of equipment for measurement and control. 3.15 Accuracy of Measurement Closeness of the agreement between the result of a measurement and a true value of the measurand. 3.16 Maximum Permissible Error (of a Measuring Instrument) Extreme values of an error permitted by specifications, regulations, etc. for a given measuring instrument. 5 N.I.G.C. July 2014 IGS-M-RS-401(1) 3.17 Flow Computer Flow calculating device which indicates the flowrate as integrated volume or mass or energy base conditions. 3.18 Conversion Device A device consisting of a flow computer and sensors used for converting the volume (flowrate) at operating conditions into a volume (flowrate) at standard conditions or to mass (flowrate) or to energy (flowrate) at base conditions, based on either pressure, temperature and gas composition, or on density, or on calorific value. 3.19 Installation Effect Any difference in performance of a measuring instrument or of the measuring system between the calibration under reference and operating conditions. 3.20 Systematic Error Mean that would result from an infinite number of measurements of the same measurand carried out under repeatability conditions minus a true value of the measurand. 3.21 Fail - Safe Characteristic of a device to go to a safe operating condition when a failure occurs. 3.22 Overpressure Protection Overpressure protection is provided by a device or equipment installed for the purpose of preventing the pressure in a pressure vessel, a pipeline, or a distribution system from exceeding a predetermined value. This protection may be obtained by installing a pressure relief device or a pressure shut off device. 3.23 Pressure Relief Device A device which is installed to vent gas from a system being protected in order to prevent the gas pressure from exceeding a predetermined limit by venting the gas into atmosphere. 3.24 Ambient Temperature Usually used to refer to the temperature of the air in which a structure or a device operates. 3.25 Block Valve A gate, plug or ball valve that prevents flow or leakage into the down stream conduit when in the closed position. Valve shall be single or double seated, bidirectional or unidirectional. Unidirectional valve shall be marked with a flow direction arrow. 3.26 Turbine Gas Meter Measuring device in which the dynamic forces of the flowing gas cause a turbine wheel to rotate with a speed as a function of the volume flowrate. The number or revolutions of the turbine wheel is the basis for the indication of the volume passed through the meter. 3.27 Measured Quantity Volume in cubic meters, at metering conditions. 6 N.I.G.C. July 2014 IGS-M-RS-401(1) 3.28 Volume Flow Rate Volume at metering conditions divided by time. 3.29 Rangeability The ratio between Qmin and Qmax, i.e. the minimum and maximum flow rate respectively for which the meter performs within the maximum permissible errors. 3.30 Metering Pressure (PM) Absolute gas pressure to which the indicated volume of gas is related. 3.31 Metering Conditions Conditions of the gas prevailing at the point of the measurement (e.g. temperature and pressure of the measured gas in the meter). 3.32 DN- Designation Numerical designation of size for components of a pipework system, which is used for reference purposes. It comprises the letters DN followed by a dimensionless whole number which is indirectly related to the physical size, in millimeters, of the bore or outside diameter of the end connections. 3.33 PN- Designation Alphanumeric term used for reference purposes related to a combination of mechanical and dimensional characteristics of a component of a pipework system with regard to pressure. It comprises the letters PN followed a dimensionless whole number. 3.34 Gas Pressure Regulator Device which maintains the outlet pressure constant independent of the variation in inlet pressure and / or flow rate within defined limits. 3.35 Cabinet Station An enclosed space (apart from any necessary ventilation apertures), which is used exclusively to house gas pressure–regulating and/or metering equipment and ancillaries. 3.36 Enclosed Installation Plant installed in an enclosed space (apart from any necessary ventilation aperture). 3.37 Open Air Installation A plant installed in the open air, which may or not be protected by a canopy. 3.38 Hazardous Area An area in which an explosive or flammable gas atmosphere is present, or may be expected to be present, in quantities such as to require special precautions for the construction, installation and use of apparatus. 3.39 Hazardous Area Zones Hazardous areas are classified in zones based upon the frequency of the occurrence and the duration of a flammable atmosphere. 7 N.I.G.C. July 2014 IGS-M-RS-401(1) 3.40 Component Any item from which a gas supply system or installation pipework is constructed. A distinction is drawn between the following groups of components: - Ancillaries (pressure regulators, valves, safety devices, expansion joints, insulating Joints) - Pipes (including bends made from pipe) - Instrumentation pipework - Fittings 3.41 Inlet Pipework Connecting pipework through which gas enters the station. 3.42 Outlet Pipework Connecting pipework through which gas leaves the station. 3.43 Standard Condition The conditions to which a volume of gas is converted (i.e. base gas temperature 15.56 °C (60°F) base pressure 1013.25 mbar absolute (14.696 psi) . 3.44 Strength Test Specific procedure to verify that the pipework and /or station meets the requirements for mechanical strength. 3.45 Tightness Test specific procedure to verify that the pipework and / or station meets the requirements for tightness. 3.46 Instrumentation Pipework Pipework required for the proper functioning of the ancillaries installed within the pressure regulating station. such as sensing, auxiliary and sampling lines. 3.47 Safety Shut - Off Device Device designed to shut off the gasflow which responds slower dynamically than a slam shut device in the event of an unacceptable pressure being detected within the system it protects. 3.48 Safety Slam - Shut Device Device designed to quickly shut off the gasflow in the event of an unacceptable pressure being detected within the system it protects. 3.49 Pressure Control System Combined system including pressure regulating, pressure safety and possibly pressure recording and alarm systems. 3.50 Pressure Regulating System System which ensures that a pressure is maintained at the outlet system within required limits. 8 N.I.G.C. July 2014 IGS-M-RS-401(1) 3.51 Pressure Safety System System which, independent of the pressure regulating system, ensures that the outlet pressure of that system does not exceed the safety limits. 4. REQUIREMENTS 4.1 Design and Service Conditions The cabinet type station shall be constructed of quality components and materials in a workmanlike manner in order to attain gas tightness, stability of performance and sustained accuracy over the range of operating conditions with minimum of maintenances, when reducing and measuring and measuring natural gas. Such stations shall have the general characteristics listed below: 4.1.1 All design aspects and criteria for these stations shall be according to ANSI B 31.8. 4.1.2 The normal inlet pressure, outlet pressure and capacity of the station shall be as Table 1. TABLE 1 - Station Type and Classification Type No. Station Inlet Pressure bar (psig) Outlet Pressure Bar (psig) Capacity (scm/h) 400.1 400.2 3-4(45-60) 3-4(45-60) 1000 2500 1 Metering 4000 1000 10-17.2(150-250) 10-17.2(150-250) 2500 5000 10000 400.1 400.2 2 Reducing & Metering 1000 10 -17.2(150-250) 3-4(45-60) 2500 5000 10000 9 N.I.G.C. July 2014 IGS-M-RS-401(1) 4.1.3 The ambient temperature range for the station is -29 °C to 60 °C (-20 °F to 140 °F). 4.1.4 The stations shall be designed, constructed and located such that the risk and nuisance to the environment of the stations and its operation are kept within acceptable limits. 4.1.5 Usually, gas delivery is a continuous process. If an unintended cessation of gas flow can cause a safety hazard or operational problems, the station shall be such that a failure of the measuring and reducing station will not stop the gas flow. Extra equipment may be added to improve the security of supply. 4.1.6 The manufacturer shall confirm that the environmental noise levels during operation of station shall be according to Appendix A. In addition no design changes or modifications shall be undertaken which cause the established noise limits to be exceeded. 4.1.7 The reference standards and specifications for the main components of station shall be as per Appendix B (data sheet) and the manufacturer/supplier shall verify the compliance of them with the related standards and specifications. 4.1.8 The design and operation of the station shall be such that the venting of gas to the atmosphere is kept to a minimum. This shall be assessed during the design stage. 4.1.9 the station shall be designed such that the correct functioning is ensured for all specified pressure and temperature ranges (i.e. MOP , TOP , MIP , minimal pressure at station entrance , Tmin , Tmax , ambient temperature) as well as impurities, dusts or condensates present in the gas. 4.1.10 Health and safety warning notices shall be positioned and maintained on, or adjacent to, the station and, additionally, to call attention to any special features of the system. An easily visible notice shall be positioned and maintained on /or near the station to indicate the action to be taken in the event of an escape of gas. Note: see legal requirements, if any. 4.1.11 The manufacture shall submit the safety procedures for the operation and maintenance of the station. 4.1.12 During the design and construction phases, quality assurance is essential to ensure the basic integrity of the installation. During operation basic integrity shall be preserved until the installation is de - commissioned. Any party involved in design, construction, commissioning, operation and maintenance should maintain an appropriate quality management system considering the presence of hazardous areas. Such a system should be agreed on between the parties and may be based e.g. on the EN ISO 9000 series. Inspection and testing of the installation are responsibilities of the operator of the station. National regulations may require that the inspection and testing have to be witnessed and accepted by independent experts. 10 N.I.G.C. July 2014 IGS-M-RS-401(1) 4.1.13 The measuring system selected shall be sufficiently accurate to reduce random and systematic errors to such a level that contractual or legal obligations are fulfilled and that can be justified on technical and economic reasons. 4.1.14 Care should be given to avoid pulsating flow and vibrations (Resonance). 4.1.15 In general it is necessary to insert at least one upstream isolating valve and one downstream isolating valve for each meter run. 4.1.16 According to needs, a station is equipped with the following main components: - Isolating valves - Monitoring systems including recorders and loggers - Dry gas filters - Equipment for reduce the noise level - Equipment for measuring the flow - Vibration damping equipment - Equipment for controlling the pressure (regulators) - High pressure safety equipment (such as safety shut off and safety Relief valve) - Pipework, insulating joints - Other components 4.1.17 The design shall be based on the minimum and maximum values for: - Volume flow rate at standard conditions - Design pressure and operating pressure - Gas and ambient temperature - The components of the gas 4.1.18 Each measuring station shall be equipped with the instrumentation required for measuring/calculating the variables needed to meet the accuracy requirements. The measuring system consists of a gas meter and in general also of a conversion device with sensors for the various parameters needed for the determination of the delivered quantity. The conversion device shall be compatible with the gas meter and the suitability of it shall be approved by the manufacture of the meter. Due regard shall be given to possibilities by which field maintenance, checking and recalibration can be carried out. 4.1.19 The meter shall be selected so that, under foreseeable fault conditions within the installation, the maximum working pressure for which the meter has been designed and tested is not be exceeded. The meter shall operate satisfactorily over all specified ranges of pressure, temperature and flow. 4.1.20 If the measurement is done under operating conditions a conversion device shall be fitted to the measuring system. The output of this device may be in volume at standard condition. 11 N.I.G.C. July 2014 IGS-M-RS-401(1) 4.1.21 The measuring system may be fitted with pulse transmitters to generate pulses proportion to the measured gas volume for transmission to other equipment such as totalizers, recorders or telemetry equipment. Transmitter range and pulse significance shall be suitable for the application. Results of measurement may be displayed recorded and logged as analogue or digital data and may be recorded or stored by suitable devices as function of time or volume. 4.1.22 For the layout of piping, the following requirements shall be taken in to account. The internal diameter of pipework of the measuring station should be calculated for gas velocities not higher than 20 m/s: - Gas meters shall be installed in the pipeline in accordance with the applicable standard and to manufacturer's instructions. - For meters a well developed velocity profile, axi symmetric and free of swirl, is essential to obtain accurate flow measurements. In order to obtain acceptable velocity profile conditions the following general measures shall be taken into account: 1- The required upstream and downstream pipe section and the gas meter shall have the same nominal diameter. 2- The inlet isolating valve for the station shall be plug valve, regular patent, flanged end and pressure balance type for class 300 and standard type for class 150. 3- The outlet isolating valve shall be ball valve, full bore, flanged end. 4- The meter for station shall be turbine type. 5- The gas turbine meter shall be installed at upstream of station. It's recommended that, if a regulator is installed upstream of a meter, precautions are taken. Use of pipe fittings or equipment that produce markedly asymmetric velocity profiles and/or swirls shall be avoided within a sufficient length upstream of the gas meter. 6- If the upstream conditions necessary for a specific meter to maintain its accuracy cannot be obtained, an adequate flow conditioning device shall be used. Downstream of any flow conditioning device, a straight length of pipe should be allowed to let the velocity profile develop to the required quality in terms of velocity and turbulence distribution. 4.1.23 All electrical and electronic systems if used in a station shall comply with the IEC related standards and the manufacturer delivers a written statement and a report showing that the performance of the instrument complies with the requirements. 4.1.24 Meters and the associated instrumentation are precision devices and as such they shall be handled with care. They should be stored in a clean dry condition, taking due regard of the manufacturer's recommendations on stacking and handling. The meter inlet and outlet connections shall be protected to prevent ingress of foreign material and moisture and shall remain so prior to installation. The installation of all instruments shall ensure a proper readable indication. 4.1.25 Gas meter pipework shall be installed and supported in such a manner to avoid undue stress being placed upon the gas meter connections e.g. by supporting them. Easy removal and replacement of the gas meter shall be possible. 12 N.I.G.C. July 2014 IGS-M-RS-401(1) 4.1.26 If necessary and specified at data sheet, inlet and outlet headers of stations shall be equipped with thermometers. 4.1.27 The area of the cabinet shall be adequate to accommodate the equipment and provide access for maintenance purpose. The closeness between the equipment and cabinet shall not less than 30 cm. Where necessary , vulnerable pipework or equipment shall be protected. 4.1.28 The extent of a hazardous area shall be determined according to API RP 500. The possible hazardous area should be taken into account When fixing the site boundary. 4.1.29 Stations shall be secured against entry by unauthorized person. If a site security fence is used, equipment shall be sited at a sufficient distance from the fence to prevent interference from outside. Consideration should be given to the provision, wherever possible, of locking devices for valves, including auxiliary valves located to a housing. Prominent sings prohibiting smoking and other ignition sources shall be displayed. Signs showing an emergency telephone number should be clearly displayed. 4.1.30 The stations should not be connected to sewer. 4.1.31 The space in which the gas pressure regulating and metering equipment is installed shall be ventilated directly to atmosphere by means of apertures. These apertures, which may be ventilation ducts shall be distributed as equally as possible between high and low level over the length of the walls and/or the roof and positioned to provide effective ventilation of the entire space. The ventilation apertures shall be protected so that materials and objects can not be inserted and the apertures can not be blocked. The combined open area of the protected apertures shall not be less that the prescribed minimum ventilation area. 4.1.32 The access doors of spaces housing gas pressure regulation and metering equipment shall be provided with locks. Doors shall be opened from the outside by mean of a key. The doors shall open outwards and it shall be possible to fix them in an open position. In the case of accessible spaces, it shall be possible to open the doors from the inside without a key. 4.1.33 Smoking and other ignition sources shall be prohibited within hazardous areas. Prominent prohibiting signs shall be displayed on the cabinet. 4.1.34 Due to the possibility of dust or liquid being entrained in the gas stream impairing the proper functioning of the equipment, consideration shall be given to a dust or liquid extraction system. The systems shall have adequate capacity based on the maximum gas flowrate at minimum pressure. For filters a differential pressure gauge should be provided to indicate the level of contamination of the filter. Closures shall be constructed in such a way that they can be opened without risk. 13 N.I.G.C. July 2014 IGS-M-RS-401(1) 4.1.35 Pressure regulating processes generate noise which can, if untreated, be radiated by some parts of a station to produce unacceptably high noise levels. These can: - Create nuisance to inhabitants in the locality of the station - Create a hearing hazard to personnel working on the equipment - Result in component failure 4.1.36 Consideration shall be given at the design stage to the incorporation of noise control features to limit noise to an acceptable level at the site boundary or near inhabited building. This level shall be according to Appendix A. 4.1.37 Gas escaping through apertures in ancillaries could result in a flammable mixture in an enclosed space . To avoid this, the following provisions may be used: - Apertures Fitted With Vent lines to outside the room - Restriction in breather connections, provided the operational performance is not impaired - Extra ventilation of the room The above apertures also include breather holes serving diaphragms in pressure regulators and safety devices. If vent lines are fitted to these apertures, they shall be of sufficient capacity so that the gas can escape freely and the functioning of pressure regulators and safety devices is not adversely affected by pressure build-up in the line. 4.1.38 Vent lines working at the same pressure may be combined. provided that leakage through one or more does not affect the operation of any equipment. The terminals of vent lines shall be located at a safe distance from sources of ignition. All vent terminals shall be designed to suit the local conditions. Suitable precautions shall be taken to prevent blockage of the outlet and to protect it against the ingress of foreign material. Dedicated vent and depressurizing lines shall not be combined with breathing lines in a manifold. If manifolds are used for a type of vent line this shall not impair the proper functioning of the connected units. 4.1.39 The possible hazardous area of the gas pressure regulating station shall be classified in zones according to EN 60079-10. Electrical installation in hazardous areas shall comply with prEN 50154. 4.1.40 Consideration should be given to measures for the protection against lightning strikes. The provision shall satisfy the relevant standards. Overvoltage protection for cables and electrical units should be used. In the case of electronic devices these provisions may be completed by using overvoltage fine protection units for adequate protection of the devices. The cabinet and all electrically conductive parts of the installation should be bonded and connected to earth. Care should be taken to avoid interaction is between the electrical earthing, instrumentation earthing and cathodic protection systems. 4.1.41 Welding of steel pipework shall be done in accordance with API 1104. 14 N.I.G.C. July 2014 IGS-M-RS-401(1) 4.1.42 The station shall be separated electrically from the inlet and outlet pipework by means of insulating flanges or isolating joints in installation. 4.1.43 Each station shall consist of two separate runs with capacity of 100% of maximum capacity of station. Note: for metering station (4-4) bar (60-60 psig) and reducing and metering 10-17.2 bar (150-250 psig) to 4 bar (60 psig) with capacity of 400 scm/h, the arrangement of station may consist of one run. 4.1.44 Each run of regulating cabinet station shall be equipped with: a- A safety shut off device integrated with the regulator of station and only one partial relief valve for station or; b- Regulator with integrated safety shut off valve and an independent safety shut off device. 4.1.45 In general, for commissioning purposes of cabinet station, each run shall consist of pressure gauge, drain valve and sensing line before outlet of isolating valve. In case of limitation of sensing line length, additional sensing line shall be considered for operation. 4.1.46 The relief system discharge capacity range for stations (type 2 Table 1) shall be (2-3) % of maximum capacity of each line of stations. 4.1.47 The cabinet shall have adequate strength against the conditions due to transportation, installation, operational conditions such as ambient temperature, different climatic conditions, wind (with velocity of 120 km/h) and earthquick (according to zone 3.1 California) without any deformation. Any device shall have suitable supports. 4.1.48 The cabinet shall be equipped with: - Suitable eye-ring for transportation and installation correlated to the center of gravity of station - Provisions for maintenance purposes - Related bolts for installation 4.2 Materials 4.2.1 The materials of all components of station whether specified or unspecified shall be suitable for pressure, temperature and other operating conditions specified as per Appendix B (data sheet). 4.2.2 All component of the station shall be resistant to or protected against corrosion, e.g. by being painted or coated. 4.2.3 All components such as pipework, filters, regulators, meters flanges, gaskets, joints, etc. installed at station shall be constructed of materials complying with the related standards and specification as per Appendix B (data sheet). 15 N.I.G.C. July 2014 IGS-M-RS-401(1) 4.2.4 The cabinet shall be made of steel plate according to ASTM A 283 grade B,C with minimum thickness of 3 mm. 5. INSPECTION, TESTS AND CERTIFICATION 5.1 Prior to Fabrication Before starting the fabrication, the manufacturer shall submit the following documents to end user: - Welders certificates - WPS (welding procedure specification) - PQR (procedure qualification reports) - QCP (quality control plan) 5.2 Inspection Documents Prior to the shipment of each station to NIGC or end users, the manufacturer shall perform the specified tests and checks performed shall be documented in a report and shall include at a minimum the following items and prepared by the manufacturer and submitted to the NIGC or end users: a- The name and address of the manufacturer b- The name and the address of the test facility c- The model and serial number d- The date(s) of the test e- The name and title of the person (s) who conducted the tests f- A written description of the test procedures At least one copy of the completed report shall be sent to the NIGC or end users and completed report is available to the operator on request, for a period of 10 years after shipment of any station. 5.3 Tests 5.3.1 Visual inspection Visual inspection including checking of workmanship, painting, connections, internal parts, nameplate, etc. No apparent imperfection shall be observed. 5.3.2 Strength test All pressure containing components of stations including pipeworks, shall be strength tested before painting. The station shall be designed to withstand the internal pressure using an appropriate safety factor for its components material at maximum inlet pressure (Pmax). It shall be tested to ensure it has sufficient strength to operate safely. Each cabinet station shall be hydrostatically tested at a pressure of 1.5 times of the related maximum operating pressure of the station for two hours. No leakage and deformation shall be observed. 16 N.I.G.C. July 2014 IGS-M-RS-401(1) 5.3.3 Tightness test After the strength test before painting, any component which has been removed from the installation during testing shall be re-installed. The entire installation shall then be subjected to a tightness test at 1.1 maximum operating pressure for a minimum 15 minutes in each section of the installation. Air, inert or gas shall be used as a test medium. There shall be no visible leakage when tested with a detection fluid. 5.3.4 Dimensional check The dimensional checks are including of compliance of the station construction with the pertinent assembly drawing and the dimensional conformity of all components, sizes, dimensions and etc. with the applicable drawings. 5.3.5 Materials checks The verification of the material used shall be carried out by the review of material certificates in compliance with this specification. 5.3.6 Paint test The painting of the cabinet type station shall be check in compliance with section 6 of this specification in terms of color, thickness and adhesion. 5.3.7 Quality assurance The manufacturer shall establish and follow a written comprehensive quality assurance program for the assembly and testing of the cabinet type station (e.g. ISO 9000, etc). This quality assurance program should be available to the inspector. 5.4 Inspection and Certificates 5.4.1 Prior to shipment of the station, the manufacturer should make the following available for the inspector’s review: Material certificates, weld inspection reports, pressure test reports and final dimensional measurements. 5.4.2 The manufactured station will be inspected and the inspection shall cover the following stages as specified in this specification and according to terms and conditions of purchase order. Manufacturer shall provide and present to NIGC inspector test result for different examinations correlated to serial number and material test certificates according to requirements of NIGC specification: 1- Visual inspection 2- Strength test 3- Tightness test 4- Dimensional check 5- Material check 6- Paint test 7- Quality assurance 17 N.I.G.C. July 2014 IGS-M-RS-401(1) 6. PAINTING 6.1 The external surface of cabinet, pipes, fittings, skid of station shall be thoroughly cleaned by removing all rust and mill scale. Surfaces to be painted shall be completely free from grease, grit and foreign material. 6.2 The systems for painting and paint specification for cabinet, pipes, fittings and skid shall be according to item 3 of IGS-CH-041 (0) : 2003. 6.3 Final colour for station shall be as following: 1- The colour of cabinet shall be green and the paint specification shall be according to BS 381 C No. 217. 2- The colour of internal equipments and components of station such as valves, filters, meters, regulators and others shall be according to the related standards and specifications. 3- The colour of pipes, fittings and flanges shall be white yellow and the specification of paint shall be according to 10 E 53 BS 4800. 4- The colour of skid shall be white orange and paint specification shall be according to BS 381 C No. 55. 7. MARKING Each station must carry, grouped together, on steel or aluminum badge plate (S) the following information: 1- The manufacturer name, model number, serial number, month and year Manufactured 2- Minimum and maximum inlet pressure bar (psig) 3- Outlet pressure bar (psig) for reducing stations and minimum and maximum outlet pressure bar(Psig) for measuring stations 4- Maximum capacity (scm/h) 5- Purchase order and item number These inscriptions must be directly visible, easily legible and indelible under the normal condition of use of the station. 8. PACKING AND PACKAGING Each instrumentation device of station shall be covered by suitable plastic. All openings such as inlet, outlet covered by plastic caps. Packing and packaging of cabinet station shall be according to manufacturer instructions. 18 N.I.G.C. July 2014 IGS-M-RS-401(1) 9. DOCUMENTATION 9.1 With Technical Quotation The manufacturer is required to complete and sign the attached data sheet (S) and as well as two sets of the following documentation in English. All documentation should be dated: 9.1.1 A description of the station, giving the technical characteristics and the principle of its operation such as the basis design data including minimum and maximum inlet pressure, outlet pressure and maximum capacity; 9.1.2 The P & I diagram for station; 9.1.3 The detailed drawing of the station including: - A dimensioned drawing - A drawing showing the location of each important components - A drawing showing the installation of each important components - The specification of each component including size, class, material and manufacturer name - Wind resistance calculation - Foundation calculation (including wind and earthquick effects) 9.1.4 The original printed technical catalogues and certificates; 9.1.5 Supports, cabinet drawing including material, size, …; 9.1.6 Recommended two years spare parts list for each major components; 9.1.7 Documentation that the design and construction comply with applicable safety codes and regulations; 9.1.8 A list of documents submitted. 9.2 After Receipt of Order In case of order placement, the manufacturer shall submit one set per station in addition five sets of the following documents: 9.2.1 A description of the station, giving the technical characteristics and the principle of its operation such as the basis design data including minimum and maximum inlet pressure, outlet pressure and maximum capacity; 9.2.2 The P & I diagram for station; 19 N.I.G.C. July 2014 IGS-M-RS-401(1) 9.2.3 The detailed drawing of the station including: - A nomenclature of components of station - A dimensioned drawing - A drawing showing the location of each component - A drawing showing the installation of each important component - The specification of each component including size, class, material and manufacturer name - Wind resistance calculation - Foundation calculation (including wind and earthquick effects) 9.2.4 The original printed technical catalogues and certificates; 9.2.5 Supports, cabinet drawing including material, size, … ; 9.2.6 All tests reports and weld records; 9.2.7 Instructions for installation, operation, maintenances and troubleshooting; 9.2.8 Foundation drawings; 9.2.9 Documentation that the design and construction comply with applicable safety codes and regulations; 9.2.10 A list of documents submitted. 10. GUARANTEE 10.1 Manufacture shall guarantee the compliance of material and performance of the supplied equipment with this specification. 10.2 The guarantee period shall be 2 years after equipments goes on stream or 3years from date of shipment, whichever occurs first and 10 years after sale services. 10.3 Supplier shall agree to repair on site or replace any part, equipment or unit which proves to be defective during the above mentioned period free of charge. 20 )IGS-M-RS-401(1 N.I.G.C. July 2014 "APPENDIX "A ﻣﺼﻮﺑﻪ ﺷﻤﺎره 236ﺷﻮراي ﻋﺎﻟﻲ ﺣﻔﺎﻇﺖ ﻣﺤﻴﻂ زﻳﺴﺖ )ﻣﺼﻮب (1381/3/21 در اﺟﺮاي ﻣﺎده 2آﻳﻴﻦ ﻧﺎﻣﻪ اﺟﺮاﻳﻲ ﻧﺤﻮه ﺟﻠﻮﮔﻴﺮي از آﻟـﻮدﮔﻲ ﺻـﻮﺗﻲ ﻣﺼـﻮب ﺟﻠﺴـﻪ ﻣـﻮرخ 1378/3/19ﻫﻴـﺄت وزﻳـﺮان ﺣﺪود ﻣﺠﺎز ﺻﺪا در ﻫﻮاي آزاد اﻳﺮان ﺑﺸﺮح ذﻳﻞ ﺗﻌﻴﻴﻦ و ﻣﻮاﻓﻘﺖ ﻣﻲﺷﻮد ﻛﻪ از ﺗﺎرﻳﺦ ﺗﺼﻮﻳﺐ در ﺳﻄﺢ ﻛﺸﻮر ﺑﻪ ﻣـﻮرد اﺟـﺮا ﮔﺬارده ﺷﻮد. روز 7ﺻﺒﺢ اﻟﻲ 10ﺷﺐ ﺷﺐ 10ﺷﺐ اﻟﻲ 7ﺻﺒﺢ (A) Leq (30) db (A) Leq (30) db 1 ﻣﻨﻄﻘﻪ ﻣﺴﻜﻮﻧﻲ 55 45 2 ﻣﻨﻄﻘﻪ ﺗﺠﺎري – ﻣﺴﻜﻮﻧﻲ 60 50 3 ﻣﻨﻄﻘﻪ ﺗﺠﺎري 65 55 4 ﻣﻨﻄﻘﻪ ﻣﺴﻜﻮﻧﻲ – ﺻﻨﻌﺘﻲ 70 60 5 ﻣﻨﻄﻘﻪ ﺻﻨﻌﺘﻲ 75 65 ردﻳﻒ ﻧﻮع ﻣﻨﻄﻘﻪ A (A) Leq (30) dbﺗﺮاز ﻣﻌﺎدل در ﻣﺪت زﻣﺎن 30دﻗﻴﻘﻪ اﻧﺪازهﮔﻴﺮي در ﺷﺒﻜﻪ وزﻧﻲ ﻣﻲ ﺑﺎﺷﺪ و واﺣﺪ آن دي ﺳﻲ ﺑﻞ اﺳﺖ. ﻣﻨﻄﻘﻪ ﻣﺴﻜﻮﻧﻲ :ﻣﺤﺪودهاي اﺳﺖ ﻛﻪ ﺑﻴﺶ از 50درﺻﺪ آن داراي ﻛﺎرﺑﺮي ﻣﺴﻜﻮﻧﻲ ﺧﺎﻟﺺ ﺑﺎﺷﺪ و ﺑﻘﻴﻪ آن )ﻋﻼوه ﺑـﺮ ﺷـﺒﻜﻪ ﻣﻌﺎﺑﺮ( ﺷﺎﻣﻞ ﺧﺪﻣﺎت ﻣﺮﺑﻮط ﺑﻪ ﻣﺴﻜﻮﻧﻲ و ﺑﺪون ﻣﺰاﺣﻤﺖ ﺑﺮاي ﻣﺴﻜﻮﻧﻲ ﺑﺎﺷﺪ. )آﻣﻮزﺷﻲ ردهﻫﺎي ﭘﺎﻳﻴﻦ ،ﺗﺠﺎري در ﺣﺪ روزﻣﺮه ،ﻓﺮﻫﻨﮕﻲ روزﻣﺮه( 21 N.I.G.C. July 2014 IGS-M-RS-401(1) APPENDIX "B" Data sheet To be Filled by NIGC To be Filled by Manufacturer/Supplier Inquiry No. : Quotation No. : Inquiry Data : Quotation Date : NIGC Standard : IGS-M-RS-401 (1) : 1392 Catalogue No. : The Data Sheet is Provided by Manufacturer Inquiry Data Item Indent item No. Inlet pressure bar (psig) Outlet pressure bar (psig) Supplier Offered Data Maximum capacity (scm/h) Manufacturer signature and stamp : 22 Item No. Inlet pressure bar (psig) Outlet pressure bar (psig) Maximum capacity (scm/h) N.I.G.C. General Item July 2014 IGS-M-RS-401(1) To be Filled by NIGC To be Filled by Manufacturer/Supplier Gas temperature -10 0C to 55 0C (+14 0F to 131 0F) ----- Ambient temperature -29 0C to 60 0C (-20 0F to 140 0F) Yes No Max. relative humidity …………… Yes No Yes No Description Station location Residential Commercial - Residential Commercial Residential – Industrial Industrial Maximum noise level limitation According to Appendix A Manufacturer signature and stamp : 23 N.I.G.C. Item July 2014 Description To be Filled by NIGC Manufacturer Type Class rating Size (in) Hydrostatic test pressure References standard including design, fabrication, material, testing, etc Fire safe Body, bonnet, cover, plug, ends Plug Valve Plug Non-metallic parts Connection Stem design Operating temperature range Anti static design Sealant injection Plug surface Additional request IGS-M-RS-401(1) To be Filled by Manufacturer/Supplier ……… Pressure balance Standard type Lubricated Wrench operated 150 300 1.5 M.A.W.P API 6D and IGS-M-PL-002-1 API 607 or API 6FA Cast carbon steel at least acc to ASTM A 216 grade WCB/WCC Forged carbon steel at least acc. to ASTM A 105 Cast carbon steel at least acc to ASTM A 216 grade WCB/WCC Forged carbon steel at least acc. to ASTM A 105 acc. to ASTM D 2004 , HK 710 or ASTM D 145 Flanged end R.F, S.F* acc. to ANSI B16.5 Anti-blow out stem -29 °C to 60 °C Yes Yes Yes No Yes No Yes No Yes No 150 300 ……….. Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes Yes Yes Yes Yes Yes No No No No No No Special treatment, electroless nickel plated with minimum 25 μm thickness as per ASTM B 656 Yes No Special treatment, hard chromium plated with minimum 25 μm thickness as per ASTM B 650 Yes No Manufacturer catalogs including detail sectional drawing, test certificates acc. to API 6D and IGS-M-PL-002-1 Yes No *:Serrated finished Manufacturer signature and stamp: 24 N.I.G.C. Item July 2014 Description To be Filled by NIGC Manufacturer Type Class rating Size (in) Hydrostatic test pressure References standard including design, fabrication, material, testing, etc Fire safe Body, bonnet, cover, ends Ball Valve Ball Connection Stem design Anti static design Ball surface Stem Stem surface Additional request IGS-M-RS-401(1) To be Filled by Manufacturer/Supplier ……… Full bore, split body, trunnion mounted 150 300 Yes No 150 300 ….. 1.5 M.A.W.P API 6D and IGS-M-PL-010-1,2 API 607 or API 6FA Cast carbon steel at least acc to ASTM A 216 grade WCB/WCC Forged carbon steel at least acc. to ASTM A 105 Cast carbon steel at least acc to ASTM A 216 grade WCB/WCC Forged carbon steel at least acc. to ASTM A 105 Flanged ends R.F, S.F* acc. to ANSI B16.5 Anti-blow out stem Yes Special treatment, electroless nickel plated with minimum 25 μm thickness as per ASTM B 656 Special treatment, hard chromium plated with minimum 25 μm thickness as per ASTM B 650 Forged carbon steel at least acc. to ASTM A 105 or BS 1503 Grade 221/550 Bar alloy steel at least acc. to AISI 4140 Electro less nickel plated Hard chromium plated Manufacturer catalogs including detail sectional drawing, test certificates acc. to API 6D and IGS-M-PL-002-1 *:Serrated finished Manufacturer signature and stamp: 25 Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes Yes Yes Yes No No No No Yes No Yes No Yes No Yes No Yes Yes No No Yes No N.I.G.C. Item July 2014 Description IGS-M-RS-401(1) To be Filled by NIGC Manufacturer Maximum capacity at minimum inlet pressure and outlet set pressure (scm/h) Class rating Size (in) Gas inlet pressure (psig) Maximum operating pressure Set pressure (psig) Lock-up pressure at maximum inlet pressure (psi) Design pressure Test pressure Type Fail safe design Regulator Safety shut-off valve type Safety shut-off valve pressure Noise reduction device Connection type Valve body material Internal metallic parts material Valve mechanism material Pilot body material Internal non-metallic parts Sensing line material Pilot type/model Pilot spring range (barg) Pilot setting (barg) Optional accessory Reference standard IGS-M-IN-202(0): 2009 To be Filled by Manufacturer/Supplier …………… min:………. max:……… min:……. max:…… min:………. max:……… 250 psig (17.2 bar) 60 psig (4.2 bar) min:……. Yes Yes max:…… No No …………… Yes No 720 psig (50 bar) 1080 psig (74 bar) Axial Conventional pilot operated Conventional spring loaded Other Regulator fail to open Regulator fail to close Slam type 72 psig (5 bar) Light metal or equivalent Flanged ends R.F, S.F* acc. to ANSI B16.5 Carbon steel acc. to ASTM A 216 grade WCB Forged carbon steel acc. to ASTM A 105 Seamless pipe acc. to API Suitable for -29 °C to 60 °C ambient temperature Corrosion resistant material such as S.S Corrosion resistant plated steel S.S type 316 Carbon steel acc. to ASTM A 216 grade WCB Forged carbon steel acc. to ASTM A 105 Die cast aluminum acc. to ASTM B 85 Brass acc. to ASTM B 283 grade C 37700 Rubber or plastic material resistant to odorized natural gas S.S type 316 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No No No No No Yes No Yes No Yes No Yes No Yes Yes No No Yes No Yes No Yes No Yes No Yes No 300 Yes *:Serrated finished Manufacturer signature and stamp: 26 Yes No …………… …………… …………… Filter Others Yes No N.I.G.C. Item July 2014 Description IGS-M-RS-401(1) To be Filled by NIGC Manufacturer …………… Installation Class rating Inlet/outlet connection Flange material Dry Gas Filter Design pressure Test pressure Inlet pressure range (psig) To be Filled by Manufacturer/Supplier 150 300 Flanged ends R.F, S.F* acc. to ANSI B16.5 ASTM A 105 1.1 *M.W.P 1.3 *Design pressure 45-60 psig (3-4 bar) 150-250 psig (10-17.2 bar) Horizontal Vertical 150 300 Yes No Yes No Yes No Yes No Yes No Yes No Yes No …………… …………… Horizontal Maximum capacity (scm/h) Construction standard ASME "U" stamped ASME sec, VIII, Div.1 Body material Yes No Yes No ASTM A 106 grade B Yes No Head and hub Forged acc. to ASTM A 105 Yes No Corrosion allowance 1.6 mm Quick opening closure with safety bleed inter lock Yes No Yes No is required Yes No is required Yes No Tow Lubricated plug valve, flange ends Yes No Yes Yes No Type of closure The documentation for calculation of filtration area The documentation for calculation design pressure vessel Drain valve Yes Other characteristics of dry gas filter acc. to IGS-M-PM-105 *:Serrated finished Manufacturer signature and stamp: 27 No N.I.G.C. Item July 2014 Description To be Filled by NIGC Flow direction To be Filled by Manufacturer/Supplier OUT to IN Yes No Polypropylene or Polyester Media Yes No Cellulose Paper Media Yes No G number of element according to related standard ………… Yes No Element ID (mm) ………… Yes No Element OD (mm) ………… Yes No Element H (mm) ………… Yes No Element filtration area (m2) ………… Yes No Caps thickness (mm) ………… Yes No Inner core thickness (mm) ………… Yes No Outside case thickness (mm) ………… Yes No IGS-M-PM-111 Yes No Material of media Dry Gas Filter Cartridge IGS-M-RS-401(1) Ref- standard for cartridge Manufacturer signature and stamp: 28 N.I.G.C. Item July 2014 Description To be filled by NIGC Manufacturer Gas inlet pressure (bar/psig) Ambient temperature range Gas temperature range Flow straightner Capacity with air at atmospheric conditions (±100 mbar) at maximum pressure loss(CMH) Meter mounting Size (in) Class rating Index Length (F to F) (mm) Minimum up stream length according manufacturer recommendation (mm) Minimum downstream length according manufacturer recommendation (mm) Connection type Material Correcting Device Turbine Meter Test pressure (psig) Type Transmission system Frequency pulse generator Measuring unit Index case Type Standard Manufacturer Model NO. The compatibility of correction device with turbine meter Body IGS-M-RS-401(1) To be filled by Manufacturer/Supplier …………… min:………. max:……… -29 °C to 60 °C -10 °C to 55 °C Is required (built in) …………… Horizontal ……….. Class 150 Class 300 412 psig (28 bar) for class 150 1080 psig (75 bar) for class 300 3D min:………. Yes Yes Yes Yes max:……… No No No No Yes No ……….. Class 150 Class 300 412 psig (28 bar) for class 150 1080 psig (75 bar) for class 300 Yes No …………… …………… Flanged ends R.F, serrated finished acc. to ANSI B16.5 Direct reading, digital Magnetic coupling Yes No Yes Yes No No LF and HF Yes No CMH Dust & hummidity proof (IP 65) Yes No Volume corrector Yes No IGS-M-IN-106 Shall be approved by the manufacturer of turbine meter …………………. ………………… ………………… Yes No Carbon steel acc. to ASTM A216 grade WCB/WCC, or Forged carbon steel acc. to ASTM A 105 …………… Stainless steel type 316 …………… Turbine wheel Aluminium acc. to ISO 6012 …………… Shaft Gearing Flange Stainless steel type 316 Stainless Forged carbon steel acc. to ASTM A 105 …………… …………… Bearing Manufacturer signature and stamp: 29 …………… N.I.G.C. Item July 2014 Description To be filled by NIGC Yes No 30:1 Yes No 50:1 Yes No Qmin ≤ Q < Qt : ±2% Yes No Qt ≤ Q ≤ Qmax : ±1% Yes No 20:1 0.2Qmax Yes No 30:1 0.15Qmax Yes No 50:1 0.1Qmax Yes No Maximum pressure loss value at Qmax with atmospheric air P=1500 Pa (P=15 mbar) Yes No Accuracy curve (issued by manufacturer) Required for each meter Yes No meter immersed in water casing Required for each meter (size/class) Yes No Hydraulic test(1.5*M.W.P) Required for each meter Yes No Required for each type of meter (size/class) Yes No Required for each meter Yes No External leak test Required for each meter Yes No Error of indication Required for each meter Yes No Linearity Required for each meter Yes No Pressure range Required for each meter Yes No Calculation of WME Required for each meter Yes No Marking Required for each meter Yes No Self lubricated for 2"/150 and 3"/150 Yes No Yes No Yes No Maximum permissible errors Transitional flow rate Qt Bearing lubrication maintenance To be filled by Manufacturer/Supplier 20:1 Type tests certificate issued by a national standard organization Body strength test Type Test Turbine Meter Routine Test Design Condition Range ability Special lubricating tools Lubricated by oil pump Required Not required Oil specification ------------------ The approval certification of meters manufacturer certify by national bureau standard Guarantee Reference standard IGS-M-RS-401(1) Is required Submitted Not submitted 18 months after shipment or 12 month after installation Yes No Yes Yes No IGS –M-IN-102 latest edition Manufacturer signature and stamp: 30 N.I.G.C. Item July 2014 Description To be Filled by NIGC To be Filled by Manufacturer/Supplier Conversion device kind PTZ Conversion device type Type 1 Type 2 Optical RS-232 RS-485 Corrosion resistance and UV protection Standard cubic meter per hour IP 65 Type 1 Type 2 Optical RS-232 RS-485 corrosion resistance UV protection Battery AC DC At least 5 years Battery AC DC Database interfaces Body material Volume measuring unit Ingress protection (IP) Power supply Gas Volume Conversion Device IGS-M-RS-401(1) Battery life time Certificate Maximum permissible error ATEX approval EN approval MID approval 1% (at rated operating condition) o.5% (at reference condition) Ability to correct the error of the gas meter Ability to adjust and correct the error of temperature and pressure sensors parameters Ambient temperature PT PTZ Yes No Yes No ATEX approval EN approval MID approval Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Normal range: -29 °C to +60 °C Special range: -40 °C to +60 °C Yes No Standard modbus protocol support Capacity of memory for archive minimum 5900 record acc. to EN 12405 Operating pressure ranges (bar/psig) T Yes No from……..… to ………… from……… to ……… Guaranty/warranty 5 years guaranty and 15 years warranty Yes No Reference standard IGS-M-IN-106 Yes No Manufacturer signature and stamp: 31 N.I.G.C. Item July 2014 Description Relief valve Type Nozzle Class rating Design pressure Test pressure Set pressure Spring range Ambient temperature Maximum relief capacity Body Nozzle Seat disc Disc holder Other characteristic of relief vale Minimum required original technical catalogue and document including: -Manufacture name, trade mark -Type model number -Reference standard for design, material fabrication and testing Drawing showing outline dimension Capacity table and relate calculations Pipe Flange Butt welding ends fitting Nipple Weldolet Pipes , fittings,….. Threadolet Stud bolts and nuts Gasket Stud coupling Sensing line Gauge needle valve Electrode IGS-M-RS-401(1) To be Filled by NIGC To be Filled by manufacturer/supplier Spring located Semi CL 150 19 bar (275 psig) for ANSI CL 150 28.4 bar (412psig) for ANSI CL 150 4.6 bar(66 psig) (3.8-5.2)bar(55-57 psig) -29 ºC to + 60 ºC (2-3) % of max. capacity of station Carbon steel acc. to ASTM A 216 grade WCB or forged carbon street acc. to ASTM A 105 Stainless steel type 316 Stainless steel type 316 Stainless steel type 316 Acc. to IGS-M-IN-302 Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No Yes No Yes Yes Yes Yes No No No No Is required Yes No Is required Yes No Is required after order Yes No Yes No Yes Yes No No Yes No Yes No Yes No Yes No Yes No Yes Yes Yes No No No Yes No Yes Yes Yes No No No Yes No Yes Yes Yes No No No Sch.40, acc. to API 5L grade B or ASTM A 53 grade B or ASTM A 106 grade B W.N,R,F,S.F as per ASTM A 105 and ANSI B 16.5 Seamless acc. to IGS-PL-022(0), part 1 Seamless, NPT, threads as API 5B or ANSI B 1.20.1 class rating 3000 Ib material acc. to pipe material Seamless, butt-weld, material acc. to ASTM A 105 class rating 3000 lb, as per related MESC Seamless, material acc. to ASTM A 105 NPT thread acc. to API 5B or ANSI B 1.20.1, class rating 3000 lb as per related MESC Acc. to PLD-107 (Rev.1) Spirally-wound, performed v-shaped, graphic filled, strip stainless steel type 316 (for classes 150 and 300 R.F, S.F flanges), other specification acc. to IGS- PL-008(1) Thickness 0.175 inch Construction & testing acc. to IGS-MS-PL-005,1993 Design, dimensions, marking acc. to BS 3381 Material strip ANSI 316 stainless steel with oil resistant graphic compound filler Material guide ring carbon steel with thickness 1/8 inch Class 150 Class 300 Related flanges RF, S.F acc. to ANSI B16.5 Compression type, stainless steel type 316, male thread acc. to API 5B or ANSI B1.20.1 design, etc acc. to BS 4368 part 2, joint type material acc. to ASTM A 403 grade WP 316 API thread acc. to API 5B or ANSI B1.20.1 supplied with union nut and olive for use with stainless steel tubing. Construction & testing acc. to IGS-M-PL-005, 1993 Construction specification acc. to IGS-PL-003(2), 1994 Construction standard specification acc. to IGS-PL-018(0), 1992 Manufacturer signaturer and stamp: 32 N.I.G.C. Item July 2014 Description Type Application Ambient temperature Connection Mounting Dial size : mm (in) Dial range : bar (psig) Scale, marking, graduation and testing Accuracy Scale graduation Dial Pressure gauge Case Movement, bourdon tube and stem material Bezel ring Pointer Glass Over pressure protection Damping liquid Adjustment screws for range and linearity calibration All internal parts Thermo well(for the meters unintegrated with thermo well) To be Filled by NIGC Insulating joint To be Filled by Manufacturer/Supplier Bourdon tube For outdoor installation at metering/metering & reducing station -29 ºC to 60 ºC 1/2 (in), NPT, male, bottom, complete with hexagon, square or two flat on the shank with minimum thickness 12 mm Direct 100 (4) 0-6 (0-100) 0-25 (0-400) Yes No Yes No Yes No Yes No Yes Yes Yes Yes No No No No Acc. to BS 1780 Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes Yes Yes No No No Is required Yes No Easily accessible Yes No Yes No Yes No Yes No Acc. to BS 1780 (1% for points above 10% and below 90% of full scale and 1.5% for outside of these limits) Dual bar & psig Aluminum alloy, white enameled with black figures Weather proof, material shall be 316 stain less steel 316 stainless steel Byonet type or threaded material, 304 stainless steel Adjustable micrometer type aluminum or steel, black color Shatter-proof Blow out disc Silicon oil Glycerin Stain less steel 316,1 "mal x 1/2" female, NPT threaded, Insertion length (tip to hexagon shall be as following table) : Pipe dia (in) 2 3 4 6 8 Construction specification IGS-M-RS-401(1) Insertion length (mm) 60 80 100 140 185 Seamless, screwed, API line pipe threaded, 3000 material acc. to ASTM A 105, Construction standard acc. to ANSI B 16.11 Reference standard IGS-M-PL-006(1), 1994 33 N.I.G.C. July 2014 Inspection, test & certification Description To be Filled by NIGC IGS-M-RS-401(1) To be Filled by manufacture/supplier Documents prior to fabrication Acc. to item 5.1 Yes No The reports & test results prior to the shipment Acc. to item 5.2 Yes No Strength test (5.3.2) Required for each station Yes No Tightness test (5.3.3) Required for each station Yes No Visual inspection (5.3.1) Required for each type of station Yes No Dimensional checks (5.3.4) Required for each type of station Yes No Material checks (5.3.5) Test certificates is required Yes No Paint test (5.3.6) Test certificates is required Yes No Acc. to item (5.3.7) Yes No Acc. to item (5.4) Yes No Quality assurance Inspection & certificates Manufacturer signaturer and stamp: 34 N.I.G.C. July 2014 To be Filled by NIGC To be Filled by Manufacture/Supplier Painting Acc. to section 6 Yes No The name plate(s) and the written information Acc. to section 7 Yes No Packing and packaging of the Instrumentations and Cabinet station Acc. to section 8 Yes No The documentation at technical quotation stage Acc. to item 9.1 Yes No The documentation after receipt of order Acc. to item 9.2 Yes No Documentation Packing & Packaging Painting Description Marking Item IGS-M-RS-401(1) Manufacturer signature and stamp: 35 N.I.G.C. Item July 2014 To be Filled by NIGC Description Manuals Spare Parts Recommended spare part lists for station Guarantee IGS-M-RS-401(1) Is required with quotation To be Filled by Manufacture/Supplier Yes No Is required after order (with price) Yes No Manuals installation, operation and maintenance Is required Yes No Guarantee according to section 10 Is required for each station Yes No Without price Manufacturer Signature and Stamp: 36 N.I.G.C. July 2014 37 IGS-M-RS-401(1) N.I.G.C. July 2014 38 IGS-M-RS-401(1) N.I.G.C. July 2014 39 IGS-M-RS-401(1) N.I.G.C. July 2014 40 IGS-M-RS-401(1) N.I.G.C. July 2014 41 IGS-M-RS-401(1) N.I.G.C. July 2014 42 IGS-M-RS-401(1)