IAQ Check List

advertisement
IAQ Check List
Building: Lake Zurich Middle School North
Date: May 5, 2014
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
IAQ Check List
True
False
N/A
1. Ground Level Indoor Inspection
a. Univents are on and air discharge grills are free of obstructions.
If false, send email to building principal and facilities director asking staff to be instructed to keep vents
clear at all times. Record locations here:
2. Ground Level Outdoor Inspection (weather permitting)
a. Univent air intakes are free of obstructions.
If false, record locations here:
b. Filters
i. Medium efficiency filters are installed in all univents.
If false, list locations and create work orders to initiate corrective action.
ii. High efficiency filters are installed in the air handling units.
If false, list locations and create work orders to initiate correction action.
iii. Filters are being changed every six months and the installed date is written on the outer filter casing.
If filter is older than 6 months, list locations and create work orders to initiate corrective action.
c. Insects, bird nests, or droppings are not evident near outdoor air intakes.
If false, indicate locations here:
d. Trash dumpsters are located away from doors, windows, and outdoor air intakes.
e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial
plants, exhaust from nearby buildings)
f. Trucks and buses are not allowed to keep their engines idling near the building.
Page 1 of 9
Revised 3/21/2011 AMJ
Created 11/2010
IAQ Check List
Building: Lake Zurich Middle School North
Date: May 5, 2014
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
g. No evidence of drainage problems exist. Water drains away from the building including roof
downspouts.
IAQ Check List
True
False
N/A
h. Sprinklers do not spray directly toward the building or into outdoor air intakes.
i.
Grass clippings from mowers are directed away from the building air intakes.
j.
Clean walk-off mats are present at exterior entrances.
3. Roof (Inspections conducted weather permitting)
a. Roofing consultant has not found any issues requiring immediate repair.
Most recent roofing inspection date/company: 5-year roofing plan completed 5/25/2010 with C. E.
Crowley & Associates.
b. There is no evidence of water ponding on the roof.
c. Intake ventilation units are operating properly and free of debris.
d. All exhaust fans are operating properly and free of debris.
One bathroom exhaust fan was not on. Shut off at the switch.
e. Air intake dampers are set to allow air flow even at minimum setting.
f. Insects, birds, animal nests or droppings are not evident near outdoor air intakes.
g. Plumbing stacks and exhaust vents are located away from air intakes.
4. Attic
a. There is no evidence of roof or plumbing leaks.
Page 2 of 9
Revised 3/21/2011 AMJ
Created 11/2010
IAQ Check List
Building: Lake Zurich Middle School North
Date: May 5, 2014
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
b. There is no evidence in attic of insects, birds, animals, or nests.
No Attic.
5. General Considerations
a. Classrooms, offices and/or common areas appear recently cleaned.
If examples of poor housekeeping are found, record locations below:
IAQ Check List
True
False
N/A
b. Only vacuums with HEPA filters are being used.
c. All supply and exhaust ventilation units are working properly.
d. Occupied space temperatures and relative humidity levels are within the standards listed below.
i. Temperature range:
 Winter temperatures 70-73 degrees.
 Summer temperatures 74-80 in air-conditioned spaces and 74-85 in non-air-conditioned
spaces.
Outdoor air temperature: 40.1; 55.9 degrees.
Highest temperature – Location: A203; Zabel ; Reading of 77.9; 75.1 degrees.
Lowest temperature – Location: Cafeteria; Todd; Reading of 72; 69.3 degrees.
ii. Relative humidity range is 30% to 60%.
 Non-air-conditioned spaces may be higher on rainy or humid summer humid days.
 All spaces may be less than 30% when the out-door air temperature is less than 32 degrees.
Outdoor relative humidity: 44.3; 43.1%
Highest relative humidity – Location: A105; Todd; Reading of 25.5; 37.1%
Lowest relative humidity – Location: Library; Zabel;Reading of 19.2; 20.3%
Readings not within acceptable standards will result in the creation of a work order, requesting
maintenance to address. (Readings are noted on the attached test data sheet)
Page 3 of 9
Revised 3/21/2011 AMJ
Created 11/2010
IAQ Check List
Building: Lake Zurich Middle School North
Date: May 5, 2014
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
e. Occupied space readings of carbon monoxide (CO) levels are less than 9.0 PPM.
Outdoor Air CO Reading: 0 both days
Highest CO Location: All Room Reading: 0
Lowest CO Location:
Reading:
IAQ Check List
True
False
N/A
If the CO level is greater than 9.0 PPM in any space as measured with a handheld device or “leave-in”
monitor, the space must be cleared of all occupants and steps taken to correct the problem. The issue
will be immediately addressed by maintenance and the Fire Department. (Readings are noted on the
attached test data sheet)
f. CO2 levels in any occupied space are below threshold limits.
i. Perform CO2 check with Gray Wolf or other portable device. Measure four times yearly or more
often if needed. Measure only in fully occupied rooms. Reading should be less than 700 PPM plus
outside air CO2 PPM.
700 PPM + 350; 385 PPM = 1050; 1085 PPM
Assume outside CO2 is 350 if temperature is below 41 degrees and air is not stagnant with no- wind.
Record all occupied space CO2 levels on forms provided. Provide the outdoor CO2 level as well as
the high and low CO2 extremes below:
Outdoor reading: 430; 419; 408; 386; 383 PPM
Highest CO2 reading – Location: A111; Zabel; Reading of 1032; 614 PPM
Lowest CO2 reading – Location: Cafeteria; Losavio; Reading of 504; 460 PPM
ii. If reading is above threshold, check univent and air handling dampers to ensure a value is set to
provide at least 15 cfm of fresh air intake per student based on average space occupancies. If
reading is consistently elevated, then use data logging to monitor CO2 concentrations over time and
look for other sources of problems.
Page 4 of 9
Revised 3/21/2011 AMJ
Created 11/2010
IAQ Check List
Building: Lake Zurich Middle School North
Date: May 5, 2014
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
iii. CO2 levels were checked three months ago.
g.
h.
i.
j.
IAQ Check List
True
False
N/A
iv. CO2 levels on “leave-in” devices, where present, where checked.
No Leave In devices
Offensive odors are not apparent.
If false, list problem areas: Odors were reported in the following areas:
1. Second Floor 6th grade faculty restroom
2. Boy's locker room
Water damage is not evident.
Check for roof leaks, pipe leaks, spills, stained ceiling tiles, etc, visually and with moisture meter. Look
for the source of any water leaks and schedule repairs. Discard porous items such as ceiling tiles if wet
for more than 24 hours. For carpeting, if less than 9 square feet of wet area, shampoo with germicide
and fan dry. For areas greater than 9 square feet, replace carpet with tile in reasonable timeframe. If
carpet is over ACM tile, replace during next unoccupied break time (winter break, spring break,
summer).
If false, record findings and locations here:
Mold or mildew growth is not evident.
If false, record findings and locations here:
All pest management issues are being handled by Integrated Pest Management.
k. No other unresolved concerns or complaints by building personnel are known.
If false, list any pending issues not previously mentioned in this report here: Consistent cleaning
l. There are no incomplete HVAC preventative maintenance (PM) work requests.
If false, list any incomplete HVAC work request here:
6. Bathrooms and General Plumbing
a. All locker or restroom exhaust fans are working.
Inoperable or malfunctioning fans are listed as follows:
Location:
Problem:
Page 5 of 9
Revised 3/21/2011 AMJ
Created 11/2010
IAQ Check List
Building: Lake Zurich Middle School North
Date: May 5, 2014
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
IAQ Check List
True
False
N/A
b. All of the following drain-trap maintenance procedures are being conducted according to the frequency
indicated.
If false, indicate all deviations and locations: Boy's locker room.
i. Water is poured into floor drains once per week (approximately 1 quart of water) or water and a
teaspoon of cooking oil poured into the drain once a month.
The Custodial staff is reminded regularly of these procedures.
ii. Water is poured into sinks at least once per week (about 2 cups of water).
iii. Toilets are flushed at least once per week.
7. Lab Chemicals & Maintenance Supplies
a. Lab chemicals are used with exhaust fans turned on.
b. Lab chemical storage areas have been inspected yearly by ROE and Fire Department.
Record last inspection dates below:
ROE: 10/2013
LZFD:
c. Flammables are not stored with igniters.
d. All chemicals that may react or produce toxic or explosive by-products are separated and maintained in
approved containers stored in approved storage. (e.g. lockable, with appropriate ventilation).
e. Chemical disposal records for all lab chemicals are available for review.
f. All cleaning products used in building contain no/low VOC.
Page 6 of 9
Revised 3/21/2011 AMJ
Created 11/2010
IAQ Check List
Building: Lake Zurich Middle School North
Date: May 5, 2014
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
IAQ Check List
True
False
N/A
List any exceptions:
g. Increased ventilation is considered when installing new carpets, cleaning upholstered furniture,
shampooing carpets, etc.
h. Exhaust ventilation systems in chemical and trash storage areas are turned on and functioning properly.
i.
Portable fuel containers are properly closed.
j.
Power equipment, like snow blowers and lawn mowers, have been serviced and maintained according to
manufacturers’ guidelines.
k. Oil based paints are stored in approved storage cabinets.
No oil based paints allowed in the district.
l. Green Cleaning products and processes are used in this building.
8.
Combustion Appliances
a. Combustion analysis is performed at the start of the heating season on all boilers. Adjustments are
made to the burners to correct any abnormalities and improve efficiency.
Barr Mechanical conducted combustion analysis on February 6, 2014.
b. In rooms that contain combustion appliances, there is no evidence of combustion gas or fuel odors.
If false, record locations here:
c. No leaks, disconnections, and/or deterioration were found on exhaust hoods.
d. Flue components are clean and free of soot.
e. All combustion appliances have flues or exhaust hoods and vent NO2.
i. If false, inspect cooking hoods, chemical hoods. Assure that cooking stoves and appliances are
correctly installed, used, and maintained according to manufacturers’ specifications.
Page 7 of 9
Revised 3/21/2011 AMJ
Created 11/2010
IAQ Check List
Building: Lake Zurich Middle School North
Date: May 5, 2014
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
ii. If not vented, ensure that “leave-in” CO monitors are placed in room. Record locations here:
IAQ Check List
True
False
N/A
iii. CO levels in rooms with combustion appliances are measured and recorded with an IAQ monitor. CO
readings outside of normal CO range will result in an immediate response by maintenance to reduce
CO level or vacating the room/building, if necessary.
Record locations here:
9. Other
a. Paint
No peeling and/or flaking paint found.
If planned building renovation will damage paint or if peeling paint is discovered, lead testing may be
necessary. If peeling paint is found, send email to the building Principal and the Facilities Director
alerting them of the problem. Staff and teachers need to pick up any flakes of paint to prevent
children from being exposed. The Facilities Director will advise the Facilities Coordinator (a Certified
Lead Paint Renovator) to test the paint for lead. Lead paint was discontinued in 1978. Buildings built
after 1978 are exempt from lead paint testing.
If lead is present, required repairs should be done immediately using lead-safe methods and, if
necessary, a licensed lead contractor.
Location(s) of known peeling paint in building:
b. The following preventive measures are being taken to reduce lead exposure.
i. Play areas and toys are cleaned nightly.
ii.
Floors are mopped nightly.
iii. Dust at least weekly.
c. Radon testing is recommended by IEMA every 5 years. Last testing date listed below:
Date: 12/14/2011 - 12/16/2011; Reading of 1.5pCi/L (Highest) in multiple rooms
Page 8 of 9
Revised 3/21/2011 AMJ
Created 11/2010
IAQ Check List
Building: Lake Zurich Middle School North
Date: May 5, 2014
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
IAQ Check List
True
False
N/A
National concern: 4.0 pCi/L
d. The IAQ testing equipment used for this inspection was calibrated and is in good working order.
Equipment Used: Gray Wolf
Last date of calibration: 1/27/14
Page 9 of 9
Revised 3/21/2011 AMJ
Created 11/2010
MSN Spring 2014 IAQ Data
Site
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
Location
Outdoor Air
A100
A102
A103
A104
A105
A106
A107
A108
A109
A110
A111
A112
A113
A114
A115
A200
A202
A203
A204
A205
A206
A207
A208
A209
A210
A211
A212
A213
A214
Date/Time
4/23/2014 8:40:18 AM
4/23/2014 9:37:41 AM
4/23/2014 11:13:38 AM
4/23/2014 11:15:48 AM
4/23/2014 9:40:36 AM
4/23/2014 9:42:44 AM
4/23/2014 9:39:35 AM
4/23/2014 11:38:44 AM
4/23/2014 9:44:21 AM
4/23/2014 9:45:53 AM
4/23/2014 9:53:16 AM
4/23/2014 9:51:02 AM
4/23/2014 10:01:24 AM
4/23/2014 9:56:11 AM
4/23/2014 9:59:35 AM
4/23/2014 9:58:00 AM
4/23/2014 11:41:49 AM
4/23/2014 10:27:47 AM
4/23/2014 10:25:41 AM
4/23/2014 11:19:27 AM
4/23/2014 10:24:04 AM
4/23/2014 12:42:01 PM
4/23/2014 10:18:31 AM
4/23/2014 10:16:28 AM
4/23/2014 10:15:04 AM
4/23/2014 10:11:50 AM
4/23/2014 10:13:33 AM
4/23/2014 10:10:02 AM
4/23/2014 10:07:45 AM
4/23/2014 10:04:36 AM
°F
40.1
74.4
72.6
73.7
74.7
75.1
74.5
75.8
75.4
76.1
75.5
76.1
76.2
76.3
75.9
76
76
76
77.9
74.9
77.6
76.1
77.3
77.4
77.3
77.1
77.1
77
77
76.7
% RH
44.3
25.5
22.3
21.6
24.6
25.5
24.9
21.2
23.9
24.8
22.6
23.7
24
23.7
23
23.3
20.6
21.3
20.7
21.1
21.1
20.8
21
21.9
22.3
22.8
21.6
22.6
22.9
23
CO ppm CO2 ppm Occupant
0
346
0
779
20
0
781
27
0
590
1
0
638
6
0
934
8
0
715
18
0
714
12
0
673
26
0
897
23
0
755
24
0
808
18
0
1032
25
0
865
25
0
872
31
0
844
27
0
656
6
0
862
24
0
697
7
0
701
10
0
771
2
0
707
7
0
743
6
0
937
29
0
855
23
0
944
27
0
862
20
0
950
27
0
1009
25
0
937
19
Window
Yes
Yes
AC
Note
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
North
A215
B100
B102
B104
B106
B108
B110
B112
B114
B116
B118
B124
B126
B200
B201
B202
B204
B205
B205A
B205B
B206
B207
B208
B209
B210
B211
B212
B213
Cafeteria
D100
Gym N
Gym S
Honegger
Library
4/23/2014 10:06:04 AM
4/23/2014 10:50:47 AM
4/23/2014 12:44:54 PM
4/23/2014 11:29:00 AM
4/23/2014 10:44:18 AM
4/23/2014 10:41:12 AM
4/23/2014 10:42:41 AM
4/23/2014 10:39:51 AM
4/23/2014 10:38:30 AM
4/23/2014 11:47:45 AM
4/23/2014 11:49:11 AM
4/23/2014 11:50:55 AM
4/23/2014 11:52:21 AM
4/23/2014 11:21:50 AM
4/23/2014 10:30:21 AM
4/23/2014 12:19:34 PM
4/23/2014 12:21:42 PM
4/23/2014 12:23:17 PM
4/23/2014 12:28:45 PM
4/23/2014 12:26:24 PM
4/23/2014 12:32:30 PM
4/23/2014 12:34:08 PM
4/23/2014 12:35:44 PM
4/23/2014 11:25:02 AM
4/23/2014 12:48:13 PM
4/23/2014 12:37:24 PM
4/23/2014 10:35:22 AM
4/23/2014 12:39:08 PM
4/23/2014 9:35:45 AM
4/23/2014 10:57:42 AM
4/23/2014 11:09:43 AM
4/23/2014 11:11:03 AM
4/23/2014 11:30:36 AM
4/23/2014 10:33:12 AM
76.6
75.7
75.6
74.8
75.9
75.5
75.3
76.1
75.9
75.4
74.6
75.2
76.4
75.4
75.9
72.3
73.3
73.6
74.9
74.3
75.7
76
75.9
75.8
75.4
76
76.9
76.3
72
74.9
72.4
72.1
75
77.4
22.6
20.5
20.7
22.7
20.5
20.7
20.5
21.1
21.1
19.4
19.8
20.1
20.2
21.4
20.3
22.2
22.9
21.5
21.5
22.3
22.7
22.2
21.9
22.1
20.4
21.8
20.3
21.5
23.2
23.4
22.1
21.6
20.7
19.2
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
869
633
729
786
696
689
689
748
747
593
666
694
614
682
697
589
759
675
771
764
881
913
874
880
737
954
702
870
504
1016
631
613
626
555
24
1
6
29
10
25
4
25
21
15
7
5
3
7
7
9
26
2
1
1
21
28
24
24
25
29
9
21
40
22
28
29
1
27
Yes
North
North
North
North
Main office 4/23/2014 9:33:51 AM
Nurse 4/23/2014 11:33:02 AM
Staff Lounge 4/23/2014 10:53:58 AM
Zabel 4/23/2014 11:31:58 AM
72.9
75.3
76
75.1
25
20.3
20.8
20.3
°F
55.9
70.7
72.1
70.1
71.4
69.3
75.1
% RH
43.1
35.7
31.9
36.3
32
37.1
20.3
0
0
0
0
642
606
722
614
6
1
3
1
CO2 Formula: 700 + 350 = 1050
Site
North
North
North
North
North
North
North
Location
Outdoor Air
C130
Losavio
Principal
Schecter
Todd
Zabel
CO2 Formula: 700 + 385 = 1085
Date/Time
4/24/2014 9:51:27 AM
4/24/2014 10:07:20 AM
4/24/2014 10:16:21 AM
4/24/2014 10:05:05 AM
4/24/2014 10:13:38 AM
4/24/2014 10:03:03 AM
4/23/2014 11:31:58 AM
CO ppm CO2 ppm Occupant
0
385
0
473
2
0
460
1
0
482
1
0
485
1
0
510
1
0
614
1
Window
AC
Note
Download