IAQ Check List
Building: Lake Zurich Middle School North
Date: May 15, 2012
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
IAQ Check List
True
False
N/A
1. Ground Level Indoor Inspection
a. Univents are on and air discharge grills are free of obstructions.
If false, send email to building principal and facilities director asking staff to be instructed to keep vents
clear at all times. Record locations here:
2. Ground Level Outdoor Inspection (weather permitting)
a. Univent air intakes are free of obstructions.
If false, record locations here:
b. Filters
i. Medium efficiency filters are installed in all univents.
If false, list locations and create work orders to initiate corrective action.
ii. High efficiency filters are installed in the air handling units.
If false, list locations and create work orders to initiate correction action.
iii. Filters are being changed every six months and the installed date is written on the outer filter casing.
If filter is older than 6 months, list locations and create work orders to initiate corrective action.
In process now.
c. Insects, bird nests, or droppings are not evident near outdoor air intakes.
If false, indicate locations here:
d. Trash dumpsters are located away from doors, windows, and outdoor air intakes.
e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial
plants, exhaust from nearby buildings)
f. Trucks and buses are not allowed to keep their engines idling near the building.
Page 1 of 9
Revised 3/21/2011 AMJ
Created 11/2010
IAQ Check List
Building: Lake Zurich Middle School North
Date: May 15, 2012
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
g. No evidence of drainage problems exist. Water drains away from the building including roof
downspouts.
IAQ Check List
True
False
N/A
h. Sprinklers do not spray directly toward the building or into outdoor air intakes.
i.
j.
Grass clippings from mowers are directed away from the building air intakes.
Our landscapeer is instructed to blow clippings away from the buildings.
Clean walk-off mats are present at exterior entrances.
3. Roof (Inspections conducted weather permitting)
a. Roofing consultant has not found any issues requiring immediate repair.
Most recent roofing inspection date/company: 5-year roofing plan completed 5/25/2010 with C. E.
Crowley & Associates.
b. There is no evidence of water ponding on the roof.
This is a rock ballasted roof. Roof was dry.
c. Intake ventilation units are operating properly and free of debris.
d. All exhaust fans are operating properly and free of debris.
Two exhaust fans were found to be non-operational. One was above the library and the other was
above North. These were addressed with work orders and are in process of being repaired.
e. Air intake dampers are set to allow air flow even at minimum setting.
Due to an Air Handling Unit (AHU) not operating fully, some outside air dampers were opened
further to increase air flow. The unit is scheduled to be repaired May 18 and 19.
f. Insects, birds, animal nests or droppings are not evident near outdoor air intakes.
g. Plumbing stacks and exhaust vents are located away from air intakes.
4. Attic
a. There is no evidence of roof or plumbing leaks.
Page 2 of 9
Revised 3/21/2011 AMJ
Created 11/2010
IAQ Check List
Building: Lake Zurich Middle School North
Date: May 15, 2012
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
IAQ Check List
True
False
N/A
There is no attic.
b. There is no evidence in attic of insects, birds, animals, or nests.
No Attic.
5. General Considerations
a. Classrooms, offices and/or common areas appear recently cleaned.
If examples of poor housekeeping are found, record locations below:
b. Only vacuums with HEPA filters are being used.
c. All supply and exhaust ventilation units are working properly.
d. Occupied space temperatures and relative humidity levels are within the standards listed below.
i. Temperature range:
 Winter temperatures 70-73 degrees.
 Summer temperatures 74-80 in air-conditioned spaces and 74-85 in non-air-conditioned
spaces.
Outdoor air temperature: 76; 70.3; 80.3; 76 degrees.
Highest temperature – Location: B207; A114; A107, A108; A114; Reading of 81.5; 77; 76.8; 86.6
degrees.
Lowest temperature – Location: B114; D100; A103; 83.2; Reading of 78.3; 71.8; 73.1; 83.2
degrees.
ii. Relative humidity range is 30% to 60%.
 Non-air-conditioned spaces may be higher on rainy or humid summer humid days.
 All spaces may be less than 30% when the out-door air temperature is less than 32 degrees.
Outdoor relative humidity: 26; 35.4; 23; 25.2%
Highest relative humidity – Location: B206, B208; A210; A112; A200; Reading of 32.2; 38.3;
Page 3 of 9
Revised 3/21/2011 AMJ
Created 11/2010
IAQ Check List
Building: Lake Zurich Middle School North
Date: May 15, 2012
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
IAQ Check List
True
False
N/A
34.4; 31%
Lowest relative humidity – Location: Zabel; A107; A108: A112;Reading of 21.5; 32.3; 28.5;
27.4%
Readings not within acceptable standards will result in the creation of a work order, requesting
maintenance to address. (Readings are noted on the attached test data sheet)
e. Occupied space readings of carbon monoxide (CO) levels are less than 9.0 PPM.
Outdoor Air CO Reading: 0; .2; 0; 0
Highest CO Location: B206, B209, B212; A114 A200;A105, A110; A115 Reading: .4; .5; .3;
.6
Lowest CO Location: Numerous Rooms; Numerous Rooms; A104, A108; A112, A114
Reading: :0; 0; .1; 0
If the CO level is greater than 9.0 PPM in any space as measured with a handheld device or “leave-in”
monitor, the space must be cleared of all occupants and steps taken to correct the problem. The issue
will be immediately addressed by maintenance and the Fire Department. (Readings are noted on the
attached test data sheet)
f. CO2 levels in any occupied space are below threshold limits.
i. Perform CO2 check with Gray Wolf or other portable device. Measure four times yearly or more
often if needed. Measure only in fully occupied rooms. Reading should be less than 700 PPM plus
outside air CO2 PPM.
700 PPM + 383; 355; 373; 422 PPM = 1083; 1055; 1073; 1122 PPM
Assume outside CO2 is 350 if temperature is below 41 degrees and air is not stagnant with no- wind.
Record all occupied space CO2 levels on forms provided. Provide the outdoor CO2 level as well as
the high and low CO2 extremes below:
Outdoor reading: 383; 355; 373; 422 PPM
Page 4 of 9
Revised 3/21/2011 AMJ
Created 11/2010
IAQ Check List
Building: Lake Zurich Middle School North
Date: May 15, 2012
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
Highest CO2 reading – Location: B208; A114; A112; A114; Reading of 1102; 1923; 1382;
1166 PPM
Lowest CO2 reading – Location: Vastine; Library; A110; A112; Reading of 436; 418; 789;
889 PPM
IAQ Check List
True
False
N/A
In North we have 1/2 of an Air Handling Unit (AHU) not operating correctly. This will be
repaired May 18 and 19. The air is moving but reduced by 1/2. We did increase Outside Air
settings to assist in improving air flow. On the fourth day a chiller was down causing the
temperatures to be higher. I will retest the high reading once the AHU is fully operational.
ii. If reading is above threshold, check univent and air handling dampers to ensure a value is set to
provide at least 15 cfm of fresh air intake per student based on average space occupancies. If
reading is consistently elevated, then use data logging to monitor CO2 concentrations over time and
look for other sources of problems.
iii. CO2 levels were checked three months ago.
iv. CO2 levels on “leave-in” devices, where present, where checked.
No Leave In devices
g. Offensive odors are not apparent.
If false, list problem areas:
h. Water damage is not evident.
Check for roof leaks, pipe leaks, spills, stained ceiling tiles, etc, visually and with moisture meter. Look
for the source of any water leaks and schedule repairs. Discard porous items such as ceiling tiles if wet
for more than 24 hours. For carpeting, if less than 9 square feet of wet area, shampoo with germicide
and fan dry. For areas greater than 9 square feet, replace carpet with tile in reasonable timeframe. If
carpet is over ACM tile, replace during next unoccupied break time (winter break, spring break,
summer).
If false, record findings and locations here: Water has been penetrating through the window in
Todd's office. We have not determined cause to date.
Page 5 of 9
Revised 3/21/2011 AMJ
Created 11/2010
IAQ Check List
Building: Lake Zurich Middle School North
Date: May 15, 2012
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
i.
j.
IAQ Check List
True
False
N/A
Mold or mildew growth is not evident.
If false, record findings and locations here:
All pest management issues are being handled by Integrated Pest Management.
k. No other unresolved concerns or complaints by building personnel are known.
If false, list any pending issues not previously mentioned in this report here:
l. There are no incomplete HVAC preventative maintenance (PM) work requests.
If false, list any incomplete HVAC work request here:
6. Bathrooms and General Plumbing
a. All locker or restroom exhaust fans are working.
Inoperable or malfunctioning fans are listed as follows:
Location:
Problem:
b. All of the following drain-trap maintenance procedures are being conducted according to the frequency
indicated.
If false, indicate all deviations and locations:
i. Water is poured into floor drains once per week (approximately 1 quart of water) or water and a
teaspoon of cooking oil poured into the drain once a month.
The Custodial staff is reminded regularly of these procedures.
ii. Water is poured into sinks at least once per week (about 2 cups of water).
iii. Toilets are flushed at least once per week.
7. Lab Chemicals & Maintenance Supplies
a. Lab chemicals are used with exhaust fans turned on.
b. Lab chemical storage areas have been inspected yearly by ROE and Fire Department.
Record last inspection dates below:
Page 6 of 9
Revised 3/21/2011 AMJ
Created 11/2010
IAQ Check List
Building: Lake Zurich Middle School North
Date: May 15, 2012
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
IAQ Check List
True
False
N/A
ROE: 11/2011
LZFD: 11/2011
c. Flammables are not stored with igniters.
d. All chemicals that may react or produce toxic or explosive by-products are separated and maintained in
approved containers stored in approved storage. (e.g. lockable, with appropriate ventilation).
e. Chemical disposal records for all lab chemicals are available for review.
f. All cleaning products used in building contain no/low VOC.
List any exceptions:
g. Increased ventilation is considered when installing new carpets, cleaning upholstered furniture,
shampooing carpets, etc.
h. Exhaust ventilation systems in chemical and trash storage areas are turned on and functioning properly.
i.
Portable fuel containers are properly closed.
j.
Power equipment, like snow blowers and lawn mowers, have been serviced and maintained according to
manufacturers’ guidelines.
k. Oil based paints are stored in approved storage cabinets.
No oil based paints allowed in the district.
l. Green Cleaning products and processes are used in this building.
Page 7 of 9
Revised 3/21/2011 AMJ
Created 11/2010
IAQ Check List
Building: Lake Zurich Middle School North
Date: May 15, 2012
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
8.
IAQ Check List
True
False
N/A
Combustion Appliances
a. Combustion analysis is performed at the start of the heating season on all boilers. Adjustments are
made to the burners to correct any abnormalities and improve efficiency.
b. In rooms that contain combustion appliances, there is no evidence of combustion gas or fuel odors.
If false, record locations here:
c. No leaks, disconnections, and/or deterioration were found on exhaust hoods.
d. Flue components are clean and free of soot.
e. All combustion appliances have flues or exhaust hoods and vent NO2.
i. If false, inspect cooking hoods, chemical hoods. Assure that cooking stoves and appliances are
correctly installed, used, and maintained according to manufacturers’ specifications.
ii. If not vented, ensure that “leave-in” CO monitors are placed in room. Record locations here:
iii. CO levels in rooms with combustion appliances are measured and recorded with an IAQ monitor. CO
readings outside of normal CO range will result in an immediate response by maintenance to reduce
CO level or vacating the room/building, if necessary.
Record locations here:
9. Other
a. Paint
No peeling and/or flaking paint found.
If planned building renovation will damage paint or if peeling paint is discovered, lead testing may be
necessary. If peeling paint is found, send email to the building Principal and the Facilities Director
alerting them of the problem. Staff and teachers need to pick up any flakes of paint to prevent
children from being exposed. The Facilities Director will advise the Facilities Coordinator (a Certified
Lead Paint Renovator) to test the paint for lead. Lead paint was discontinued in 1978. Buildings built
after 1978 are exempt from lead paint testing.
Page 8 of 9
Revised 3/21/2011 AMJ
Created 11/2010
IAQ Check List
Building: Lake Zurich Middle School North
Date: May 15, 2012
Building Inspection Performed by: Lyle Erstad
Report Compiled by: Lyle Erstad
Check List
IAQ Check List
True
False
N/A
If lead is present, required repairs should be done immediately using lead-safe methods and, if
necessary, a licensed lead contractor.
Location(s) of known peeling paint in building:
b. The following preventive measures are being taken to reduce lead exposure.
i. Play areas and toys are cleaned nightly.
ii.
Floors are mopped nightly.
iii. Dust at least weekly.
c. Radon testing is recommended by IEMA every 5 years. Last testing date listed below:
Date: 12/14 - 16/2012; Reading of 1.5pCi/L (Highest) in multiple rooms
National concern: 4.0 pCi/L
d. The IAQ testing equipment used for this inspection was calibrated and is in good working order.
Equipment Used: Gray Wolf
Last date of calibration: 1-20-2012
Page 9 of 9
Revised 3/21/2011 AMJ
Created 11/2010
Middle School North 2012 Spring IAQ Testing Results
Site
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Location
Outdoor Air
B104
B106
B108
B110
B114
B116
B118
B126
B206
B207
B208
B209
B211
B212
B213
C130
Conf Room
Main office
Nurse
Richter
Vastine
Zabel
Date/Time
5/10/2012 - 1:27:05 PM
5/10/2012 - 1:49:24 PM
5/10/2012 - 1:51:47 PM
5/10/2012 - 1:54:01 PM
5/10/2012 - 1:56:31 PM
5/10/2012 - 1:58:47 PM
5/10/2012 - 2:00:45 PM
5/10/2012 - 2:02:33 PM
5/10/2012 - 2:04:33 PM
5/10/2012 - 2:18:54 PM
5/10/2012 - 2:17:23 PM
5/10/2012 - 2:13:16 PM
5/10/2012 - 2:15:38 PM
5/10/2012 - 2:11:32 PM
5/10/2012 - 2:09:46 PM
5/10/2012 - 2:08:08 PM
5/10/2012 - 1:35:25 PM
5/10/2012 - 1:46:50 PM
5/10/2012 - 1:30:55 PM
5/10/2012 - 1:44:48 PM
5/10/2012 - 1:36:59 PM
5/10/2012 - 1:40:24 PM
5/10/2012 - 1:42:21 PM
Temperature °F
76
79.3
79.9
79.2
79.8
78.3
78.9
79
79.2
81.2
81.5
80.5
80.7
80
79.7
79.4
80.2
79.5
79.6
79.6
80.3
79.6
79.3
Relative Humidity %RH
26
29.8
29.9
28.3
27.9
28.3
30.7
30.1
32.1
32.2
31.1
32.2
31.2
31.4
30.7
32.1
23.8
22.2
24
23.2
23.9
22
21.5
Carbon Monoxide ppm
0
0
0.1
0.2
0.1
0.3
0
0.3
0.2
0.4
0.2
0.3
0.4
0.3
0.4
0.2
0.1
0.2
0.1
0
0.1
0.1
0
Carbon Dioxide ppm
383
852
940
706
668
796
1023
918
1050
1036
978
1102
1040
1021
993
1043
606
469
492
475
575
436
444
Occupant Windows
Location
Outdoor Air
A100
A102
A103
A104
A105
A106
A107
A108
A109
A110
A111
A112
A113
A114
Date/Time
5/11/2012 - 10:48:10 AM
5/11/2012 - 10:57:59 AM
5/11/2012 - 11:00:56 AM
5/11/2012 - 11:02:54 AM
5/11/2012 - 11:05:11 AM
5/11/2012 - 11:19:04 AM
5/11/2012 - 11:13:59 AM
5/11/2012 - 11:34:09 AM
5/11/2012 - 11:24:00 AM
5/11/2012 - 11:29:47 AM
5/11/2012 - 11:36:10 AM
5/11/2012 - 11:31:29 AM
5/11/2012 - 11:40:08 AM
5/11/2012 - 11:55:38 AM
5/11/2012 - 11:49:18 AM
Temperature °F
70.3
73.3
73.6
73.1
73.4
75.1
74.9
74.9
75.9
76.1
75.3
75.9
75.3
76
77
Relative Humidity %RH
35.4
35
35.9
33.3
34.2
34.5
34.5
32.3
34
33.6
34
33.3
34.4
33.4
36.8
Carbon Monoxide ppm
0.2
0.2
0.3
0.3
0.2
0.3
0.2
0.3
0.3
0.4
0.2
0.2
0.2
0.2
0.5
Carbon Dioxide ppm
355
1092
1212
927
1109
1243
1161
968
1098
1232
1196
847
1382
1218
1923
Occupant
11
24
16
1
18
24
19
41
26
28
13
11
8
5
6
2
2
4
2
1
1
1
Yes
Yes
Yes
Formula: 700 + 383 = 1083
Site
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
25
24
1
13
14
22
9
20
20
19
21
26
26
18
Window
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
A115
A200
A202
A203
A205
A206
A207
A208
A209
A210
A211
A212
A213
A214
A215
B100
B202
B203
B204
B205
B205A
B208
B208
B210
Cafeteria
D100
Gymnasium
Library
Staff Lounge
Todd
5/11/2012 - 11:59:09 AM
5/11/2012 - 12:41:04 PM
5/11/2012 - 12:34:19 PM
5/11/2012 - 12:58:42 PM
5/11/2012 - 12:05:55 PM
5/11/2012 - 1:01:09 PM
5/11/2012 - 12:03:59 PM
5/11/2012 - 1:03:40 PM
5/11/2012 - 12:02:08 PM
5/11/2012 - 1:09:46 PM
5/11/2012 - 1:05:55 PM
5/11/2012 - 1:13:26 PM
5/11/2012 - 1:11:27 PM
5/11/2012 - 1:15:45 PM
5/11/2012 - 1:18:39 PM
5/11/2012 - 10:55:03 AM
5/11/2012 - 12:12:00 PM
5/11/2012 - 1:41:21 PM
5/11/2012 - 12:27:56 PM
5/11/2012 - 12:13:35 PM
5/11/2012 - 1:35:12 PM
5/11/2012 - 12:25:01 PM
5/11/2012 - 12:25:01 PM
5/11/2012 - 1:08:14 PM
5/11/2012 - 12:48:24 PM
5/11/2012 - 12:53:15 PM
5/11/2012 - 12:51:03 PM
5/11/2012 - 1:38:48 PM
5/11/2012 - 1:26:34 PM
5/11/2012 - 1:30:18 PM
76.6
75.6
75
73.3
74.7
74
74.8
73.8
74.9
73.6
74.1
74.8
74.1
74.3
73.6
72.8
74.4
74.3
74.5
74.6
74.3
74.4
74.4
74.2
73.4
71.8
71.9
74.4
74.3
74.5
34.1
35.1
35.4
35.9
33.6
36.7
32.6
36.6
33.1
38.3
36.4
36.6
37.2
36.2
36.3
33.8
33.6
36
35.1
34.1
38.1
36.2
36.2
38.1
34.5
35
34.5
34.9
37
34.6
0.3
0.5
0.3
0.2
0.2
0.3
0.2
0.2
0.3
0.2
0.3
0.3
0.3
0.3
0.3
0.2
0.3
0.2
0.2
0.3
0
0.2
0.2
0.2
0.2
0.2
0.3
0
0.2
0
1231
1068
1005
728
970
874
843
825
1035
1007
899
930
913
862
886
919
882
782
956
946
1006
1038
1038
1015
518
954
446
418
781
436
24
21
22
1
7
22
11
27
22
28
24
22
24
26
25
2
12
5
24
6
4
30
30
28
250
21
23
25
3
1
Location
Date/Time
Outdoor Air 5/14/2012 - 11:47:10 AM
A102 5/14/2012 - 11:52:31 AM
A104 5/14/2012 - 11:58:19 AM
A105 5/14/2012 - 12:01:23 PM
A106 5/14/2012 - 11:59:58 AM
A107 5/14/2012 - 12:03:20 PM
A108 5/14/2012 - 12:08:09 PM
A109 5/14/2012 - 12:05:55 PM
A110 5/14/2012 - 12:09:56 PM
A112 5/11/2012 - 11:40:08 AM
Temperature °F
80.3
78.2
76
76.4
76.3
76.8
76.8
76.4
75.9
75.3
Relative Humidity %RH
23
29.3
28.7
29.5
29.2
28.9
28.5
29.6
28.7
34.4
Carbon Monoxide ppm
0
0
0.1
0.3
0.2
0.2
0.1
0.2
0.3
0.2
Carbon Dioxide ppm
373
1082
1013
1047
1025
926
806
1102
789
1382
Occupant
Yes
Yes
Yes
Yes
Formula: 700 + 355 = 1055
Site
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
24
8
10
20
10
16
20
18
26
Window
Formula: 700 + 373 = 1073
Site
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Middle School North
Formula: 700 + 422 = 1122
Location
Date/Time
Temperature °F Relative Humidity %RH
Carbon Monoxide ppm
Carbon Dioxide ppm Occupant Window
Outdoor Air
5/15/2012 11:56
88.7
25.2
0
422
A109
5/15/2012 12:10
84.7
30.1
0.3
904
21
A111
5/15/2012 12:11
84.3
29.8
0.5
1004
24
Yes
A112
5/15/2012 12:00
85.5
27.4
0
889
26
A113
5/15/2012 12:06
85.6
28.6
0.4
903
26
A114
5/15/2012 12:02
86.6
28.4
0
1166
28
Yes
A115
5/15/2012 12:04
85.5
28.9
0.6
999
25
A200
5/15/2012 12:14
83.2
31
0.1
992
21
Yes
Download