IAQ Check List Building: Lake Zurich Middle School North Date: May 15, 2012 Building Inspection Performed by: Lyle Erstad Report Compiled by: Lyle Erstad Check List IAQ Check List True False N/A 1. Ground Level Indoor Inspection a. Univents are on and air discharge grills are free of obstructions. If false, send email to building principal and facilities director asking staff to be instructed to keep vents clear at all times. Record locations here: 2. Ground Level Outdoor Inspection (weather permitting) a. Univent air intakes are free of obstructions. If false, record locations here: b. Filters i. Medium efficiency filters are installed in all univents. If false, list locations and create work orders to initiate corrective action. ii. High efficiency filters are installed in the air handling units. If false, list locations and create work orders to initiate correction action. iii. Filters are being changed every six months and the installed date is written on the outer filter casing. If filter is older than 6 months, list locations and create work orders to initiate corrective action. In process now. c. Insects, bird nests, or droppings are not evident near outdoor air intakes. If false, indicate locations here: d. Trash dumpsters are located away from doors, windows, and outdoor air intakes. e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings) f. Trucks and buses are not allowed to keep their engines idling near the building. Page 1 of 9 Revised 3/21/2011 AMJ Created 11/2010 IAQ Check List Building: Lake Zurich Middle School North Date: May 15, 2012 Building Inspection Performed by: Lyle Erstad Report Compiled by: Lyle Erstad Check List g. No evidence of drainage problems exist. Water drains away from the building including roof downspouts. IAQ Check List True False N/A h. Sprinklers do not spray directly toward the building or into outdoor air intakes. i. j. Grass clippings from mowers are directed away from the building air intakes. Our landscapeer is instructed to blow clippings away from the buildings. Clean walk-off mats are present at exterior entrances. 3. Roof (Inspections conducted weather permitting) a. Roofing consultant has not found any issues requiring immediate repair. Most recent roofing inspection date/company: 5-year roofing plan completed 5/25/2010 with C. E. Crowley & Associates. b. There is no evidence of water ponding on the roof. This is a rock ballasted roof. Roof was dry. c. Intake ventilation units are operating properly and free of debris. d. All exhaust fans are operating properly and free of debris. Two exhaust fans were found to be non-operational. One was above the library and the other was above North. These were addressed with work orders and are in process of being repaired. e. Air intake dampers are set to allow air flow even at minimum setting. Due to an Air Handling Unit (AHU) not operating fully, some outside air dampers were opened further to increase air flow. The unit is scheduled to be repaired May 18 and 19. f. Insects, birds, animal nests or droppings are not evident near outdoor air intakes. g. Plumbing stacks and exhaust vents are located away from air intakes. 4. Attic a. There is no evidence of roof or plumbing leaks. Page 2 of 9 Revised 3/21/2011 AMJ Created 11/2010 IAQ Check List Building: Lake Zurich Middle School North Date: May 15, 2012 Building Inspection Performed by: Lyle Erstad Report Compiled by: Lyle Erstad Check List IAQ Check List True False N/A There is no attic. b. There is no evidence in attic of insects, birds, animals, or nests. No Attic. 5. General Considerations a. Classrooms, offices and/or common areas appear recently cleaned. If examples of poor housekeeping are found, record locations below: b. Only vacuums with HEPA filters are being used. c. All supply and exhaust ventilation units are working properly. d. Occupied space temperatures and relative humidity levels are within the standards listed below. i. Temperature range: Winter temperatures 70-73 degrees. Summer temperatures 74-80 in air-conditioned spaces and 74-85 in non-air-conditioned spaces. Outdoor air temperature: 76; 70.3; 80.3; 76 degrees. Highest temperature – Location: B207; A114; A107, A108; A114; Reading of 81.5; 77; 76.8; 86.6 degrees. Lowest temperature – Location: B114; D100; A103; 83.2; Reading of 78.3; 71.8; 73.1; 83.2 degrees. ii. Relative humidity range is 30% to 60%. Non-air-conditioned spaces may be higher on rainy or humid summer humid days. All spaces may be less than 30% when the out-door air temperature is less than 32 degrees. Outdoor relative humidity: 26; 35.4; 23; 25.2% Highest relative humidity – Location: B206, B208; A210; A112; A200; Reading of 32.2; 38.3; Page 3 of 9 Revised 3/21/2011 AMJ Created 11/2010 IAQ Check List Building: Lake Zurich Middle School North Date: May 15, 2012 Building Inspection Performed by: Lyle Erstad Report Compiled by: Lyle Erstad Check List IAQ Check List True False N/A 34.4; 31% Lowest relative humidity – Location: Zabel; A107; A108: A112;Reading of 21.5; 32.3; 28.5; 27.4% Readings not within acceptable standards will result in the creation of a work order, requesting maintenance to address. (Readings are noted on the attached test data sheet) e. Occupied space readings of carbon monoxide (CO) levels are less than 9.0 PPM. Outdoor Air CO Reading: 0; .2; 0; 0 Highest CO Location: B206, B209, B212; A114 A200;A105, A110; A115 Reading: .4; .5; .3; .6 Lowest CO Location: Numerous Rooms; Numerous Rooms; A104, A108; A112, A114 Reading: :0; 0; .1; 0 If the CO level is greater than 9.0 PPM in any space as measured with a handheld device or “leave-in” monitor, the space must be cleared of all occupants and steps taken to correct the problem. The issue will be immediately addressed by maintenance and the Fire Department. (Readings are noted on the attached test data sheet) f. CO2 levels in any occupied space are below threshold limits. i. Perform CO2 check with Gray Wolf or other portable device. Measure four times yearly or more often if needed. Measure only in fully occupied rooms. Reading should be less than 700 PPM plus outside air CO2 PPM. 700 PPM + 383; 355; 373; 422 PPM = 1083; 1055; 1073; 1122 PPM Assume outside CO2 is 350 if temperature is below 41 degrees and air is not stagnant with no- wind. Record all occupied space CO2 levels on forms provided. Provide the outdoor CO2 level as well as the high and low CO2 extremes below: Outdoor reading: 383; 355; 373; 422 PPM Page 4 of 9 Revised 3/21/2011 AMJ Created 11/2010 IAQ Check List Building: Lake Zurich Middle School North Date: May 15, 2012 Building Inspection Performed by: Lyle Erstad Report Compiled by: Lyle Erstad Check List Highest CO2 reading – Location: B208; A114; A112; A114; Reading of 1102; 1923; 1382; 1166 PPM Lowest CO2 reading – Location: Vastine; Library; A110; A112; Reading of 436; 418; 789; 889 PPM IAQ Check List True False N/A In North we have 1/2 of an Air Handling Unit (AHU) not operating correctly. This will be repaired May 18 and 19. The air is moving but reduced by 1/2. We did increase Outside Air settings to assist in improving air flow. On the fourth day a chiller was down causing the temperatures to be higher. I will retest the high reading once the AHU is fully operational. ii. If reading is above threshold, check univent and air handling dampers to ensure a value is set to provide at least 15 cfm of fresh air intake per student based on average space occupancies. If reading is consistently elevated, then use data logging to monitor CO2 concentrations over time and look for other sources of problems. iii. CO2 levels were checked three months ago. iv. CO2 levels on “leave-in” devices, where present, where checked. No Leave In devices g. Offensive odors are not apparent. If false, list problem areas: h. Water damage is not evident. Check for roof leaks, pipe leaks, spills, stained ceiling tiles, etc, visually and with moisture meter. Look for the source of any water leaks and schedule repairs. Discard porous items such as ceiling tiles if wet for more than 24 hours. For carpeting, if less than 9 square feet of wet area, shampoo with germicide and fan dry. For areas greater than 9 square feet, replace carpet with tile in reasonable timeframe. If carpet is over ACM tile, replace during next unoccupied break time (winter break, spring break, summer). If false, record findings and locations here: Water has been penetrating through the window in Todd's office. We have not determined cause to date. Page 5 of 9 Revised 3/21/2011 AMJ Created 11/2010 IAQ Check List Building: Lake Zurich Middle School North Date: May 15, 2012 Building Inspection Performed by: Lyle Erstad Report Compiled by: Lyle Erstad Check List i. j. IAQ Check List True False N/A Mold or mildew growth is not evident. If false, record findings and locations here: All pest management issues are being handled by Integrated Pest Management. k. No other unresolved concerns or complaints by building personnel are known. If false, list any pending issues not previously mentioned in this report here: l. There are no incomplete HVAC preventative maintenance (PM) work requests. If false, list any incomplete HVAC work request here: 6. Bathrooms and General Plumbing a. All locker or restroom exhaust fans are working. Inoperable or malfunctioning fans are listed as follows: Location: Problem: b. All of the following drain-trap maintenance procedures are being conducted according to the frequency indicated. If false, indicate all deviations and locations: i. Water is poured into floor drains once per week (approximately 1 quart of water) or water and a teaspoon of cooking oil poured into the drain once a month. The Custodial staff is reminded regularly of these procedures. ii. Water is poured into sinks at least once per week (about 2 cups of water). iii. Toilets are flushed at least once per week. 7. Lab Chemicals & Maintenance Supplies a. Lab chemicals are used with exhaust fans turned on. b. Lab chemical storage areas have been inspected yearly by ROE and Fire Department. Record last inspection dates below: Page 6 of 9 Revised 3/21/2011 AMJ Created 11/2010 IAQ Check List Building: Lake Zurich Middle School North Date: May 15, 2012 Building Inspection Performed by: Lyle Erstad Report Compiled by: Lyle Erstad Check List IAQ Check List True False N/A ROE: 11/2011 LZFD: 11/2011 c. Flammables are not stored with igniters. d. All chemicals that may react or produce toxic or explosive by-products are separated and maintained in approved containers stored in approved storage. (e.g. lockable, with appropriate ventilation). e. Chemical disposal records for all lab chemicals are available for review. f. All cleaning products used in building contain no/low VOC. List any exceptions: g. Increased ventilation is considered when installing new carpets, cleaning upholstered furniture, shampooing carpets, etc. h. Exhaust ventilation systems in chemical and trash storage areas are turned on and functioning properly. i. Portable fuel containers are properly closed. j. Power equipment, like snow blowers and lawn mowers, have been serviced and maintained according to manufacturers’ guidelines. k. Oil based paints are stored in approved storage cabinets. No oil based paints allowed in the district. l. Green Cleaning products and processes are used in this building. Page 7 of 9 Revised 3/21/2011 AMJ Created 11/2010 IAQ Check List Building: Lake Zurich Middle School North Date: May 15, 2012 Building Inspection Performed by: Lyle Erstad Report Compiled by: Lyle Erstad Check List 8. IAQ Check List True False N/A Combustion Appliances a. Combustion analysis is performed at the start of the heating season on all boilers. Adjustments are made to the burners to correct any abnormalities and improve efficiency. b. In rooms that contain combustion appliances, there is no evidence of combustion gas or fuel odors. If false, record locations here: c. No leaks, disconnections, and/or deterioration were found on exhaust hoods. d. Flue components are clean and free of soot. e. All combustion appliances have flues or exhaust hoods and vent NO2. i. If false, inspect cooking hoods, chemical hoods. Assure that cooking stoves and appliances are correctly installed, used, and maintained according to manufacturers’ specifications. ii. If not vented, ensure that “leave-in” CO monitors are placed in room. Record locations here: iii. CO levels in rooms with combustion appliances are measured and recorded with an IAQ monitor. CO readings outside of normal CO range will result in an immediate response by maintenance to reduce CO level or vacating the room/building, if necessary. Record locations here: 9. Other a. Paint No peeling and/or flaking paint found. If planned building renovation will damage paint or if peeling paint is discovered, lead testing may be necessary. If peeling paint is found, send email to the building Principal and the Facilities Director alerting them of the problem. Staff and teachers need to pick up any flakes of paint to prevent children from being exposed. The Facilities Director will advise the Facilities Coordinator (a Certified Lead Paint Renovator) to test the paint for lead. Lead paint was discontinued in 1978. Buildings built after 1978 are exempt from lead paint testing. Page 8 of 9 Revised 3/21/2011 AMJ Created 11/2010 IAQ Check List Building: Lake Zurich Middle School North Date: May 15, 2012 Building Inspection Performed by: Lyle Erstad Report Compiled by: Lyle Erstad Check List IAQ Check List True False N/A If lead is present, required repairs should be done immediately using lead-safe methods and, if necessary, a licensed lead contractor. Location(s) of known peeling paint in building: b. The following preventive measures are being taken to reduce lead exposure. i. Play areas and toys are cleaned nightly. ii. Floors are mopped nightly. iii. Dust at least weekly. c. Radon testing is recommended by IEMA every 5 years. Last testing date listed below: Date: 12/14 - 16/2012; Reading of 1.5pCi/L (Highest) in multiple rooms National concern: 4.0 pCi/L d. The IAQ testing equipment used for this inspection was calibrated and is in good working order. Equipment Used: Gray Wolf Last date of calibration: 1-20-2012 Page 9 of 9 Revised 3/21/2011 AMJ Created 11/2010 Middle School North 2012 Spring IAQ Testing Results Site Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Location Outdoor Air B104 B106 B108 B110 B114 B116 B118 B126 B206 B207 B208 B209 B211 B212 B213 C130 Conf Room Main office Nurse Richter Vastine Zabel Date/Time 5/10/2012 - 1:27:05 PM 5/10/2012 - 1:49:24 PM 5/10/2012 - 1:51:47 PM 5/10/2012 - 1:54:01 PM 5/10/2012 - 1:56:31 PM 5/10/2012 - 1:58:47 PM 5/10/2012 - 2:00:45 PM 5/10/2012 - 2:02:33 PM 5/10/2012 - 2:04:33 PM 5/10/2012 - 2:18:54 PM 5/10/2012 - 2:17:23 PM 5/10/2012 - 2:13:16 PM 5/10/2012 - 2:15:38 PM 5/10/2012 - 2:11:32 PM 5/10/2012 - 2:09:46 PM 5/10/2012 - 2:08:08 PM 5/10/2012 - 1:35:25 PM 5/10/2012 - 1:46:50 PM 5/10/2012 - 1:30:55 PM 5/10/2012 - 1:44:48 PM 5/10/2012 - 1:36:59 PM 5/10/2012 - 1:40:24 PM 5/10/2012 - 1:42:21 PM Temperature °F 76 79.3 79.9 79.2 79.8 78.3 78.9 79 79.2 81.2 81.5 80.5 80.7 80 79.7 79.4 80.2 79.5 79.6 79.6 80.3 79.6 79.3 Relative Humidity %RH 26 29.8 29.9 28.3 27.9 28.3 30.7 30.1 32.1 32.2 31.1 32.2 31.2 31.4 30.7 32.1 23.8 22.2 24 23.2 23.9 22 21.5 Carbon Monoxide ppm 0 0 0.1 0.2 0.1 0.3 0 0.3 0.2 0.4 0.2 0.3 0.4 0.3 0.4 0.2 0.1 0.2 0.1 0 0.1 0.1 0 Carbon Dioxide ppm 383 852 940 706 668 796 1023 918 1050 1036 978 1102 1040 1021 993 1043 606 469 492 475 575 436 444 Occupant Windows Location Outdoor Air A100 A102 A103 A104 A105 A106 A107 A108 A109 A110 A111 A112 A113 A114 Date/Time 5/11/2012 - 10:48:10 AM 5/11/2012 - 10:57:59 AM 5/11/2012 - 11:00:56 AM 5/11/2012 - 11:02:54 AM 5/11/2012 - 11:05:11 AM 5/11/2012 - 11:19:04 AM 5/11/2012 - 11:13:59 AM 5/11/2012 - 11:34:09 AM 5/11/2012 - 11:24:00 AM 5/11/2012 - 11:29:47 AM 5/11/2012 - 11:36:10 AM 5/11/2012 - 11:31:29 AM 5/11/2012 - 11:40:08 AM 5/11/2012 - 11:55:38 AM 5/11/2012 - 11:49:18 AM Temperature °F 70.3 73.3 73.6 73.1 73.4 75.1 74.9 74.9 75.9 76.1 75.3 75.9 75.3 76 77 Relative Humidity %RH 35.4 35 35.9 33.3 34.2 34.5 34.5 32.3 34 33.6 34 33.3 34.4 33.4 36.8 Carbon Monoxide ppm 0.2 0.2 0.3 0.3 0.2 0.3 0.2 0.3 0.3 0.4 0.2 0.2 0.2 0.2 0.5 Carbon Dioxide ppm 355 1092 1212 927 1109 1243 1161 968 1098 1232 1196 847 1382 1218 1923 Occupant 11 24 16 1 18 24 19 41 26 28 13 11 8 5 6 2 2 4 2 1 1 1 Yes Yes Yes Formula: 700 + 383 = 1083 Site Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North 25 24 1 13 14 22 9 20 20 19 21 26 26 18 Window Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North A115 A200 A202 A203 A205 A206 A207 A208 A209 A210 A211 A212 A213 A214 A215 B100 B202 B203 B204 B205 B205A B208 B208 B210 Cafeteria D100 Gymnasium Library Staff Lounge Todd 5/11/2012 - 11:59:09 AM 5/11/2012 - 12:41:04 PM 5/11/2012 - 12:34:19 PM 5/11/2012 - 12:58:42 PM 5/11/2012 - 12:05:55 PM 5/11/2012 - 1:01:09 PM 5/11/2012 - 12:03:59 PM 5/11/2012 - 1:03:40 PM 5/11/2012 - 12:02:08 PM 5/11/2012 - 1:09:46 PM 5/11/2012 - 1:05:55 PM 5/11/2012 - 1:13:26 PM 5/11/2012 - 1:11:27 PM 5/11/2012 - 1:15:45 PM 5/11/2012 - 1:18:39 PM 5/11/2012 - 10:55:03 AM 5/11/2012 - 12:12:00 PM 5/11/2012 - 1:41:21 PM 5/11/2012 - 12:27:56 PM 5/11/2012 - 12:13:35 PM 5/11/2012 - 1:35:12 PM 5/11/2012 - 12:25:01 PM 5/11/2012 - 12:25:01 PM 5/11/2012 - 1:08:14 PM 5/11/2012 - 12:48:24 PM 5/11/2012 - 12:53:15 PM 5/11/2012 - 12:51:03 PM 5/11/2012 - 1:38:48 PM 5/11/2012 - 1:26:34 PM 5/11/2012 - 1:30:18 PM 76.6 75.6 75 73.3 74.7 74 74.8 73.8 74.9 73.6 74.1 74.8 74.1 74.3 73.6 72.8 74.4 74.3 74.5 74.6 74.3 74.4 74.4 74.2 73.4 71.8 71.9 74.4 74.3 74.5 34.1 35.1 35.4 35.9 33.6 36.7 32.6 36.6 33.1 38.3 36.4 36.6 37.2 36.2 36.3 33.8 33.6 36 35.1 34.1 38.1 36.2 36.2 38.1 34.5 35 34.5 34.9 37 34.6 0.3 0.5 0.3 0.2 0.2 0.3 0.2 0.2 0.3 0.2 0.3 0.3 0.3 0.3 0.3 0.2 0.3 0.2 0.2 0.3 0 0.2 0.2 0.2 0.2 0.2 0.3 0 0.2 0 1231 1068 1005 728 970 874 843 825 1035 1007 899 930 913 862 886 919 882 782 956 946 1006 1038 1038 1015 518 954 446 418 781 436 24 21 22 1 7 22 11 27 22 28 24 22 24 26 25 2 12 5 24 6 4 30 30 28 250 21 23 25 3 1 Location Date/Time Outdoor Air 5/14/2012 - 11:47:10 AM A102 5/14/2012 - 11:52:31 AM A104 5/14/2012 - 11:58:19 AM A105 5/14/2012 - 12:01:23 PM A106 5/14/2012 - 11:59:58 AM A107 5/14/2012 - 12:03:20 PM A108 5/14/2012 - 12:08:09 PM A109 5/14/2012 - 12:05:55 PM A110 5/14/2012 - 12:09:56 PM A112 5/11/2012 - 11:40:08 AM Temperature °F 80.3 78.2 76 76.4 76.3 76.8 76.8 76.4 75.9 75.3 Relative Humidity %RH 23 29.3 28.7 29.5 29.2 28.9 28.5 29.6 28.7 34.4 Carbon Monoxide ppm 0 0 0.1 0.3 0.2 0.2 0.1 0.2 0.3 0.2 Carbon Dioxide ppm 373 1082 1013 1047 1025 926 806 1102 789 1382 Occupant Yes Yes Yes Yes Formula: 700 + 355 = 1055 Site Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North 24 8 10 20 10 16 20 18 26 Window Formula: 700 + 373 = 1073 Site Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Middle School North Formula: 700 + 422 = 1122 Location Date/Time Temperature °F Relative Humidity %RH Carbon Monoxide ppm Carbon Dioxide ppm Occupant Window Outdoor Air 5/15/2012 11:56 88.7 25.2 0 422 A109 5/15/2012 12:10 84.7 30.1 0.3 904 21 A111 5/15/2012 12:11 84.3 29.8 0.5 1004 24 Yes A112 5/15/2012 12:00 85.5 27.4 0 889 26 A113 5/15/2012 12:06 85.6 28.6 0.4 903 26 A114 5/15/2012 12:02 86.6 28.4 0 1166 28 Yes A115 5/15/2012 12:04 85.5 28.9 0.6 999 25 A200 5/15/2012 12:14 83.2 31 0.1 992 21 Yes