Metalux

advertisement
Metalux
D ES C R IPTION
Type
Catalog #
ArcLine is a premium grade specification lensed troffer series. This
innovative, high quality luminaire is dedicated to the latest lamp and
micro electronic ballast technology for optimal performance and energy
efficiency. The ArcLine is compatible with all of today’s popular ceiling
systems and is available with a number of options and accessories for
application versatility.
Project
Date
Comments
Prepared by
The ArcLine series features efficiency, quality and performance. The
series is an excellent choice for commercial office spaces, schools,
hospitals or retail merchandising areas.
SPE C IFIC A TION FEA T U R E S
C on s t r u c t i o n
E le ctrica l
H inging/Latching
Rigid housing is die formed of
code gauge prime cold rolled steel
and features full length die-formed
stiffeners and unibody endplate
for added strength. Side flanges
are hemmed. Innovative design
provides superior lens brightness
uniformity and visual comfort.
Die formed captive lampholder
brackets fully enclose lampholder
wiring permitting easy lampholder
replacement. Unibody endplates
are securely attached with
interlocking tabs and screws. Four
auxiliary fixture end suspension
points provided. KOs for
continuous row wiring. Endplates
have integral Gridlock feature for
safety and convenience.
Ballasts are CBM/ETL Class “P” and
are positively secured by mounting
bolts. Rotor lock lampholders.
UL/CUL listed. Suitable for damp
locations.**
Positive cam action steel latches
with baked white enamel finish.
Safety-lock T-hinges allow hinging
and latching either side. Door
assembly hinges down for easy
access from below without tools.
F in ish
Multistage, iron phosphate
pretreatment ensures maximum
bonding and rust inhibition.
Housing and ballast cover finished
with new 90% reflective white
enamel for superior performance.
Frame/Shielding
Die formed, heavy gauge, flat
steel door with reinforced mitered
corners and paint after fabrication,
baked matte white enamel finish.
Positive light seals. Light stabilized,
acrylic frosted lens.
2ALN
328T8
332
2' X 4' TROFFER
3 T8 LAMPS
Specification Architectural
Troffer
3-1/4"
[83mm]
For Use In Insulated
Ceilings
23-3/4" [603mm]
MOUNTING D A TA
D OOR F RA ME S
ALN
Flat, White Steel
47-15/16" [1218mm]
ENERGY DATA
23-3/4"
[603mm]
Input Watts:
EB Ballast & STD Lamps
328T8 (66), 332 (80)
L A MP CONF IGURA T IONS
3-1/4" [83mm]
*Reference the lamp/ballast data in the
Technical Section for specific lamp/ballast
requirements.
**Consult Pre Sales Technical Support.
****When ordering Flange Kit for
installation in drywall ceilings, see options
and accessories compatibility section and
ordering logic.
23-3/4" [603mm]
C EILING C OM PA TIB IL I T Y
G
Grid/Lay-in
Standard
G
Concealed T
G
Slot Grid
Ceiling
Type
Trim
Type
Exposed Grid
Concealed T
Slot Grid
G
G
G
(Verify compatibility/ consult
factory.)
LAMPS CONTAIN MERCURY. DISPOSE ACCORDING
TO LOCAL, STATE OR FEDERAL LAWS
Safe and convenient means of
disconnecting power.
ADF122021
2015-06-09 11:42:23
2 ALN T 8
PH OTOM ETR IC S
90˚
75˚
900
60˚
1800
45˚
2700
0˚
15˚
30˚
2ALNG-332-UNVEB81-U
Electronic Ballast
(3) F32T8 Lamps
2950 Lumens
Spacing criterion:
(II) 1.2 x mounting
height, (⊥) 1.3 x
mounting height
Efficiency 84.7%
Lumens: 7494
LER = FL77
Yearly Cost of
1000 lumens, 3000
hrs at .08 KWH =
$3.12
Test Report:
2ALNG-332-UNVEB81-U.IES
Candlepower
Along II
2571
2567
2524
2463
2368
2251
2106
1944
1777
1583
1388
1192
990
794
605
418
255
110
0
Angle
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
45°
2571
2561
2529
2476
2398
2303
2191
2055
1901
1735
1550
1356
1151
942
744
547
361
170
0
Across ⊥
2571
2573
2550
2504
2449
2373
2274
2160
2024
1858
1676
1478
1274
1053
838
627
409
170
0
C o e f fi c i e n t s o f U t i l i z a t i o n
rc
rw
RCR
0
1
2
3
4
5
6
7
8
9
10
Effective floor cavity reflectance
80%
70%
70 50 30 10
70 50 30 10
101
92
83
76
69
64
59
55
51
47
44
101
88
76
67
59
53
47
43
39
36
33
101 101
84 81
70 65
60 54
52 46
45 39
40 34
35 30
32 27
29 24
26 22
98
89
81
74
67
62
57
53
49
46
43
98
86
75
65
58
52
47
42
39
35
33
98
82
69
59
51
45
39
35
32
29
26
98
79
65
54
45
39
34
30
27
24
22
20%
50%
50 30 10
30%
50 30 10
50
94
82
72
63
56
50
45
41
37
34
32
90
79
69
61
54
48
44
40
36
34
31
86
76
66
58
52
47
42
39
35
33
30
94
79
67
57
50
44
39
35
31
28
26
94
77
63
53
45
39
34
30
27
24
22
90
76
65
56
48
43
38
34
31
28
26
Zonal Lumen Summary
Luminance Data
Zone
0-30
0-40
0-60
0-90
0-180
Angle
in Deg
45
55
65
75
85
Lumens
2008
3294
5830
7494
7494
%Lamp
22.7
37.2
65.9
84.7
84.7
%Fixture
26.8
43.9
77.8
100.0
100.0
Average
0-Deg
cd/sm
3294
3044
2752
2389
1854
Eaton
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.eaton.com/lighting
90
74
62
52
44
38
33
30
27
24
22
10%
30 10
Average
45-Deg
cd/sm
3592
3443
3276
3068
2499
86
74
63
54
47
42
37
33
30
28
25
86
72
60
51
44
38
33
29
26
24
22
0%
0
85
70
58
49
42
36
31
28
25
22
20
Average
90-Deg
cd/sm
3901
3853
3758
3774
2701
Specifications and
dimensions subject to
change without notice.
ADF122021
2015-06-09 11:42:23
2 ALN T 8
ORDER ING INFOR M A TION
SAMPLE NUMBER: 2ALNG-332-UNV-EB81-U
Rating
Blank=
Standard
ATW-SW4=
Chicago
Rated
Width
2=2' Width
Series
ALN=ArcLine Series
Number of
Lamps
3=3 Lamps
Voltage (2)
347V=347 Volt
UNV=Universal
Voltage 120-277 (3)
Wattage (Length)
28T8=28W T8 (48")
32=32W T8 (48")
Options
GL=Single Element Fuse
GM=Double Element Fuse
Lamps=Lamps Installed
(see options and
accessories)
Flex=Flex Installed
(Reference Flex ordering
information)
EL=Emergency Installed (4)
(Not included)
Shielding
Blank=Smooth Frosted
Acrylic (standard)
Trim Type
G=Grid/Lay-in (Standard) (1)
G=Concealed T
G=Slot Grid
Door Frame
Standard=Flat White Steel Door
(Leave Blank)
(1)
(2)
NOTES: An EQ Grid Clip is recommended for all 9/16" ceiling systems. Products also available in non-US voltages and
(3)
(4)
frequencies for international markets. Not available when specifying emergencies, voltage must be specific. Non-integral
(5)
solution only, must specify voltage. For a complete listing of Fifthlight Technology products and other solutions from Cooper
Controls, visit www.coopercontrol.com
Specifications & dimensions subject to change without notice. Consult your Cooper Lighting Representative for availability and
ordering information.
Ballast Type (2)
EB8 =T8 Electronic Start.
Total Harmonic
Distortion < 10%
EB8 /PLUS= T8 Electronic Start.
Total Harmonic
Distortion < 10%. High
Ballast Factor > 1.15.
ER8 = T8 Electronic Program
Rapid Start. Total Harmonic
Distortion < 10%
High Performance T8 Ballast (HPT8)
HB8 =T8 Electronic Instant Start.
Total Harmonic Distortion <
10%. Standard Ballast
Factor .86 – .88
HB8 L=T8 Electronic Instant Start.
Total Harmonic Distortion <
10%. Low Ballast Factor
.77 – .82
HB8 N=T8 Electronic Instant Start.
Total Harmonic Distortion <
10%. Normal Ballast Factor
1.0
HB8 H=T8 Electronic Instant Start.
Total Harmonic Distortion <
10%. Normal Ballast Factor
1.15 – 1.20
HR8 T8 Electronic Program Rapid
Start. Total Harmonic
Distortion < 10%. Standard
Ballast Factor .86 – .88
HR8 DIM=T8 Electronic Program
Rapid Start. Total
Harmonic Distortion <
10%. Step Dimming.
Ballast Factor .88
HR8 L=T8 Electronic Program
Rapid Start. Total Harmonic
Distortion < 10%. Low
Ballast Factor .71 – .79
HR8 H=T8 Electronic Program
Rapid Start. Total Harmonic
Distortion < 10%. High
Ballast Factor 1.15 – 1.20
Options
G1=Gasket, Door Frame
and Housing (Standard)
G2=G1 plus Gasket
between Lens and Door
G3=G1 and G2 plus
Gasketing on Mounting
Surface of Fixture Trims
Packaging
U=Unit Pack
PALC=Job Pack, in carton
Fifthlight Ballasts (5)
5LT8 =T8 DALI Program Rapid Start.
Total Harmonic Distortion <
10%. Ballast Factor 1.0
Number of Ballasts
1=1 Ballast
2=2 Ballasts
ACCESSORIES
EQ-CLIP-U=T-BAR Safety Earthquake Clips (1)
DF-24-W=2' x 4' Drywall Flange Kit
SH IP P ING D ATA
Catalog No.
2ALNG-328T8
2ALNG-332
Eaton
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.eaton.com/lighting
Specifications and
dimensions subject to
change without notice.
Wt.
20 lbs.
20 lbs.
ADF122021
2015-06-09 11:42:23
Download