Room Controller Network Greengate Technical Data Overview

Greengate
Technical Data
Room Controller Network
Catalog#
Prepared by
Project
Date
Comments
Type
Overview
The Room Controller Network includes three relays and up to
three 0-10 VDC dimming outputs to control compatible dimmable
luminaires. The Room Controller Network is shipped to work outof-the-box when connected to Room Controller devices, allowing
quick and easy daylighting controls, occupancy/vacancy sensing and
manual switching.
Network up to 254 ControlKeeper and Room Controller Network
lighting control panels for a complete network system.
Features
Click & Go ready, RJ45 connections
Preconfigured for automatic functionality upon power-up
Manual or Automatic On, bi-level, tri-level and dimming control
strategies
Local and network Demand Response input for automatic energy
reduction
Each 0-10V control supports up to 50 dimming drivers sourcing
2mA
Model RC3D-PL-N Shown
Integral pillow speaker connections for GPCS (RC3DEHC-PL-N)
Integral Solatube® connection for classrooms
Provides multi-level corridor lighting control
Guaranteed compatibility with Cooper Lighting LED and 0-10V
fluorescent fixtures
Ladderless UL 924 Emergency Mode testing
(RC3DE & RC3DEHC)
Network up to 254 ControlKeeper and Room Controller Network
lighting control panels
Inside View

Room Controller Network


July 2015
Specifications
Size
Input/Output
Voltage
11 1/2”H x 7 1/2”W x 2 1/4”D
120/277 VAC, 60Hz
Maximum 20A combined load per Room Controller
Ballast load: 20A @ 120/277 VAC
Incandescent load: 15A @ 120 VAC
Motor load: 1HP @ 120 VAC
Emergency
Output (RC3DE/
RC3DEHC only)
UL 924
Class 2 Dimming
Output
LED Drivers
Operating
Environment
Standards
Ballast or Incandescent load: 3A
0-10 VDC, sinks up to 100mA per (40 µA max per
circuit leakage to line)
Each 0-10V output supports up to 50 ballasts/
drivers that draw the standard 2mA each
Requires isolated LED drivers for optimal
performance
Temperature: 32°F to 104°F (0°C to 40°C)
For indoor use
UL Approved
UL 508 Listed
UL 924 Listed
System Includes
UL listed - UL 508 standard, UL 924 Optional
Description/Operation
The Room Controller products can be networked together to expand
their out of the box capabilities. Perfect for projects that have
multiple rooms that have similar requirements. The Room Controllers
can be installed and provide control capabilities on day one without
requiring network programming. As the project schedule allows
network programming can be completed to provide centralized
control and user training.
Installation
The line voltage section of the Room Controller provides the
installing contractor space to make all line voltage connections
and direct conduit access, reducing the need for additional
junction boxes, while providing easy access to line voltage circuits.
Low voltage devices are connected using Cat5 cables (ordered
separately).
UL 924 relay is provided on some units for automatic emergency
lighting control. The UL 924 relay automatically tracks with output 1
and can be connected to any of the three 0-10V dimmers. The
UL 924 relay automatically closes and disconnects the 0-10V control
open loss of normal power providing adequate egress lighting
control. Ladderless maintenance testing of the UL 924 relay can be
acheived by pressing the ALL OFF button four times.
ControlKeeper and Room Controller Network lighting control panels
are joined together using a RS-485 network cable sold separately
(GG9841, GG9842, GG89841P, GG89842P).
Sample Room Layout
NEMA 1 enclosure
Load 3
12 Zone or Scene Wallstations
Programmable Scene control
Open loop three zone daylight sensor
Time clock input
Occupancy/Vacancy Sensor Connection
Load 2
Load 2
Load 2
Dimmer 1
Dimmer 2
Dimmer 3
Load 1
Load 1
Load 1
Dimmer 1
Dimmer 2
Dimmer 3
Load 1
Load 1
Load 1
Dimmer 1
Dimmer 2
Dimmer 3
Occupancy based receptacle control
Occupancy based HVAC output
RS-485 network standard
CEPC-1-D (UL 924 0-10V Accessory)
Ethernet Interface Module
EISSBox OpenADR device
Receptacle Rated Switchpack
Zone Wallstations
Scene Wallstations
Dimming Slider
Daylight Sensor
Occupancy Sensors
Input/Output Device
Personal Remote
QuickConnect Cable
2
www.eaton.com/lightingsystems
Load 1
Dimmer 1
Load 1
Dimmer 2
Dimming Zone 3
Keeper Enterprise Software
Dimming Zone 1
Accessories (sold separately)
Dimming Zone 2
Software programmable
Load 1
Dimmer 3

Room Controller Network


July 2015
Wiring Diagram
ALL MODELS
Neutral
White/Black = 120V Neutral
White/Orange = 277V Neutral
Connect Neutral for Appropriate Voltage.
NNote: All provided wiring leads
are #14 AWG wiring.
Wire connections should
be rated suitable for the
wire size employed.
Line In
(120V or 277V)
Cap OFF all Unused Leads
OR
Blue = Room Line In
Black = Power Supply Line In
Yellow = Load 1 Out
Adjustable Skylights
QuickConnect Cables
Sensors
Sensors
Slider
Station
Wallstations
+
+
+
+
A/V
Mode
Demand
Response
Alert
Mode
Time
Clock
6
5
4
Integration Controls
Adjustable Skylights
Switchpack
Receptacle
BMS/Out
3
2
1
Energy Options DIP Switch
Not Used
3
4
Occ
Vac (default)
Reset
Occupancy
2
Status
1
Energy
Options
Demand Response
Default 10%
20%
30%
40%
0-10V Dimming Outputs
+ + + Dimmer 3
Dimmer 2
RS-485 Connection
0-10V Gain
Adjustment
Blue - EM Line In
Blue - EM Loads Out
Black - Line In
White/Black - 120V N
White/Orange - 277V N
Load 3
Green
High End
Purple = Load 3 Out
Black
Low End
Blue - Load In
Yellow - Load 1 Out
Load 2
White
Red
Integration Controls
Red - Load 2 Out
Purple - Load 3 Out
Red = Load 2 Out
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
Load Neutrals
Load 1
Terminating Jumper
Communication
Status LEDs
Dimmer 1
-
Dimmer 3
+
-
Dimmer 2
+
Reset Button
-
Dimmer 1
+
0-10V Dimming
Emergency
Panel Neutral
Emergency
Load
Address DIP Switch
Yellow = Emergency Load Out
Emergency Line In
(120V or 277V)
Blue = Emergency Line In
RC3DE MODEL ONLY
Room Connections
QuickConnect Coupler
(GGRC-COUPLER)
Alert
Mode
Time
Clock
6
QuickConnect Cables
5
Blue
Red
Black
Integration Controls
4
Brown
3
OCC-RJ45
(Occupancy Coupler)
2
1
Energy Options DIP Switch
Not Used
3
4
Occ
Vac (default)
Reset
20%
Energy
Options
Occupancy
2
1
High End
Demand Response
Default 10%
30%
Status
Low End
40%
Dimmer 2
Dimmer 3
Dimmer 1
-
Dimmer 3
+
-
Dimmer 2
+
-
Dimmer 1
+
0-10V Dimming
Half Lights
Full Lights
All Off
Blue - EM Line In
Dimmer 2
Dimmer 1
-
Dimmer 3
+
Dimmer 2
+
-
Adjustable Skylights
Adjustable Skylights
Alert
Mode
Time
Clock
QuickConnect Cables
5
-
Red
Black
Brown
3
OCC-RJ45
(Occupancy Coupler)
2
1
Energy Options DIP Switch
1
20%
Occupancy
2
Not Used
3
4
Occ
Energy
Options
Demand Response
Default 10%
Vac (default)
30%
40%
0-10V Dimming Outputs
+ + + Dimmer 3
Dimmer 2
Occupancy/
Vacancy Sensor
(OAWC-DT-120W)
Dimmer 1
+
0-10V Dimming
Blue
4
Integration Controls
Demand
Response
6
Dimmer 3
Dimmer 1
+
Wallstations
High End
Yellow - Load 1 Out
Blue - Load In
Red - Load 2 Out
Purple - Load 3 Out
Reset
Status
0-10V Gain
Adjustment
0-10V Dimming Outputs
+ + + Dimmer 3
Sensors
Reset
4
Vac (default)
30%
Sensors
Low End
Not Used
3
Occ
Energy
Options
Occupancy
2
High End
1
20%
40%
Receptacle
BMS/Out
Slider
Station
+
+
+
+
Status
1
Energy Options DIP Switch
Demand Response
Default 10%
Occupancy/
Vacancy Sensor
(OAWC-DT-120W)
Green
A/V
Mode
Daylight sensor
(DSRC-FMOIR)
SPRC-R-20-120
20A Receptacle
Control
0-10V Gain
Adjustment
2
Switchpack
White
Red
Black
Integration Controls
Integration Controls
OCC-RJ45
(Occupancy Coupler)
3
White/Black - 120V N
White/Orange - 277V N
Black
Brown
Black - Line In
Adjustable Skylights
QuickConnect Cables
Blue
Red
4
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
Time
Clock
5
Blue - EM Loads Out
Alert
Mode
6
Low End
Purple - Load 3 Out
Adjustable Skylights
Red - Load 2 Out
Blue - Load In
Demand
Response
Integration Controls
Yellow - Load 1 Out
White/Black - 120V N
White/Orange - 277V N
Black - Line In
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
Sensors
Wallstations
+
Daylight sensor
(DSRC-FMOIR)
SPRC-R-20-120
20A Receptacle
Control
Model: OCC-RJ45
Occupancy Sensor Coupler
Blue - EM Line In
Receptacle
BMS/Out
Sensors
Slider
Station
+
+
+
A/V
Mode
QuickConnect Coupler
(GGRC-COUPLER)
Model: OCC-RJ45
Occupancy Sensor Coupler
Blue - EM Loads Out
Switchpack
White
Black
Green
Slider Station
Wallstation
QuickConnect Coupler
(GGRC-COUPLER)
Red
Occupancy/
Vacancy Sensor
(OAWC-DT-120W)
0-10V Gain
Adjustment
Red - Load 2 Out
Purple - Load 3 Out
Adjustable Skylights
Sensors
Sensors
Slider
Station
+
Integration Controls
Blue - Load In
Yellow - Load 1 Out
Black - Line In
White/Black - 120V N
White/Orange - 277V N
Receptacle
BMS/Out
Wallstations
+
+
-+
A/V
Mode
Demand
Response
0-10V Dimming Outputs
+ + + -
Blue - EM Line In
Blue - EM Loads Out
The Ethernet Interface Module (EIM)
and Wireless Ethernet Interface
Module (WEIM) may be connected to
any Lighting Control Panel in the system
using the RS-232 cable included.
(Part #:52-018703-00)
Red
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
ControlKeeper
TouchScreen
Switchpack
White
Black
Green
Daylight sensor
(DSRC-FMOIR)
SPRC-R-20-120
20A Receptacle
Control
Model: OCC-RJ45
Occupancy Sensor Coupler
120V Power
Receptacle Required
Adjustable Skylights
EIM
-
Dimmer 2
+
-
Dimmer 1
+
-
0-10V Dimming
Half Lights
Half Lights
Full Lights
Full Lights
All Off
Wallstation
All Off
Slider Station
Wallstation
Slider Station
www.eaton.com/lightingsystems
3

Room Controller Network


July 2015
Ordering
Catalog #
Desctiption
Voltage
Ballast/Incandescent
RC3-PL-N
3 relays, Plenum, Network Room Controller
120/277 VAC, 60 Hz
RC3D-PL-N
3 relays, 3 0-10V dimming Plenum, Network Room
Controller
120/277 VAC, 60 Hz
Maximum Combined
Load 20A
Maximum Combined
Load 20A
RC3DE-PL-N
3 relays, 3 0-10V dimming, UL924 Plenum, Network
Room Controller
3 relays, 3 0-10V dimming UL924 for healthcare Plenum,
Network Room Controller
120/277 VAC, 60 Hz
RC3DEHC-PL-N
120/277 VAC, 60 Hz
Room Controller Upgrade Ordering Option
Catalog #
Desctiption
RCNN
Room Controller Network Node, upgrades stand alone
Room Controller to the network option.
Additional Options (Sold Separately)
Catalog #
Desctiption
GGRC-COUPLER
GGRC-SPLITTER
GGRJ45-006-G
GGRJ45-03-G
GGRJ45-10-G
GGRJ45-25-G
GGRJ45-50-G
GGRJ45-100-G
GGRJ45-10P-G
GGRJ45-25P-G
GGRJ45-50P-G
GGRJ45-100P-G
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
Coupler
Splitter
cables 6 inches
cables 3 feet
cables 10 feet
cables 25 feet
cables 50 feet
cables 100 feet
cables 10 feet plenum rated
cables 25 feet plenum rated
cables 50 feet plenum rated
cables 100 feet plenum rated
NNote: Please refer to the Room Controller page on our website for more
information
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton
Lighting systems
203 Cooper Circle
Peachtree City, GA 30269
www.eaton.com/lightingsystems
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. TD503020EN
July 10, 2015
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
Maximum Combined
Load 20A
Maximum Combined
Load 20A