COOPER LIGHTING - METALUX

advertisement
COOPER LIGHTING - METALUX
®
DESCRIPTION
The HBE series is an outstanding value for mounting heights greater than
40 feet. The HBE optic has been optimized to provide maximum
performance from T8 lamps. Optional uplight component is provided to
enable excellent ceiling uniformity. HBE‘s high lumen package allows the
benefits of fluorescent to be applied at high mounting heights that were
traditionally exclusive to H.I.D. The primary benefits include exceptional
color rendering, high system efficacy, 95% lumen maintenance, long
lamp life, instant on/instant re-strike, economical dimming, and uniform
brightness control. Primary applications include "big box" retail,
shopping malls, light industrial, etc.
Type
Catalog #
Project
Date
Comments
Prepared by
S P E C I F I C AT I O N F E AT U R E S
C o n s t ru c t i o n
Full body construction is achieved
with channel and end plates, along
w/stiffening brackets and side rails
to help create a strong, clean
finished frame for this luminaire.
Side rails are standard on all HBE
products.
Finish
White enamel finish preceded by a
multistage cleaning cycle, iron
phosphate coating with rust
inhibitor to protect against
contaminants and oxidation.
Optics
Die formed, segmented optical
design optimizes performance
across three distributions. Optical
choices include a narrow
distribution for aisles, medium
distribution for assembly and
loading areas, or wide distribution
for general, open area lighting. An
uplight option is offered to permit
ceiling uniformity and allow for
ample lamp and luminaire heat
dissipation.
E l e c t ri c a l
The HBE comes with a standard
Class "P" electronic ballast and
twist-lock lampholders. UL/cUL
listed for high ambient
environments up to 55°C (131°F)
for all lamp and EB/PLUS or
ER/PLUS ballast combinations
when used in open uplight
configurations. Suitable for damp
locations.
Shielding
Door frame and lens assembly is
optional for more demanding
environments.
Options
Integral Occupancy Sensor
available and provides from 600
sq. ft. and up to 1250 sq. ft. of
coverage in a maximum mounting
height of 40' using interchangeable
lens caps provided.
Mounting
The HBE series is ideally suited for
suspension mounting with optional
wire hook and chain set, or cable
mounting. Single monopoint
mounting is also available with
SPM tong hanger.
HBE
SERIES
2 5 " X 4 8 " H I G H - B AY
8 O R 10 T 8 L A M P S
High-Bay Efficiency
Fluorescent Luminaire
2-15/32"
[63mm]
25-11/32" [644mm]
E N E R G Y D ATA
L A M P C O N F I G U R AT I O N S
D I M E N S I O N TO P V I E W
8 LAMP
8/10 LAMP
48-7/16" [1230mm]
2-15/32" [63mm]
X=2-1/4"
[57mm]
20-11/32" [517mm]
X
X
X
25-11/32" [644mm]
X
X
24-19/32" [625mm]
X
Input Watts:
EB Ballast
832 (218), 1032 (270)
EB/Plus Ballast
832 (290), 1032 (363)
ER Ballast
832 (224), 1032 (282)
ER/Plus Ballast
832 (288), 1032 (362)
Luminaire Efficacy Rating
LER = 90 (Narrow Beam)
Catalog Number: HBE-832-UPL
10 LAMP
25-11/32"
[644mm]
2-15/32" [63mm]
X=1-7/8"
[48mm]
X
X
X
X
X
25-11/32" [644mm]
X
X
X
*Reference the lamp/ballast data in the
Technical Section for specific lamp/ballast
requirements.
**Consult Pre Sales Technical Support.
LAMPS CONTAIN MERCURY. DISPOSE ACCORDING
TO LOCAL, STATE OR FEDERAL LAWS
Safe and convenient means of
disconnecting power.
Specifications and dimensions subject to change without notice.
Consult your representative for additional options and finishes.
ADF091709 pc
2011-03-30 09:42:32
HBE T8
P H OTO M E T R I C S
P H OTO M E T R I C S
HBE-832-N-A-UPL
HBE-832-N-UPL
Candela
(2) Electronic Ballasts
(8) 32W T8 Lamps
2850 lumens
Spacing criterion:
(II) 1.2 x mounting
height, (⊥) 1.1 x
mounting height
Efficiency 72.8%
Test Report:
HBE832-A-UPL.IES
LER =FL73
Yearly Cost of 1000
lumens, 3000 hrs at
.08 KWH = $3.28
Angle
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
Along II
6785
6738
6626
6445
6176
5835
5414
4910
4314
3659
2963
2325
1763
1286
930
674
495
271
20
Across ⊥
6785
6720
6519
6188
5783
5393
5033
4679
4283
3776
3179
2549
1924
1384
996
771
576
317
65
45°
6785
6726
6574
6312
5953
5526
5087
4630
4117
3541
2966
2396
1770
1179
742
519
409
238
41
C o e f fi c i e n t s o f U t i l i z a t i o n
rc
rw
RCR
0
1
2
3
4
5
6
7
8
9
10
85
75
66
59
53
47
43
39
36
33
31
85
72
62
54
47
41
37
33
30
27
25
85
70
58
49
42
37
32
29
26
23
21
82
76
69
64
59
54
50
47
44
41
38
82
73
64
57
51
46
42
38
35
32
30
82
70
60
52
46
41
36
33
30
27
25
82
68
57
48
42
36
32
28
26
23
21
20%
50%
50 30 10
30%
50 30 10
10%
50 30 10
0%
0
77
69
61
54
49
44
40
37
34
31
29
72
65
58
51
46
42
38
35
32
30
28
68
61
55
49
44
40
36
33
31
29
27
66
57
48
42
36
32
28
25
23
21
19
77
67
58
50
44
39
35
32
29
26
24
77
65
55
47
40
35
32
28
25
23
21
72
63
55
48
42
38
34
31
28
25
23
Zonal Lumen Summary
Luminance Data
Zone
0-30
0-40
0-60
0-90
0-180
Angle
in Deg
45
55
65
75
85
Lumens
4982
7923
12846
15091
16593
%Lamp
21.9
34.7
56.3
66.2
72.8
Angle
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
Along II
7207
7180
7059
6858
6586
6281
5941
5583
5181
4711
4184
3613
2998
2374
1755
1183
636
198
8
Across ⊥
7207
7058
6815
6517
6037
5277
4682
4478
4389
4332
4084
3646
3447
3038
2399
1731
1084
473
8
45°
7207
7107
6889
6641
6334
5914
5269
4548
4020
3765
3564
3362
2995
2570
2269
1692
1061
459
8
C o e f fi c i e n t s o f U t i l i z a t i o n
Effective floor cavity reflectance
80%
70%
70 50 30 10
70 50 30 10
85
78
72
66
61
56
52
48
45
42
40
Candela
(2) Electronic Ballasts
(8) 32W T8 Lamps
2850 lumens
Spacing criterion:
(II) 1.2 x mounting
height, (⊥) 1.1 x
mounting height
Efficiency 89.9%
Test Report:
HBE832N-UPL.IES
LER =FL82
Yearly Cost of 1000
lumens, 3000 hrs at
.08 KWH = $2.93
%Fixture
30.0
47.7
77.4
91.0
100.0
Average
0-Deg
cd/sm
6618
5184
3891
3330
3980
72
62
52
45
39
34
31
27
25
22
20
68
60
52
46
41
36
33
30
27
25
23
68
59
50
44
38
34
30
27
24
22
20
Average
45-Deg
cd/sm
6405
5343
3567
2563
3493
Average
90-Deg
cd/sm
6830
5683
4187
3811
4644
rc
rw
RCR
0
1
2
3
4
5
6
7
8
9
10
Effective floor cavity reflectance
80%
70%
70 50 30 10
70 50 30 10
106
96
87
79
72
67
61
57
53
50
47
106
92
79
69
61
55
49
45
41
38
35
106 106
87 84
73 68
62 56
53 47
47 41
41 35
37 31
33 28
30 25
28 23
103
93
84
76
70
64
59
55
51
48
45
103
89
77
68
60
53
48
44
40
37
34
103
85
71
61
52
46
41
36
33
30
27
20%
103
82
66
55
47
40
35
31
28
25
23
50%
50 30 10
30%
50 30 10
50
97
84
73
64
57
51
46
42
38
35
33
91
79
69
61
54
48
44
40
37
34
31
86
75
66
58
51
46
42
38
35
33
30
97
81
68
58
50
44
39
35
32
30
27
97
78
64
53
45
39
34
30
27
24
22
91
77
65
56
49
43
38
34
31
28
26
Zonal Lumen Summary
Luminance Data
Zone
0-30
0-40
0-60
0-90
0-180
Angle
in Deg
45
55
65
75
85
Lumens
5225
8250
14471
19168
20501
%Lamp
22.9
36.2
63.5
84.1
89.9
%Fixture
25.5
40.2
70.6
93.5
100.0
Average
0-Deg
cd/sm
8520
8055
7184
5843
2899
91
75
62
52
44
38
34
30
27
24
22
10%
30 10
86
73
62
54
47
41
37
33
30
27
25
86
72
59
50
43
37
33
29
26
24
22
Average
45-Deg
cd/sm
9217
7497
7777
8362
6733
0%
0
84
69
57
48
41
35
31
27
24
22
20
Average
90-Deg
cd/sm
9217
8129
9194
8555
6945
Modular F-Bay Power Supply Option
Cooper Lighting’s F-Bay Modular Power Supply option is available for use with all F-Bay products. The modular power supply
allows external fixture access for safe and easy servicing. There is no need to remove lamps or reflectors to disconnect fixture
power with F-Bay Modular Power Supply. Access to the individual fixture’s power supply allows servicing without turning off
all the fixtures, disrupting occupants. F-Bay Modular Power Supply is a time-saver in installation – simply plug & power.
Code Compliance
• UL/cUL Certified for Make/Break
under load (UL2549)
• Meets NEC requirements for
ballast disconnect (NEC 410.73G)
1
• Allows for addition of Occupancy
Sensor without hard connections
2
1. Modular Power Supply Receptacle supplied
mounted into fixture Access Plate
2. Modular Power Cord & Plugs in 120, 277, 347,
& 480V configurations for easy plug & power
into existing supply
No internal fixture
access required for
installation or
disconnecting power
Modular Motion Sensor Option
supplied with Mounting Box and
Modular Power Supply Receptacle
• Receptacles complete with
insulating/dust cap
Specifications and dimensions subject to change without notice.
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770 468.4801
ADF091709 pc
2011-03-30 09:42:32
HBE T8
O R D E R I N G I N F O R M AT I O N
SAMPLE NUMBER: HBE-832-N-A-UNV-L8850-EB82/PLUS-U
Ballast Type (4)
EB8 =T8 Electronic Instant Start.
Total Harmonic Distortion < 10%
No. of Ballast
1, 2 or 3
EB8 /PLUS=T8 Electronic Instant Start. (10)
High Ballast Factor >1.15.
No. of
Total Harmonic Distortion < 10%
Ballast
1, 2 or 3
ER8 =T8 Electronic Program Rapid Start.(7)
Total Harmonic Distortion < 10%
No. of Ballast
1, 2 or 3
ER8 /PLUS=T8 Electronic Program Start.(7)
High Ballast Factor >1.15.
No. of
Total Harmonic Distortion < 10%
Ballast
1, 2 or 3
Voltage (1)
UNV=Universal
120/277 Voltage
UNC=Universal 347/480
Voltage (EB8/PLUS only) (10)
120V=120 Volt
277V=277 Volt
347V=347 Volt
Series
HBE=High Bay
Efficiency
No. of Lamps
8=8 Lamps
10=10 Lamps
Lamp Type
32=32W T8 Lamps (48")
Distribution
N=Narrow Beam (Standard)
M=Medium Beam
W=Wide Beam
Shielding (6)
Blank=None
A=Prismatic Acrylic Lens & Doorframe
WG=Wireguard & Doorframe
CL=Clear Acrylic Lens & Doorframe
A/WG=Acrylic Lens, Wireguard & Doorframe
CL/WG=Clear Lens, Wireguard & Doorframe
(1)
Includes V Hangers for rapid installation(5)
Options
Lamps Installed
L8830=T8 Lamp, 80CRI 3000K
L8835=T8 Lamp, 80CRI 3500K
L8841=T8 Lamp, 80CRI 4100K
L8850=T8 Lamp, 80CRI 5000K
HL=Add HL at end of lamp for
high lumen lamps
GL=Single Element Fuse
GM=Double Element Fuse
EL=Emergency Installed (1)
(2)
NOTES: Voltage must be specified when ordered with plugs, motion sensor or emergency ballasts. When ordering MS option, specify as UNV (for 120 or
(3)
277V), 347 or 480V. Requires use of MC or MPC cord accessories, specify voltage for plugs. (4) T8 ballast systems suitable for operation in ambient environments up to 131°F (55°C) in open uplight configuration. (5) Can be used in high abuse applications such as gymnasiums. (6) Not recommended in 10 lamp
configurations at ambient temperatures above 102°F (40°C). (7) Recommended when utilizing motion sensor options. (8) Cannot be combined with Modular
Power Receptacle (MP). (9) For MWS with MP, choose MP in fixture logic and then choose MWS accessory such as MDS6. (10) 2/3 lamp ballast configuration
in EB8/PLUS only for UNC version.
Packaging
Options
U=Unit Pack
Blank=Side Rails (Standard)
PALC=Job Pack
MP=Modular Power
In Carton
Receptacle (Used for all
PAL=Job Pack
Cord or Cord and Plug
Out of Carton
options )(3), (9)
UPL=Uplight Apertures on
Reflector
MWS=Modular Wiring System (8)
MS=360° or 180° motion sensor installed,
120V through 347V, or 480V (2)
Accessories (order separately)
HBL-SPM=Single Monopoint Hanger w/Hub
RH-1=Retrofit Hanger
FH-1=Fixture Hook
FL-1=Fixture Loop
Y-TOGGLE=Y Mounting Toggle, #2 Cable (Specify
10' or 30', requires 2 per fixture)
HBAYC-CHAIN/SET/U=(2) V-Hook Hangers,
36" Chain Sets w/S-Hooks
MC3=3' Modular Power Cord
MPC3=3' Modular Power Cord & Plug (Specify
Voltage)
MC6=6' Modular Power Cord
MPC6=6' Modular Power Cord & Plug (Specify
Voltage)
MMS=360° or 180° Aisle Motion Sensor with
Modular Power Receptacle (120-277V) (3)
MDS6=6' Modular Power Cord with MWS
27DS18/2G06MP Connector (9)
WG/HBL8-4FT-B=8 Lamp Wireguard w/Clips
S H I P P I N G DATA
Catalog No.
HBE-832
HBE-1032
Specifications and dimensions subject to change without notice.
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770 468.4801
Wt.
18 lbs.
18 lbs.
ADF091709 pc
2011-03-30 09:42:32
Download