EBP1400NCX and EBP1400NCF Instruction Manual INS # ADX142715 Brand Logo

Brand Logo
reversed out of
blackINS #
ADX142715
EBP1400NCX and EBP1400NCF Instruction Manual
WARNING
Risk of Fire/Electric Shock
If not qualified, consult an electrician.
WARNING
Risk of Electric Shock
Disconnect power at fuse or circuit breaker before
installing or servicing.
For use in temperature rating
20°C to 55°C
EBP1400NCX
EBP1400NCF
CONTAINS NICKEL-CADMIUM
RECHARGEABLE BATTERY.
MUST BE RECYCLED OR
DISPOSED OF PROPERLY.
Ni - Cd
Important Safeguards
NOTES:
WHEN USING ELECTRICAL EQUIPMENT, BASIC
SAFETY PRECAUTIONS SHOULD ALWAYS BE
OBSERVED INCLUDING THE FOLLOWING.
Note 1. To prevent high voltage from being present on
the output terminals (red/white, red, and yellow), do
not connect the test button indicator light to the EBP
until Step 7 of the installation instructions.
1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS
2. Do not use outdoors.
3. Do not mount near gas or electric heaters.
4. Equipment should be mounted in locations and
at heights where it will not readily be subject to
tampering by unauthorized personnel.
5. The use of accessory equipment not recommended
by Sure-Lites may cause an unsafe condition.
6. Do not use this equipment for other than its
intended purpose.
7. SAVE THESE INSTRUCTIONS
Note 2. This product is for use with most 2’ through
8’ (6W-215W single and bi-pin fluorescent lamps
including energy saving, circline, U-shaped and biax.
For specific lamp compatibility, please see the table
later in the instructions.
Note 3. Make sure all of the connections are in
accordance with the National Electrical Code and any
local regulations.
Note 4. To reduce the risk of electrical shock,
disconnect both normal and emergency power
supplies and the test button indicator light (which
disconnects the battery) before servicing.
Note 5. This emergency ballast is for factory or field
installation in the ballast channel.
Note 6. This product is for use in indoor fixtures. This
product is not intended for use near air handling
heated air outlets or in wet or hazardous locations.
Note 7. An unswitched AC power source is required
(120, 240, or 277 volts).
Note 8. Do not attempt to service the battery. A sealed,
no-maintenance battery is used that is not field
replaceable. Contact the manufacturer for information
on service.
Note 9. Servicing should be performed by qualified
service personnel.
EBP1400NCX and EBP1400NCF Instruction Manual
INSTALLATION
Illustration 1
WARNING: to prevent high voltage on Red / White, Red,
and Yellow output terminals prior to installation, the Test
Button / Indicator Light must be disconnected. Connect
the Test Button / Indicator Light after installation.
NOTE: Make sure that the necessary branch circuit
wiring is available. An unswitched source of power is
required.
1. Disconnect AC power from the fixture. Remove the
ballast channel cover. Install the emergency ballast
with grounding screws either in the ballast channel
(see illustrations 1 & 2) or on top of the fixture (see
illustration 3 / EBP1400NCX only).
2. Select the appropriate wiring diagram to connect
the emergency ballast to the AC ballast and lamp.
Make sure all connections are in accordance with the
National Electrical Code and any local regulations.
(See Illustrations 4 and 5 for terminals).
3. Refer to the lamp compatibility table for the HIGH
(Red) or Low (Red / White) connection per the lamp(s)
being illuminated by the emergency ballast.
4. Install the test button / indicator light through the
ballast channel cover of a troffer (Illustration 1 & 6)
or through the side of a strip fixture (Illustration 2 &
7). Drill or punch a 7/8” hole to install the test button
/ indicator light as shown in illustration 6. Drill or
punch a 1/2” hole to install the test button / indicator
light as shown in illustration 7. Install the test button
/ indicator light as shown in the selected illustration.
Apply the two included labels (“Charging Indicator
Light” and “Emergency Light Push to Test”) adjacent
to the test button indicator light.
5. In a readily visible location, attach the included label
“CAUTION – This unit Has More Than One Power
Connection Point. To Reduce The Risk Of Electric
Shock, Disconnect Both The Branch Circuit-Breakers
Or Fuses and the Test Button / Indicator Light Before
Servicing”.
6. In an area readily visible during relamping, attach the
included relamping label. Write in the lamp type and
wattage.
7. After installation is complete, connect the test
button / indicator light. The factory installed version
(EBP1400NCF) will have 2 twisted wires (brown and
purple) at the access plate which must be connected
for the fixture to operate in emergency mode.
Emergency
Ballast
Test Button/
Indicator Light
Ballast
Channel
Cover
Illustration 2
Emergency
Ballast
Test Button/
Indicator Light
Illustration 3
Wire Bundle
Cover
Drill 1/8˝ Hole
for Mounting
Screws
Wire Bundle
Cover
8 Replace covers being careful not to pinch wires, install
lamps, supply AC power to the emergency ballast.
9.A short term discharge test may be conducted after
the emergency ballast has been charging for one
hour. Charge for 24 hours before conducting a long –
term discharge test. Refer to OPERATION.
2
EATON
ADX142715
Installation instructions
Emergency
Ballast
1/2˝ Std. Knockout
7/8˝ Hole w/Bushing
EBP1400NCX only
EBP1400NCX and EBP1400NCF Instruction Manual
Illustration 4
Color coded label
located here.
Emergenc
Suitable fo
Emergenc
Suitable fo
Terminal labels
located here.
AUX COM
AUXAUX
COMN.O.
AUX AUX
N.O. N.C.
LINE HOT
AUX N.C.
120/240/277
LINE HOT LINE
120/240/277NEUTRAL
LINE
NEUTRAL
TEST BU
LIGHT C
TEST BU
LIGHT C
Illustration 5
RED / WH
RED / WH
RED
RED
BLUE
BLUE
BLUE / WH
BLUE / WH
YELLOW
YELLOW
YELLOW / BK
YELLOW / BK
AUX
COMMON
AUX
N.C.
LINE HOT
120/ 277
AUX AUX
N.O.
COMMON
AUX
N.O.
AUX
N.C.
LINE
LINE HOT
120/ 277NEUTRAL
LINE
NEUTRAL
Test Button / Indicator Light Connector
Illustration 7
Illustration 6
TROFFER STYLE FIXTURE
STRIP STYLE FIXTURE
Fixture
Emergency
Ballast
Ballast Channel
Cover
Leads to Test Button/
Indicator Light
7/8" Punch
Plastic Tubing
(cut to necessary
length)
7/8" Bushing
Inserted into
Ballast Channel
Cover
Test Button/
Indicator Light
Test Button/
Indicator Light
Nut
EATON
ADX142715
Installation instructions
3
EBP1400NCX and EBP1400NCF Instruction Manual
Lamp Compatibility Table
Lamp Type
Number
of Lamps
Lamps Connected to
Low/High (Red) Output
Wattage
T5
1
HIGH (RED)
6 - 25, 39
T5
1
"LOW (RED / WHITE)"
28 - 35
T5HO
1
HIGH (RED)
24
T5HO
1
"LOW (RED / WHITE)"
54 - 80
T5 CIR
1
HIGH (RED)
22 - 55
T8
1
HIGH (RED)
15 - 32
T8
1
"LOW (RED / WHITE)"
59 - 86
T8U
1
HIGH (RED)
32
T9 CIR
1
HIGH (RED)
20 - 32
T12
1
HIGH (RED)
20 - 75
T12
1
"LOW (RED / WHITE)"
75 - 95
T12HO
1
HIGH (RED)
35
T12HO
1
"LOW (RED / WHITE)"
95 - 110
T12VHO
1
"LOW (RED / WHITE)"
215
BIAX
1
HIGH (RED)
18 - 55
OPERATION
When AC power is applied, the charging indicator light is illuminated, indicating the battery is being charged. When
power fails, the emergency ballast automatically switches to emergency power, operating one lamp at reduced
illumination for at least 90 minutes.
MAINTENANCE
Although no routine maintenance is required to keep the emergency ballast functional, it should be checked periodically
to comply with local codes. The following schedule is recommended:
1. Visually inspect the charging light monthly. It should be illuminated.
2. Test the emergency operation of the fixture at 30 day intervals for a minimum of 30 seconds. Depending on
installation, one lamp should operate at reduced illumination.
3. Conduct a 90 – minute discharge test once a year. Depending on installation, one lamp should operate at reduced
illumination for at least 90 minutes.
Refer any service requirements indicated by these checks to qualified personnel.
NOTE: After installing the test button / indicator light, mark it with the appropriate label.
4
EATON
ADX142715
Installation instructions
AC BALLAST
LAMP ("EMERGENCY")
RED
RED
BLUE
BLUE
YELLOW
BLUE/WH
BLUE
RED OR RED/WH
CHOOSE BASED
ON LAMP
LINE NEUTRAL
LINE HOT
AUX NC
AUX NO
AUX COM
EMERGENCY BALLAST
YELLOW/BK
LINE NEUTRAL
(UNSWITCHED) 120/277
SWITCHED OR UNSWITCHED LINE HOT
EATON
YELLOW
YELLOW
LINE NEUTRAL
LINE HOT
AC BALLAST
ADX142715
YELLOW
YELLOW
YELLOW
LINE NEUTRAL
AC BALLAST
RED
RED
BLUE
BLUE
LAMP-2 ("EMERGENCY")
LINE NEUTRAL
(UNSWITCHED) 120/277
SWITCHED OR UNSWITCHED LINE HOT
LAMP-2 ("EMERGENCY")
LINE NEUTRAL
LINE HOT
AUX NC
AUX NO
LINE HOT
LAMP ("EMERGENCY")
BLUE
LINE NEUTRAL
LINE HOT
AUX NC
BLUE
RED OR RED/WH
CHOOSE BASED
ON LAMP
AUX NO
YELLOW
BLUE/WH
AUX COM
EMERGENCY BALLAST
YELLOW/BK
LINE NEUTRAL
(UNSWITCHED) 120/277
SWITCHED OR UNSWITCHED LINE HOT
BLUE/WH
BLUE
RED OR RED/WH
CHOOSE BASED
ON LAMP
YELLOW
YELLOW/BK
LINE NEUTRAL
LINE HOT
AUX NC
AUX NO
AUX COM
EMERGENCY BALLAST
LINE NEUTRAL
(UNSWITCHED) 120/277
SWITCHED OR UNSWITCHED LINE HOT
2 LAMP RAPID START SERIES LAMP
SERIES YELLOW FILAMENT
AC BALLAST
LAMP-1
BLUE/WH
BLUE
RED OR RED/WH
CHOOSE BASED
ON LAMP
AUX COM
RED
LINE NEUTRAL
LINE HOT
1 LAMP INSTANT START
LAMP-1
RED
RED
BLUE
BLUE
YELLOW/BK
EMERGENCY BALLAST
2 LAMP RAPID START SERIES / PARALLEL LAMP
PARALLEL YELLOW FILAMENT
LINE NEUTRAL
LINE HOT
1 LAMP RAPID START
EBP1400NCX and EBP1400NCF Instruction Manual
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLAST. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS
WIRING DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION
Installation instructions
5
6
EATON
ADX142715
Installation instructions
YELLOW
YELLOW
BLUE
BLUE
LINE NEUTRAL
LINE HOT
YELLOW
YELLOW
LINE NEUTRAL
LINE HOT
LAMP-2 ("EMERGENCY")
LAMP-1
RED
RED
BLUE
BLUE
BLUE/WH
BLUE
RED OR RED/WH
CHOOSE BASED
ON LAMP
LINE NEUTRAL
LINE HOT
AUX NC
AUX NO
AUX COM
LINE NEUTRAL
(UNSWITCHED) 120/277
SWITCHED OR UNSWITCHED LINE HOT
AC BALLAST
LAMP-3
LAMP-2 ("EMERGENCY")
LAMP-1
RED
RED
BLUE/WHT
BLUE/WHT
BLUE/WH
BLUE
RED OR RED/WH
CHOOSE BASED
ON LAMP
YELLOW
YELLOW/BK
LINE NEUTRAL
LINE HOT
AUX NC
AUX NO
AUX COM
EMERGENCY BALLAST
LINE NEUTRAL
(UNSWITCHED) 120/277
SWITCHED OR UNSWITCHED LINE HOT
3 LAMP RAPID START SERIES LAMP
PARALLEL YELLOW FILAMENT
AC BALLAST
YELLOW
YELLOW/BK
EMERGENCY BALLAST
2 LAMP RAPID START OSRAM SYLVANIA SERIES
LAMP PARALLEL YELLOW FILAMENT
LINE NEUTRAL
LINE HOT
LINE NEUTRAL
LINE HOT
AC BALLAST
AC BALLAST
YELLOW
RED OR RED/WH
CHOOSE BASED
ON LAMP
BLUE
BLUE/WH
LAMP-3 ("EMERGENCY")
LAMP-2
LAMP-1
RED OR YELLOW
BLUE
BLUE
BLUE
BLUE/WH
YELLOW
YELLOW/BK
RED OR RED/WH
CHOOSE BASED
ON LAMP
BLUE
LINE NEUTRAL
LINE HOT
AUX NC
AUX NO
AUX COM
LINE NEUTRAL
LINE HOT
AUX NC
AUX NO
AUX COM
EMERGENCY BALLAST
3 LAMP INSTANT START
LAMP-2 ("EMERGENCY")
LAMP-1
RED
BLUE
BLUE
YELLOW/BK
EMERGENCY BALLAST
2 LAMP INSTANT START
LINE NEUTRAL
(UNSWITCHED) 120/277
SWITCHED OR UNSWITCHED LINE HOT
LINE NEUTRAL
(UNSWITCHED) 120/277
SWITCHED OR UNSWITCHED LINE HOT
EBP1400NCX and EBP1400NCF Instruction Manual
WIRING DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLAST. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS
EATON
YELLOW
YELLOW
LINE HOT
LINE NEUTRAL
AC BALLAST
LAMP-4 ("EMERGENCY")
LAMP-3
LAMP-2
LAMP-1
RED
RED
BLUE/WHT
BLUE/WHT
BLUE
BLUE
EMERGENCY
BALLAST
BLUE/WH
BLUE
RED OR RED/WH
CHOOSE BASED
ON LAMP
YELLOW/BK
YELLOW
LINE NEUTRAL
LINE HOT
AUX NC
AUX NO
AUX COM
LINE NEUTRAL
(UNSWITCHED) 120/277
SWITCHED OR UNSWITCHED LINE HOT
ADX142715
RED
RED
BLUE
BLUE
LAMP-3 ("EMERGENCY")
LAMP-2
LAMP-1
AC BALLAST
RED/WHT
RED/WHT
EMERGENCY
BALLAST
BLUE/WH
BLUE
RED OR RED/WH
CHOOSE BASED
ON LAMP
YELLOW/BK
YELLOW
LINE NEUTRAL
LINE HOT
AUX NC
AUX NO
AUX COM
LINE NEUTRAL
(UNSWITCHED) 120/277
SWITCHED OR UNSWITCHED LINE HOT
3 LAMP RAPID START PARALLEL LAMP
PARALLEL YELLOW FILAMENT
YELLOW
YELLOW
BROWN
BROWN
LINE HOT
LINE NEUTRAL
4 LAMP RAPID START SERIES LAMP
PARALLEL YELLOW FILAMENT
YELLOW
YELLOW
LINE NEUTRAL
LINE HOT
YELLOW
YELLOW
LINE NEUTRAL
LINE HOT
LAMP-4 ("EMERGENCY")
LAMP-3
LAMP-2
LAMP-1
RED
RED
BLUE
BLUE
RED OR RED/WH
CHOOSE BASED
ON LAMP
YELLOW
BLUE/WH
BLUE
LINE NEUTRAL
LINE HOT
AUX NC
AUX NO
AUX COM
LINE NEUTRAL
(UNSWITCHED) 120/277
SWITCHED OR UNSWITCHED LINE HOT
LAMP-4 ("EMERGENCY")
LAMP-3
LAMP-2
LAMP-1
AC BALLAST
BLUE/WHT
BLUE/WHT
RED/WHT
RED/WHT
BLUE
BLUE
RED
RED
EMERGENCY
BALLAST
BLUE/WH
BLUE
RED OR RED/WH
CHOOSE BASED
ON LAMP
YELLOW/BK
YELLOW
LINE NEUTRAL
LINE HOT
AUX NC
AUX NO
AUX COM
LINE NEUTRAL
(UNSWITCHED) 120/277
SWITCHED OR UNSWITCHED LINE HOT
4 LAMP RAPID START PARALLEL LAMP
PARALLEL YELLOW FILAMENT
AC BALLAST
YELLOW/BK
EMERGENCY BALLAST
4 LAMP INSTANT START
EBP1400NCX and EBP1400NCF Instruction Manual
WIRING DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLAST. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS
Installation instructions
7
EBP1400NCX and EBP1400NCF Instruction Manual
WIRING DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLAST. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS
BI LEVEL BALLAST
SWITCHED LINE HOT
EMERGENCY BALLAST
YELLOW/BK
SWITCHED LINE HOT
LINE NEUTRAL
BI-LEVEL
AC BALLAST
WIRE LAMPS USING DIAGRAM PER
# OF LAMPS AND BALLAST TYPE
AUX COM
YELLOW
BLUE/WH
AUX NO
BLUE
RED OR RED/WH
CHOOSE BASED
ON LAMP
AUX NC
LINE HOT
LINE NEUTRAL
(UNSWITCHED) 120/277
LINE NEUTRAL
When using the auxillary relay to switch the neutral line, the Emergency and A.C. ballasts
must be on the same branch circuit.
Warranties and Limitation of Liability
Please refer to www.cooperlighting.com/WarrantyTerms for our terms and conditions.
Eaton
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.eaton.com/lighting
Canada Sales
5925 McLaughlin Road
Mississauga, Ontario L5R 1B8
P: 905-501-3000
F: 905-501-3172
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. ADX142715