Brand Logo reversed out of blackINS # ADX142715 EBP1400NCX and EBP1400NCF Instruction Manual WARNING Risk of Fire/Electric Shock If not qualified, consult an electrician. WARNING Risk of Electric Shock Disconnect power at fuse or circuit breaker before installing or servicing. For use in temperature rating 20°C to 55°C EBP1400NCX EBP1400NCF CONTAINS NICKEL-CADMIUM RECHARGEABLE BATTERY. MUST BE RECYCLED OR DISPOSED OF PROPERLY. Ni - Cd Important Safeguards NOTES: WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE OBSERVED INCLUDING THE FOLLOWING. Note 1. To prevent high voltage from being present on the output terminals (red/white, red, and yellow), do not connect the test button indicator light to the EBP until Step 7 of the installation instructions. 1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS 2. Do not use outdoors. 3. Do not mount near gas or electric heaters. 4. Equipment should be mounted in locations and at heights where it will not readily be subject to tampering by unauthorized personnel. 5. The use of accessory equipment not recommended by Sure-Lites may cause an unsafe condition. 6. Do not use this equipment for other than its intended purpose. 7. SAVE THESE INSTRUCTIONS Note 2. This product is for use with most 2’ through 8’ (6W-215W single and bi-pin fluorescent lamps including energy saving, circline, U-shaped and biax. For specific lamp compatibility, please see the table later in the instructions. Note 3. Make sure all of the connections are in accordance with the National Electrical Code and any local regulations. Note 4. To reduce the risk of electrical shock, disconnect both normal and emergency power supplies and the test button indicator light (which disconnects the battery) before servicing. Note 5. This emergency ballast is for factory or field installation in the ballast channel. Note 6. This product is for use in indoor fixtures. This product is not intended for use near air handling heated air outlets or in wet or hazardous locations. Note 7. An unswitched AC power source is required (120, 240, or 277 volts). Note 8. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field replaceable. Contact the manufacturer for information on service. Note 9. Servicing should be performed by qualified service personnel. EBP1400NCX and EBP1400NCF Instruction Manual INSTALLATION Illustration 1 WARNING: to prevent high voltage on Red / White, Red, and Yellow output terminals prior to installation, the Test Button / Indicator Light must be disconnected. Connect the Test Button / Indicator Light after installation. NOTE: Make sure that the necessary branch circuit wiring is available. An unswitched source of power is required. 1. Disconnect AC power from the fixture. Remove the ballast channel cover. Install the emergency ballast with grounding screws either in the ballast channel (see illustrations 1 & 2) or on top of the fixture (see illustration 3 / EBP1400NCX only). 2. Select the appropriate wiring diagram to connect the emergency ballast to the AC ballast and lamp. Make sure all connections are in accordance with the National Electrical Code and any local regulations. (See Illustrations 4 and 5 for terminals). 3. Refer to the lamp compatibility table for the HIGH (Red) or Low (Red / White) connection per the lamp(s) being illuminated by the emergency ballast. 4. Install the test button / indicator light through the ballast channel cover of a troffer (Illustration 1 & 6) or through the side of a strip fixture (Illustration 2 & 7). Drill or punch a 7/8” hole to install the test button / indicator light as shown in illustration 6. Drill or punch a 1/2” hole to install the test button / indicator light as shown in illustration 7. Install the test button / indicator light as shown in the selected illustration. Apply the two included labels (“Charging Indicator Light” and “Emergency Light Push to Test”) adjacent to the test button indicator light. 5. In a readily visible location, attach the included label “CAUTION – This unit Has More Than One Power Connection Point. To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses and the Test Button / Indicator Light Before Servicing”. 6. In an area readily visible during relamping, attach the included relamping label. Write in the lamp type and wattage. 7. After installation is complete, connect the test button / indicator light. The factory installed version (EBP1400NCF) will have 2 twisted wires (brown and purple) at the access plate which must be connected for the fixture to operate in emergency mode. Emergency Ballast Test Button/ Indicator Light Ballast Channel Cover Illustration 2 Emergency Ballast Test Button/ Indicator Light Illustration 3 Wire Bundle Cover Drill 1/8˝ Hole for Mounting Screws Wire Bundle Cover 8 Replace covers being careful not to pinch wires, install lamps, supply AC power to the emergency ballast. 9.A short term discharge test may be conducted after the emergency ballast has been charging for one hour. Charge for 24 hours before conducting a long – term discharge test. Refer to OPERATION. 2 EATON ADX142715 Installation instructions Emergency Ballast 1/2˝ Std. Knockout 7/8˝ Hole w/Bushing EBP1400NCX only EBP1400NCX and EBP1400NCF Instruction Manual Illustration 4 Color coded label located here. Emergenc Suitable fo Emergenc Suitable fo Terminal labels located here. AUX COM AUXAUX COMN.O. AUX AUX N.O. N.C. LINE HOT AUX N.C. 120/240/277 LINE HOT LINE 120/240/277NEUTRAL LINE NEUTRAL TEST BU LIGHT C TEST BU LIGHT C Illustration 5 RED / WH RED / WH RED RED BLUE BLUE BLUE / WH BLUE / WH YELLOW YELLOW YELLOW / BK YELLOW / BK AUX COMMON AUX N.C. LINE HOT 120/ 277 AUX AUX N.O. COMMON AUX N.O. AUX N.C. LINE LINE HOT 120/ 277NEUTRAL LINE NEUTRAL Test Button / Indicator Light Connector Illustration 7 Illustration 6 TROFFER STYLE FIXTURE STRIP STYLE FIXTURE Fixture Emergency Ballast Ballast Channel Cover Leads to Test Button/ Indicator Light 7/8" Punch Plastic Tubing (cut to necessary length) 7/8" Bushing Inserted into Ballast Channel Cover Test Button/ Indicator Light Test Button/ Indicator Light Nut EATON ADX142715 Installation instructions 3 EBP1400NCX and EBP1400NCF Instruction Manual Lamp Compatibility Table Lamp Type Number of Lamps Lamps Connected to Low/High (Red) Output Wattage T5 1 HIGH (RED) 6 - 25, 39 T5 1 "LOW (RED / WHITE)" 28 - 35 T5HO 1 HIGH (RED) 24 T5HO 1 "LOW (RED / WHITE)" 54 - 80 T5 CIR 1 HIGH (RED) 22 - 55 T8 1 HIGH (RED) 15 - 32 T8 1 "LOW (RED / WHITE)" 59 - 86 T8U 1 HIGH (RED) 32 T9 CIR 1 HIGH (RED) 20 - 32 T12 1 HIGH (RED) 20 - 75 T12 1 "LOW (RED / WHITE)" 75 - 95 T12HO 1 HIGH (RED) 35 T12HO 1 "LOW (RED / WHITE)" 95 - 110 T12VHO 1 "LOW (RED / WHITE)" 215 BIAX 1 HIGH (RED) 18 - 55 OPERATION When AC power is applied, the charging indicator light is illuminated, indicating the battery is being charged. When power fails, the emergency ballast automatically switches to emergency power, operating one lamp at reduced illumination for at least 90 minutes. MAINTENANCE Although no routine maintenance is required to keep the emergency ballast functional, it should be checked periodically to comply with local codes. The following schedule is recommended: 1. Visually inspect the charging light monthly. It should be illuminated. 2. Test the emergency operation of the fixture at 30 day intervals for a minimum of 30 seconds. Depending on installation, one lamp should operate at reduced illumination. 3. Conduct a 90 – minute discharge test once a year. Depending on installation, one lamp should operate at reduced illumination for at least 90 minutes. Refer any service requirements indicated by these checks to qualified personnel. NOTE: After installing the test button / indicator light, mark it with the appropriate label. 4 EATON ADX142715 Installation instructions AC BALLAST LAMP ("EMERGENCY") RED RED BLUE BLUE YELLOW BLUE/WH BLUE RED OR RED/WH CHOOSE BASED ON LAMP LINE NEUTRAL LINE HOT AUX NC AUX NO AUX COM EMERGENCY BALLAST YELLOW/BK LINE NEUTRAL (UNSWITCHED) 120/277 SWITCHED OR UNSWITCHED LINE HOT EATON YELLOW YELLOW LINE NEUTRAL LINE HOT AC BALLAST ADX142715 YELLOW YELLOW YELLOW LINE NEUTRAL AC BALLAST RED RED BLUE BLUE LAMP-2 ("EMERGENCY") LINE NEUTRAL (UNSWITCHED) 120/277 SWITCHED OR UNSWITCHED LINE HOT LAMP-2 ("EMERGENCY") LINE NEUTRAL LINE HOT AUX NC AUX NO LINE HOT LAMP ("EMERGENCY") BLUE LINE NEUTRAL LINE HOT AUX NC BLUE RED OR RED/WH CHOOSE BASED ON LAMP AUX NO YELLOW BLUE/WH AUX COM EMERGENCY BALLAST YELLOW/BK LINE NEUTRAL (UNSWITCHED) 120/277 SWITCHED OR UNSWITCHED LINE HOT BLUE/WH BLUE RED OR RED/WH CHOOSE BASED ON LAMP YELLOW YELLOW/BK LINE NEUTRAL LINE HOT AUX NC AUX NO AUX COM EMERGENCY BALLAST LINE NEUTRAL (UNSWITCHED) 120/277 SWITCHED OR UNSWITCHED LINE HOT 2 LAMP RAPID START SERIES LAMP SERIES YELLOW FILAMENT AC BALLAST LAMP-1 BLUE/WH BLUE RED OR RED/WH CHOOSE BASED ON LAMP AUX COM RED LINE NEUTRAL LINE HOT 1 LAMP INSTANT START LAMP-1 RED RED BLUE BLUE YELLOW/BK EMERGENCY BALLAST 2 LAMP RAPID START SERIES / PARALLEL LAMP PARALLEL YELLOW FILAMENT LINE NEUTRAL LINE HOT 1 LAMP RAPID START EBP1400NCX and EBP1400NCF Instruction Manual TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLAST. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS WIRING DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION Installation instructions 5 6 EATON ADX142715 Installation instructions YELLOW YELLOW BLUE BLUE LINE NEUTRAL LINE HOT YELLOW YELLOW LINE NEUTRAL LINE HOT LAMP-2 ("EMERGENCY") LAMP-1 RED RED BLUE BLUE BLUE/WH BLUE RED OR RED/WH CHOOSE BASED ON LAMP LINE NEUTRAL LINE HOT AUX NC AUX NO AUX COM LINE NEUTRAL (UNSWITCHED) 120/277 SWITCHED OR UNSWITCHED LINE HOT AC BALLAST LAMP-3 LAMP-2 ("EMERGENCY") LAMP-1 RED RED BLUE/WHT BLUE/WHT BLUE/WH BLUE RED OR RED/WH CHOOSE BASED ON LAMP YELLOW YELLOW/BK LINE NEUTRAL LINE HOT AUX NC AUX NO AUX COM EMERGENCY BALLAST LINE NEUTRAL (UNSWITCHED) 120/277 SWITCHED OR UNSWITCHED LINE HOT 3 LAMP RAPID START SERIES LAMP PARALLEL YELLOW FILAMENT AC BALLAST YELLOW YELLOW/BK EMERGENCY BALLAST 2 LAMP RAPID START OSRAM SYLVANIA SERIES LAMP PARALLEL YELLOW FILAMENT LINE NEUTRAL LINE HOT LINE NEUTRAL LINE HOT AC BALLAST AC BALLAST YELLOW RED OR RED/WH CHOOSE BASED ON LAMP BLUE BLUE/WH LAMP-3 ("EMERGENCY") LAMP-2 LAMP-1 RED OR YELLOW BLUE BLUE BLUE BLUE/WH YELLOW YELLOW/BK RED OR RED/WH CHOOSE BASED ON LAMP BLUE LINE NEUTRAL LINE HOT AUX NC AUX NO AUX COM LINE NEUTRAL LINE HOT AUX NC AUX NO AUX COM EMERGENCY BALLAST 3 LAMP INSTANT START LAMP-2 ("EMERGENCY") LAMP-1 RED BLUE BLUE YELLOW/BK EMERGENCY BALLAST 2 LAMP INSTANT START LINE NEUTRAL (UNSWITCHED) 120/277 SWITCHED OR UNSWITCHED LINE HOT LINE NEUTRAL (UNSWITCHED) 120/277 SWITCHED OR UNSWITCHED LINE HOT EBP1400NCX and EBP1400NCF Instruction Manual WIRING DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLAST. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS EATON YELLOW YELLOW LINE HOT LINE NEUTRAL AC BALLAST LAMP-4 ("EMERGENCY") LAMP-3 LAMP-2 LAMP-1 RED RED BLUE/WHT BLUE/WHT BLUE BLUE EMERGENCY BALLAST BLUE/WH BLUE RED OR RED/WH CHOOSE BASED ON LAMP YELLOW/BK YELLOW LINE NEUTRAL LINE HOT AUX NC AUX NO AUX COM LINE NEUTRAL (UNSWITCHED) 120/277 SWITCHED OR UNSWITCHED LINE HOT ADX142715 RED RED BLUE BLUE LAMP-3 ("EMERGENCY") LAMP-2 LAMP-1 AC BALLAST RED/WHT RED/WHT EMERGENCY BALLAST BLUE/WH BLUE RED OR RED/WH CHOOSE BASED ON LAMP YELLOW/BK YELLOW LINE NEUTRAL LINE HOT AUX NC AUX NO AUX COM LINE NEUTRAL (UNSWITCHED) 120/277 SWITCHED OR UNSWITCHED LINE HOT 3 LAMP RAPID START PARALLEL LAMP PARALLEL YELLOW FILAMENT YELLOW YELLOW BROWN BROWN LINE HOT LINE NEUTRAL 4 LAMP RAPID START SERIES LAMP PARALLEL YELLOW FILAMENT YELLOW YELLOW LINE NEUTRAL LINE HOT YELLOW YELLOW LINE NEUTRAL LINE HOT LAMP-4 ("EMERGENCY") LAMP-3 LAMP-2 LAMP-1 RED RED BLUE BLUE RED OR RED/WH CHOOSE BASED ON LAMP YELLOW BLUE/WH BLUE LINE NEUTRAL LINE HOT AUX NC AUX NO AUX COM LINE NEUTRAL (UNSWITCHED) 120/277 SWITCHED OR UNSWITCHED LINE HOT LAMP-4 ("EMERGENCY") LAMP-3 LAMP-2 LAMP-1 AC BALLAST BLUE/WHT BLUE/WHT RED/WHT RED/WHT BLUE BLUE RED RED EMERGENCY BALLAST BLUE/WH BLUE RED OR RED/WH CHOOSE BASED ON LAMP YELLOW/BK YELLOW LINE NEUTRAL LINE HOT AUX NC AUX NO AUX COM LINE NEUTRAL (UNSWITCHED) 120/277 SWITCHED OR UNSWITCHED LINE HOT 4 LAMP RAPID START PARALLEL LAMP PARALLEL YELLOW FILAMENT AC BALLAST YELLOW/BK EMERGENCY BALLAST 4 LAMP INSTANT START EBP1400NCX and EBP1400NCF Instruction Manual WIRING DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLAST. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS Installation instructions 7 EBP1400NCX and EBP1400NCF Instruction Manual WIRING DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLAST. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS BI LEVEL BALLAST SWITCHED LINE HOT EMERGENCY BALLAST YELLOW/BK SWITCHED LINE HOT LINE NEUTRAL BI-LEVEL AC BALLAST WIRE LAMPS USING DIAGRAM PER # OF LAMPS AND BALLAST TYPE AUX COM YELLOW BLUE/WH AUX NO BLUE RED OR RED/WH CHOOSE BASED ON LAMP AUX NC LINE HOT LINE NEUTRAL (UNSWITCHED) 120/277 LINE NEUTRAL When using the auxillary relay to switch the neutral line, the Emergency and A.C. ballasts must be on the same branch circuit. Warranties and Limitation of Liability Please refer to www.cooperlighting.com/WarrantyTerms for our terms and conditions. Eaton 1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.eaton.com/lighting Canada Sales 5925 McLaughlin Road Mississauga, Ontario L5R 1B8 P: 905-501-3000 F: 905-501-3172 © 2015 Eaton All Rights Reserved Printed in USA Publication No. ADX142715 June 19, 2015 9:44 AM Eaton is a registered trademark. All trademarks are property of their respective owners. Product availability, specifications, and compliances are subject to change without notice