COOPER LIGHTING - SURE-LITES Catalog # Type ®

advertisement
COOPER LIGHTING - SURE-LITES ®
DESCRIPTION
The GC Series combines a clean, sleek contemporary appearance with
state-of-the-art electronics. Specifically designed for initial and retrofit
installations where a recessed unit is required to minimize overhead
obstacles and maximize aesthetics. The unit is ideal for locations with
limited wall space and where panoramic positioning is necessary for the
ceiling mounted lampholders to provide proper light distribution. Ideal
for stores, offices, hospitals and school corridors.
Type
Catalog #
Project
Date
Comments
Prepared by
S P E C I F I C AT I O N F E AT U R E S
E l e c t ro n i c
H o u s i n g C o n s t ru c t i o n
Wa rra n t y
- Dual Voltage Input 120/277 VAC,
60 Hz
- Line-latching,
- Solid-state Voltage Limited
Charger
- Solid-state Switching
- Low-Voltage Disconnect
- Brownout Circuit
- Overload/Short Circuit Protection
- Test Switch/Power
- Indicator Light
- 20-Gauge Die-Formed Steel
- Knockout, Conduit or Cord Set
- Flanged for Mounting in Grid
Type Suspended Ceilings
- Above ceiling access required
for maintenance
- Single modular electrical
Connector
- White Powder Coat Finish
- Unit: 1-year
- Battery: 15-year pro-rata
H e a d / L a m p Da t a
- Two Heads Standard
- Glare-Free Lens
- Fully Adjustable
- Remote Capability
- High Impact - Thermoplastic
- Matches Housing Finish
Code Compliance
- UL 924 Listed
- Life Safety NFPA 101
- NEC/OSHA
- Most State and Local Codes
B a tte r y
- Sealed Nickel Cadmium
- Maintenance-Free, Long-Life
- Full Recharge Time, 24 hrs. (max.)
- Color Coded Leadwires
GC
SERIES
6 5/8” [168mm]
23 3/4” [603mm]
5 3/4” [146mm]
6 VO LT
SEALED NICKEL
C A D M I U M B AT T E RY
6 5/8”
[168mm]
E M E R G E N CY L I G H T I N G
5 1/8”
[130mm]
E L E C T R I C A L R AT I N G S
R a t e d W a t t a g e to 87 1/2% of Rated D.C. Voltage
Model
GC15122
GC15132
GC15142
DC Voltage
6
6
6
1 1/2 Hours
15
24
48
2 Hours
12
18
36
3 Hours
8
12
24
Lamp Information
4 Hours
6
10
20
Type
Wattage
Number
Incandescent
7.2
7.2
7.2
29-88
29-88
29-88
Incandescent
Incandescent
ORDERING INFORMATION
E N E R G Y D ATA
GC15122
Input Current (Max.):
120V= .06A
Series
GC15122
GC15132
GC15142
5
277V= .03A
Options 1, 2
V=Voltmeter3
Accessories
Protective Housing
GC15132
SD=Self Diagnostics4
TDM=Time Delay Monitor
WG12=Wire Guard
Input Current (Max.):
WG17=Wire Guard for use with CL heads
120V= .07A
VK1=Voltmeter
277V= .04A
GC15142
Notes:
1 Add as a suffix. 2 Consult your Cooper Lighting Representative for alternate lamps and additional options. 3 Provisions for one meter only. 4 Self Diagnostics
(GC15122, GC15132, GC15172 ,GC15182 only) 5 Order separately.
Input Current (Max.):
120V= .08A
277V= .05A
Specifications and dimensions subject to change without notice.
Consult your representative for additional options and finishes.
ADX041156 pc
2010-07-22 15:38:08
GC SERIES
P H OTO M E T R I C S
Horizontal Distribution
15
FEET
LEFT
0
FEET
RIGHT
15
0
1FC
Ve r t i c a l D i s t r i b u t i o n
0.5
0.3
0.2
0.1 LAMP
AXIS
10
20
30
40
50
60
15
FEET
LEFT
0
FEET
RIGHT
15
0
1FC
0.5
0.3
0.2
0.1 LAMP
AXIS
10
20
30
40
60
50
FEET FROM LAMP (Measured on axis)
FEET FROM LAMP (Measured on axis)
Lamp No. 29-88
Lamp No. 29-88
Initial Lumens – 29-88 @ 101
T E C H N I C A L DATA
Heads
S o l i d - S t a te C h a rge r
L ow- Vo l t a ge D i s c o n n e c t
The lamp housing is constructed of flameresistant and impact-resistant injection molded
thermoplastic with matching finish. The three
dimensional swivel assembly permits
approximate aiming adjustment from 80°
vertical and 358° rotation. The placement is
secured with a lockable pivot mounted on a
rotating base ring.
Supplied with a 120/277 VAC, voltage regulated
solid-state charger. Immediately upon
restoration of AC current after a power failure,
the charger provides a high charge rate. The
charge circuit reacts to the condition of the
battery and alters the rate of charge in order to
maintain peak battery capacity and maximize
battery life. Solid-state construction recharges
the battery following a power failure in
accordance with UL 924.
When the battery’s terminal voltage falls below
80% of the rated voltage, the low-voltage
circuitry disconnects the lighting load. The
disconnect remains in effect until normal utility
power is restored, preventing deep battery
discharge.
Lamps
Designed specifically for emergency lighting
applications, the PAR 36 sealed beam type
design insures optimum glare-free light
distribution along with horizontal and vertical
adjustment by rotating the lens within the
housing.
Housing
The rugged 20-gauge die-formed cold rolled
steel housing is finished with white corrosionresistant polyester powder coat paint. Cabinet
has knockouts in side for AC/DC wiring
connections and has universal mounting
pattern. Removable full width cover provides
easy above-ceiling access to batteries and
electronics.
L i n e - L a t ch e d
Sure-Lites’ line-latched electronic circuitry
makes installation easy and economical. A labor
efficient AC-activated load switch prevents the
lamps from turning on during installation to a
non-energized AC circuit. Line-latching
eliminates the need for a contractor’s return to a
job site to connect the batteries when the
building’s main power is permanently turned
on.
O ve rl o a d a n d S h o rt C i rc u i t P ro te c t i o n
The solid-state overload monitoring device in
the DC circuit disconnects the lamp load from
the battery should excessive wattage demands
be made and automatically resets when the
overload or short circuit is removed. This
overload current protective feature eliminates
the need for fuses or circuit breakers for the DC
load.
B row n o u t C i rc u i t
The brownout circuit in Sure- Lites’ units
monitors the flow of AC current to the unit and
activates the emergency lighting system when a
predetermined reduction of AC power occurs.
This dip in voltage will cause most ballasted
fixtures to extinguish causing loss of normal
lighting even though a total power failure has
not occurred.
Te s t Sw i t ch / Powe r I n d i c a to r L i g h t
Conveniently located Test Switch allows for
manual verification of proper operation of the
transfer circuit and emergency lamps. The
Power Indicator Light provides visual assurance
that the AC power is on.
S e a l e d N i cke l C a d m i u m B a tte r y
Sure-Lites sealed nickel cadmium batteries are
maintenance-free with a life expectancy of 15
years. The sealed rechargeable nickel cadmium
battery utilizes positive and negative sintered
plate construction which offers high discharge
rates and stable performance over a wide range
of temperatures. The specially designed
resealable vent automatically controls cell
pressure, assuring safety and reliability. This
battery is best suited for harsh ambient
temperatures because the electrolyte is not
active in the electrochemical process. The nickel
cadmium battery can be operated from 0°C to
50°C.
Wa rra n t y
S o l i d - S t a te Tra n s fe r
The unit incorporates a solid-state switching
transistor which eliminates corroded and pitted
contacts or mechanical failures associated with
relays. The switching circuit is designed to
detect a loss of AC voltage and automatically
energizes the lamps. Upon restoration of the AC
power, the emergency lamps will switch off and
the charger will automatically recharge the
battery.
All Sure-Lites’ units are backed by a firm oneyear warranty against defect in material and
workmanship (excluding lamps). Maintenancefree, long-life, sealed lead calcium batteries
carry a five-year pro-rata warranty.
Specifications and dimensions subject to change without notice.
Sure-Lites • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • TEL 770.486.4800 • FAX 770.486.4801
ADX041156 pc
2010-07-22 15:38:08
2010-07-22 16:07:00
Download