Component Products The Cooper Posi-Break™ Solution to Separable Connector Switching Problems at Wisconsin Electric Power Company by Kevin Fox Senior Product Specialist S ince the late 1980s, many utilities noticed an increased number of flashovers occurring on their 25 kV underground systems. This happened only during the break operation and involved 25 kV, 200 A loadbreak elbows and protective caps. These events would usually cause a protective device to operate, resulting in a customer outage and damage to associated equipment. In 1994, Cooper Power Systems’ Components & Protective Equipment Group, with the cooperation of several utilities including Northern States Power, Public Service of Colorado, Missoula Electric and most notably, Wisconsin Electric, began research to find a solution to this flashover problem. A synthetic circuit that replicated field conditions was built to monitor circuit parameters. Testing conducted by Cooper’s Systems Engineering Group at the Thomas A. Edison Technical Center began in early 1995 and lasted through the winter of 1997. The result of this testing and research revealed several common factors: • The flash to ground occurred before actual contact separation between the two components. • Majority of the flashovers involved little to no load current (there is no load present when removing protective caps). Armed with this new data, a process of elimination was started to determine the cause of the flashovers. Several system and operator variables were tested to evaluate their influence on the flashover phenomena. Most were eliminated, however the discovery of a partial vacuum effect justified further study. The Partial Vacuum Effect The partial vacuum effect occurs only on the break operation of separable connectors and would usually involve stuck interfaces. In colder weather when the rubber and silicone lubricant is stiffer, or in warmer climates where the grease has evaporated or “bled” off, the elbow or cap will be harder to remove. • Regionally, most failures occurred in the northeastern and north central United States. However, there were occurrences in the southeast and western United States. • Failures occur only on a “break” operation. • Most failures occurred below 35° F ambient. • Stuck interfaces increased the likelihood of a flashover. • A failure can occur on any component with a 25 kV, 200 A interface or 35 kV small interface, from all manufacturers. the component, the air space located at the back of the elbow or cap (by the bushing nosepiece) expands, creating a partial vacuum. A partial vacuum environment is a very poor insulator. The relationship of the decreased voltage withstand of air, due to a drop in pressure is known as “Paschen’s Law.” Figure 1 Paschen’s Law curve showing the relationship between air pressure and its corresponding dielectric strength During a break operation, as the lineman applies more force to unlatch Figure 2 Strike path of a standard 25 kV elbow and insert during a partial vacuum flashover As this air space continues to expand and the vacuum increases, the energized copper probe and conductive insert becomes surrounded by the partial vacuum, thus reducing the dielectric strength. When enough force is applied to “unlatch” the component and the interfaces between the elbow or cap and the bushing insert separate, a flashover occurs from the exposed probe and conductive insert to the nearest ground, usually the collar of the bushing. This will occur within the first 0.4” of travel. The POSI-BREAK Solution Once the cause was determined, Components and Protective Equipment set out to find a solution. Working with actual utilities, several design parameters were set as “must have”, including: • Must meet current IEEE-386 standards. • Must be completely interchangeable with all old and new components. • Must be retrofittable without a customer outage. • Must maintain the stress relieving Faraday cage. This was ultimately accomplished by encapsulating the molded conductive insert inside the elbow and cap, in insulating rubber. This isolates the conductive components away from the insulated interface of the bushing. In a standard elbow and cap this conductive insert is in direct contact with the bushing interface. Next, a rigid insulating sleeve was added to the top portion of the copper probe of the elbow and cap. These two efforts increased the strike distance from an energized component to ground from approximately Figure 3 The increased strike distance of the POSI-BREAK elbow and cap is achieved by insulating the molded conductive insert and the copper probe 3.2” to 5.9”, an increase of over 84%. The name Cooper POSI-BREAK™ was selected because it reflects the higher degree of positive switching performance that these products provide. By the fall of 1997, only three months after the design was conceptualized, we had limited production parts ready for field evaluation. With the cooperation of Wisconsin Electric and Missoula Electric, trial POSIBREAK units were installed on their two systems. These two utilities agreed to install and periodically switch units throughout the winter of 1997-98 and to keep detailed records to assist in the product evaluation. In the meantime, Cooper continued their own testing of the POSIBREAK components. One of the main objectives was to determine how much additional margin this design provided over the existing product. In “real world” applications, transient overvoltages can result in a rise of more than 43 kV peak (30 kV rms) during switching operations. Consequently, switching tests were conducted at 30 kV L-G for both the elbow and cap. This is well in excess of the 26.3 kV currently required by the IEEE standard. After over 60 operations, the POSI-BREAK components passed without a single failure. This extra margin assures reliable operations under the worst-case situations seen in the field. By the end of April, both Wisconsin Electric and Missoula Electric had completed their trials. Wisconsin Electric had installed the POSI-BREAK components on two separate, existing 14.4 kV circuits and switched in temperatures from -5° F to +39° F. They successfully switched the components in excess of 200 times without a single failure. Missoula constructed a circuit especially to test the POSI-BREAK components. They designed the circuit to have both the standard and new design installed side by side for a direct comparison. After switching all winter, they too had a 100% success rate with the POSI-BREAK design. However they did have a standard design cap fail under the same conditions that they had just successfully switched with the POSI-BREAK design. Both utilities had previously reported a relatively high number of “unexplained” flashovers, especially in the winter months. Wisconsin Electric stated they would have from 10 to 15 of these flashes during the months between October to March. As a temporary solution, they implemented preheating the elbows in pad-mounted equipment with a portable kerosene heater. They did this for approximately 20 minutes before they tried pulling the elbow or cap off the bushing. While the number of flashovers dropped, the manpower cost was prohibitive for a long-term solution. Missoula Electric was experiencing up to a 40% flashover rate of caps in one feeder alone and was considering making their 25 kV system deadbreak. This was a safety and reliability concern that would also have a significant economic impact on their operating practices. No design eliminates the partial vacuum. The increased strike distance this design provides, increases the withstand margin of the component that effectively negates any adverse effects that can be created by the partial vacuum. By virtue of this increased margin, the POSI-BREAK design has broader applications than just solving the partial vacuum puzzle. The increase in dielectrics also increases the components’ tolerance to other system and operator issues, including transient overvoltages caused by ferroresonance and circuit capacitance and interface contamination that can occur during installation or switching. Figure 4 The POSI-BREAK is setting a new standard in the utility industry Working closely with utility users has helped Cooper develop a new product concept that not only addressed their concerns but also increased their system reliability in ways not previously considered. This solution was conceived by using feedback from actual users in the field, not just lab data. Voltages used in the test procedure were taken from actual field measurements and the vacuum analysis was based on readings observed on elbows and caps that were really stuck on bushing interfaces in the middle of winter. Utilizing all these resources helped Cooper create a solution that met all the criteria set forth by the utility user, including complete compliance to IEEE386, fully retrofittable without an outage, and completely interchangeable with all available mating components. Used in combination with the Cooper exclusive latch indicator insert that provides immediate reliable feedback on the quality of the installation, the Cooper POSI-BREAK 25 kV elbow and cap represent the most dependable, costeffective loadbreak system available. Bulletin Number 98065 • © 1998 Cooper Power Systems • MI 10/98 5M