High Speed Fuses Ferrule — FWP 690V/700V (IEC/UL): 20-100A, Striker Optional FWP (22 x 58mm) Arc Voltage This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%. Specifications Description: Ferrule style high speed fuses with and without indicating striker. Dimensions: See dimensions illustration. Ratings: Volts: — 690Vac (IEC) — 700Vac (UL) Amps: — 20-100A IR: — 200kA RMS Sym. — 50kA @ 500Vdc Agency Information: CE, UL Recognition 5 4 Eg 200 Power Losses FWP with striker option. K 300 400 500 600 700 1.0 Kp 0.8 0.6 0.5 High Speed Fuses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current. Total Clearing I2t 1.4 1.2 1.0 0.9 0.8 0.7 0.6 UL 3 Electrical Characteristics The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). 1.4 1.2 103 9 8 7 6 0.4 0.3 0.2 Ib 0.1 30 40 50 60 70 80 90 100% Catalog Numbers 0.5 0.4 Eg 0.3 200 300 400 500 600 Dimensions - mm (inches) Without Striker 58.0 (2.283") 22.2 (0.875") 15.0 (0.591") Size 22 x 58mm (7⁄8" x 29⁄32") 22 x 58mm (7⁄8" x 29⁄32") Watts Loss 20 25 32 40 50 63 80 100* 19.0 34.0 53.5 68 135 280 600 1100 260 410 605 750 1600 3080 6600 12500 5 6 8 9 9.5 11 13.5 16 20 25 32 40 50 63 80 100* 19.0 34.0 53.5 68 135 280 600 1100 260 410 605 750 1600 3080 6600 12500 5 6 8 9 9.5 11 13.5 16 *IEC/UL Voltage rating 690/700 With Striker 66 (2.598") 58 (2.283") 5 (0.197") 700 Catalog Numbers Without Striker FWP-20A22Fa FWP-25A22Fa FWP-32A22Fa FWP-40A22Fa FWP-50A22Fa FWP-63A22Fa FWP-80A22Fa FWP-100A22Fa With Striker FWP-20A22FI FWP-25A22FI FWP-32A22FI FWP-40A22FI FWP-50A22FI FWP-63A22FI FWP-80A22FI FWP-100A22FI Electrical Characteristics I2t (A2 Sec) Minimum Clearing At Melting Rated Voltage Rated Current RMS-Amps • • • • Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks • • • • Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters 16 (0.630" 22.2 (0.874") Data Sheet: 720026 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 209 High Speed Fuses Ferrule — FWP 690V/700V (IEC/UL): 20-100A, Striker Optional Without Striker FWP 20-100A: 660V/700V (22 x 58mm) Time-Current Curve 104 6 4 2 103 6 4 2 FWP-50A22F FWP-63A22F FWP-80A22F FWP-100A22F 102 6 4 Virtual Pre-Arcing Time In Seconds 2 101 6 4 2 10 0 6 4 FWP-20A22F FWP-25A22F FWP-32A22F FWP-40A22F 2 10–1 6 4 2 10–2 6 4 2 10–3 6 4 2 10–4 2 101 4 6 8 2 102 4 6 8 103 Prospective Current In Amps RMS Peak Let-Through Curve 104 FWP-100A22F FWP-80A22F 6 FWP-63A22F Peak Let-Through Current 4 FWP-50A22F 2 103 6 FWP-40A22F FWP-32A22F 4 FWP-25A22F FWP-20A22F 2 102 102 2 4 6 103 2 4 6 104 2 4 6 105 2 Prospective Short-Circuit Current Symmetrical RMS Data Sheet: 35785291 210 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa