INS # Application Note Room Controller application for use with an Outdoor Contact Input Photocell Overview The Room Controller can utilize a standard Outdoor Contact Input Photocell (PPS-5) to provide On/Off control of the lighting loads based on a daylight threshold. Description The Room Controller low voltage interface ports provide +24 VDC to power the Keypad(s) Slider Station, Daylight Sensor and Occupancy Sensors(s). The external +24 VDC power is limited to 90mA. The Outdoor Contact Input Photocell draws a maximum of 35mA per sensor and is the largest consumer of external dc power. Table 1. Maximum Current Consumption of Various Accessories Accessory Max Current Consumption (mA) Keypad 3.00 Slider 2.00 Daylight Sensor* 8.00 Occupancy Sensor, PIR 10.00 Occupancy Sensor, dual tech 25.00 Network node 18.00 Outdoor Contact Input Photocell 35.00 *One daylight sensor is allowed per Room Controller panel Implementation Applications that require the use of an Outdoor Photocell to control exterior lighting can be achieved by using the Outdoor Contact Input Photocell (PPS-5) with a Room Controller. It is possible to also connect other controls to the Room Controller as long as the 90mA available power is not exceeded. If using the Outdoor Contact Input Photocell, occupancy sensors cannot be used as their operation will conflict with the PPS-5 control logic. The Outdoor Contact Input Photocell (PPS-5) is connected to the Room Controller Input/Output Device (Model # OCC-RJ45) which connects to the Room Controller RJ45 port 3 or 4 via Cat 5 cable. When the Outdoor Contact Input Photocell (PPS-5) does not detect adequate light levels it provides a closure to the Room Controller which will turn ON the desired lighting loads. When the Outdoor Contact Input Photocell (PPS-5) detects adequate ambient light levels it will automatically turn OFF all lighting loads Wiring Information Wire the Outdoor Contact Input Photocell (PPS-5) to the Room Controller Input/Output device (OCC-RJ45) as shown in Figure 1 below. PPS-5 (Outdoor Contact Input Photocell) OCC-RJ45 (Input/Output Device) Model: OCC-RJ45 Occupancy Sensor Coupler Brown Black Red Orange Black Red Blue Figure 1. Input/Output Device Wiring Connect the OCC-RJ45 to the Room Controller port 3 or port 4 as shown in Figure 2 below. Sensors Sensors Demand Response Alert Mode Time Clock Integration Controls Wallstations + + + + Adjustable Skylights Switchpack Receptacle BMS/Out Slider Station A/V Mode 6 4 3 2 4 Dimmer 2 Red Blue 0-10V Gain Adjustment 0-10V Dimming Outputs + + + Dimmer 3 Black Energy Options 3 High End Occ Vac (default) Brown Reset 1 2 Low End Default 10% 20% 30% 40% Not Used Occupancy QuickConnect Cable (Class 2) 1 Energy Options DIP Switch Demand Response OCC-RJ45 (Input/Output Device) 5 Integration Controls Adjustable Skylights Green QuickConnect Cables Black Status Black - Line In White/Black - 120V N White/Orange - 277V N Blue - EM Line In Blue - EM Loads Out White Red PPS-5 (Outdoor Contact Input Photocell) Model: OCC-RJ45 Occupancy Sensor Coupler Blue - Load In Yellow - Load 1 Out Red - Load 2 Out Purple - Load 3 Out (Line In & Load Out) Room Controller CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation. Normal Power Dimmer 1 - Dimmer 3 + - Dimmer 2 + - Dimmer 1 + 0-10V Dimming Figure 2. Connecting the OCC-RJ45 to the Room Controller 2 Room Controller application for use with an Outdoor Contact Input Photocell www.eaton.com Programming Information In order for the Outdoor Contact Input Photocell (PPS-5) to turn ON the lighting loads within the Room Controller the Room Controller must be put into the Occupancy Auto On Mode. This is done by moving DIP Switch #3 and #4 into the On (UP) position. The Outdoor Contact Input Photocell (PPS-5) will now turn ON the lighting loads when the ambient light level is low and turn OFF the lighting loads with the ambient light level is high. By default the ON scene is all relays ON and all dimmers to 100%. Use the Room Controller Personal Remote (HHPR-RC) to adjust the Automatic On scene to any desired light level. Sensors Sensors Slider Station Wallstations - A/V Mode + Demand Response + Alert Mode + Time Clock + Adjustable Skylights Switchpack Receptacle BMS/Out 6 5 4 Integration Controls Adjustable Skylights Green QuickConnect Cables Red Black Integration Controls 2 4 Reset 3 Energy Options Not Used Occupancy Occ Vac (default) High End 1 2 Status 0-10V Gain Adjustment 0-10V Dimming Outputs + + + Dimmer 3 Dimmer 2 4 1 Energy Options DIP Switch Demand Response Default 10% 20% 30% 40% 3 3 Low End Blue - Load In Yellow - Load 1 Out Blue - EM Line In Blue - EM Loads Out Black - Line In White/Black - 120V N White/Orange - 277V N White CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation. Red - Load 2 Out Purple - Load 3 Out To OCC-RJ45 (Input/Output Device) Dimmer 1 - Dimmer 3 + - Dimmer 2 + - Dimmer 1 + 0-10V Dimming 4 3 1 2 3 4 All Relays On to Automatic On Scene* * DIP Switches 3&4 up triggers programmable Scene 6, which can be adjusted using the Personal Remote (HHPR-RC) Figure 3. Room Controller Automatic ON Scene Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, GA coopercontrol.com © 2014 Eaton All Rights Reserved Printed in USA Publication No. ACC140952 October 10, 2014 Eaton is a registered trademark. All trademarks are property of their respective owners.