SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
APPLICATION
The following wiring diagrams provide instructions for connecting field wiring leads to Champ and Hazard•Gard HID luminaires with quartz auxiliary lamp. A 120 volt tap is required for auxiliary lamp operation
(Quartz lamp is not supplied).
In the event of a power interruption or ballast failure, following restoration of power the auxiliary lamp will light. The auxiliary lamp will remain ON for 2 minutes after the HID lamp restrikes.
WARNING
Electrical power must be
OFF before and during installation and maintenance.
Wiring diagrams - see page 2
Situation #1
- The fixture is being energized with a cold HID lamp.
Under this condition, the Quartz lamp and the HID lamp will come on when the fixture is powered up and the Quartz lamp will remain on for a period of time ranging from 2-4 minutes while the HID lamp is warming up.
Situation #2
- The fixture’s HID lamp has been on for a length of time (hot HID lamp) and power is lost and then restored to the fixture.
Under this condition, the Quartz lamp will come on once the power is restored. The Quartz lamp will remain on as long as the HID isn’t operating (2-5 min) and once the HID lamp restrikes, it will go off in 2-4 minutes.
LAMP ORDERING CODE
Maximum wattage for auxiliary lamp in fixture with suffix qtz (Quartz) is 100 watts.
SYLVANIA, GE or PHILLIPS
100 watt - 100Q/CL/DC, Q100 CL/DC, Q100 DC or equivalent.
IF 510 • 11/08 Copyright © 2008, Cooper Industries, Inc.
Page 1
LINE
VOLTAGE
277V
CAP.
CAP.
277V
240V
208V
120V
COMMON
PULSE START METAL HALIDE
METAL HALIDE BALLAST 70W - 100W
50W - 150W LX
175W - 400W S828
BLACK
CAP.
BALLAST
COMMON
LAMP
X3
IGNITOR
X3
X1
X2
BLACK
WHITE
RED
WHITE
AUX.
LAMP
HOLDER
WHITE
WHITE
AUXILIARY
SWITCH
(SUFFIX-QTZ)
YELLOW
WHITE
BLACK
LAMP
HOLDER
CAP.
277V CAP.
BLACK
LINE
VOLTAGE
COMMON
277V
240V
208V
120V
BALLAST
BLACK
RED
WHITE
AUX.
LAMP
HOLDER
WHITE
AUXILIARY
SWITCH
(SUFFIX-QTZ)
YELLOW
WHITE
BLACK
LAMP
HOLDER
COMMON
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Crouse-Hinds "Terms and Conditions of Sale", and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
Cooper Industries Inc.
Crouse-Hinds Division
PO Box 4999, Syracuse, New York 13221 • U.S.A.
Copyright© 2002, Cooper Industries, Inc.
IF 510
Revision 2
Revised 11/08
Supercedes 04/03