Communications Point Data Base COOPER POWER SERIES

Voltage Regulators
Technical Data
TD225002EN
Effective XXX 2015
Supersedes 240-40 August 2012
COOPER POWER
SERIES
Communications Point Data Base
for Communications Protocol 2179
For use with Eaton’s Cooper Power series
CL-7 Voltage Regulator Control
CL-7 Cooper 2179 Device Profile Data Dictionary
CL-7 2179 Map Points
June 3, 2015
v2.00
THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF EATON.
UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED.
Document
1.00
2.00
Date
6/21/2013
6/3/2015
Description
Initial Release
Updates for Summer 2015 release
This document references the "CL7 Default" point map available in the ProView NXG software.
Page 1
Cover Page
CL-7 Cooper 2179 Device Profile Data Dictionary
INPUT SUBSYSTEM
Binary Input Status
Description
VR1 Bandwidth Low
VR1 Bandwidth High
VR1 Voltage Limiter Low
VR1 Voltage Limiter High
Voltage Reduction Active
VR1 Auto Operation Blocking Status Blocked (Follows FC069)
VR1 HMI LED Auto Tap Blocked ON
VR1 System Power Direction Indeterminate
VR1 System Power Direction Reverse
VR1 Control Power Direction Reverse
VR1 Blocking Relay Active
VR1 HMI LED Neutral Position On
VR1 HMI Switch Auto/Manual Auto
HMI Switch Supervisory Off
HMI LED Alarm On
HMI LED Warning On
HMI LED Diagnostic Error On
VR1 Motor Trouble
Tap To Neutral Active
Soft Add-Amp Active
AltConfigActive
Configurable Logic Output from SCADA Tap to Neutral Activate
Configurable Logic Output from SCADA Voltage Reduction Level 1 Activate
Configurable Logic Output from SCADA Voltage Reduction Level 2 Activate
Configurable Logic User Defined LED 1 On
Configurable Logic User Defined LED 2 On
Configurable Logic User Defined LED 3 On
Configurable Logic Point 01 to SCADA
Configurable Logic Point 02 to SCADA
Configurable Logic Point 03 to SCADA
Configurable Logic Point 04 to SCADA
No Assignment
Register Bit ID
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
2-Bit Status
Sequence
Simple Status
Sequence
00
01
02
03
04
0 (0x0)
05
06
07
48(0x30)
08
09
10
11
12
1 (0x1)
13
14
15
00
01
02
03
04
2 (0x2)
05
06
07
49(0x31)
08
09
10
11
12
3 (0x3)
13
14
15
Page 2
Basic Scan, Status
CL-7 Cooper 2179 Device Profile Data Dictionary
INPUT SUBSYSTEM
Counters
Description
VR1 Operations Counter
VR1 Operations 24HR Counter
VR1 Operations 30DY Counter
VR1 Operations Month Counter
VR1 Operations Last Month Counter
VR1 Operations Year Counter
VR1 Operations Last Year Counter
VR1 TPI Neutral Resynch Counter
VR1 Lower to Neutral Sync Retry Counter
VR1 Raise to Neutral Sync Retry Counter
VR1 Taps Past 16R Counter
VR1 Taps Past 16L Counter
Measured/Incremental TPI Mismatch Count
COM1 Rx Message Counter
COM2 Rx Message Counter
COM1 Tx Message Counter
COM2 Tx Message Counter
COM1 Message Error Counter
COM2 Message Error Counter
Index
Sequence
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
64 (0x40)
65 (0x41)
66 (0x42)
67 (0x43)
68 (0x44)
69 (0x45)
70 (0x46)
71 (0x47)
72 (0x48)
73 (0x49)
74 (0x4A)
75 (0x4B)
76 (0x4C)
77 (0x4D)
78 (0x4E)
79 (0x4F)
80 (0x50)
81 (0x51)
82 (0x52)
Page 3
Basic Scan, Counters
CL-7 Cooper 2179 Device Profile Data Dictionary
INPUT SUBSYSTEM
Analog Inputs
Description
VR1 Load Voltage Secondary
VR1 Load Voltage Primary
VR1 Compensated Voltage Secondary
VR1 Load Current Primary
VR1 Source Voltage Secondary
VR1 Source Voltage Primary
VR1 Tap Position
VR1 Percent Reg
VR1 Power Factor
VR1 KVA Load
VR1 kW Load
VR1 KVAR Load
Frequency
VR1 Harm Total Voltage Harmonics
VR1 Harm Total Current Harmonics
VR1 kWh Forward
VR1 KWH Reverse
VR1 KQH Forward
VR1 KQH Reverse
VR1 Operation Counter
VR1 Load Current Real
VR1 Load Current Reactive
VR1 Phase Angle
Voltage Reduction In Effect
Active Configuration
Active Adaptive Add Amp Level
Index
Sequence
Scale
Factor
Units
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
128 (0x80)
129 (0x81)
130 (0x82)
131 (0x83)
132 (0x84)
133 (0x85)
134 (0x86)
135 (0x87)
136 (0x88)
137 (0x89)
138 (0x8A)
139 (0x8B)
140 (0x8C)
141 (0x8D)
142 (0x8E)
143 (0x8F)
144 (0x90)
145 (0x91)
146 (0x92)
147 (0x93)
148 (0x94)
149 (0x95)
150 (0x96)
151 (0x97)
152 (0x98)
153 (0x99)
10
100
10
10
10
100
1
10
1000
10
10
10
100
10
10
1
1
1
1
1
10
10
1
10
1
1
Volts
kVolts
Volts
Amps
Volts
kVolts
-%
-kVA
kW
kvar
Hz
%
%
kWHr
kWHr
kvarHr
kvarHr
-Amps
Amps
Degrees
%
%
--
Page 4
Basic Scan, Analogs
CL-7 Cooper 2179 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Select-Before-Operate Points
Description
VR1 Raise Tap *
VR1 Lower Tap *
Auto Block Enable
VR1 Source Side Voltage Calculation
Interval Operations Counters Enable
VR1 Operations Counter Month Reset *
VR1 Operations Counter Year Reset *
VR1 Operations Counter 24HR Reset *
VR1 Operations Counter 30DY Reset *
VR1 Operations Counter Last Month Reset *
VR1 Operations Counter Last Year Reset *
VR1 TPI Neutral Mismatch Reset *
VR1 Lower To Neutral Sync Retry Count Reset *
VR1 Raise To Neutral Sync Retry Count Reset *
VR1 Taps Past 16L Counter Reset *
VR1 Taps Past 16R Counter Reset *
Rx COM1 Counter Reset *
Rx COM2 Counter Reset *
Tx COM1 Counter Reset *
Tx COM2 Counter Reset *
Message Error COM1 Counter Reset *
Message Error COM2 Counter Reset *
Reset Energy All *
Reset All Demand Values *
Event Recorder Enable
Data Profiler Enable
Data Profiler Snapshot *
Tap To Neutral Feature Enable
PMT Mode A Enable
PMT Mode B Enable
PMT Mode A Test *
PMT Mode B Test *
Data Alarms Enable
Status Alarms Enable
VR1 Time On Tap Reset *
Top Side Port LoopShare Enabled
Bottom Side Port LoopShare Enabled
Leader/Follower Enable
Register Sequence
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
0 (0x0)
1 (0x1)
2 (0x2)
3 (0x3)
4 (0x4)
5 (0x5)
6 (0x6)
7 (0x7)
8 (0x8)
9 (0x9)
10 (0xA)
11 (0xB)
12 (0xC)
13 (0xD)
14 (0xE)
15 (0xF)
16 (0x10)
17 (0x11)
18 (0x12)
19 (0x13)
20 (0x14)
21 (0x15)
22 (0x16)
23 (0x17)
24 (0x18)
25 (0x19)
26 (0x1A)
27 (0x1B)
28 (0x1C)
29 (0x1D)
30 (0x1E)
31 (0x1F)
32 (0x20)
33 (0x21)
34 (0x22)
35 (0x23)
36 (0x24)
37 (0x25)
Page 5
Conditioned by
Supervisory State
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
SBO
CL-7 Cooper 2179 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Select-Before-Operate Points
Configurable Logic Output from SCADA Tap to Neutral Activate
Configurable Logic Output from SCADA Voltage Reduction Level 1 Activate
Configurable Logic Output from SCADA Voltage Reduction Level 2 Activate
Configurable Logic Output from SCADA 1
Configurable Logic Output from SCADA 2
Configurable Logic Output from SCADA 3
Configurable Logic Output from SCADA 4
HMI Remote Security Override Mode
38
39
40
41
42
43
44
45
38 (0x26)
39 (0x27)
40 (0x28)
41 (0x29)
42 (0x2A)
43 (0x2B)
44 (0x2C)
45 (0x2D)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
* Momentary/Self Resetting
Page 6
SBO
Technical Data TD225002EN
Communications
Point Data Base

Effective June 2015
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Power Systems Division
2300 Badger Drive
Waukesha, WI 53188
United States
Eaton.com/cooperpowerseries
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. TD225002EN
June 2015
Supersedes R225-70-29 (6/2013)
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
For Eaton's Cooper Power series CL-7 voltage
regulator control information
call 1-877-277-4636 or visit:
www.eaton.com/cooperpowerseries.