Frequently Asked Questions MagneX Interrupter and How to Determine Watts Loss GENERAL QUESTION Q How do I determine the watts loss for a MagneX Interrupter, since there are several different sensors and I plan to use them in transformers with different kVA sizes? I also want to know what the losses would be at different load currents for these transformers. How can I determine these losses? 1. Based on the kVA and transformer primary voltage, determine full load current of the transformer. 2. Use the same information to determine the MagneX Interrupter sensor size by going to Table 6 in Catalog section 240-34. This table is also shown below. 3. Then go to the charts on the reverse side. Find the corresponding sensor curve and read watts loss on the vertical scale. 4. For a load current less than 100%, determine the percent load and multiply the full load current by this percentage. 5. Example: 50% load = .50 x full load current. 6. Follow the same procedure as in Step 3 above. Primary Voltage kV kVA/kV 2.4 4.16 4.8 6.9 7.2 7.627.97 8.32 12.00 12.4713.2 13.814.4 19.92 10 E06 E06 E03 E03 E03 E03 E03 E01 E01 E01 E01 15 E10 E06 E06 E03 E03 E03 E03 E03 E03 E03 E01 25 E18 E10 E10 E06 E06 E06 E06 E03 E03 E03 E03 37.5 E25 E18 E12 E10 E10 E10 E10 E06 E06 E06 E03 50 E30 E18 E18 E12 E12 E12 E10 E06 E06 E06 E06 75 E50 E30 E25 E18 E18 E18 E18 E10 E10 E10 E06 100 - E40 E30 E25 E25 E25 E18 E12 E12 E12 E10 167 - - E50 E40 E40 E30 E30 E18 E18 E18 E12 Notes: Recommendations are based on: • Minimum trip curves, and Maximum trip and clear curves, R240-91-310. • Deration factor of 0.5% per °C above 25°C. • Allowable loading greater than 140% for four hours in accordance with ANSI/IEEE Standard C57.91-1961 Guide for Loading Distribution Transformers, Table 6. Cooper Power Systems 1045 Hickory Street Pewaukee, WI 53072 P: 877-CPS-INFO FAQ-MagneX October 2007 - New Issue www.cooperpower.com All Cooper logos are valuable trademarks of Cooper Industries in the U.S. and other countries. You are not permitted to use Cooper trademarks without the prior written consent of Cooper Industries. MagneX FAQ MagneX Interrupter and How to Determine Watts Loss MagneX Watts Loss vs. Load Current 30 E50 Watts Loss, W 25 E40 20 E30 15 E25 10 E18 E01 E03 E06 5 E12 E10 0 0 10 20 30 40 50 Primary Load Current, A MagneX Watts Loss vs. Load Current E01, E03, E06 and E10 Sensors Only 5 4.5 E01 E06 Watts Loss, W 4 E03 3.5 3 E10 2.5 2 1.5 1 0.5 0 0 1 2 3 4 5 6 7 8 9 10 Primary Load Current, A Note: The curves in the above charts were calculated based on the nominal resistance between incoming terminal and the outgoing terminal of the MagneX Interrupter. Contact your Cooper Power Systems representative or call 1-877-CPS-INFO to learn more about the MagneX Interrupter. Cooper Power Systems 1045 Hickory Street Pewaukee, WI 53072 P: 877-CPS-INFO www.cooperpower.com FAQ-MagneX October 2007 - New Issue Printed in USA