Receptacle Control Solutions INS # Application Note

Application Note
INS #
Receptacle Control Solutions
Receptacle Control Solutions
Energy Codes now require automatic shut-off controls for plug loads and lighting in many spaces.
With the increase in lighting control requirements and new lighting technologies like LED fixtures, plug load
equipment has increased as a percentage of electrical power in many spaces. Research data has shown that plug
loads have grown as a percentage of electricity usage from 15% to almost 50% in high efficiency offices today.
Additional energy savings can be captured by implementing receptacle or plug load control to automatically
ensure that the plug loads are turned OFF when the space is vacant. Receptacle control has been added to the
latest energy codes as a requirement in many spaces.
What is plug load control?
Plug Load or Receptacle Control is now required in ASHRAE 90.1-2010 and California’s Title 24 2013. ASHRAE
90.1-2010 is the minimum building standard for the Department of Energy, several states currently have building
codes that comply with or exceed ASHRAE 90.1-2010.
••
••
ASHRAE 90.1-2010 requires automatic receptacle control of 50% of the 15 and 20 Amp receptacles, including
those found in modular partitions, located in private offices, open offices and computer classrooms. Plug-in
strips and devices can no longer be used for automatic receptacle control; the receptacle itself must be
controlled.
Title 24 2013 requires controlled 120v receptacles in all buildings. Applicable areas include private offices, open
office areas, conference rooms, kitchenettes and more. Plug-in strips and devices can no longer be used for
automatic receptacle control; the receptacle itself must be controlled.
How can we control plug loads?
There are two strategies for providing automatic plug load or receptacle control.
••
••
Occupancy based control: Occupancy or Vacancy sensors constantly monitor if the space is occupied. When
the space is vacant the sensor will ensure the receptacles are automatically turned OFF either directly or by
sending a signal to the lighting control system.
Schedule based control: The lighting control system or some other time clock device ensures the receptacles
are automatically turned OFF based on user defined time.
Eaton’s Lighting Systems Solutions
Eaton’s Lighting Systems Solutions
MANUAL MODE OPERATION:
1. SWITCHES ARE REQUIRED TO TURN
CORRESPONDING LOADS ON.
Eaton’s
Lighting Systems provides multiple solutions to
2 LOADS TURN OFF WHEN SENSOR
TIMES OUT OR WITH THE SWITCH.
control
receptacle or plug loads including simple occupancy
AUTOMATIC MODE OPERATION:
based
control, room based controls, schedule based
1. WHEN SENSOR ACTIVATES, BOTH
controls,
centralized
relay controls and DALI based controls.
LOADS AND RECEPTACLE
TURN ON.
2. SWITCHES CAN BE USED TO TURN
LIGHTS ON OR OFF.
Occupancy Sensor Solution:
3. IF DAYLIGHT SENSOR IS ENABLED AND
LIGHT LEVEL IS ABOVE SETPOINT,
SWITCHPACK CONNECTED TO YELLOW
•• LEAD WILL NOT TURN LOAD ON.
Automatic receptacle control based on occupancy
RECOMMENDED WIRE:
18-3 AWG STRANDED WIRE SHIELDED OR
NON/SHIELDED
What do we need to order:
••
Occupancy or vacancy sensor (OAC-*, VAC-*)
••
Receptacle rated switchpack (SP-R-20-120)
••
Manual switch (GMDS-W)
NOTES
**USE BLACK LEAD FOR 120VAC.
USE ORANGE LEAD FOR 277VAC.
CAP UNUSED LEAD.
1. SPD20-MV-NO SWITCHPACK SHOWN.
120/277VAC 20AMP RATING PER RELAY.
HOT
2. BLUE AND RED WIRE LEADS ARE
NON-POLARITY SENSITIVE.
LINE
NEUTRAL
RED (10-30VDC)
BLUE (OCC)
RED (24VDC)
BLUE
(CONTROL -RELAY 1)
BLACK (COMMON)
BLACK
PURPLE (NORMALLY CLOSED)
GRAY (ISOLATED RELAY COMMON)
ORANGE (NORMALLY OPEN)
YELLOW (OCC/DAY)
YELLOW
(CONTROL- RELAY 2)
BROWN (BLUE
CONTROL)
WHITE/BROWN
(YELLOW CONTROL)
MODEL GMDS - LOAD "A"
(NORMALLY OPEN
MOMENTARY SWITCH)
MODEL GMDS - LOAD "B"
(NORMALLY OPEN
MOMENTARY SWITCH)
LOAD "A"
HOT **
BLUE (RELAY 1)
BLUE (RELAY 1)
RED (RELAY 2)
RED (RELAY 2)
**USE BLACK LEAD FOR 120VAC.
CAP UNUSED LEAD.
HOT
LINE
NEUTRAL
RED
(24VDC)
BLUE
(CONTROL)
BLACK
(COMMON)
HOT **
WHITE
BLUE (RELAY 1)
BLUE (RELAY 1)
SP-R-20-120
(Receptacle Rated Switchpack)
2
www.coopercontrol.com
LOAD "B"
WHITE
Receptacle
Room Controller Solution
Room Controller Solution
••
Automatic receptacle control based on room occupancy
••
Exclusive Automatic On receptacle event in Vacancy Mode
••
Out-of-the-box functionality
What do we need to order:
••
Room Controller (RC3, RC3D, RC3DE, RC3DEHC)
••
Receptacle rated switchpack (SPRC-R-20-120)
••
Occupancy sensor (Any Greengate Sensor)
••
Wallstation (Any Room Controller Wallstation)
Sensors
Sensors
Wallstations
Alert
Mode
Time
Clock
Adjustable Skylights
QuickConnect Cables
Switchpack
Receptacle
BMS/Out
Slider
Station
+
+
+
+
6
4
3
2
1
3
4
Status
0-10V Dimming Outputs
+ + + Dimmer 3
Dimmer 2
QuickConnect Cable
(Class 2)
Reset
Not Used
Occupancy
Occ
Vac (default)
0-10V Gain
Adjustment
1 2
Energy
Options
Demand Response
High End
Energy Options DIP Switch
Default 10%
20%
30%
40%
5
5
Integration Controls
Green
A/V
Mode
Demand
Response
Low End
Red - Load 2 Out
Purple - Load 3 Out
Red
Black
Integration Controls
Blue - Load In
Yellow - Load 1 Out
White
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
Black - Line In
White/Black - 120V N
White/Orange - 277V N
Blue - EM Line In
Blue - EM Loads Out
Adjustable Skylights
Connect a QuickConnect cable between
the Receptacle Rated Switchpack and
the Receptacle/BMS Click & Go port
on the Room Controller.
Control Sequence: The Room Controller can
control up to five 20A Receptacle Rated
Switchpacks based on space occupancy.
Receptacle Rated Switchpacks turn On based
upon occupancy regardless of light level or state
and turn Off 30 seconds after vacancy time out
period.
Dimmer 1
-
Dimmer 3
+
-
Dimmer 2
+
-
Dimmer 1
+
0-10V Dimming
GGRC-SPLITTER
(1 to 2 Cable Splitter)
* NOTE: Each cable lenght not to exceed
100ft. Total length not to exceed 400ft.
120VAC Hot
Line In
Line Voltage Wiring
to Receptacle(s)
120VAC Hot
Line In
Line Voltage Wiring
to Receptacle(s)
Neutral
Neutral
Click & Go Port
Click & Go Port
Black
White/Black
Blue
Blue
Black
White/Black
Blue
Blue
Receptacle
Receptacle
SPRC-R-20-120
(Receptacle Rated Switchpack)
ices use Click & Go technology:
ally recognize any smart device connected with the quick
working immediately upon power up with no
anual On/Automatic Off vacancy sensor mode for
tions buttons can toggle zones or trigger preset scenes
station.
SPRC-R-20-120
(Receptacle Rated Switchpack)
ROOM CONTROLLER
WIRING DIAGRAM
TITLE:
LIGHTING CONTROLS
Receptacle Control
THE INFORMATION ON THIS DRAWING IS THE PROPERTY
OF
EATON CORPORATION. IT IS DISCLOSED IN CONFIDENCE
AND IS NOT TO BE REPRODUCES, USED, OR DISCLOSED
EXCEPT FOR THE PURPOSE FOR WHICH FURNISHES.
DRAWN:M.A.L
DATE:8/16/14
CH'KD:X.X.
SCALE: NTS
APPR: X.X.
SHEET: 1/1
SIZE:
PROJ:
DWG #:
E2
DATE
REV
DESCRIPTION
REVISION TABLE
www.coopercontrol.com
BY
3
Schedule Based and Centralized Solution
Schedule Based and Centralized Solution
••
Automatic receptacle control based on room occupancy
••
Contractor friendly installation
••
Built-in astronomical time clock
••
Controlled via low voltage inputs, occupancy or
BMS input
What do we need to order:
Any lighting control relay panel that uses the Latching
Relay Module (CKT, CKM, LK, SCRP)
••
••
Occupancy sensor (Any Greengate Sensor)
••
Wallstation (Any compatible low voltage wallstation)
Zone 1
Zone 2
Zone 3
Zone 4
GDS Cable type: Cooper
LCCNP or Cooper LCCP
or Belden 1502, maximum
distance 1000 feet per
GDS network
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 5
Zone 6
Zone 6
ControlKeeper M Relay
Panel Power Metering
ControlKeeper M
Relay Panel
Power Metering
Zone 1
Zone 2
Zone 3
Zone 1
ControlKeeper T
Relay Panel
Zone 2
Zone 3
Zone 4
Zone 4
Zone 5
Zone 5
Zone 6
Zone 6
ControlKeeper 4A
Distributed 0-10V
Dimming panel
Q1
SW1
X4 SRC
C1
LED1
PCI 2005
LINE
8
LOAD
7
C
C5
LED5
50-022110-01
DIGITA
K1
6
CAN-TX
Q2
5
U4
TB2
4
MOV2
3
LED4
SW2
RS-232
2
CAN-RX
TB1
54-022510-
SW2
1
MOV1
50-022510-00
ADDRESS
LED3
ALL ON
U2
PCI-NET
1
U1
LED3
K2
C14
TB3
Q3
RSC PIC
MOV3
SWIN PIC
LOAD
U2
LED5
K3
RSC STAT
MOV4
L1
PE-52627
PE-52647
or
Talema
SWV-0-90-330
U3
U4
LED7
LINE
STATUS
LOAD
SW4
LED9
Q4
SD1
Gnd
K4
1
0 OHM
OPT-47K
RESET PICS
TB4
+NET -NET
SW3
LINE
RS-232-SP
PCI-NET TERM
SWIN STAT
1
LED8
LOCAL
REMOTE
POWER
TB2
J7
J8
ANALOG INPUTS
TB3
ANALOG INPUTS
+24 GND
AN AN AN AN
1
2
3 4
ANALOG GND
TB4
DIMMING OUTPUTS
DIMMING OUTPUTS
DO RTN DO RTN DO RTN
1 1
2 2
3 3
SWITCH INPUTS
TB5
TB6
LSO TEST
SWITCH INPUTS AND LIGHTED SWITCH OUTS
DO RTN IN +24
4 4
1
IN LS
2
1
IN +24 IN LS
3
4 2
TP1
IN +24 IN LS IN
5
6 3 7
+24
IN
8
LS
4
To other lighting control panels
Cable type: Belden 9841 or equal
Maximum distance 4000 feet per network
www.coopercontrol.com
U6
PCI-NET
Ethernet link:
Programming access or
Power Metering data access
To other lighting control panels
4
LED2
ALL OFF
LINE
LED1
NETWORK
LOAD
Ethernet link:
Programming access or
Power Metering data access
DALI Based Controls
DALI Based Controls
••
Automatic receptacle control based on room occupancy
••
Contractor friendly installation
••
Controlled via low voltage inputs, occupancy or schedule
What do we need to order:
••
Fifth Light LCP (LCP-*)
••
DALI Multi-Sensor (FLT-MTS12-DALI
••
DALI Field Relay (FLT-HPRS-DALI)
DALI COMMUNICATION BUS
Maximum of up to 64 devices on each DALI Bus.
All devices must be within 900 feet of the
Lighting Control Panel (LCP).
16/2 AWG recommended wire.
Scene 1
Scene 2
Scene 3
Scene 4
DALI FIELD
RELAY
DALI DIMMABLE
BALLAST
11:46 06/26/09
DALI MULTI
SENSOR
DALI DIMMING
MODULE
DALI DAC
0-10 VDC
1000
FIFTH LIGHT TECHNOLOGY
1
10%
2
10%
20%
3
30%
4
40%
DALI
Wallstation
DALI RELAY PANEL
Units Are: 1027.1028
LIGHTS
LIGHTING
CONTROL PANEL
GROUPS
SCENES
SUPPORT
VOIP PHONE
TOUCH
SCREEN
MOBILE
APP
ETHERNET
NETWORK SWITCH
CENTRAL SERVER UNIT
GROUND (EARTH GROUND)
LINE VOLTAGE
NEUTRAL
DALI BUS
DALI BUS
LINE IN/BLACK
LINE OUT/BLACK


Receptacle
TO OTHER
LIGHTING
LOADS
Room Controller and Smart Devices use Click & Go technology:
The Room Controller will automtically recognize any smart device connected with the quick
connect cable (provided) and start working immediately upon power up with no
programming required.
The Room Controller defaults to Manual On/Automatic Off vacancy sensor mode for
maximum energy savings. Wallstations buttons can toggle zones or trigger preset scenes
and can be mixed within each wallstation.
FIFTH LIGHT
WIRING DIAGRAM
TITLE:
LIGHTING CONTROLS
RECEPTACLE CONTROL
THE INFORMATION ON THIS DRAWING IS THE PROPERTY
OF
EATON CORPORATION. IT IS DISCLOSED IN CONFIDENCE
AND IS NOT TO BE REPRODUCES, USED, OR DISCLOSED
EXCEPT FOR THE PURPOSE FOR WHICH FURNISHES.
DRAWN:M.A.L
DATE:8/16/14
CH'KD:X.X.
SCALE: NTS
APPR: X.X.
SHEET: 1/1
SIZE:
PROJ:
DWG #:
E8
DATE
REV
-
-
DESCRIPTION
REVISION TABLE
BY
www.coopercontrol.com
5
What’s next:
Automatic Receptacle Control requirements are continuing to expand in future versions of building energy codes. Both
ASHRAE 90.1-2013 and Title 24 version 2016 include automatic receptacle control requirements in more spaces.
Conclusion:
Lighting and receptacle controls continue to play a vital role in meeting energy code requirements that also help meet your
operating budgets and our national energy conservation goals. The automatic receptacle control methods outlined in this
document help reduce plug loads as a percentage of electricity used in spaces when not occupied.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, GA 30269
coopercontrol.com
© 2014 Eaton
All Rights Reserved
Printed in USA
Publication No. ACC141030
Eaton is a registered trademark.
All trademarks are property
of their respective owners.