Concrete Inserts
Concrete inserts offered in this section are designed to provide a pre-set support point in concrete ceilings, walls, and floors. A range of inserts with varying design loads are available.
Carbon Steel and Malleable Iron are used in the manufacture of concrete inserts. Stainless Steel and other materials are available.
The standard finishes for mechanical supports are plain steel (oil coated) sometimes referred to as black and
Electro-Galvanized Zinc (ASTM B633 SC3). Hot-Dip Galvanized After Fabrication (ASTM A123), Red Primer, Plastic
Coating, DURA-GREEN ™ and other special coatings are available upon request.
(as noted)
Items in this section are Underwriters Laboratories Listed and comply with Federal Specification WW-H-171E &
A-A-1192A or Manufacturers Standardization Society ANSI/MSS SP-69 & SP-58.
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
191
Pipe Hangers & Supports
Size Range: 3 / 8 "-16 thru 7 / 8 "-9 rod
Material: Steel
Function: For use in metal deck formed concrete to attach hanger rods. Allows for pre-positioning of hanger rods in poured concrete decks.
Approvals: 3 /
8
" - 5 /
8
" rod size is Underwriters Laboratories listed in the USA (UL) and Canada (cUL) . Included in our Seismic Restraints
Catalog approved by the State of California Office of Statewide Health
Planning and Development (OSHPD) . For additional load, spacing and placement information relating to OSHPD projects, please refer to the
TOLCO Seismic Restraints Systems Guidelines.
Finish: Plate: Plain Steel. Rod: Electro-Galvanized. Contact B-Line for alternative finishes and materials.
Order By: Part number, rod size and finish. Contact B-Line for custom rod lengths.
Concrete Inserts
Standard Bolt Length
8” (203.2mm)
12” (305mm)
Minimum
1” (25.4mm)
Minimum
2 5 /
8
”
(66.7mm)
12” (305mm)
Minimum
1” (25.4mm)
Minimum
2
5
/ 8 ”
(66.7mm)
12” (305mm)
Minimum
1” (25.4mm)
Minimum
2
5
/ 8 ”
(66.7mm)
1”
(25.4mm)
Minimum
Fig. 109A
Fig. 109A Fig. 109A
Part No.
Rod
Size
Max.
Pipe Size in.
(mm)
Max. Hanger Max. Recommended
Spacing Loads in.
(m) lbs.
(kN)
109A3 / 8
3 / 8 "-16 4" (101.6) 15’-0” (4.57)
109A1 / 2
1 / 2 "-13 8" (203.2) 15’-0” (4.57)
572
579
(2.54)
(2.57)
109A5 / 8
5 / 8 "-11
109A3 / 4
3 / 4 "-10
109A7 /
8
7 /
8
"-9
Contact B-Line
Contact B-Line
Contact B-Line
715
1000
1000
(3.18)
(4.45)
(4.45) lbs.
Approx.
Wt./100
(kg)
67.0
(30.4)
69.0
(31.3)
71.0
(32.2)
213.0
(96.6)
217.0
(98.4)
Max. Recommended Loads shown include safety factor of 5.
Weight is based on the standard bolt length.
NOTES:
1. Mounting holes are standard. If the plate is not mechanically secured to the deck ribs, a jam nut is required to prevent the anchor bolt from laying over when concrete is poured.
2. Minimum spacing between inserts shall be not less than 4 1 ⁄ 2 " (114.3mm) for 3 ⁄ 8 " and 6" (1152.4mm) for 1 ⁄ 2 "
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers & Supports
192
Revised 11/4/2014
Size Range: 3 / 8 "-16 thru 7 / 8 "-9 rod
Material: Steel
Function: For use in metal deck formed concrete to attach hanger rods.
Allows for pre-positioning of hanger rods in poured concrete decks.
Approvals: Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and
Development (OSHPD) . For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO
Seismic Restraints Systems Guidelines. Hangers certified by a registered professional engineer to conform to Section 6-1.1 of
NFPA #13 (1999) and Section 9.1.1.2 of NFPA 13 (2002).
Finish: Plate: Plain Steel. Rod: Electro-Galvanized. Contact B-Line for alternative finishes and materials.
Order By: Figure number, rod size and finish. Contact B-Line for custom rod lengths.
Qualifies as an acceptable alternate seismic brace fastener per Section
9.3.5.9.6 Certification calculations for this application are available upon request. See dimensions and installation Detail below.
Standard Bolt
Length
8” (203.2mm)
12” (305mm)
Minimum
1” (25.4mm)
Minimum
12” (305mm)
Minimum
1” (25.4mm)
Minimum
12” (305mm)
Minimum
1” (25.4mm)
Minimum
‘D’
‘D’ ‘D’
Fig. 109A Fig. 109A
1” (25.4mm)
Minimum
Fig. 109A
‘D’
1” (25.4mm)
Minimum
Part No.
Rod Max. Horizontal Load
Size Brace At 45° lbs.
(kN)
109A3 / 8
3 / 8 "-16
109A1 /
2
1 /
2
"-13
109A5 / 8
5 / 8 "-11
109A3 / 4
3 / 4 "-10
109A7 /
8
7 /
8
"-9
560
660
680
700
700
(2.49)
(2.93)
(3.02)
(3.11)
(3.11)
‘D’ Min. Anchor
Embedment Depth in.
2 5 / 8 "
2 5 /
8
"
2 5 / 8 "
2 5 / 8 "
2 5 /
8
"
(mm)
(66.7)
(66.7)
(66.7)
(66.7)
(66.7)
Approx.
Wt./100 lbs.
(kg)
67.0
(30.4)
69.0
(31.3)
71.0
(32.2)
213.0
(96.6)
217.0
(98.4)
Seismic bracing design load calculated in compliance with the requirements of IBC 2009 / CBC 2010.
Part No.
109A3 / 8
3 / 8 "-16
109A1 / 2
1 / 2 "-13
109A5 / 8
5 / 8 "-11
109A3 / 4
109A7 / 8
Rod Max. Horizontal Load
Size Brace At 45°
3 / 4 "-10
7 / 8 "-9 lbs.
337
395
395
395
395
(kN)
(1.50)
(1.75)
(1.75)
(1.75)
(1.75)
‘D’ Min. Anchor
Embedment Depth in.
2 5 / 8 "
2 5 / 8 "
2 5 / 8 "
2 5 / 8 "
2 5 / 8 "
(mm)
(66.7)
(66.7)
(66.7)
(66.7)
(66.7)
67.0
(30.4)
69.0
(31.3)
71.0
(32.2)
213.0
(96.6)
217.0
(98.4)
Seismic bracing design load calculated in compliance with the requirements of IBC 2012 / CBC 2013.
Approx.
Wt./100 lbs.
(kg)
Fig. 109A
NOTES:
1. Mounting holes are standard. If the plate is not mechanically secured to the deck ribs, a jam nut is required to prevent the anchor bolt from laying over when concrete is poured. There is no structural strength added from the use of a mechanical fastener to hold the product in place before the pour.
2. Minimum spacing between inserts shall be not less than 4 for 3 ⁄ 8 " and 6"
1
(1152.4mm)
⁄ 2 "
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
(114.3mm) for 1 ⁄ 2 "
Pipe Hangers & Supports
192a
Revised 8/8/2014
Concrete Inserts
Size Range: 3 /
8
"-16 thru 3 /
4
"-10 rod
Material: Steel
Function: For use in metal deck formed concrete to attach hanger rods. Allows for pre-positioning of hanger rods in poured concrete decks.
Finish: Plate: Plain Steel. Rod: Electro-Galvanized. Contact
Cooper B-Line for alternative finishes and materials.
Order By: Part number and finish. Contact B-Line for custom rod lengths.
Steel Size
B
D
D
Underside of anchor bolt to bottom of plate
Thread Size 'A' with Thread
Length 'C'
Part No.
Thread
A in.
B
(mm) in.
Thread
Length C
(mm)
D in.
(mm)
B30193 /
8
3 /
8
"-16 2 1 /
2
" (63.5) 6 3 /
8
" (161.9) 1 1 /
4
" (31.7)
B30191 /
2
1 /
2
"-13 2 1 /
2
" (63.5) 6 1 /
2
" (165.1) 1 1 /
4
" (31.7)
B30195 / 8
5 / 8 "-11 2 1 / 2 " (63.5) 6 3 / 4 " (171.4) 1 1 / 4 " (31.7)
B30193 / 4
3 / 4 "-10 2 1 / 2 " (63.5) 6 3 / 16 " (157.2) 2 1 / 4 " (57.1)
For maximum load rating, install plate on top of deck ribs.
Steel Size in.
7 Ga. x 1 1 /
4
" x 10"
(mm)
(4.5 x 31.7 x 254.0)
7 Ga. x 1 1 /
4
" x 10" (4.5 x 31.7 x 254.0)
7 Ga. x 1 1 / 4 " x 10"
1 / 4 " x 3" x 10"
(4.5 x 31.7 x 254.0)
(6.3 x 76.2 x 254.0)
Design
Design Load
Lbs (kN)
Approx.
Wt./100
Lbs.
(kg)
730 (3.25) 80 (36.3)
1350 (6.00) 99 (44.9)
2160 (9.61) 129 (58.5)
3230 (14.37) 238 (107.9)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
193
Pipe Hangers & Supports
Size Range: 3 /
8
"-16 thru 7 /
8
"-9 rod
Material: Steel
Function: Designed to be embedded in concrete to provide a point of support.
Approvals: Underwriters Laboratories listed in the USA (UL) and
Canada (cUL) for 3 / 8 " and 1 / 2 ". Included in our Seismic Restraints
Catalog approved by the State of California Office of Statewide Health
Planning and Development (OSHPD) . For additional load, spacing and placement information relating to OSHPD projects, please refer to the
TOLCO Seismic Restraint Systems Guidelines.
Finish: Plain anchor bolt with Electro-Galvanized hardware and plate.
Order By: Part number, rod size and finish.
Note: The hex or jam nut has NO value in determining the loads.
Their function is to assist in locking the coupling snug to the bottom of the deck form preventing the concrete from leaking into the coupling threads. Any other suitable locking device may be substituted if desired.
Anchor Bolt
ASTM A307
E
Rod Coupling
Edge of Concrete
Design Load-Shear
Design Load 45°
DE Min.
Design Load-Vertical
Mounting Hole for
Securing to Form
Part No.
lbs.
Approx.
Wt./100
(kg)
109AF3 / 8 38.1
(17.3)
109AF1 / 2 54.7
(24.8)
109AF5 / 8 82.2
(37.3)
109AF3 / 4 113.8
(51.6)
109AF7 /
8
130.6
(59.2)
Part No.
109AF3
109AF1
109AF5
109AF3
/ 8
/ 2
/ 8
/ 4
Rod
Size
Design Load Vertical
Hard Rock Light Wt.
lbs.
(kN) lbs.
(kN)
Design Load Shear
Hard Rock Light Wt.
lbs.
(kN) lbs.
(kN)
Design Load 45°
Hard Rock Light Wt.
lbs.
(kN) lbs.
(kN)
Embedment
Depth E in.
(mm) in.
DE
Min.
(mm)
3 / 8 "-16 1255 (55.82) 735 (3.28) 978 (4.35) 733 (3.26) 777 (3.45) 525 (2.33) 3 1 / 2 ” (88.9) 2” (50.8)
1 / 2 "-13 2321 (10.32) 1392 (6.19) 978 (4.35) 733 (3.26) 980 (4.36) 679 (3.02) 3 1 / 2 ” (88.9) 2” (50.8)
5 / 8 "-11 780 (3.47) 468 (2.08) 1278 (5.68) 958 (4.26) 688 (3.06) 445 (1,98) 4” (101.6) 2” (50.8)
3 / 4 "-10 1346 (5.99) 806 (3.58) 1278 (5.68) 958 (4.26) 927 (4.12) 619 (2,75) 4” (101.6) 2 1 / 2 ” (63.6)
109AF7 / 8
7 / 8 "-9 2321 (10.32) 1391 (6.19) 1278 (5.68) 958 (4.26) 1166 (5.18) 803 (3,57) 4” (101.6) 6” (152.4)
Max. Recommended Loads shown include safety factor of 5.
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers & Supports
194
(B-Line B2501)
Size Range: 3 /
8
"-16 thru 7 /
8
"-9 rod
Material: Steel
Function: Designed to be embedded in concrete to provide a point of support.
Approvals: Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and
Development (OSHPD) . For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO
Seismic Restraint Systems Guidelines.
Finish: Electro-Galvanized anchor bolt with Electro-Galvanized hardware and plate.
Order By: Figure number, rod size and finish.
Note: The hex or jam nut has NO value in determining the loads.
Their function is to assist in locking the coupling snug to the bottom of the deck form preventing the concrete from leaking into the coupling threads. Any other suitable locking device may be substituted if desired.
Edge of Concrete
E
Anchor Bolt
ASTM A307
Rod Coupling
Qualifies as an acceptable alternate seismic brace fastener per
Section 9.3.5.9.6 Certification calculations for this application are available upon request. See dimensions and installation Detail below.
Design Load
45°
Mounting Hole for
Securing to Form
DE Min.
Rod
Size
Part No.
109AF3 / 8
3 / 8 "-16
109AF1 / 2
1 / 2 "-13
109AF1 / 2
1 / 2 "-13
109AF5 / 8
5 / 8 "-11
109AF5 / 8
5 / 8 "-11
109AF3 / 4
3 / 4 "-10
109AF-
109AF-
109AF-
3
7
7
/
/
/
4
8
8
3 / 4 "-10
7 / 8 "-9
7 / 8 "-9
Max. Horizontal Seismic
Load With Brace At 45° in.
(mm)
925
925
(4.11)
(4.11)
950
1250
1424
1275
1424
1330
1424
(4.22)
(5.56)
(6.33)
(5.67)
(6.33)
(5.91)
(6.33)
Embedment
Depth E in.
(mm)
3 1 / 2 ”
3 1 / 2 ”
(88.9)
(88.9)
4”
4”
5”
4”
6”
4”
7”
(101.6)
(101.6)
(127.0)
(101.6)
(152.4)
(101.6)
(177.8)
2”
2”
2”
2” in.
2”
2”
2”
2”
2”
DE
Min.
(mm)
(50.8)
(50.8)
(50.8)
(50.8)
(50.8)
(50.8)
(50.8)
(50.8)
(50.8)
Lbs.
Approx.
Wt./100
(kg)
38.1
54.7
(17.3)
(24.8)
54.7
82.2
82.2
113.8
(24.8)
(37.3)
(37.3)
(51.6)
113.8
130.6
130.6
(51.6)
(59.2)
(59.2)
Seismic bracing design load calculated in compliance with the requirements of IBC 2009 / CBC 2010.
Rod
Size
Part No.
109AF3 / 8
3 / 8 "-16
109AF1 / 2
1 / 2 "-13
109AF1 / 2
1 / 2 "-13
109AF5 / 8
5 / 8 "-11
109AF5 / 8
5 / 8 "-11
109AF3 / 4
3 / 4 "-10
109AF3 / 4
3 / 4 "-10
109AF7 / 8
7 / 8 "-9
109AF7 / 8
7 / 8 "-9
Max. Horizontal Seismic
Load With Brace At 45° in.
(mm)
781 (3.47)
781
807
999
1275
1029
1424
1074
1424
(3.47)
(3.59)
(4.44)
(5.67)
(4.57)
(6.33)
(4.78)
(6.33)
Embedment
Depth E in.
(mm)
3 1 / 2 ”
3 1 / 2 ”
4”
4”
5”
4”
6”
4”
7”
(88.9)
(88.9)
(101.6)
(101.6)
(127.0)
(101.6)
(152.4)
(101.6)
(177.8) in.
2”
2”
2”
2”
2”
2”
2”
2”
2”
DE
Min.
(mm)
(50.8)
(50.8)
(50.8)
(50.8)
(50.8)
(50.8)
(50.8)
(50.8)
(50.8)
Lbs.
Approx.
Wt./100
(kg)
38.1
(17.3)
54.7
54.7
82.2
82.2
(24.8)
(24.8)
(37.3)
(37.3)
113.8
113.8
130.6
130.6
(51.6)
(51.6)
(59.2)
(59.2)
Seismic bracing design load calculated in compliance with the requirements of IBC 2012 / CBC 2013.
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers & Supports
194a
Revised 8/8/2014
Size Range: 5 / 8 "-11 thru 1 1 / 2 "-6 rod
Material: Steel
Function: Designed to be embedded in concrete to provide a point of support for 5 / 8 "-11 thru 1 1 / 2 "-6 rod or bolt sizes .
Finish: Plain anchor bolt with Electro-Galvanized coupling. Contact
B-Line for alternative finishes and materials.
Note: For rod sizes 3 / 8 "-16 and 1 / 2 "-13, refer to Fig. 109AF.
Order By: Part number and rod size.
For 1 1 / 8 "-7, 1 1 / 4 "-6, and 1 1 / 2 "-6 consult factory.
A
A
3 /
16
" Dia.
(4.8)
B
Rod
Size
Part No.
B24995 / 8
5 / 8 "-11
B24993 /
4
3 /
4
"-10
B24997 /
8
7 /
8
"-9
B2499-1 1"-8 in.
3"
A
(mm)
(76.2)
3" (76.2)
Min. Embedment
B in.
3" (76.2) 3 1 / 2 "
3" (76.2) 3 1 /
2
"
4"
4"
(m)
(88.9)
(88.9)
(101.6)
(101.6)
Max. Recommended Loads
(In 3000 lb. (13.34kN)
Hard Rock Concrete) lbs.
(kN)
1810
2710
3770
4960
Consult factory for specifications on rod sizes 1 1 / 8 "-7, 1 1 / 4 "-6, and 1 1 / 2 "-6
(8.05)
(12.05)
(16.77)
(22.06)
Approx. Wt./100 lbs.
118.0
(kg)
(53.5)
154.0
(69.8)
210.0
(95.3)
276.0
(125.2)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
195
Pipe Hangers & Supports
Material: Steel
Function: Designed to be embedded in concrete to attach 1 /
4
"-20 to
7 /
8
"-9 hanger rods .
How to Install: Attach concrete insert to forms and install reinforcing rods as required. After forms are dismantled, the knockout can be removed from the insert. The N2500 insert nut can be installed and the rod fastened to the nut. The rod should touch the inside top of the insert but should not be forced further to avoid damaging the insert.
Approvals: Underwriters Laboratories Listed for maximum pipe size 6" (150) . Conforms to Federal Specification WW-H-171E &
A-A-1192A, Type 19 and Manufacturers Standardization Society
ANSI/MSS SP-69 & SP-58, Type 18.
Weight: Approx. Wt./100 - 46 Lbs. (20.8kg)
Finish: Electro-Galvanized.
Order By: Part number and finish.
(Order N2500 nuts separately).
Design Load: Loading based on a straight pull of 600 Lbs. (2.67kN) .
Note: Before installation ensure that concrete is sufficient to carry the load.
Size Range: 1 / 4 "-20 through 7 / 8 "-9.
Material: Steel
Function: Designed for use with B2500 spot insert.
Finish: Plain or Electro-Galvanized.
Order By: Part number and size.
1 1 /
4
"
(31.7)
2"
(50.8)
Concrete Inserts
3 1 /
4
"
(82.5)
1 9 /
16
"
(39.7)
1 1 /
2
"
(38.1)
Hanger Rod and Nut
Not Included
Material Thickness
12 Gauge (2.6)
1 1 /
4
"
(31.7)
5 /
16
"
(7.9)
A
Part No.
N25001 / 4
N25003 / 8
N25001 /
2
N25005 / 8
N25003 / 4
N25007 / 8
Tap Size
A
1 / 4 "-20
3 / 8 "-16
1 /
2
"-13
5 / 8 "-11
3 / 4 "-10
7 / 8 "-9
11
11
10
Lbs.
Approx. Wt./100
(kg)
14
13
12
(6.3)
(5.9)
(5.4)
(5.0)
(5.0)
(4.5)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers & Supports
196
Concrete Inserts
Material: Malleable Iron
Function: Designed to be embedded in concrete to attach 3 /
8
"-16 to
7 /
8
"-9 hanger rods .
How to Install: Attach concrete insert to forms and install reinforcing rods as required. After forms are dismantled, the B3014N nut can be installed and the rod fastened to the nut. The rod should touch the inside top of the insert.
Approvals: Underwriters Laboratories Listed when used with
B3014N Insert Nut. Conforms to Federal Specification WW-H-171E &
A-A-1192A, Type 18 and Manufacturers Standardization Society
ANSI/MSS SP-69 & SP-58, Type 18.
Weight: Approx. Wt./100 - 166 Lbs. (75.3kg)
Finish: Plain or Electro-Galvanized.
Order By: Part number and finish.
(Order B3014N nuts separately).
Design Load: Design Loads based on B3014N malleable iron insert nut below.
Note: Before installation ensure that concrete is sufficient to carry the load.
2 1 /
4
"
(57.1)
13 /
16
"
(20.6)
2"
(50.8)
3 3 /
8
"
(85.7)
3 1 /
4
"
(82.5)
Horizontal Adjustment:
For 3 /
8
"-16, 1 /
2
"-13, 5 /
8
"-11 rods - Adjustment is 1 3 /
4
" (44.4)
For 3 /
4
"-10, 7 /
8
"-9 rods - Adjustment is 1 3 /
16
" (30.2)
Size Range: 3 / 8 "-20 through 7 / 8 "-9.
Material: Malleable Iron
Standard Finish: Plain or Electro-Galvanized
Service: Designed for use with the B3014 malleable iron insert shown above.
Ordering: Part number and finish.
1 7 /
8
"
(47.6)
1 1 /
4
"
(31.7)
1 /
2
"
(12.7)
For 3 /
8
"-16 thru
5 /
8
"-11 Tap Sizes 'A'
1 7 /
8
"
(47.6)
1 /
2
"
(12.7)
For 3 /
4
"-10 &
7 /
8
"-9 Tap Size 'A'
1 5 /
8
"
(41.3)
Part No.
B3014N3 / 8
B3014N1 / 2
B3014N5 / 8
B3014N3 / 4
B3014N7 / 8
Tap Size
'A'
3 / 8 "-16
1 / 2 "-13
5 / 8 "-11
3 / 4 "-10
7 / 8 "-9
UL Max.
Pipe Size
4”
8”
10”
10”
10”
* When used with B3014 Malleable Iron Insert.
Design Load*
Lbs.
(kN)
730
1350
1400
1400
1400
(3.25)
(6.00)
(6.23)
(6.23)
(6.23)
Approx. Wt./100
Lbs.
(kg)
22
22
20
29
29
(10.0)
(10.0)
(9.1)
(13.1)
(13.1)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
197
Pipe Hangers & Supports
Concrete Inserts
Material: Steel (Stainless steel available on B2505 only)
Standard Finish: Plain or Pre-Galvanized
Function: Designed to be embedded in concrete to attach 1 /
4
"-20 to
7 /
8
"-9 hanger rods .
How to Install: Attach concrete insert to forms and install reinforcing rods as required. After forms are dismantled, the channel nut can be installed and the rod fastened to the nut. The rod should touch the inside top of the insert.
Approvals: Underwriters Laboratories Listed. Conforms to
Manufacturers Standardization Society ANSI/MSS SP-69 & SP-58,
Type 18.
Order By: Part number and finish. When supporting
10" (254mm) pipe, order B2505 Insert with 5 /
8
"-11 channel nuts.
Note: For appropriate channel nut selection, see page 16. Before installation ensure that concrete is sufficient to carry the load.
2 5 /
8
"
(66.7)
End Caps
Channel
Size
5 1 /
16
"
(128.6)
Styrofoam Filled
Part No.
B2505
B2506
B2507
B2508
Channel
Size
B22
B32
B42
B52
End Cap
Part No.
B3322
B3332
B3342
B3352
Design Load
Lbs.
(kN)
1200
1000
1000
1000
(5.34)
(4.45)
(4.45)
(4.45)
Max. Pipe Size Approx. Wt./100 in.
(mm) Lbs.
(kg)
10"
8"
8"
8"
(250)
(200)
(200)
(200)
96
88
77
69
(43.5)
(39.9)
(34.9)
(31.3)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers & Supports
198
Concrete Inserts
Material: Steel
Standard Finish: Electro-Galvanized
Function: Designed to be embedded in concrete where heavy loads are required in curtain wall applications. Styrofoam end caps prevent concrete seepage into the channel.
How to Install: Attach concrete insert to forms and install reinforcing rods as required. After forms are dismantled, the channel nut can be installed and the rod fastened to the nut. The rod should touch the inside top of the insert.
Approvals: Conforms to Manufacturers Standardization Society
ANSI/MSS SP-69 & SP-58, Type 18.
Design Load: 5000 Lbs. (22.2kN
).
Loading based on two N225 channel nuts spaced 3” (76.2mm) on center and a minimum of 2” (50.8mm) from the end of the insert.
Weight: Approx. Wt./100 - 42 Lbs. (19.0kg)
Order By: Part number and finish. Channel nuts are sold separately, see page 16 for appropriate selection.
5 /
32
" (4.0)
Dia. Nail Holes
2"
(50.8)
12"
(304.8)
8"
(203.2)
Styrofoam
End Caps
5 1 /
2
”
(139.7)
1 5 /
8
”
(41.3)
1 5 /
8
”
(41.3)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
199
Pipe Hangers & Supports
Material: Steel
Standard Finish: Plain, Pre-Galvanized, or Hot-Dip Galvanized
Function: Concrete insert should be secured to forms on
16” (406.4mm) to 24” (609.6mm) intervals.
How to Install: Attach concrete insert to forms and install reinforcing rods as required. After forms are dismantled, the channel nut can be installed and the rod fastened to the nut.
The rod should touch the inside top of the insert.
Approvals: Conforms to Manufacturers Standardization
Society ANSI/MSS SP-69 & SP-58, Type 18.
Design Load: 2000 Lbs. (8.89kN
) per foot for B22-I-12 thru
B22-I-240 in 3000 psi concrete. Loads concentrated within the last 2” (50.8mm) of inserts 8” (203.2mm) and longer should not exceed 1000 Lbs. (4.45kN) .
Order By: Part number and finish. Channel nuts are sold separately, see page 16 for appropriate selection.
To order inserts without styrofoam and end caps add insert only to the part number.
Part No.
B22-I-3
B22-I-4
B22-I-6
B22-I-8
Part No.
B22-I-12
B22-I-16
B22-I-20
B22-I-24
B22-I-32
B22-I-36
B22-I-40
B22-I-48
B22-I-60
B22-I-72
B22-I-84
B22-I-96
B22-I-108
B22-I-120
B22-I-144
B22-I-168
B22-I-192
B22-I-216
B22-I-240
Concrete Inserts
2 5 /
8
”
(66.7)
1 5 /
8
”
(41.3)
3 1 /
8
”
(79.4)
1 5 /
8
”
(41.3)
B3322
End Cap
1 5 /
8
”
(41.3)
Styrofoam
Filler
B22-I-3 thru B22-I-8
4”
(101.6)
1 1 /
2
”
(38.1)
3 /
4
”
(19.0)
.188”
(4.8)
Knockouts for Nailing Inserts
To Forms
11 /
16
”
(17.4)
1 5 /
8
”
(41.3)
B22-I-12 thru B22-I-240 in.
3”
4”
6”
8” in.
108”
120”
144”
168”
60”
72”
84”
96”
32”
36”
40”
48”
12”
16”
20”
24”
192”
216”
240”
Length
(mm)
(76)
(101)
(152)
(203)
Length
(mm)
(1524)
(1829)
(2133)
(2438)
(2743)
(3048)
(3657)
(4267)
(305)
(406)
(508)
(609)
(813)
(914)
(1016)
(1219)
(4877)
(5486)
(6096)
Approx. Wt./100
Lbs.
(kg)
72
88
120
152
(32.6)
(39.9)
(54.4)
(68.9)
Approx. Wt./100
Lbs.
(kg)
1018
1218
1417
1616
1816
2016
2416
2816
553
620
686
820
224
289
353
420
3216
3616
4016
(461.7)
(552.5)
(642.7)
(733.0)
(823.7)
(914.4)
(1095.9)
(1277.3)
(101.6)
(131.1)
(160.1)
(190.5)
(250.8)
(281.2)
(311.1)
(371.9)
(1458.7)
(1640.2)
(1821.6)
Lbs.
Design Load
(kN)
500
800
1000
1200
(2.22)
(3.56)
(4.45)
(5.34)
Material:
12 Gauge (2.6)
Styrofoam
Filler
B205
End Cap
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers & Supports
200
Concrete Inserts
Material: Steel
Standard Finish: Plain, Pre-Galvanized, or Hot-Dip Galvanized
Function: Concrete insert should be secured to forms on
16” (406.4mm) to 24” (609.6mm) intervals.
How to Install: Attach concrete insert to forms and install reinforcing rods as required. After forms are dismantled, the channel nut can be installed and the rod fastened to the nut.
The rod should touch the inside top of the insert.
Approvals:
Society ANSI/MSS SP-69 & SP-58, Type 18.
Design Load: (8.89kN
B32-I-240 in 3000 psi concrete. Loads concentrated within the last 2” (50.8mm) of inserts 8” (203.2mm) and longer should not exceed 1000 Lbs. (4.45kN) .
Order By: Part number and finish. Channel nuts are sold separately, see page 16 for appropriate selection.
To order inserts without styrofoam and end caps add insert only to the part number.
Part No.
B32-I-3
B32-I-4
B32-I-6
B32-I-8
Conforms to Manufacturers Standardization
2000 Lbs.
Part No.
B32-I-12
B32-I-16
B32-I-20
B32-I-24
B32-I-32
B32-I-36
B32-I-40
B32-I-48
B32-I-60
B32-I-72
B32-I-84
B32-I-96
B32-I-108
B32-I-120
B32-I-144
B32-I-168
B32-I-192
B32-I-216
B32-I-240
) per foot for B32-I-12 thru
2 7 /
8
”
(73.0)
2 5 /
8
”
(66.7)
1 5 /
8
”
(41.3)
B3332
End Cap
1 3 /
8
”
(34.9)
Styrofoam
Filler
B32-I-3 thru B32-I-8
4”
(101.6)
1 1 /
2
”
(38.1)
11 /
16
”
(17.4)
3 /
4
”
(19.0)
.188”
(4.8)
Knockouts for Nailing Inserts
To Forms
1 5 /
8
”
(41.3)
1 3 /
8
”
(34.9)
B32-I-12 thru B32-I-240 in.
3”
4”
6”
8”
Length
(mm)
(76)
(101)
(152)
(203) in.
96”
108”
120”
144”
48”
60”
72”
84”
168”
192”
216”
240”
12”
16”
20”
24”
32”
36”
40”
Length
(mm)
(1219)
(1524)
(1829)
(2133)
(2438)
(2743)
(3048)
(3657)
(305)
(406)
(508)
(609)
(813)
(914)
(1016)
(4267)
(4877)
(5486)
(6096)
Lbs.
Approx. Wt./100
(kg)
65
80
108
137
(29.5)
(36.3)
(49.0)
(62.1)
Approx. Wt./100
Lbs.
(kg)
736
915
1095
1274
1453
1633
1813
2173
2533
2893
3253
3613
202
262
316
376
496
556
616
(333.8)
(415.0)
(496.7)
(577.9)
(659.0)
(740.7)
(822.3)
(985.6)
(91.6)
(118.8)
(143.3)
(170.5)
(225.0)
(252.2)
(279.4)
(1148.9)
(1312.2)
(1475.5)
(1638.8)
Lbs.
Design Load
(kN)
500
800
1000
1200
(2.22)
(3.56)
(4.45)
(5.34)
Material:
12 Gauge (2.6)
B206
End Cap
Styrofoam
Filler
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
201
Pipe Hangers & Supports
Material: Steel
Standard Finish: Plain, Pre-Galvanized, or Hot-Dip Galvanized
Function: Concrete insert should be secured to forms on
16” (406.4mm) to 24” (609.6mm) intervals.
How to Install: Attach concrete insert to forms and install reinforcing rods as required. After forms are dismantled, the channel nut can be installed and the rod fastened to the nut.
The rod should touch the inside top of the insert.
Approvals: Conforms to Manufacturers Standardization
Society ANSI/MSS SP-69 & SP-58, Type 18.
Design Load: 1500 Lbs. (6.67kN
) per foot for B52-I-12 thru
B52-I-240 in 3000 psi concrete. Loads concentrated within the last 2” (50.8mm) of inserts 8” (203.2mm) and longer should not exceed 750 Lbs. (3.33kN) .
Order By: Part number and finish. Channel nuts are sold separately, see page 16 for appropriate selection.
To order inserts without styrofoam and end caps add insert only to the part number.
Part No.
B52-I-3
B52-I-4
B52-I-6
B52-I-8
Part No.
B52-I-12
B52-I-16
B52-I-20
B52-I-24
B52-I-32
B52-I-36
B52-I-40
B52-I-48
B52-I-60
B52-I-72
B52-I-84
B52-I-96
B52-I-108
B52-I-120
B52-I-144
B52-I-168
B52-I-192
B52-I-216
B52-I-240
2 5 /
16
”
(58.7)
Concrete Inserts
2 9 /
16
”
(65.1)
1 5 /
8
”
(41.3)
B3352
End Cap
13 /
16
”
(20.6)
Styrofoam
Filler
B52-I-3 thru B52-I-8
13 /
16
”
(20.6)
4”
(101.6)
1 1 /
2
”
(38.1)
11 /
16
”
(17.4)
3 /
4
”
(19.0)
.188”
(4.8)
Knockouts for Nailing Inserts
To Forms
B52-I-12 thru B52-I-240
1 5 /
8
”
(41.3) in.
3”
4”
6”
8” in.
108”
120”
144”
168”
60”
72”
84”
96”
32”
36”
40”
48”
12”
16”
20”
24”
192”
216”
240”
Length
(mm)
(76)
(101)
(152)
(203)
Length
(mm)
(1219)
(1524)
(1829)
(2133)
(2438)
(2743)
(3048)
(3657)
(305)
(406)
(508)
(609)
(813)
(914)
(1016)
(4267)
(4877)
(5486)
(6096)
Approx. Wt./100
Lbs.
(kg)
53
63
85
106
(24.0)
(28.6)
(38.5)
(48.1)
Approx. Wt./100
Lbs.
(kg)
692
829
965
1107
1237
1374
1648
1922
373
419
464
556
157
202
237
282
2196
2470
2744
(252.2)
(313.9)
(376.0)
(437.7)
(502.1)
(561.1)
(623.2)
(747.5)
(71.2)
(91.6)
(107.5)
(127.9)
(169.2)
(190.0)
(210.4)
(871.8)
(996.1)
(1120.4)
(1244.6)
Lbs.
Design Load
(kN)
400
500
750
1000
(1.78)
(2.22)
(3.33)
(4.45)
Material:
12 Gauge (2.6)
Styrofoam
Filler
B220
End Cap
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers & Supports
202
Concrete Inserts
Material: Steel
Function: Designed to attach pipe sleeves to wall or floor forms before concrete pours.
Standard Finish: Zinc Phosphate
Order By: Part number and finish.
Part No.
BD40
Sleeve Diameter
All Diameters
2" (50.8mm) to 6" (152.4mm)
Wall Thickness
5 / 16 " (7.9mm) and under
Schedule 40 Pipe
Approx. Wt./100
Lbs.
(kg)
1.5
(.68)
Material: Steel
Function: Designed to attach pipe sleeves to wall or floor forms before concrete pours.
Standard Finish: Zinc Phosphate
Order By: Part number and finish.
Part No.
BE-5-8
BE-9-12 in.
Sleeve Diameter
(mm)
6"
8" to 10"
9" to 14"
(152.4)
(203.2 to 254.0)
(228.6 to 355.6)
Wall Thickness
Schedule 80 Pipe
Schedule 40 Pipe
Schedule 80 Pipe
Approx. Wt./100
Lbs.
(kg)
3.5
(1.6)
4.0
(1.8)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
203
Pipe Hangers & Supports
Concrete Inserts
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers & Supports
204