Series 13 Fiberglass Straight Section Part Numbering Prefix Series

advertisement
Fiberglass -
3” Straight Section
1" (25)
Rung
Spacing
NEMA
2" Fill
3" (76)
For side rail data, see
charts on pages APP-8
1" (25)
One pair of splice plates with SS6
(316 Stainless Steel) hardware included
Overall Width
(Width + 7/8”)
Series 13 Fiberglass Straight Section Part Numbering
Prefix
Example: 13 F 09 - 24 - 120
Series
Fiberglass
13
Material
Type
Width
F = Polyester
FV = Vinyl Ester
FA = Zero Halogen/
Dis-Stat
Ladder 06 = 6" rung spacing
09 = 9" rung spacing
12 = 12" rung spacing
06
09
12
18
24
FA = Zero Halogen/
Dis-Stat is
=
=
=
=
=
6"
9"
12"
18"
24"
13F
13FV
13FA
120 = 10 ft.
240 = 20 ft.
¨Primary
NEMA & CSA
Classifications
Span
ft
Load
lbs/ft
Deflection
Multiplier
Span
meters
Load
kg/m
Deflection
Multiplier
1.00
NEMA: 8C
6
257
0.005
1.8
382
0.086
NEMA
2” fill
3.00
Side Rail
Dimensions
NEMA & CSA
Classifications
1.00
NEMA: 8C
NEMA
2” fill
3.00
1.00
13
Length.
Length.
¡Secondary
Side Rail
Dimensions
1.00
B-Line
Series
¡
Length
See page CTS-23 for
explanation of lengths.
See page FCT-52 for additional rung options.
B-Line
Series
¨
8
145
0.016
2.4
216
0.267
10
93
0.040
3.0
138
0.681
12
64
0.083
3.7
95
1.411
14
47
0.153
4.3
70
2.614
Span
ft
Load
lbs/ft
Span
meters
Load
kg/m
6
178
1.8
264
8
100
2.4
149
10
64
3.0
95
12
44
3.7
65
Values are based on simple beam tests per NEMA VFG-1 on 24" wide cable tray rungs spaced on 12" centers. Published load
safety factor is 1.5. To convert 1.5 safety factor to 2.0, multiply published load by 0.75. To obtain mid-span deflection, multiply a
load by the deflection multiplier. Cable tray must be supported on spans shorter than or equal to the length of the cable being
installed.
When trays are used in continuous spans, the deflection of the tray is reduced by as much as 50%.
Green = Fastest shipped items
Black = Normal lead-time items
Red = Normally long lead-time items
Dimensions shown in parentheses are in millimeters, unless otherwise specified.