Series 2, 3, 4, & 5 Aluminum - Straight Sections

advertisement
Series 2, 3, 4, & 5 Aluminum -
Straight Sections
4" NEMA VE 1 Loading Depth
5" Side Rail Height
Straight Section Part Numbering
Prefix
Example: 25 A 09 - 24 - 144
Series
Material
*Type
A = Aluminum
25
*Width
Ladder06 = 6" rung spacing
09 = 9" rung spacing
12 = 12" rung spacing
35
Trough6" thru 36" wide
VT = Vented Trough
ST = Non-Ventilated Trough
06
09
12
18
24
30
36
=
=
=
=
=
=
=
6"
9"
12"
18"
24"
30"
36"
¨
¡
¨
¡
Length
144
240
240
144
=
=
=
=
¨Primary
12
20
20
12
ft.
ft.
ft.
ft.
25
35
Length.
Length.
¡Secondary
See page CTS-23 for
explanation of lengths.
Rung
Spacing
Width
(Inside)
Overall Width
(Width + 11/2")
For
side rail
& rung data,
see chart on
pages AP-5 & AP-6
Series 2, 3, 4, & 5 Aluminum
See page APP-1 for additional rung options. *Special sizes available.
Ladder Type
Ventilated Trough
Non-Ventilated Trough
(Specify Rung Spacing)
Green = Fastest shipped items
Black = Normal lead-time items
HAT-5
Red = Normally long lead-time items
Cable Tray Systems
Series 2, 3, 4, & 5 Aluminum -
Straight Sections
4" NEMA VE 1 Loading Depth
5" Side Rail Height
Values are based on simple beam tests per NEMA VE 1 on 36" wide cable tray with rungs spaced on 12" centers. Cable trays will
support without collapse a 200 lb. (90.7 kg) concentrated load over and above published loads. Published load safety factor is 1.5.
To convert 1.5 safety factor to 2.0, multiply published load by 0.75. To obtain mid-span deflection, multiply a load by the deflection
multiplier. Cable tray must be supported on spans shorter than or equal to the length of the cable tray being installed.
Individual rungs will support without collapse a 200 lb. (90.7 kg) concentrated load applied at the mid-span of the rung, over and
above the NEMA rated cable load with a 1.5 safety factor for highlighted NEMA spans and loads.
B-Line
Series
Side Rail
Dimensions
1.75
25
3.93
5.00
NEMA, CSA & UL
Classifications
Span
ft
Load
lbs/ft
Deflection
Multiplier
NEMA: 20A, 12C
CSA: 67 kg/m 6.0m
D-6m
UL Cross-Sectional
Area: 1.00 in2
10
12
14
16
18
20
200
139
102
78
62
50
0.0049
0.010
0.019
0.032
0.051
0.078
Design Factors Span
for Two Rails meters
Area=1.24 in2
Sx=1.80 in3
Ix=4.62 in4
3.0
3.7
4.3
4.9
5.5
6.1
Load
kg/m
Deflection
Multiplier
298
207
152
116
92
74
0.083
0.172
0.319
0.545
0.873
1.330
Design Factors
for Two Rails
Area=8.00 cm2
Sx=29.50 cm3
Ix=192.30 cm4
When trays are used in continuous spans, the deflection of the tray is reduced by as much as 50%. Design factors: Ix = Moment
of Inertia, Sx = Section Modulus.
B-Line
Series
Side Rail
Dimensions
NEMA, CSA & UL
Classifications
Span
ft
Load
lbs/ft
Deflection
Multiplier
1.75
NEMA: 20B, 16C
CSA: 112 kg/m 6.0m
10
12
14
16
18
20
310
215
158
121
96
77
0.0035
0.0073
0.014
0.023
0.037
0.057
35
5.06
3.96
E-6m
UL Cross-Sectional
Area: 1.50 in2
Design Factors Span
for Two Rails meters
Area=1.67 in2
Sx=2.35 in3
Ix=6.37 in4
3.0
3.7
4.3
4.9
5.5
6.1
Load
kg/m
Deflection
Multiplier
461
320
235
180
142
115
0.060
0.125
0.232
0.395
0.633
0.965
Design Factors
for Two Rails
Area=10.77 cm2
Sx=38.51 cm3
Ix=265.14 cm4
When trays are used in continuous spans, the deflection of the tray is reduced by as much as 50%. Design factors: Ix = Moment
of Inertia, Sx = Section Modulus.
Series 2, 3, 4, & 5 Aluminum