CODE MECKLENBURG COUNTY ENGINEERING & BUILDING STANDARDS DEPARTMENT INTERPRETATION VOLUME: 2002 North Carolina Residential Code for One and Two-Family Dwellings SUBJECT: Foundation Vents REVIEWED BY: Consistency Team QUESTION: Where should foundation vents be placed? CODE REFERENCE: Sections R408.1 and R408.2 ANSWER: Foundation vents should be installed to eliminate dead air pockets. Vents should be placed at each corner and spread out along the foundation walls equally on all sides. The ventilation openings should equal the square footage prescribed by the code. Exceptions: • Ventilation openings may be vented to the interior of a building where warranted by climatic conditions. • The total area of ventilation may be reduced to 1/1500 under the floor area when an approved 6 mil vapor barrier material is used and when ventilation openings are installed within (3) three feet from each corner of the building (required openings Section R408.1). • Ventilation openings may be omitted when continuously operated mechanical ventilation is provided and the ground is covered with an approved vapor barrier material. Approved By ______________________________ Date: 07/01/02