MECKLENBURG COUNTY CODE DEFECT LIBRARY DEFECT INFORMATION SHEET North Carolina State Building Code Residential Building Code Volume VII CODE DEFECT: Missing foundation anchors. Improper anchors. Improper installation. Applicable Code Sections: Section 403 “Exterior walls of houses on foundation systems with more that 30 inches of unbalanced fill, and slab on grade houses shall be anchored to the foundation system or slab with at least ½” diameter bolts placed 6 feet on center and not more than 12 inches from corners. Bolts shall extend a minimum of 15 inches into masonry or 7 inches into concrete.” Metal wall strap anchors are allowed, but for installation requirements, the manufacturer recommendations shall be followed. Approved Application: Floors must be anchored and connected to restrain the top of the wall; the bottom must be restrained at the footing by concrete floor slab, keyed footing or mechanical anchorage (reinforcing steel). See attached illustrations for approved methods.