REMOVE (E) CEILING AS REQUIRED FOR NEW WALL Aptos, California 95003 SHEET NOTES 1. 2. DASHED OR DOTTED LINES DENOTE EXISTING TO BE REMOVED. THIS PLAN IS FOR REFERENCE ONLY. ARCHITECT DOES NOT GUARANTEE ACCURACY OF THE EXISTING CONDITION. 3. FOR REMOVAL OF PLUMBING ITEMS SEE PLUMBING DRAWINGS. 4. FOR REMOVAL OF MECHANICAL ITEMS SEE MECHANICAL DRAWINGS. 5. FOR REMOVAL OF ELECTRICAL FIRE ALARM AND SIGNALS ITEMS SEE ELECTRICAL DRAWINGS. 6. WHERE (E) WALLS ARE DESIGNATED TO REMAIN, REMOVE PLUMBING ITEMS & RELATED PIPING BACK TO WALL AND CAP INSIDE WALL. 7. WHERE (E) WALLS ARE DESIGNATED TO REMAIN, REMOVE ELECTRICAL OUTLETS & RE-FINISH WALL SURFACES TO MATCH (E). 8. REMOVE DOORS AT (E) LOCKERS AND CHALKBOARDS FOR RE-USE AND TURN OVER TO THE OWNER. 9. ABATEMENT UNDER SEPARATE CONTRACT INCLUDES THE FOLLOWING (ONLY KEY ITEMS NOTED): A. REMOVAL OF GYP. BD. AND STUD WALLS, U.O.N. B. REMOVAL OF ALL FLOOR FINISHES & UNDERLAYMENT DOWN TO STRUCTURAL PLYWOOD. C. REMOVAL OF CEILING PLASTER AND 1X4 FURRING STRIPS D. CABINETS & COUNTERTOPS E. PIPE INSULATION F. INTERIOR DOORS G. FLUORESCENT LIGHT FIXTURES 10. SOME GYP. BD. WILL REMAIN IN ROOM IN ROOM 612: CONTRACTOR TO IDENTIFY ANY GYB. BD. AREAS REQUIRING CUTTING AND ADVISE DISTRICT TO BRING THE ABATEMENT CONTRACTOR BACK TO PERFORM THE WORK. 04/11/13 BID SET 01-113103 MM MS 1/4" = 1'-0" NOTE: BEAMS & SUPPORT POSTS TO REMAIN WALL LEGEND EXISTING WALL TO REMAIN 1 A-101 DEMOLITION FLOOR PLAN 1/4" = 1'-0" WALL TO BE DEMOLISHED & REMOVED POST TO REMAIN 4015839 14'-0" 14'-0" 14'-0" 14'-0" 14'-0" 14'-0" 14'-0" 14'-0" 44'-2" 11 1 A-201 3'-4 1/2" 3 EQUAL 14'-0" 48" MIN. 2'-0" EQUAL 4'-7" 10'-0" G V 14'-0" G V 4'-0" 6'-6" 12'-11" 14'-0" 9'-2" 4'-0" 4'-2" Aptos, California 95003 SHEET NOTES 6'-11" 1. 5'-0" 2. 3. 11 04/11/13 SEE SHEET A-601 FOR CASEWORK, FINISH AND COLOR AND OPENINGS SCHEDULES. SEE SHEET A-502 FOR WALL TYPES. FOR EXIT AND ROOM IDENTIFICATION SIGNS SEE 12/A501 BID SET 14'-0" 01-113103 MM 7 MS 8 1/4" = 1'-0" WALL LEGEND TWO HOUR RATED FIRE BARRIER WALL NEW WALL GAS VALVE WATER FLOOR PLAN 1 A-102 1/4" = 1'-0" EXISTING WALL TO REMAIN NEW FURRING WALL / EXISTING WALL 4015839 10'-0" Aptos, California 95003 BUILDING SECTION 1 A-201 1/4" = 1'-0" A-102 04/11/13 BID SET (E) 1/2" PLYWOOD (E) 2 X 12 BLOCKING 01-113103 (E) 3 X 16 CEILING JOIST (E) TIMBER TRUSS 2 X 4 BLOCKING 5/8" GYP. BD. FIRE BLOCKING IL 5/8" GYP.BD. CEILING (E) 2 X 12 BLOCKING MS (E) 3 X 16 CEILING JOIST 10'-0" TO FINISH FLOOR 1/4" = 1'-0" SUSPENDED ACOUSTICAL CEILING 4015839 WALL TYPE "B", SEE A-502 WALL HEAD DETAIL @ (E) TRUSS 6 A-201 1/4" = 1'-0" - A. NORTH B. EAST 5 A-505 5 A-501 ASSISTIVE LISTENING SYSTEM AVAILABLE PLEASE ASK STAFF C. SOUTH D. WEST ROOM 610 - INTERIOR ELEVATIONS 1 A-402 1/4" = 1'-0" A-102 12B A-505 Aptos, California 95003 12B A-505 04/11/13 BID SET 2A. NORTH 3A. NORTH 01-113103 IL SM 2C. SOUTH 3C. SOUTH 1/4" = 1'-0" ROOM 610 - ALTERNATE #1 2 A402 1/4" = 1'-0" A-102 4015839 4A. NORTH 3B. EAST ROOM 610 - ALTERNATE #2 3 A402 1/4" = 1'-0" ROOM 611 - ALTERNATE #1 A-102 4 A402 1/4" = 1'-0" A-102 12" MIN. 5 - ADDED 2 X 4 WITH 2- # 12 X 3" WOOD SCREWS TOP & BOTTOM TO (E) CEILING JOISTS, TYP. EACH JOIST ABOVE HOOD; SHAPE EDGE AS NECESSARY TO BE PARALLEL TO FUME HOOD (E) 3 X16 CEILING JOISTS @ 24" O.C. VENT STACK CEILING CEILING BACKING, SEE 1/A-503 REMOVABLE ENCLOSURE PANEL 3"x6"X10 GA. GALV. CLIP ANGLE, 8" LONG ATTACHED TO WALL W/ (2) #12x2" S.M.S. & (2) # 13x2" HEX TEC SCREW TO TOP OF HOOD (MIN. OF 2) 4- # 12 S.M.S. EQUALLY SPACED FUME HOOD INSULATED ROOF CURB 8" MIN. REMOVABLE ENCLOSURE PANEL PAINTED 2 X HEADER WITH # 12 X 3" F.H.W. SCREWS EACH ADDED 2X ALARM LOCATION 3"x 6" x 10 GA. GALV. CLIP ANGLE, 8" LONG ATTACHED TO WALL W/ (2) #12 x 2" S.M.S. & (2) # 13 x 2" HEX TEC SCREW TO EACH SIDE OF HOOD UTILITIES BASE CABINET, SEE A-601 34" MAX. TO WORKSURFACE LIGHT SWITCH & RECEPTACLE OPEN FINISH FLOOR CONTROL MOUNTING HEIGHT 48" MAX. RECEPTACLE ADD 2 x 4 (FLAT) BLOCKING ALL AROUND 4- # 10 x 2 1/2" WAFFER HEAD SCREW, EQUALL Y SPACED BACKING, SEE 1/A-503 NOTE: FUME HOOD & BASE UNIT MFR. TO PROVIDE DETAILED DRAWINGS OF SEISMIC ANCHORAGE SYSTEM, DETAILS AS SHOWN ARE MIN. REQUIREMENTS FUME HOOD BASE UNIT 5B A-503 5A A-503 EXISTING ROOF FRAMING ADD 2 X FRAMING ALL AROUND OPENING WITH L50 EACH END EACH 2X VERIFY FUME HOOD ELEVATION FUME HOOD SECTION 11 A-501 1" = 1'-0" A-102 5 A-501 1" = 1'-0" - 6 1/4" FUME HOOD EXHAUST DUCT, SEE MECHANICAL DRAWINGS Aptos, California 95003 16 GA X 2" RING AROUND EXHAUST DUCT WITH 4 # 10 S.M.S. TO DUCT AND # 10 X 2" WOOD SCREWS TO EACHE ADDED 2 X 04/11/13 BID SET 1/2" 1/2" NOTE: FOR FURTHER NOTES SEE ROOM IDENTIFICATION SIGN ROOF CURB DETAIL 2 A-501 3" = 1'-0" A-201 01-113103 48" MIN. TO FINISH FLOOR MAX. 1/2" 3/8" 2" 1/2" EXISTING ASPHALT SHINGLES ON BUILDING PAPER, REMOVE AS REQUIRED TO INSTALL NEW CURB WATER TIGHT WITH FLASHING AND COUNTER FLASHING EXIT SIGN IL MS (E) 2 X 6 STUD WALL EYE WASH/SHOWER STATION BASE DETAIL 8 A-501 1 1/2" = 1'-0" - 10" TO DOOR OPENING LATCH SIDE, TYP. LETTER 6" HIGH, STROKE 3/4" PROVIDE BLACK LETTER ON WHITE BACKGROUND 6 1/4" NOTE: SIGN, CHARACTER AND BRAILLE TO CONFORM TO 2010 CBC AMENDMENT DATED 8-1-12 SECTION 1117.5 SIGNS AND IDENTIFICATION SIGN # 1 2 3 4 5 6 7 8 COPY 608B 608A 610A 610B 611A 611B 612 611C 48" RADIUS CORNERS 36" MAX. 3'-0" LETERRING 1/32" RAISED UPPER CASE HELVETIC MEDIUM CORRESPONDING GRADE 2 BRAILLE AS NOTED (E) OPENING FRAME 3'-0" TO FINISH FLOOR 48" MIN. TO FINISH FLOOR RADIUS CORNERS, TYP. BACKGROUND COLOR BY ARCHITECT 1'-2 3/8" 1/2" MIN 608 MAX. 1/2" 3/8" 2" 1/2" 1/2" MIN. 2- LAYERS OF 5/8" TYPE "X" GYP. BD. BOTH SIDES 1'-6" MIN. 82 1/2" CL ACCESS DOOR ( 90 MIN. RATED) 8 - 8" NOTE: JAMB DETAIL SIMILAR 4015839 ROOM IDENTIFICATION SIGN DOOR BLOCKED SIGN SIGNAGE DETAILS 12 A-501 3" = 1'-0" A-102 9 A-501 1" = 1'-0" ATTIC ACCESS DOOR HEAD DETAIL EYE WASH / SHOWER STATION A-102 6 A-501 1" = 1'-0" A-102 3 A-501 3" = 1'-0" A-201 C L NOTES 362S150-33 STUDS @ 16" O.C. MAX. 362S150-33 STUDS @ 16" O.C. MAX. (E) 1 /2" PLYWOOD GYPSUM BOARD FINISHES WILL COMPLY WITH GA-214 LEVELS OF GYPSUM BOARD FINISH. a. FINISH TO WALLS TO RECEIVE PAINTED WHITEBOARD TO HAVE FINISH LEVEL 5. b. ALL OTHER WALLS TO RECEIVE FINISH LEVEL 4. 2. CONTRACTOR WILL VERIFY AND COORDINATE WALLS AND PARTITIONS THAT REQUIRE NON-TYPICAL THICKNESSES OWING TO STRUCTURAL, MECHANICAL, ELECTRICAL, OR EQUIPMENT REQUIREMENTS. 3. BLOCKING WILL BE PROVIDED FOR THE ATTACHMENT TO WALLS FOR ALL CASEWORK AND EQUIPMENT, SEE 1/A-503. 4. INSTALL MOISTURE RESISTANT GYP. BD. BEHIND AND SIDE WALL NEXT TO EMERGENCY SHOWER. 5. FOR TYPICAL PARTITION SECTIONS, SEE 2 /A-505 6. PROVIDE #10 S.M.S. EACH FLANGE EACH STUD TO TOP AND BOTTOM TRACK. 7. MAXIMUM STUDS HEIGHT = 10'-0" 250S125-33 STUDS @ 16" O.C. MAX. FIRE SEALANT (E) 6 X 8 RAFTER 5/8" GYP. BD. BOTH SIDES (E) 3 /8" PLYWOOD EXISTING CONCRETE MASONRY UNIT (E) 2 X 6 STUD WALL (E) ACCESS DOOR OPENING FRAME TO RECEIVE NEW 90 MIN. ACCESS DOOR, SEE A-201 BATT INSULATION 5/8" TYPE "X" GYP. BD. 5/8" GYP. BD. ONE SIDE 2- LAYERS OF 5/8" GYP. BD. BOTH SIDES VOID 3'-0" X 4'-0" ACCESS DOOR 90 MIN. RATED BEYOUND. SEE DETAIL 3/A-501, 2 HOUR RATED WALL GA FILE WP 4135 FIRE TEST: FM WP 360, 9-27-74 1. NOTE: SEE DETAIL 12/FOR ATTACHMENT TOP AND BOTTOM 5" 1/2" WALL TYPE 2 HOUR RATED WALL (E) 2 X 6" SILL PLATE 5/8" TYPE "X" GYP. BD. (E) 8" C.M.U. PROVIDE 2 HOUR RATING (CBC TABLE 720.1(2)). REFER TO SECTION 12 /- FOR ENTIRE WALL DETAILS WALL TYPES ANCHOR BOLTS AT 4'-0" O.C. 250S125-33 STUDS @ 16" O.C. MAX. FIRE SEALANT (E) 10" X 24" BOND BEAM ACUSTICAL INSULATION (E) EXTERIOR CONCRETE MASONRY UNIT (E) 3 X 16 JOISTS BATT INSULATION SCREW ANCHORS @ 16" O.C. VOID 5/8" GYP. BD. BOTH SIDES 5/8" GYP. BD. 04/11/13 NOTE: SEE DETAIL 12/FOR ATTACHMENT TOP AND BOTTOM 5 /8 " ACOUSTICAL TILE GLUED TO 1/2" GYPSUM BOARD Aptos, California 95003 DOUBLE WALL WITH 362 S150-33 STUDS @ 16" O.C. MAX. BID SET 1'-2 1 /2" SUSPENDED CEILING, WHERE OCCURS, SEE REFLECTED CEILING PLANS WALL TYPE WALL TYPE 01-113103 FOR CEILING PERIMETER ATTACHMENT SEE 4/A-504 362S150-33 STUDS @ 16" O.C. MAX. (@ LAB SIDE). WALL TYPE "C OR "D", FOR METAL STUDS NOTES AND ATTACHMENTS SEE 2/ A-505 250 S125-33 STUDS @ 16" O.C. MAX. SET PLUMB & FASTENED TO C.M.U. 400S162-43 STUDS @ 16" O.C. MAX. EXISTING OPENING IN MASONRY WALL EXISTING CONCRETE MASONRY UNIT FINISH FLOOR, ON UNDERLAYMENT AND BASE AS SCHEDULED (E) 8" C.M.U. PROVIDE 2 HOUR RATING (CBC TABLE 720.1(2)). REFER TO SECTION 12 /- FOR ENTIRE WALL DETAILS FIRE SEALANT 2 LAYERS 5/8" TYPE "X" GYP. BD. (E) 1 1 /8" PLYWOOD SUB FLOORING AS NOTED 5/8" TYPE "X" GYP. BD. 400T150-43 ALL AROUND 18 GA TRACK WITH # 12 x 3" SCREWS @ 16" O.C. TO (E) FLOOR JOISTS; PRE DRILL TRACK FOR SCREW ( E) CONCRETE FOOTING, FILL ALL (E) OPENINGS WITH FIRE STOPPING MATERIAL 2-HOUR RATED WALL 12 A-502 3" = 1'-0" AXXX TAP CON SCREW ANCHORS @ 16" O.C. NOTE: SEE DETAIL 12/FOR ATTACHMENT TOP AND BOTTOM FIRE SEALANT 1/2" WALL TYPE 2 HOUR RATED WALL 1/2" (E) 8" C.M.U. PROVIDE 2 HOUR RATING (CBC TABLE 720.1(2)). REFER TO SECTION 12 /- FOR ENTIRE WALL DETAILS WALL TYPE (DOOR OPENING FILLER) WALL TYPE SCHEDULE 6 A-502 3" = 1'-0" A102 2 HOUR RATED WALL GA WP 5015, UL R4024-13 4015839 12 G IN AC (E) CMU WALL 3 UD 4" SP ST CABINET TOP METAL STUDS, 16 GA. MIN. (2) #8 x 5 8" PAN HEAD TACK SCREWS 16 GA. X 1 1/2" x 1 1/ 2" x 4" LONG ANGLE @ 24" O.C., MIN. (2) PER CABINET, ATTACH WITH (2) 1/4" X 2 1/4" TAPCON ANCHOR BOLTS (2" O.C. EACH WAY), TOP & BOTTOM 9 2'-3" MIN.. A 2'-10" MAX. ISOMETRIC 36" 600S162-54 STUD, FASTEN TO FRAMING STUDS W/ (3) #12 SELF-TAPPING SCREWS EACH STUD CABINET BACK 6B NOTE: MOUNT ITEM TO BACKING WITH #12 SELF-TAPPING SCREWS U.O.N. 6A 4" 30" MIN. CABINET BOTTOM SECTION "A" INSTRUCTION BENCH SECTION 7 A503 11/2" = 1'-0" WALL CAB. CMU ANCHORAGE 4 A503 3" = 1'-0" A-601 TYPICAL BACKING DETAIL - 1 A503 NTS A-601 PLAN 4 AT CMU WALL 1" EPOXY TOP ADJUSTABLE LEGS (E) WINDOW CABINET TOP # 8 x 3/4" F.H.W.S. @ 16" O.C. CONT. 1x 4 SPACER 2 X 2 BLOCKING TO (E) MULLION WITH (2) # 12 x 3" F.H.S.S. A. TOP BACKING, SEE 1/- COUNTERTOP & SPLASH CONT. 1x 4 SPACER TYPICAL DETAIL ALT. # 1 FURRING WALL TYPE "E" BEYOND B. BOTTOM TRIM FROM 1 X TO METAL CAP WITH # 8 SELF-TAPPING SCREWS 1 1/2" X 1 1/2" x 2" LONG, 16 GA ANGLE @ 16" O.C. 3 PER CABINET, MIN. T.O. CASEWORK, SEE SCHEDULE Aptos, California 95003 WALL CABINET W/ ADJUSTABLE SHELVES, CONFIGURATION VARIES 1" 2" TRIM FROM 1 X TO BLOCKING WITH FINISH NAILS. 8 1'-6" BACKING, SEE 1/- (E) HORIZONTAL MULLION 4" 2'-0" AT TYPE 1 3 2'-3" AT TYPE 2 (E) CMU WALL BEYOND ELEC. FLUSH TABLE BOX @TYPE 1 TABLE 2"1" A-601 #14 2 1/2" SELF-TAPPING S.M.S. @ 16" O.C. CABINET BACK 5'-0" 1 1/2" X 1 1/2" x 2" LONG, 16 GA ANGLE @ 16" O.C. 3 PER CABINET, MIN. 4'-8" 2" 2" NOTE: ELECTRICAL 'TABLE BOX' WITH FOUR 3 PRONG 110V ELEC. RECEPTACLES. TABLE BOX TO BE FLUSH MOUNTED IN EPOXY TABLE TOP WITH RETRACTABLE COVER. UNDERSIDE OF E. TABLE BOX TO HAVE A 6' LONG CONVENIENCE CORD WITH 3 PRONG PLUG TO PLUG INTO FLOOR BOX. # 8 x 3/4" F.H.W.S. 3/4" CABINET BOTTOM WALL CABINET ANCHORAGE ADJUSTABLE HEIGHT TABLE 5 A503 1" = 1'-0" - 01-113103 A-102 FOR NOTES SEE BELOW COUNTERTOP W/ SPLASH BACKING, SEE 1/A-503 (E) 1-81" PLYWOOD 2" X 2" x 2" LONG, 16 GA ANGLE @ 16" O.C. - 3 PER CABINET, MIN. - 1 1/2" X 1 1/2" X 2 " LONG, 16 GA ANGLE CONT. 1x 4 SPACER 1 1/2" PARTITION, SEE PARTITION SCHEDULE RADIUS ON TOP FRONT EDGE 3 4" CABINET BOTTOM 1 1/2" X 1 1/2" X 2 " LONG, 16 GA ANGLE @ 16" O.C. BASE FROM 2 X B. BOTTOM 1 1/2" #14 x 3" SELF-TAPPING S.M.S. @ 16" O.C. #14 X 3" WOOD SCREW @ 16" O.C. TO (E) FLOOR JOISTS (E) 1-81" PLYWOOD COUNTER TOP EDGE DETAIL ADD 4 x 4 BLOCKING AS NECESSARY BASE CABINET ANCHORAGE - 9 A503 3" = 1'-0" 6 # 14 X 3 1/2" F.H.W.S. SET FLUSH 3" BASE FROM 2 X 4" COMPOSITE COUNTERTOP (DELETE PLYWOOD BASE AND PROVIDE ROUNDED EDGE). BASE CABINET W/ ADJUSTABLE SHELVES, CONFIGURATION VARIES # 8 X 1 1/2" F.H.W.S. OR BOLT (WITH ACORN NUT) # 8 X 1 1/2" F.H.W.S. @16" O.C., TYP. CABINET BACK 4015839 BASE, SEE SCHEDULE (E) 1-81" PLYWOOD A. WITH TOE SPACE TYPICAL CABINET SECTION BASE CABINET ANCHORAGE - 6 A503 3" = 1'-0" AS NOTED DRAWER W.O. SINK W.O. B. NO TOE SPACE #14 2 1/2" SELF-TAPPING S.M.S. @ 16" O.C. A. TOP BASE CABINET TO DOOR DETAIL 12 A503 3" = 1'-0" MS 12 SEE SCHEDULE CONT. 1x WOOD SPACER 2" IL # 8 x 3/4" F.H.W.S. @ 16" O.C. ALTERNATE # 1 DETAIL 1 COMPOSITE COUNTERTOP 4" SPLASH 9 11 A503 3" = 1'-0" 04/11/13 BID SET #14 2 1/2" SELF-TAPPING S.M.S. @ 16" O.C. 8 A503 3" = 1'-0" ALT. # 1 FURRING WALL LOW AT CABINET SEE SCHEDULE ACCESSIBLE SINK CABINET 10 A503 N.T.S. - 3 A503 1 1/2" = 1'-0" A-601 12'-8" 19 @ 8" EA. 12" PARTITION AS SCHEDULED 8" 5'-4" 8 @ 8" EA. 8" 3/8" STROKE 8" (E) FRAMING 3 X 16 1/2" MIN. GAP BETWEEN TRACK AND TOP OF STUDS DOUBLE STUD JAMB STEEL DOOR FRAME WITH CLIP STUD ANCHORS @ 24" O.C. WITH MIN. (2) #12 SMS. 5/8" 6" 1/2" 5 /8 " GYPSUM BOARD CEILING WHERE OCCURS . SIGN: SEE T24 - SECTION 1104B.2 ADD 4 x 4 BLOCKING @ 2'-0" O.C. WITH U 44 EACH END AS REQUIRED TO ANCHOR PARTITION DOOR AS SCHEDULED 1 15/16" 1 15/16" 5 /8 " ACOUSTICAL TILE GLUED & STAPLE TO 1/2" NON-SAG GYP.BD., WHERE OCCURS JAMB SHOWN, HEAD SIMILAR 10 A-505 PERIODIC TABLE PAINTED GRID 1/2" = 1'-0" 7 A-505 A-401 SIGN FOR HEARING IMPAIRED 3" = 1'-0" A-102 4 A-505 DOOR DETAIL 3" = 1'-0" SUSPENDED CEILING, WHERE OCCURS, SEE REFLECTED CEILING PLANS A-601 1'-0" UNDERLAYMENT 11 A-505 CARPET BYPSUM BOARD OR SUSPENDED CEILING 1/2" 7'-0" TO FINISH FLOOR 1/4" MAX. VYNIL TILE 5" 1/4" MAX. TO COMPRESSED CARPET RESILIENT TRANSITIONAL MOLDING 1" 1" 1" 1" RADIUS CORNERS SCREEN CASE FULL SIZE 8 A-505 A-102 5/8" GYP. BD. TYP., WALL TYPE VARIES, SEE WALL TYPE SCHEDULE (E) PLYWOOD FLOORING 18GA. TRACK W/ #12 X 3" SCREWS @ 16"O.C. TO (E) FLOOR JOISTS; PRE-DRILL TRACK FOR SCREW CASE CLAMP AND HANGER HOOK BRACKET BY SCREEN MANUFACTURER, TYPICAL OF TWO PER SCREEN ROOM CAPACITY SIGN 3" = 1'-0" A-102 5 A-505 (2) # 12 SELF-TAPING SCREWS @ EACH HANGER HOOK. ACOUSTICAL SEALANT, WALLS TYPE A AND B ONLY ADD 4 x 4 BLOCKING AS NECESSARY 04/11/13 BID SET (E) FLOOR JOISTS SCREEN MOUNTING DETAIL 3" = 1'-0" Aptos, California 95003 FLOOR FINISHES ON UNDERLAYMENT AND BASE, SEE SCHEDULE TYPICAL BACKING SEE 1/A-503 1 3/4" TRANSITION FLOOR - CARPET/VINYL SEALANT 18 GA. SLIPTRACK WITH #12 X 2" WOOD SCREWS @ 24"O.C. TO CEILING JOISTS OR ADDED BLOCKING; PRE-DRILL TRACK FOR SCREWS TO (E) LUMBER 2 A-505 A-401 TYPICAL INTERIOR PARTITION DETAIL 3" = 1'-0" A-502 01-113103 (E) CMU WALL SEALANT AND BACKER ROD LINE OF CEILING ACOUSTICAL PANEL, ALTERNATE # 2 PAINT REVEAL BLACK BATT INSULATION ACOUSTICAL PANEL (E) EXTERIOR CONCRETE MASONRY UNIT 1/2" CORE ATTACH TO MOUNTING SURFACE WITH STAPLES AND ADHESIVE BY MANUFACTURER INSTRUCTIONS FABRIC PERIMETER AND INTERMEDIATE TRACK ATTACH TO MOUNTING SURFACE WITH STAPLES OR SCREWS PER MANUFACTURER INSTRUCTIONS FACE OF GYP. BD. BEYOND 12 A-505 3" = 1'-0" ACOUSTICAL CEILING TILE ON GYP. BD. 5/8" GYP. BD. PROJECTOR MOUNT BRACKET ANCHOR PROJECTOR (N.I.C.) MAX. WEIGHT= 10# JAMB ( HEAD SIMILAR) NOTE: DETAIL ALSO APPLIES TO ALTERNATE # 1 B. SECTION A-102 9 A-505 SM AS NOTED 2 1/2" METAL STUDS @ 16" O.C. MAX. (E) WINDOW (STRECHED FABRIC WALL SYSTEM) ACOUSTICAL PANEL DETAIL, ALT. # 2 IL PROVIDE PLUMB SHIM TO RECEIVE METAL STUDS (E) FRAMING BASE AND FINISH FLOOR 5/8" GYP. BD. (E) WINDOW A. PLAN ADD 6 x12 (FLAT) WITH L50 EACH SIDE EACH END TO RECEIVE TWO # 14 X 3 1 /2" WOOD SCREWS WALL FURRING @ (E) WINDOW 3" = 1'-0" A-102 80" MIN. TO FINISH FLOOR 1/2" FURRING WALL, ALTERNATE # 1, REFER TO DETAIL 9/- FOR NOTES 6 A-505 SEALANT AND BACKER ROD NOTE: CUTTING OR DAMAGING THE EXISTING REINFORCEMENT DURING THE INSTALLATION OF NEW ANCHORAGE SYSTEM IS NOT PERMITTED. THE CONTRACTOR SHALL USE DRILLS EQUIPPED WITH GROUND FAULT INTERRUPTER, OR DETERMINE THE EXACT LOCATION OF THE EXISTING REINFORCING BARS PRIOR TO DRILLING OPERATIONS NOTE: FOR PROJECTOR MOUNTING BELOW SUSPENDED CEILING USE TUBE EXTENSION AND METAL PLATE PER BRACKET MANUFCATURER PARTITION @ (E) CMU WALL PROJECTOR MOUNT DETAIL 3" = 1'-0" A-103 3 A-505 3" = 1'-0" A-102 4015839 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 GENERAL NOTES 1. SCOPE OF WORK INCLUDES FURNISHING AND INSTALLING FIRST-CLASS WORKING SYSTEMS, TESTED READY FOR OPERATION, COMPLETE WITH LABOR, MATERIALS, APPARATUS, TRANSPORTATION AND TOOLS REQUIRED FOR THE INSTALLATION IN CONFORMANCE WITH DRAWINGS AND SPECIFICATIONS. 15.THE ELECTRICAL CONTRACTOR SHALL VERIFY THE TYPE OF CEILING SYSTEM WITH THE GENERAL CONTRACTOR OR CEILING CONTRACTOR TO INSURE THAT ALL RECESSED LIGHTING FIXTURES ARE COMPATIBLE WITH THE CEILING SYSTEM BEING INSTALLED. LIGHTING FIXTURES SHALL NOT BE ORDERED UNTIL TYPE OF CEILING HAS BEEN VERIFIED. 2. COMPLY WITH ALL APPLICABLE CODES AND ORDINANCES. 16.ELECTRICAL PLANS ARE DIAGRAMMATIC. DO NOT SCALE DRAWINGS. 3. ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC), UL AND ALL LOCAL CODES HAVING JURISDICTIONAL AUTHORITY. SECURE AND PAY FOR ALL REQUIRED PERMITS AND INSPECTIONS, UNO. 4. SUBMIT SIX COPIES OF SHOP DRAWINGS TO PROJECT MANAGER FOR REVIEW. SUBMITTED DATA MUST SHOW MANUFACTURER'S NAME, PUBLISHED RATINGS OR CAPACITY DATA AND OTHER PERTINENT DATA. SUBMITTALS ARE REQUIRED FOR BUT ARE NOT LIMITED TO THE FOLLOWING ITEMS: 1) CIRCUIT BREAKERS 4) LIGHTING FIXTURES & LAMPS 2) SAFETY SWITCHES 5) PANELBOARDS 3) WIRING DEVICES 6) TRANSFORMER 5. PROVIDE HARD AND ELECTRONIC COPIES OF AS BUILT DRAWINGS TO OWNER AT END OF PROJECT. 6. CONTRACTOR SHALL GUARANTEE ALL ELECTRICAL WORK FOR A PERIOD OF ONE YEAR FROM DATE OF SUBSTANTIAL COMPLETION. 7. COORDINATE WORK CLOSELY WITH ALL TRADES. A. CONSULT PLANS OF ALL OTHER TRADES FOR COORDINATION AND FOR RELATED AND ADJOINING WORK. B. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF ALL MECHANICAL EQUIPMENT. C. REFER TO PLUMBING DRAWINGS FOR EXACT LOCATION OF ALL PLUMBING EQUIPMENT. 8. KEEP ALL WORK AREAS CLEAN. CLEAN ALL EQUIPMENT, ETC., PRIOR TO FINAL PAINTING AND AT COMPLETION OF PROJECT. 9. ALL CUTTING AND PATCHING FOR ELECTRICAL WORK SHALL BE PAID FOR BY THE ELECTRICAL CONTRACTOR BUT PERFORMED BY THE CONTRACTOR WHOSE WORK IS CUT OR PATCHED. 10. PROVIDE CONDUIT AND WIRING UP TO AND INCLUDING STARTERS, CONTROLLERS, DISCONNECT SWITCHES OR JUNCTION BOXES FOR MECHANICAL EQUIPMENT UNLESS OTHERWISE INDICATED. STARTERS, CONTROLLERS, CONTROL WIRING AND FINAL CONNECTION TO EQUIPMENT SHALL BE BY ELECTRICAL CONTRACTOR, EXCEPT FOR STARTERS, FACTORY INSTALLED AS AN INTERNAL COMPONENT OF THE EQUIPMENT. 11. WIRE SHALL BE COPPER, 600 VOLT INSULATION, MINIMUM AWG. #12, TYPE THW, THWN, THHN, AS APPLICABLE. SIZES SHALL NOT BE LESS THAN INDICATED. BRANCH CIRCUIT CONDUCTORS SHALL NOT BE SMALLER THAN #12 AWG. CONDUCTOR FOR BRANCH CIRCUITS OF 120 VOLTS MORE THAN 100 FEET LONG AND OF 277 VOLTS MORE THAN 230 FEET LONG, FROM PANEL TO LOAD, SHALL NOT BE SMALLER THAN #10 AWG. CLASS 1 REMOTE CONTROL AND SIGNAL CIRCUIT CONDUCTORS SHALL NOT BE SMALLER THAN #14 AWG. CLASS 2 REMOTE CONTROL AND SIGNAL CIRCUIT CONDUCTORS SHALL NOT BE SMALLER THAN #16 AWG. PROVIDE RATED CABLES IN PLENUM CEILINGS WHERE USED. 12. ALL WIRING SHALL BE IN CONDUIT, MINIMUM SIZE 3/4 INCH WITH LARGER SIZES AS INDICATED OR REQUIRED BY NEC. ALL CONDUITS IN WET OR DAMP LOCATIONS SHALL BE RIGID GALVANIZED STEEL OR SCHEDULE 40 PVC. ALL OTHERS MAY BE EMT UNLESS OTHERWISE INDICATED. PROVIDE PVC CONDUIT ENCASED IN CONCRETE FOR U/G AS INDICATED. A. AT THE OPTION OF THE CONTRACTOR, AND IF LOCAL AUTHORITY HAVING JURISDICTION ALLOWS THE USE OF FLEXIBLE METAL CONDUIT, ARMORED CABLE, OR METAL-CLAD CABLE, THEN THE CONTRACTOR MAY USE THIS WIRING METHOD IN COMPLIANCE WITH APPLICABLE CODES. B. USE MAXIMUM 6 FOOT LENGTHS OF FLEXIBLE CONDUIT FOR FINAL CONNECTIONS TO LUMINAIRES, FOR EQUIPMENT SUBJECT TO VIBRATION, NOISE TRANSMISSION, OR MOVEMENT, AND FOR ALL MOTORS. USE LIQUIDTIGHT TYPE IN WET OR DAMP LOCATIONS. INSTALL SEPARATE GROUND CONDUCTOR ACROSS FLEXIBLE CONNECTIONS. 13. ALL CONDUITS SHALL BE RUN CONCEALED ABOVE CEILINGS, IN WALLS, AND IN OR BELOW FLOORS. EXPOSED CONDUITS SHALL BE RUN PARALLEL AND PERPENDICULAR TO BUILDING CONSTRUCTION. FINISH SHALL MATCH EXPOSED SURFACES. 14.RECEPTACLES AND SWITCHES: GENERAL-ALL DEVICES SHALL BE 20A COMMERCIAL SPECIFICATION GRADE OR BETTER-COLOR SHALL BE WHITE OR AS DIRECTED BY ARCHITECT. 17. CONSULT ARCHITECTURAL OR STRUCTURAL PLANS FOR CONSTRUCTION DETAILS, HEADROOM, ROOM FINISHES, CEILINGS, ETC. LEGEND & SYMBOLS 100AS FUSED DISCONNECT SWITCH, 30A UNO 70AF "AS" -SWITCH AMPS "AF" -FUSE AMPS 3P 100AS NON-FUSED DISCONNECT SWITCH, 30A 3P UNO "AS" -SWITCH AMPS 100AS COMBINATION DISCONNECT/MAGNETIC 70AF MOTOR STARTER. NUMBER INDICATES 2 3P NEMA SIZE "AS" -SWITCH AMPS "AF" -FUSE AMPS 15 18. CIRCUIT NUMBERS ARE FOR IDENTIFICATION PURPOSES ONLY. CONTRACTOR SHALL BE RESPONSIBLE FOR CORRECTLY PHASING THE CIRCUITS IN THE PANEL AND BALANCE THE LOAD ON THE PHASES UNDER NORMAL OPERATING CONDITIONS. 19. CONTRACTOR SHALL VERIFY WIRE SIZES, CIRCUIT BREAKER AND FUSE RATINGS FOR ALL HVAC EQUIPMENT, AND BRING TO THE ATTENTION OF THE PROJECT MANAGER ONLY DISCREPANCIES AFFECTING THE WORK PRIOR TO PROCEEDING. 20.ALL EMPTY CONDUIT RUNS IN EXCESS OF 10 FEET SHALL BE PROVIDED WITH A PULL WIRE OR FISH TAPE/CORD. CAP ALL CONDUIT STUB UP'S. 6ab 25.MAINTAIN GROUNDING CONTINUITY TO ALL DEVICES AND EQUIPMENT IN COMPLIANCE WITH THE LATEST NATIONAL ELECTRICAL CODE. A. GROUNDING: GROUNDING/BONDING OF RACEWAYS, WIREWAY SYSTEMS AND EQUIPMENT, SIZES OF WIRES AND CONNECTIONS TO APPROVED GROUND, SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. 26.COORDINATE ALL WORK WITH CONSTRUCTION SPECIFICATIONS OF THIS PROJECT. 27.TEST AND INSPECTION: A. AT THE TIME OF FINAL INSPECTION, TEST ALL CONNECTIONS TO PANELBOARDS, BETWEEN CONDUCTORS AND GROUND AS RECOMMENDED BY THE NATIONAL ELECTRICAL CODE. B. THE CONTRACTOR SHALL FURNISH THE INSTRUMENTS FOR MAKING THESE TESTS. TESTS SHALL BE CONDUCTED IN THE PRESENCE OF AUTHORIZED CONSTRUCTION ENGINEER. C. THE CONTRACTOR SHALL CORRECT AT OWN COST ANY EQUIPMENT OR SYSTEMS THAT DO NOT TEST SATISFACTORILY 28.THE CONTRACTOR SHALL FIELD INVESTIGATE THE SOURCE OF THE ELECTRICAL CIRCUITS. IF ADDITIONAL CIRCUITS ARE REQUIRED, USE SPARE CIRCUIT FROM THE SAME PANEL. IF NO SPARES ARE AVAILABLE, INSTALL 20A CIRCUIT BREAKER IN THE PANEL & RUN FIXTURES. BALANCE THE LOADS IN EACH PHASE OF THE PANEL AS MUCH AS PRACTICAL. FLUORESCENT LIGHTING FIXTURE, RECESSED IN CEILING, DRAWN TO SCALE. "a" OUTER LAMPS SWITCHED BY Sa, "b" -INNER LAMPS SWITCHED BY Sb LIGHTING FIXTURE ON EMERGENCY CIRCUIT FLUORESCENT LIGHTING FIXTURE, SURFACE OR PENDANT MOUNTED 6a ABOVE COUNTER TOP AFF ABOVE FINISHED FLOOR AF AMPERE FRAME AIC AT BKR AMPERES INTERRUPTING CAPACITY AMPERE TRIP BREAKER HORN/STROBE LIGHT COMBINATION (EXTERNAL), 80" AFF (MIN), 96" AFF (MAX) HL HORN/STROBE LIGHT COMBINATION (INTERNAL), 80" AFF (MIN), 96" AFF (MAX) F MANUAL PULL STATION 48"AFF C CONDUIT SD SMOKE DETECTOR CEILING MOUNTED PHOTOELECTRIC TYPE CKT CIRCUIT CO CONDUIT ONLY EMH ELECTRICAL MANHOLE (EOL) END OF LINE RESISTOR ENCL ENCLOSURE FACP FIRE ALARM CONTROL PANEL FDR FEEDER FS FLOW SWITCH 3 #18 AWG, CLASS 2 CABLE FOR LOW VOLTAGE WIRING IN 1/2" C GFP, GFI GROUND FAULT PROTECTION G, GND GROUND, GROUNDING CONDUIT AND WIRE HOMERUN TO PANEL & CIRCUITS AS NOTED ON FLOOR PLAN GRS GALVANIZED RIGID STEEL CONDUIT HH HANDHOLE HP HORSEPOWER HZ HERTZ IDF INTERMEDIATE DISTRIBUTION FRAME IMC INTERMEDIATE METAL CONDUIT KVA KILOVOLT AMPERE LCP LIGHTING CONTROL PANEL MCC MOTOR CONTROL CENTER MDB MAIN DISTRIBUTION BOARD MH MANHOLE 2c#16 AWG F2 2c#14 AWG CONDUIT CONCEALED, OR IN CEILING SPACE CONDUIT UNDERGROUND 2#12 1/2"C 3#12 1/2"C 4#12 1/2"C 5#12 1/2"C CEILING MOUNTED PASSIVE INFRARED DUAL TECHNOLOGY OCCUPANCY SENSOR SIMILAR TO SENSOR SWITCH WV-PDT OR EQUAL UNO CENTER LINE HEAT DETECTOR -COMBINATION FIXED TEMP/RATE-OF-RISE F1 LPB-2,4,6 6#12 1"C #10 OR OTHER AWG ADJACENT TO HASHMARKS INDICATES A WIRE SIZE OTHER THAN #12AWG. SEE NEC FOR MINIMUM CONDUIT SIZES, TABLE 310-16. 7#12 1"C MTG, MTD MOUNTING, MOUNTED MV FEEDER NAME. MV DENOTES MEDIUM VOLTAGE NEMA NATIONAL ELECTRICAL MANUFACTURER ASSOCIATION TXC POWER EQUIPMENT NAME. TXC DENOTES TRANSFORMER DESIGNATION PA PUBLIC ADDRESS PATC PUBLIC ADDRESS TERMINAL CABINET PB PULLBOX PP POWER PANEL PVC POLYVINYL CHLORIDE JUNCTION BOX RMC RIGID METALLIC CONDUIT RECEPTACLE DUPLEX 3-WIRE GROUNDING TYPE, NEMA 5-15R, 120VAC FLUSH WALL MOUNTED AT 15"AFF UNO RPS REMOTE POWER SUPPLY SDBC SW UG SOFT DRAWN BARE COPPER SWITCH UNDERGROUND UNO UNLESS NOTED OTHERWISE V VOLT WP XFMR WEATHERPROOF TRANSFORMER LED EXIT SIGN WITH EMERGENCY BATTERY BACK-UP ARROWS AS SHOWN ON FLOOR PLAN. LIGHTING FIXTURE DESIGNATION, SEE LIGHTING FIXTURE SCHEDULE. LETTER INDICATES FIXTURE TYPE PER FIXTURE SCHEDULE, NUMBER INDICATES TOTAL INPUT WATTS PER FIXTURE. J ACT HL SINGLE POLE WALL MOUNTED PASSIVE INFRARED TECHNOLOGY OCCUPANCY SENSOR MOUNTED 48" MAX AFF. SIMILAR TO SENSOR SWITCH WSD OR EQUAL UNO L1 60 AMPERE L TOGGLE SWITCH 120/277V 20A SINGLE POLE SINGLE THROW UNO. MOUNTED AT 48" MAX ABOVE FINISHED FLOOR. ab = SWITCHING 3 = 3-WAY M = MANUAL STARTER OC A, AMP STROBE LIGHT MOUNTED 80" AFF (MIN.), 96" AFF(MAX) HD 22.ALL PENETRATIONS OF FLOORS AND WALLS SHALL BE FIRE STOPPED IN ACCORDANCE WITH NEC AND NFPA. 24.THE ELECTRICAL CONTRACTOR SHALL COORDINATE ALL MOUNTING HEIGHTS FOR SWITCHES, RECEPTACLES, WALL MOUNTED LIGHT FIXTURES AND TELEPHONE OUTLETS BY THE USE OF THE ARCHITECTURAL AND ENGINEERING DRAWINGS. SHOULD ANY CONFLICTS BECOME APPARENT, THE CONTRACTOR SHALL REQUEST CLARIFICATION PRIOR TO INSTALLATION. IF THE WORK IS NOT COORDINATED, ANY REMEDIAL WORK SHALL BE DONE AT NO ADDITIONAL COST TO THE OWNER. MOTOR WITH FLEXIBLE CONDUIT CONNECTION "15" - HORSE POWER MAIN FIRE ALARM CONTROL PANEL (EXISTING SIMPLEX SYSTEM) POWER TRANSFORMER RATINGS AS NOTED 21.OPENINGS IN EXISTING BUILDING STRUCTURE FOR PASSAGE OF CONDUITS/CABLES SHALL NOT BE CUT UNTIL THE CONTRACTOR HAS ASKED FOR AND RECEIVED WRITTEN APPROVAL FROM THE ARCHITECT. 23.CONDUCTORS SHALL BE INSTALLED CONTINUOUS BETWEEN DEVICES, WITH SPLICES LOCATED ONLY IN JUNCTION BOXES OR IN CABINETS. CONDUCTORS SHALL BE OF SUFFICIENT LENGTH TO REACH THE FARTHEST TERMINAL IN PANELS. A MINIMUM OF 6" LOOPS SHALL REMAIN WHERE CONNECTIONS OR TAPS ARE TO BE MADE IN BRANCH CIRCUIT WIRING. FACP ABBREVIATIONS T RECEPTACLE QUAD 3-WIRE GROUNDING TYPE, NEMA 5-15R, 120VAC FLUSH WALL MOUNTED AT 15"AFF UNO RECEPTACLE APPLETON PLUG, 125VAC, 20A FLUSH WALL MOUNTED AT 15"AFF UNO THERMOSTAT BY MECHANICAL Aptos, California 95003 2 ADDENDUM #12 04/11/13 BID SET A. HERNANDEZ R. FEE RECEPTACLE QUAD 3-WIRE GROUNDING TYPE, NEMA 5-15R, 120VAC FLUSH FLOOR MOUNTED RECEPTACLE APPLETON PLUG, 125VAC, 20A FLUSH FLOOR MOUNTED 1/8" = 1'-0" 2 RECEPTACLE 3-WIRE GROUNDING TYPE, NEMA 5-15R, 120VAC FLUSH CEILING MOUNTED LIGHTING PANELS SURFACE MOUNTED POWER PANELS SURFACE MOUNTED DATA OUTLET FLUSH WALL MOUNTED AT 15" AFF UNO 4015839 DEMO NOTES: 2 CONTRACTOR SHALL VERIFY ABATEMENT CONTRACTOR HAS COMPLETED HIS SCOPE OF WORK BEFORE PROCEEDING. CONTRACTOR SHALL REMOVE RECEPTACLES, LIGHT FIXTURES, LIGHT SWITCHES, TELE/DATA OUTLETS AND FIRE ALARM DEVICES ALONG WITH CONDUIT AND WIRES BACK TO SOURCE. EXISTING PANELS R6C AND R6D ARE TO BE REMOVED, CLEANED AND REUSED. SHEET NOTES: 5 3 2 J 1 CONNECT TO HVAC EQUIPMENT, SEE MECHANICAL DRAWINGS FOR EXACT LOCATION AND ADDITIONAL INFORMATION. 2 RECEPTACLE AND TELEPHONE OUTLET TO BE INSTALLED ON THE COUNTERTOP, SEE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION. 3 PROVIDE 1"CO WITH PULL WIRE UP TO ACCESSIBLE CEILING SPACE, COMMUNICATIONS WIRES BY OTHERS. 4 FLOOR MOUNTED RECEPTACLES WITH SHUNT TRIP BREAKER. EYE WASH WATER FLOW SHALL TRIP BREAKER FOR FLOOR RECEPTACLES. SEE DETAIL 2 ON SHEET E-205 FOR REFERENCE. 5 WALL MOUNTED POWER STRIP AT 36" AFF. 6 4" SQUARE J-BOX FOR WI-FI SYSTEM. PROVIDE 1"CO WITH PULL ROPE TO MAIN UNIT, COORDINATE WITH OWNER'S REPRESENTATIVE FOR EXACT LOCATION. 7 EMERGENCY PUSH BUTTON FOR POWER AND GAS SHUT-OFF AT INSTRUCTION BENCH CABINET. ALLEN BRADLEY 800P MODEL. 6 EF 1 EF 2 J 1 J Aptos, California 95003 4 2 J P J MAU 2 7 2 ADDENDUM #12 04/11/13 BID SET MAU 1 J P 2 7 2 P 7 J A. HERNANDEZ R. FEE J 6 6 2 1/8" = 1'-0" R6C R6D 4015839 L4 4.7 L1 27 4 1 2 2 OC OC LECTURE 612 OC OC L2 62 Aptos, California 95003 L3 20 OC OC 2 2 OC 2 2 OC 04/11/13 BID SET 2 OC ADDENDUM #12 L3 20 OC 3 L2 62 2 2 A. HERNANDEZ CLASSROOM 607 R. FEE SHEET NOTES: 2 OC OC OC OC 2 1 REFER TO SHEET E-200 FOR LIGHTING FIXTURE SCHEDULE. 2 FIXTURE WITH EMERGENCY BATTERY BACK-UP. 3 OCCUPANCY SENSORS/CONTROLS TO BE INTEGRATED TO EXISTING LIGHTING CONTROL SYSTEM. 4 EXISTING LIGHTING FIXTURES TO BE REMOVED AND RELOCATED. CONTRACTOR TO CLEAN FIXTURES, RE-LAMP AS NECESSARY AND RE-WIRE TO NEW LOCATION. 1/8" = 1'-0" 4015839 674 GENERAL NOTES 16 3 S-101 (E) 3 X JOISTS (E) TRUSS D NOTE: LOCATE OPENING TO BEST CLEAR DUCTS AND EQUIPMENT (E) SOLID BLOCKING Site Condition: The Contractor shall examine and check all existing conditions, dimensions, levels and material and notify the Architect any discrepancies. Glulaminated Beams: Glulaminated beams shall be Douglas Fir, 1 12 " laminations, combination 24F-V4 (Fb ten = 2400 psi; Fb comp = 1200 psi; Fv = 165 psi; F = 650 psi; E = 1,800,000 psi) for single span beams and 24F-V8 (Fb ten = 2400 psi; Fb comp = 2400 psi; Fv = 165 psi; F = 650 psi; E = 1,800,000 psi) for multi-span or cantilever beams, with exterior glue unless noted. Fabricate in accordance with AITC 117-84 MANUFACTURING, Chapter 23A of the California Building Code, 2010 Edition (Title 24), and California Building Code Standards. All beams shall be Industrial appearance grade unless noted otherwise. All structural glued laminated timber shall be continuously inspected during fabrication by an inspector specifically approved by the Division of the State Architect (DSA). An AITC Certificate will not meet this requirement. (E) 3 X 16 CEILING JOISTS @ 24" O.C. (E) 2 X6 SILL 2 S-101 2 S-101 (E) CONC. BEAM CENTER LINE 6 - SDS 1/4 -6 END OF ADDED GL Lumber: Lumber shall be Douglas Fir No. 1 S4S for 4x and smaller and Douglas Fir No.1 for 6x and larger unless otherwise shown. Pieces with serious defects shall be discarded. All lumber shall be kiln dried to a maximum moisture content of 12% or less prior to delivery to the job site. Plywood shall be APA STRUCT I in accordance with U.S. Comercial Standard PS1. 2 ADD 3 1/8" X 12 GL TO (E) 3 X 16 EACH SIDE OF NEW OPENING Light Gage Steel Framing: Light gage steel studs, joists and accessories shall conform to AISI S200-07, North American Standard for Cold-formed Steel framing - General Provisions and AISI S100-07 North American Specifications of Cold-formed Steel Structural Members. Member sizes shall be of a depth as noted on the drawings and of a gage necessary to resist 25 psf wind loads for exterior walls and 5 psf for interior walls with a maximum deflection of L/240. Do not use less than 20 gage members for interior walls and 18 gage members for exterior walls. Submit shop drawings including typical details and fasteners and calculations for the review of the Structural Engineer prior to fabrication. 6" 3" 6" 28'-0" E 6" NEW ACCESS OPENING ADD 3 1/8 X 15 GL TO (E) 3 X 16 EACH SIDE OF OPENING WITH HU325 /12 HANGER EACH END DETAIL 4 S-101 1 1/2" = 1'-0" - 2 Nailing: Nailing shall be common wire nails, galvanized when exposed to the exterior. Subdrill where there fastening to existing lumber or where there is danger of splitting. See Nailing Schedule and CBC Table 2304.9.1 for size and spacing unless noted otherwise. ADD HU316, TYPICAL @ CUT JOISTS (E) CMU WALL BELLOW Bolts: (E) CONCRETE BEAM BELLOW Bolt holes in wood shall be 1/16 inch oversize. Washers shall be used on all bearings of heads and nuts against wood. Washers shall be standard plain washers except as otherwise noted. Bolts shall conform to ASTM A-307. Bolts, nuts and washers shall be galvanized where exposed to the weather. F Wedge Anchors NAILING SCHEDULE All masonry anchor bolts of the expansion type (loaded in either pullout or shear), shall be proof tested in tension to twice the allowable tension load. Wedge anchors to be Hilti Kwik-Bolt 3 per ICBO Report No. ESR-1385 re-issued February 1, 2010 or equal. Minimum Proof Load Tests Values and Embedments Direct Pull-Out Tension Torque Wrench-Torque 1250# 15 ft-# 1500# 25 ft-# 2100# 65 ft-# Embedments 2 1/4" 3 1/4" 4" Bolt Tightening: All nuts shall be tightened when placed and retightened at completion of project or immediately before finishing construction work which will make them inaccessible. 2 4 (CBC TABLE 2304.91) CONNECTION Size 3/8" dia. 1/2" dia. 5/8"dia. 2 S-101 COMMON WIRE NAILS PARTIAL CEILING FRAMING PLAN Joists or rafters to sides of studs: Eight (8) inch joists or less For each add'l four (4) inches in depth of joist 3- 16d 1- 16d Joists or rafters at all bearings: Toe nails, each side Ceiling joists, laps over partitions, face nail Ceiling joists to parallel rafters, face nail Ceiling joists to Top plate, Toe nail 2- 10d* 3- 16d 3- 16d 3- 8d 1 S-101 1/4" = 1'-0" Aptos, California 95003 (E) 3 X JOISTS 2 04/11/13 2 Tapcon Anchors: Tapcon anchors per ICC ESR-1671, re-issued August 1, 2012. Stud Walls: Horizontal solid 2x blocking shall be installed in all walls and partitions where studs are greater than 8' in height. Stud walls supporting beams shall have posts under bearing unless otherwise noted. Double Plates: Double plates shall lap a minimum of four feet at splices and be nailed with no less than 10 - 16d nails each side of spice except as otherwise noted or shown. All cuts in plates shall occur over a bearing. Cutting: Cutting & drilling of joists and beams for pipes shall not be permitted without the approval of the Engineer. Framing Anchors: Joist hangers, sheet metal framing clips and angles shall be as manufactured by Simpson Strong Tie Company or equal. Special Inspections: The following special inspections, as required by Section 1704A of the California Building Code, 2010 Edition, shall be provided during construction on the following types of work. The Contractor shall make arrangements for such tests, inspections and approvals with an independent testing laboratory or entity acceptable to the Owner. The Owner shall bear costs of the test and/or inspections. A. Glulam beams, per Section 1704.6.2.1. Blocking between joists or rafters: To joist or rafters - Toe nails each side each end To joist or rafters - Toe nails, each side To top plate, Toe nail 2- 10d* 2- 10d* 3- 8d Blocking between studs, each end 2- 10d toe nails or 2-16d Bridging to joist, toe nail, each end Sole plate to joist or blocking, face nail Top plate to studs, end nail 2x6 Studs and Smaller 2x8 Studs and Larger ADD 3 1/8" GL WITH (2) SDS 1/4 -6 SCREWS @ 24" O.C. 2- 8d 16d @ 16" o.c. 2- 16d unless noted DETAIL 3- 16d 2-16d Endnails or 4-8d Toe-nails, U.N. 3-16d Endnails or 4-8d Toe-nails, U.N. Doubled studs, face nail 16d @ 24" o.c. Top plates laps and intersections, face nail Double top plates, face nail Built-up corner studs 2-16d 16d @ 16" o.c. unless noted 16d @ 24" o.c. Rim Joist to top plate, Toe nail 8d @ 16" o.c. Built-up girder and beams 01-113103 2 S-101 1 1/2" = 1'-0" Stud to sole plate 2x6 Studs and Smaller 2x8 Studs and Larger Continuous header to stud, toe nail All construction not specifically detailed shall be built to conform with similar construction shown and the requirements of the California Building Code, 2010 Edition (Title 24). BID SET - IL C L (E) TRUSS 3" 6" SH (E) PLY SPLICE PLATE, REMOVE AS NECESSARY TO INSTALL GL AS NOTED CENTER LINE 4 - SDS 1/4 -6 4-8d 20d @ 32" o.c. at top and bottom and staggered; 2-20d at ends and at each splice; 2-20d at each bearing. NOTES: *When possible, nails driven perpendicular to the grain shall be used instead of toe nails. 2 ADDED 3/8" x 6" x 12" PLY SHIM ONE SIDE WITH 6-8d TO GLUMLAM ON SIDE ADDED 3 1/8" GL WITH HU 48 MAX. HANGER, PRE-DRILL FOR NAILS, PROVIDE 3/8" PLY SHIM ON SIDE DETAIL 3 S-101 1 1/2" = 1'-0" (E) 3X JOISTS NOTCHED @ TRUSS BOTTOM CHORD, TYP. (E) 2- 4X8 TRUSS BOTTOM CHORD - 4015839