International Journal of Engineering Trends and Technology (IJETT) - Volume4Issue5- May 2013 A Control Scheme to Enhance Power Productivity Using Static Synchronous Condenser for Wind Energy System PREMDEEP A1, RASOOL AHEMMED2 1 EEE KL UNIVERSITY, INDIA 2 AsstProfessor, EEE KL University, INDIA Abstract—Power we gain from wind energy system is not constant because of the fluctuations of wind and it won’t be in phase with the grid load power. This may affect the power productivity. The power quality and wind turbine performance are measured on the basis of measurements and norms being specified in international-technical Commission standard.Injection of the active power, reactive power, variation of voltage, flicker, harmonics, and electrical behavior of switching operations that are measured as per the national/international guidelines. The paper mainly concerns about the power stability problem due to wind turbine installation with the grid. In this scheme a static synchronous compensator is connected at a common coupling with a battery energy storage system (BESS) to lessen the power productivity issues. The BESS is integrated to sustain the real power source under fluctuating wind power. The static synchronous compensator control scheme for wind energy system for power quality improvement is simulated using MATLAB/SIMULINK in power system block set. The proposed scheme lessens the effect of reactive power demand of the load on the main supply source and on the induction generator. The control scheme for power productivity improvement and grid coordination rule been presented are as per IEC-standard. Index Terms—International electro-technical commission (IEC), power quality, wind generating system (WGS). I. INTRODUCTION In order to enhance the utilization of conventional renewable Energy resources like wind, biomass, hydro, co-generation, etc. In sustainable energy system, energy conservation and the use of renewable source are the key paradigm. The need to integrate the renewable energy like wind energy into power system is to make it possible to minimize the environmental impact on conventional plant. The integration of wind energy into existing power system presents a technical challenges and that requires consideration of voltage regulation, stability, power quality problems. The power quality is an essential customer-focused measure and is greatly affected by the operation of a distribution and transmission network. The issue of power quality is of great importance to the wind turbine. The main criteria that being concerned is the power factor we need the unity power factor in order to maintain the synchronization along source and load side for constant power flow. ISSN: 2231-5381 The individual units can be of large capacity up to 3 MW, feeding into distribution network, particularly with customers connected in close proximity. In the fixed-speed wind turbine operation, all the fluctuation in the wind speed are transmitted as fluctuations in the mechanical torque, electrical power on the grid and leads to large voltage fluctuations. During the normal operation, wind turbine produces a continuous variable output power. These power variations are mainly caused by the effect of turbulence, wind shear, and tower-shadow and of control system in the power system. Thus, the network needs to manage for such fluctuations. The power quality issues can be viewed with respect to the wind generation, transmission and distribution network, such as voltage sag, swells, flickers, harmonics etc. However the wind generator introduces disturbances into the distribution network. One of the simple methods of running a wind generating system is to use the induction generator connected directly to the grid system.However; induction generators require reactive power for magnetization. When the generated active power of an induction generator is varied due to wind, absorbed reactive power and terminal voltage of an induction generator can be significantly affected. A proper control scheme in wind energy generation system is required under normal operating condition to allow the proper control over the active power production. In the event of increasing grid disturbance, a battery energy storage system for wind energy generating system is generally required to compen- sate the fluctuation generated by wind turbine. A STATCOMbased control technology has been proposed for improving the power quality which can technically manages the power level associates with the commercial wind turbines. The proposed STATCOM control scheme for grid connected wind energy generation for power quality improvement has following objectives. The paper is organized as follows. The Section II introduces the power quality standards, issues and its consequences of wind turbine. The Section III introduces the grid coordination rule for grid quality limits. The Section IV describes the topology for power quality improvement. The Sections V, VI, VII describes the control scheme, system performance and conclusion respectively. http://www.ijettjournal.org Page 1553 International Journal of Engineering Trends and Technology (IJETT) - Volume4Issue5- May 2013 II. P O W E R QUALITY STANDARDS, ISSUES AND ITS CONSEQUENCES A. International Electro Technical Commission Guidelines The guidelines are provided for measurement of power quality of wind turbine. The International standards are developed by the International Electro-technical Commission (IEC), IEC standard 61400-21, describes the procedure for determining the power quality characteristics of the wind turbine [4]. The standard norms are specified. 1) IEC 61400-23: Wind turbine generating system, part-21. Measurement and Assessment of power quality characteristic of grid connected wind turbine 2) IEC 61400-15: Wind Turbine—measuring procedure in determining the power behavior. 3) IEC 61400-3-5: Assessment of emission limit for fluctuating load IEC 61400-12: Wind Turbine performance. The data sheet with electrical characteristic of wind turbine provides the base for the utility assessment regarding a grid connection. B. Voltage Variation The voltage variation issue results from the wind velocity and generator torque. The voltage variation is directly related to real and reactive power variations. The voltage variation is commonly classified as under: • Voltage Sag/Voltage Dips. • Voltage Swells. • Short Interruptions. • Long duration voltage variation. The voltage flicker issue describes dynamic variations in the network caused by wind turbine or by varying loads. Thus the power fluctuation from wind turbine occurs during continuous operation. The amplitude of voltage fluctuation depends on grid strength, network impedance, and phase-angle and power factor of the wind turbines. It is defined as a fluctuation of voltage in a frequency 10–35 Hz. C. Harmonics The harmonic results due to the operation of power electronic converters. The harmonic voltage and current should be limited to the acceptable level at the point of wind turbine connection to the network. To ensure the harmonic voltage within limit, each source of harmonic current can allow only a limited contribution, as per the IEC-61400-35 guideline. The rapid switching gives a large reduction in lower order harmonic current compared to the line commutated converter, but the output current will have high frequency current and can be easily filter-out. ISSN: 2231-5381 D. Self-Excitation of Wind Turbine Generating System The self-excitation of wind turbine generating system (WTGS) with an asynchronous generator takes place after disconnection of wind turbine generating system (WTGS) with local load. The risk of self-excitation arises especially when WTGS is equipped with compensating capacitor. The capacitor connected to induction generator provides reactive power compensation. E. Consequences of the Issues The voltage variation, flicker, harmonics causes the malfunction of equipment’s namely microprocessor based control system, adjustable speed drives. It may leads to tripping of protection devices and may stop the process and even can damage of sensitive equipment. Thus it degrade the power productivity in the grid. III. GRID COORDINATION RULE The American Wind Energy Association (AWEA) led the effort for adoption of the grid code for the interconnection of the wind plants to the generating system. The first grid code was focused on the distribution level, later it took a stand in developing its own grid code for contributing to a stable grid operation. The rules for realization of grid operation of wind generating system at the distribution net- work are defined According to Energy-Economic Law, the operator of transmission grid is responsible for the organization and operation of interconnected system. 1) Voltage Rise (u): The voltage rise at the point of common coupling can be approximated as a function of maximum ap- parent power S m a x of the turbine, the grid impedances R and X at the point of common coupling and the phase angle Φ, given in (1) Δu = Smax (Rcos sin ) /U2 ……. (1) Where Δ u —voltage rise, S m a x … Apparent power, Φ—phase difference, U—is t h e n om i n a l vol t a ge o f g r i d. The Limiting voltage rise value is ≤ 2. 2) Voltage Dips (d): The voltage dips is due to startup of wind turbine and it causes a sudden reduction of voltage. It is the relative % voltage change due to switching operation of wind turbine. The decrease of nominal voltage change is given in (2). d = Ku . Sn/ Sk …. (2) Where d is relative voltage change, Sn rated apparent power, Sk short circuit apparent power, and Ku sudden voltage reduction factor. The acceptable voltage dips limiting value is ≤ 3%. http://www.ijettjournal.org Page 1554 International Journal of Engineering Trends and Technology (IJETT) - Volume4Issue5- May 2013 3) Flicker: The measurements are made for the maximum no.of specified switching operation of wind turbine with 10 min period and 2-h period are specified in (3). PLT = C (ΨK) …..(3) Where PLT is long term flicker, C (ΨK) is flicker coefficient calculated from Rayleigh distribution of the wind speed. The boundary for flicker coefficient is < 0.4 for avg time of 2h. 4) Harmonics: The harmonic distortion is assessed for variable speed turbine with an electronic power converter at the point of common connection [9]. The total harmonic voltage distortion of voltage is given as in (4): VTHD = ∑ 100……… (4) Fig. 1. Grid connected system for power quality improvement. Where Vn is the nth harmonic voltage and is the fundamental frequency (50) Hz. The THD limit for 132 KV is < 3%. THD of current ITHD is given as in (5) ITHD= ∑ 100……. (5) Where IN is the nth harmonic current and I1 is the fundamental frequency (50) Hz. The THD of current and limit for 132 KV is < 2.5%. IV. TOPOLOGY FOR POWER QUALITY IMPROVEMENT The STATCOM based current control voltage source inverter injects the current into the grid in such a way that the source current are harmonic free and their phase-angle with respect to source voltage has a desired value. Thus it improves the power factor and the power quality. To accomplish these goals, the grid voltages are sensed and are synchronized in generating the current command for the inverter. The proposed grid connected system is implemented for power quality improvement at point of common coupling (PCC), as shown in Fig. 1. The grid connected system in Fig. 1, consists of wind energy generation system and battery energy storage system with STATCOM. A. Wind Energy Generating System Wind generations are based on constant speed topologies with pitch control turbine. The induction generator is used in the proposed scheme because of its simplicity, it does not require a separate field circuit, it can accept constant and variable loads, and has natural protection against short circuit. The available power of wind energy system is presented as PWIND = ƿ . ISSN: 2231-5381 Where ƿ (kg/m3) is the air density and A (m2) is the area swept out by turbine blade, Vwind is the wind speed in mtr/s. It is not possible to extract all kinetic energy of wind, thus it extract a fraction of power in wind, called power coefficient Cp of the wind turbine, and is given in (7). Pmech = Cp .Pwind……… (7) Where Cp is the power coefficient, depends on type and operating condition of wind turbine. This coefficient can be express as a function of tip speed ratio λ and pitch angle ϴ. The mechanical power produce by wind turbine is given in (8) Pmech = ½ Ƿ II R2 V3 wind Cp …. (8) Where R is the radius of the blade in meters. B. BESS-STATCOM The battery energy storage system (BESS) is used as an energy storage element for the purpose of voltage regulation. Since it rapidly injects or absorbed reactive power to stabilize the grid system. It also control the distribution and transmission system in a very fast rate. When power fluctuation occurs in the system, the BESS can be used to level the power fluctuation by charging and discharging operation. The battery is connected in parallel to the dc capacitor of STATCOM [10]–[14]. The STATCOM is a three-phase voltage source inverter having the capacitance on its DC link and connected at the point of common coupling. The STATCOM injects a compensating current of variable magnitude and frequency component at the bus of common coupling. C. System Operation The shunt connected STATCOM with battery energy storage is connected with the interface of the induction generator and non-linear load at the PCC in the grid system. The STATCOM compensator ou t p ut i s va r i e d a c c or d i n g t o t h e c on t r ol l e d http://www.ijettjournal.org Page 1555 International Journal of Engineering Trends and Technology (IJETT) - Volume4Issue5- May 2013 as sample tem- plate Vsm, sampled peak voltage, as in (9). 1/2 Vsm = { ( + + )} ………. (9) Voltage and the RMS value of unit vector usa,usb,usc as shown in (10). usa = usb = usc = ……. (10) In-phase unit voltage template as, in (11) i*Sa= I.uSa Fig. 2. System operational scheme in grid system. i*Sb= I.uSb i*Sc= I.uSc ……. (11) Where I is proportional to magnitude of filtered source voltage for respective phases. This ensures that the source current is controlled to be sinusoidal. The unit vectors implement the important function in the grid connection for the synchronization for STATCOM. This method is simple, robust and favorable as compared with other methods [18]. B. Bang-Bang Controller Bang-Bang current controller is implemented in the current control scheme. The reference current is generated as in (10) and actual current are detected by current sensors and are subtracted for obtaining a current error for a hysteresis based bang-bang controller. Thus the ON/OFF switching signals for IGBT of STATCOM are derived from hysteresis controller [19]. The switching function SA for phase ‘a’ is expressed as (12). Fig. 3. Control system scheme iSa ˂ ( isa* - HB) → SA=0 Strategy, so as to maintain the power quality norms in the grid iSa > ( isa* - HB) → SA=1………. (12) system. The current control strategy is included in the control scheme that defines the functional operation of the STATCOM Where HB is a hysteresis current-band, similarly the switching compensator in the power system to the nonlinear load in the function SB, SC can be derived for phases “b” and “c”. VI. SYSTEM P ERFORMANCE grid system. The main block diagram of the system operational scheme is shown in Fig. 2. The proposed control scheme is simulated using SIMULINK in power system block set. The system parameter for given V. CONTROL SCHEME system is given Table I. The system performance of proposed system under dynamic The control scheme approach is based on injecting the cur- condition is also presented. rents into the grid using “bang-bang controller.” The controller uses a hysteresis current controlled technique. Using such tech- A. Voltage Source Current Control—Inverter Operation nique, the controller keeps the control system variable between The three phase injected current into the grid from boundaries of hysteresis area and gives correct switching sig- STATCOM will cancel out the distortion caused by the nonnals for STATCOM operation as shown in Fig.3. linear load and wind generator. The IGBT based three-phase The control algorithm needs the measurements of several inverter is connected to grid through the transformer. The genvariables such as three-phase source current isabc.. DC voltage eration of switching signals from reference current is simulated Vdc, inverter current iiabc with the help of sensor. The current within hysteresis band of 0.08. The choice of narrow hysteresis control block, receives an input of reference current isabc* and band switching in the system improves the current quality. The actual current iSabc are subtracted so as to activate the operation control signal of switching frequency within its operating band, as shown in Fig. 4. of STATCOM in current control mode [16]–[18]. The choice of the current band depends on the operating voltage and the interfacing transformer impedance. The comA. Grid Synchronization. In three-phase balance system, the RMS voltage source am- pensated current for the nonlinear load and demanded reactive plitude is calculated at the sampling frequency from the power is provided by the inverter. The real power transfer from source Phase voltage (V sa, Vsb , Vsc) and is expressed, TABLE 1 SYSTEM PARAMETERS ISSN: 2231-5381 http://www.ijettjournal.org Page 1556 International Journal of Engineering Trends and Technology (IJETT) - Volume4Issue5- May 2013 TABLE 1 SYSTEM PARAMETERS S.No. Parameters Ratings 1. Grid Voltage 3-phase,415V,50 Hz 2. Induction Motor/Generator 3.35 kVA,415V,50 Hz, P=4, Speed=1440rpm,Rs=0.01Ω, Rr=0.015Ω,Ls=0.06H,Lr=0.06H 3. Load Parameter Non-linear Load 25kw 4. Inverter Parameters DC Link Voltage = 800V, DC link Capacitance=100µF, Switching frequency = 2 kHz. 5. IGBT Rating Collector Voltage=1200v, Forward Current=50A, Gate voltage=20v. Fig. 4. Switching signal within a control hysteresis band The batteries is also supported by the controller of this inverter, C. STATCOM—Performance Under Load Variations The wind energy generating system is connected with grid having the nonlinear load. The performance of the system is measured by switching the STATCOM at time t = 0.7s in the system and how the STATCOM responds to the step change command for increase in additional load at 1.0 s is shown in the simulation. When STATCOM controller is made ON, without change in any other load condition parameters, it starts to mitigate for reactive demand as well as harmonic current. The dynamic performance is also carried out by step change in a load, when applied at 1.0 s. This additional demand is fulfill by STATCOM compensator. Thus, STATCOM can regulate the available real power from source. The result of source current, load current are shown in Fig. 5(a) and (b) respectively. While the result of injected current from STATCOM are shown in Fig. 5(c) and the generated current from wind generator at PCC are depicted in Fig. 5(d). Fig. 5. (a) Source Current. (b) Load Current. (c) Inverter Injected Current. (d) Wind generator (Induction generator) current. Thus the DC link along with the static synchronous condenser is provided for the supporting purpose in order to act in the both ways as to relive the main supply from the reactive power demand from the non-linear loads and also to support the back up power supply to the static synchronous condenser and also the main functionality of it is it injects the currents in to the point of common coupling in order to cancel out the harmonics that are being introduced by the non-linear loads in to the source at the point of common coupling as the control is being carried out the mechanism is been maintained by a microcontroller through its pulses in order to elimianate the harmonics the switching operation should be in a position to withstand the heavy dips and swells and also it provides the respective reactive power for the wind energy systen for its operation. Fig. 6. STATCOM output voltage. ISSN: 2231-5381 http://www.ijettjournal.org Page 1557 International Journal of Engineering Trends and Technology (IJETT) - Volume4Issue5- May 2013 REFERENCES [1] F. Zhou, G. Joes, and C. Abbey, “Voltage stability in weak connection wind farm,” in IEEE PES Gen. Meeting, 2005, vol. 2, pp. 1483–1488. [2] T . Kinjo and T. Senjyu, “Output leveling of renewable energy by electric double layer capacitor applied for energy storage system,” IEEE Trans. Energy Conv., vol. 21, no. 1, Mar. 2006. [3] R. S. Bhatia, S. P. Jain, D. K. Jain, and B. Singh, “Battery energy storage system for power conditioning of renewable energy sources,” In Proc. Int. Conf. Power Electron Drives System, Jan. 2006, vol. 1, pp. 501–506. Fig. 7. Supply Voltage and Current at PCC. C. Power Quality Improvement It is observed that the source current on the grid is affected due to the effects of nonlinear load and wind generator, thus purity of waveform may be lost on both sides in the system. The inverter output voltage under STATCOM operation with load variation is shown in Fig. 8. The dynamic load does affect the inverter output voltage. The source current with and without STATCOM operation is shown in Fig. 9. This shows that the unity power factor is maintained for the source power when the STATCOM is in operation. The current waveform before and after the STATCOM operation is analyzed. The Fourier analysis of this waveform is expressed and the THD of this source current at PCC without STATCOM is 4.71%. The power quality improvement is observed at point of common coupling, when the controller is in ON condition. The STATCOM is placed in the operation at 0.7 s and source current waveform is shown in Fig. 11 with its FFT. It is shown that the THD has been improved considerably and within the norms of the standard. The above tests with proposed scheme has not only power quality improvement feature but it also has sustain capability to support the load with the energy storage through the batteries. [4] S. W. Mohod and M. V. Aware, “Grid power quality with variable speed wind energy conversion,” in Proc. IEEE Int. Conf. Power Electronic Drives and Energy System (PEDES), Delhi, Dec. 2006. [5] F u . S. Pai and S.-I. Hung, “Design and operation of power converter for micro turbine powered distributed generator with capacity expansion capability,” IEEE Trans. Energy Conv., vol. 3, no. 1, pp. 110–116, Mar. 2008. [6] J. Zeng, C. Yu, Q. Qi, and Z. Yan, “A novel hysteresis current control for active power filter with constant frequency,” Elect. Power Syst. Res., vol. 68, pp. 75–82, 2004. [7] M. I. Milands, E. R. Cadavai, and F. B. Gonzalez, “Comparison of control strategies for shunt active power filters in three phase four wire system,” IEEE Trans. Power Electron., vol. 22, no. 1, pp. 229–236, Jan.2007. VII. CONCLUSION This paper introduces the enhancement of power productivity using a static synchronous condenser based control scheme in wind energy system with nonlinear load. The operation of the control system acquired for wind energy system with static synchronous condenser for maintaining power quality is simulated in MATLAB/SIMULINK. It has an ability to set off the harmonic parts of the load current. It ensures the source voltage and load current are in-phase and aids the reactive power demand for the wind generator and load at PCC. Thus it gives a chance to improve the utilization factor of transmission lines. The integrated wind generation and static synchronous condenser with BESS have shown excellent performance. Thus the scheme proposed accomplishes the power productivity. ISSN: 2231-5381 http://www.ijettjournal.org Page 1558