International Journal of Engineering Trends and Technology (IJETT) – Volume 34 Number 6- April 2016 Harmonic Mitigation in Standalone PV System for Three Phase System J.Preethi#1, S.Purushotham*2 M.E- Power system engineering, Sonacollege of technology Salem,India Abstract-This paper presents an research and review of three types of filters to minimize harmonics distortion triggered in standalone PV system for three phase system.In order to achieve the certain filtering impact, it's important to incorporate different filtration system topologies generally these topologies can be split into two categories that happen to be series AC reactor and shunt passive filter such as tuned filters and high pass filters.This paper affords firstly the primary design and components of PV system, also portrays the reasons for harmonics and their belongings and gives the way to enhance power quality and to protect the equipment in our power system.The system which is proposed is validated by the simulation using Matlab/Simulink environment. I.INTRODUCTION The worldwide vitality interest is always expanding, and the toxin way of fossil energies has expanded the enthusiasm of the improvement of renewable energies.Solar energy vitality is ample around the world, and the most ideal approach to create power without contamination[I].We can utilize sun based PV frameworks for residential utilize and store overabundance power in batteries for later utilize this is a Standalone PV System, or food into the power lattice to decrease the power bill [2-3]. In standalone PV framework power electronic gear and non linear loads are broadly utilized and came about genuine consonant issues. Regularly, standalone PV framework is intended to work at frequencies of 50Hz..Albeit certain sorts of burdens produce current and voltage signal with frequencies that are number products of the 50Hz crucial recurrence. [4].These higher frequencies are called electrical contamination that is known as power system harmonics. Harmonics causes block to the typical operation of the hardware or the framework.Harmonics are produced by different reasons, for example, immersion, exchanging like thyristor/diode rectifiers, cyclo converters can interface antagonistically in the PV framework.It is basic to examine, evaluate and decrease these harmonics to a level which meets the IEEE 519-1992 standard .Countless topologies and separating systems are proposed in writing including passive, active and hybrid filters [6]. This paper concentrates on the examination and configuration of symphonious inactive channels for three phase standalone PV framework, single tuned channel for low order frequencies and high passive channel for high order frequencies [6-7].This work is composed as takes ISSN: 2231-5381 after segment I talks about to sum things up the demonstrating of the standalone PV frameworks; segment II portrays the inactive channels outline for the harmonic moderation in the standalone PV framework.Figure 1 demonstrates the piece chart of the proposed standalone framework PV module. Figure 1.Block diagram of PV System The framework involves a PV module containing various PV cells associated in arrangement to get a fancied DC voltage,a DC/DC help converter is utilized to produce a higher DC voltage, a DC/AC inverter is important to give an AC yield voltage.For the standalone application and non straight loads, Passive Filter must be utilized for harmonic alleviations. II.MODELING OF STAND ALONE PV SYSTEM A.PV cell Photovoltaic cell produces power by changing over daylight, because of the way that the voltage and current yield of a sign PV cell can be too little, PV cell is associated in arrangement or parallel mix to acquire the voltage and current level suitable for handy use.The PV cell can be demonstrated as a present source Iph in parallel with a diode, shunt resistor Rsh and arrangement Rs resistor as appeared in figure 2. http://www.ijettjournal.org Page 252 International Journal of Engineering Trends and Technology (IJETT) – Volume 34 Number 6- April 2016 The most regularly utilized files to evaluate voltage and current twists are voltage and current THD that can be figured as takes after. THDx = (5) where x can be the voltage or the current. Figure 2.Model of PV cell D. LC filter: By applying Kirchhoff's law in the proportional circuit of sun powered cell, the current created can be acquired as: I= - - (1) Where Iph is the light creating current which relies on upon the sunlight based irradiance, Id is the current moving through the diode which relies on upon the sun powered cell temperature; Ish is the current streaming in the comparable shunt resistance of the sun oriented cell [2]. =V+ I = (V + I )/ = [ exp( h -1)] (2) (3) (4) 2 . f. L. <0.03 (6) Where I_Lmax is the most extreme RMS (Root Mean Square) Load current, f is yield voltage frequency 50Hz and V_o is the RMS estimation of inverter yield voltage, the channel capacitance esteem C is then ascertained from the reverberation connection as given in: C= n :Ideality factor of p-n junction of cell. : Voltage across the diode. q : Electronic charge: 1.602 x C. K: Boltzmann's constant: 1,38x . T : Solar temperature . : short circuit current. (7) Where is cut off frequency. III.HARMONIC PASSIVE FILTER B. DC/DC Boost Converter: A. Three phase Non-linear load: A Boost converter is proposed and favored of DC/DC converter in the standalone PV framework since he can venture up little DC voltage delivered by PV board to a more elevated amount suitable for the DC/AC inverter [2]. C. Full-Bridge Inverter: Single stage Full-Bridge inverter is utilized to change over the DC yield voltage of the DC/DC Boost Converter into AC voltage required for an AC loads, in the standalone PV framework. Beat Width Modulation (PWM) is utilized to make legitimate gating signals for switches. The door signs are heartbeats gotten by contrasting a reference sinusoidal sign Vref and a triangular sign Vc[2-34]. When all is said in done, there is much harmonic part in yield inverter voltage, along these lines by picking a high estimation of the transporter recurrence encourages sifting of current and diminishes the consonant yield voltage yet control switches have a restricted time of conduction then it's important to discover a bargain, subsequently a LC channel is planned and used to channel the high frequency harmonic in yield inverter voltage. ISSN: 2231-5381 To diminish harmonics contained in yield inverter voltage and to make a perfect yield sinusoidal voltage the LC Low pass channel is utilized. It is set between the inverter and the heap in a standalone PV framework. The LC channel picked is a second request which dispenses with all high request harmonics; the channel inductance esteem L is computed such that the voltage drop over the inductor is under 3% of the inverter yield voltage Vo [2]. Three stage Non-straight loads comprising of parts, for example, rectifiers, lighting electronic stabilizer, bright lights create and infuse current and voltage Harmonics in the force framework. The principle issues are extra power misfortunes in the electrical hardware, mistakes in estimation. In this manner relief is required to keep up Power Quality and enhance vitality productivity and decrease the potential for gadget disappointment by utilizing Harmonic Passive channels [8]. B. Series-connected AC Reactor : Arrangement AC Reactor is constituted of an inductor associated in arrangement with the non straightloads, this sort of designs is considered as a low pass channel. Figure 3 outlines the fundamental arrangement of arrangement associated reactor in the force framework.It can pass low recurrence sounds and gives high impedance to high recurrence symphonious streams to limit their duplication into the power system.The value of this channel is in its ease, little size and gives no framework reverberation condition. The estimation of the inductor is set to a voltage drop of somewhere around 3% and 5% of the ostensible voltage of the system [9]. http://www.ijettjournal.org Page 253 International Journal of Engineering Trends and Technology (IJETT) – Volume 34 Number 6- April 2016 Figure 5. Simulation model of standalone PV system connected to three phase load with filter. Figure 3. Series AC reactor C. Shunt Passive Filters: Shunt Passive channels dependably been considered as a decent answer for take care of consonant current issues [10], shunt inactive channels can be ordered into three fundamental classifications as takes after: 1. Band pass filters 2. High pass filters 3. Composite filters. Shunt passives filters as shown in figure 4. The harmonic spectra and THD is analysed with no filter, with a series AC reactor and with composite filters. Figure 6 illustrates the output voltage of PV cell. Figure 6. Solar output Voltage Figure 7 Illustrates the voltage and current waveforms which is distorted without filter. a)Tuned filter b)High pass filter Figure 4. Shunt passive filters IV. SIMULATION RESULTS Figure 7: Output waveform without filter The standalone PV framework with passive filter associating with a full wave span rectifier with three stage non-direct load is proposed and mimicked utilizing Matlab/Simulink in this paper as appeared in figure 5, the simulation is carried out as series AC reactor alone, and mix of arrangement reactor and two single tuned channels to the third and fifth harmonics and a high pass channel to remunerate higher order harmonics.Thus the simulation is done using MATLAB. The detail models are given in the figures below. It includes the passive filter model and standalone PV system module connected to a three phase load. Figure 8 show the voltage and current waveform which is sinusoidal in nature. Figure 8: Output waveform with filter ISSN: 2231-5381 http://www.ijettjournal.org Page 254 International Journal of Engineering Trends and Technology (IJETT) – Volume 34 Number 6- April 2016 V.CONCLUSION This paper has exhibited a consonant moderation study in the framework, utilizing three sorts of latent channels in particular, arrangement reactor and shunt inactive channels: single tuned and high pass channels in eliminating harmonics. Line reactor offers the upside of his straightforwardness and ease it gives no framework reverberation condition and its can accomplish a noteworthy diminishment in harmonics however the aggregate consonant twisting can't be underneath to 5% that is the reason utilization of shunt latent channels was important to enhance framework quality. From the output shown above has been proved that harmonics can be reduced with greater extent using filters with the THD % of 4.4%. REFERENCES [I] N. Hadjsaid, "La distribution d'energieelectrique en presence deproductiondecentralisee", Edition Lavoisier, 2010. [2] Paras Karki, BrijeshAdhikary, "MATLAB/Simulink based modelling and simulation of gird-connected solar photovoltaic system in distribution power network," Fifth International Conference on Power and Energy Systems, Kathmandu, Nepal, 28 -30 October 2013. [3] A.z.M.S. Muttalib, S.M. Ferdous, AM. Saleque, N.M.A. Hasan, M.M.Chowdhury, "Design and simulation of an inverter with high frequency sinusoidal PWM switching technique for harmonic reduction in a standalonel utility grid synchronized photovoltaic system," IEEE Informatics, Electronics & Vision (lCIEV), International Conference, pp.1l68-1173, 18-19 May 2012. [4] A S. K. Chowdhury, M. S. Shehab, M. AAwal, M. A Razzak, "Design and implementation of a highly efficient pure sine-wave inverter for photovoltaic applications," IEEE Informatics, Electronics & Vision (lCIEV), International Conference, pp. 1-6, May 2013. [5] IEEE Standard 519-1992, "IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems", 1993. [6] M. Jayaraman, V.T. Sreedevi, R. Balakrishnan, "Analysis and design of passive filters for power quality improvement in standalone PV systems," Engineering (NUiCONE), Nirma University International Conference , pp.I-6, 28-30 Nov. 2013. [7] D.C. Bhonsle, R.B. Kelkar, "Harmonic pollution survey and simulation of passive filter using MATLAB,"Recent Advancements in Electrical, Electronics and Control Engineering (ICONRAEeCE), International Conference, pp.230-236, IS-17 Dec. 2011. [8] Z. A Memon, M. AUquaili, M. AUnar, "Harmonics mitigation of industrial power system using passive filters," Mehran University Research Journal of Engineering and Technology, vol. 31, no 2, p. 355360, April 2012. [9] M.F. Arman, "An 'Active' Passive-Filter Topology for Low Power DC/AC Inverters," Ph.D. Thesis, Dept. Elect. & Compo Eng., Brunei Univ.-London, UK, 2011. [10] S. Chun-Lien, H. Ci-Jhang, "Design of passive harmonic filters toenhance power quality and energy efficiency in ship power systems",IEEE 49th Industrial and Commercial Power System (l&CPS) Technical, pp. I -8, 2013. [11] J.c. Das, "Passive Filters-Potentialities and Limitations," IEEE Trans.on Industry Applications, Vol. 40, No. I, pp. 232-241, January 2004. [12] P. MATHAN MOHAN, G. AMUTHAN, "Comparative Evaluation of Various Single Phase Harmonic Filters for Non-Linear Load," IEEE International ConfrenceOn Advances In Engineering, Science And Management (ICAESM-2012), pp. 622-627, 30-31 March 2012. ISSN: 2231-5381 http://www.ijettjournal.org Page 255