NEW Series EMCRT Three-Phase Motor Reverser 480 Vac, Up to 7.5 kW

advertisement
NEW Series EMCRT
Three-Phase Motor Reverser
480 Vac, Up to 7.5 kW
FEATURES/BENEFITS
• Controls and reverses three-phase motors without direct third leg (two legs)
• IP20 touch-proof housing
• Up to 10hp motors
• Very high immunity components, 1600 Vpeak
• All solid-state components
• Built-in snubber and MOV
• Forward/Reverse display LED
Part Number
Description
EMCRT48D50
3x480 Vac 4kW Motor Reverser
EMCRT48D75
3x480 Vac 7.5 kW Motor Reverser
.17 (4.4)
MECHANICAL SPECIFICATION
3.26 (82.7)
.75 (19) .75 (19)
M4
2.99 (76)
Switch Type2
Line Voltage
Output Current – Amps
(Resistive)
1
1.57 (40)
Series
50
D
.90 (23)
48
M3.5
EMCRT
2.30 (58.4)
Part Number Explanation
NOTES
1) Line Voltage (nominal): 48 = 480 Vdc nominal
2) Switch Type: D = zero-cross turn-on
3.94 (100)
ELECTRICAL SPECIFICATIONS
(+25°C ambient temperature unless otherwise specified)
Min
Max
Units
Control Range12
30
Vdc
Input Current Range15
25
mAdc
Must Turn-Off Voltage
6
2.22 (56.5)
INPUT (CONTROL) SPECIFICATIONS
Vdc
Reverse Voltage
30
Vdc
Reversing Time (fixed)
70
ms
Protection Against Simultaneous Control Yes
LED
Yes
BLOCK DIAGRAM
1L1
-A2/B2
0V
3L2
5L3
Weight: 4.58 oz. (130g)
Forward Reverse
Figure 1
+B1
+A1
Control
logic
RC-MOV
protection
Insulation
(photocouplers)
2T1
4T2
6T3
Figure 2
© 2005 TELEDYNE RELAYS
(800) 284-7007 • www.teledynerelays.com
EMCRT Page EMCRT\102005\Q1
NEW Series EMCRT
Three-Phase Motor Reverser
480 Vac, Up to 7.5 kW
INTERNAL DIAGRAM FOR TWO-LEG MODELS
Forward
Reverse
LED
Common A2 –
Controls
/B2
Reverse
Insu
lation
Switch
RC network
1L1
~
Mains
or
load
2T1
~
Load
or
mains
3L2
~
Mains
or
load
4T2
~
Load
or
mains
5L3
~
Mains
or
load
6T3
~
Load
or
mains
VDR
Control lock
B1
+
Insu
Forward
RC network
Switch
lation
VDR
A1
+
Input circuit
Insu
lation
Insu
RC network
Switch
Switch
lation
RC network
VDR
L3-T3
depending
of models
VDR
Figure 3
ELECTRICAL SPECIFICATIONS
(+20°C ambient temperature unless otherwise specified)
GENERAL SPECIFICATIONS
(+20°C ambient temperature unless otherwise specified)
OUTPUT (LOAD) SPECIFICATIONS
ENVIRONMENTAL SPECIFICATIONS
Max
Units
24
24
520
550
Vac
Vac
Max
Units
–40
+100
°C
Storage Temperature
–40
+100
Input-Output Isolation
3300
Vrms
Output-Case Isolation
3000
Vrms
Rated Impulse Voltage
4000
V
Operating Temperature
Non-Repetitive Peak Voltage1600
V
Load Current (Motor Load)
EMCRT48D50
EMCRT48D75
A
A
0.1
8.5
0.116
Three-Pole Power Motor
EMCRT48D50
EMCRT48D75
4
7.5
Vrms
Non-Repetitive Overload Current
EMCRT48D50
550
EMCRT48D751000
A
A
I2t@ 10ms
EMCRT48D501500
EMCRT48D75
5000
A 2s
A 2s
Power Factor (Rated Current)
0 up to 1
Turn-On Time
20
ms
Reversing Time100
ms
Turn-Off Time10
ms
Leakage Current
5
mArms
Off-State Voltage Rise (dv/dt)
500
V/µs
Operating Frequency
440Hz
25
°C
Thermal Resistance (Per Leg) θJC
0.5
°C/W
Thermal Resistance θJA
5
°C/W
kW
kW
Voltage Drop1.4
EMCRT Page Min
TYPICAL APPLICATION
3x 400VAC
Reverse
Forward
+A1 +B1–A2/B2
F
R
Mains Voltage Range
EMCRT48D50
EMCRT48D75
Min
+A1 +B1 –A2/B2
1L1
3L2
5L3
1L1
3L2
2T1
4T2
5L3
Solid State
Motor Reverser
2T1
4T2
6T3
6T3
M3~
Figure 4
Specifications are subject to change without notice
© 2005 TELEDYNE RELAYS
EMCRT\102005\Q1
NEW Series EMCRT
Three-Phase Motor Reverser
480 Vac, Up to 7.5 kW
E.M.C.
Max Conducted Immunity Level
Test according to I.E.C. 1000-4-4 (bursts)
Max Conducted Immunity Level
Test according to I.E.C. 1000-4-5 (el. shocks)
4KV direct at output, 4KV with a clamp at input
no turn-on or damage
2KV in common mode, 1KV in differential mode (input & output)
no turn-on or damage
Max Radiated Immunity Level
Test according to I.E.C. 1000-4-3
10V/m
no turn-on or damage
Max Conducted Emission Level (0.8<Pf<1)
Test according to EN55011
Conducted noise made by SSR depends on the wiring
configuration and the load type. Because test methods may vary
from reality, we advise choosing the right filter for your use.
Max Radiated Emission Level
Test according to EN55011 @Ic
<30dBµV from 30 to up 230MHz;
<37dBµV from 230 up to 1000 MHz
MOUNTING ON A HEAT SINK
THERMAL CHARACTERISTICS
30
30
1.2°C/W
with FW121 heat sink
Power Dissipation (W)
25
25
20
20
15
15
Without heat sink
10
10
5
5
0
0
0
2
4
6
8
10
12
0
10 20 30 40 50 60 70 80 90 100
Load Current (Arms)
Figure 5
Ambient Temperature (°C)
Figure 7a — EMCRT48D50
45
TEMPLATE
Power Dissipation (W)
1.57 (40)
3.58 (91)
45
1.2°C/W
with FW121 heat sink
40
40
35
35
30
30
25
25
20
20
Without heat sink
15
15
10
10
5
5
0
0
5
10
15
20
0
0
10 20 30 40 50 60 70 80 90 100
Load Current (Arms)
Figure 6
Ambient Temperature (°C)
Figure 7b — EMCRT48D75
SURGE CURRENT
1500
400
Apeak
Apeak
600
Non-Repetitive
200
Repetitive with initial Tj = 70°C
0
0
0.1
t(s)
1
10
Figure 8a — EMCRT48D50
© 2005 TELEDYNE RELAYS
1000
Non-Repetitive
500
Repetitive with initial Tj = 70°C
0
0
0.1
t(s)
1
10
Figure 8b — EMCRT48D75
(800) 284-7007 • www.teledynerelays.com
EMCRT Page EMCRT\102005\Q1
NEW Series EMCRT
Three-Phase Motor Reverser
480 Vac, Up to 7.5 kW
REVERSERS + HEATSINK SELECTION IN COMPLIANCE WITH EN60947-4-2
SSR SELECTION
Motors Soft-Starters
for a Permanent Current
Relays
without
Heat Sink
Heat Sink
Overload Relay
Type
Ferraz Fuse Type
Ambient = 40°C
Heat Sink = 80°C
14x51 size/
max. rating
Klöckner-Moeller
Motor
Power
Motor current
(@480V)
Two Legs Models
With Integrated DIN
Rail adaptor
0.75kW
2A
EMCRT48D50
None
am 8A/500V
Z00-2.4
1.1kW
2.6A
EMCRT48D50
None
am 8A/500V
Z00-6
1.5kW
3.5A
EMCRT48D50
None
am 12A/500V
Z00-6
2.2kW
5A
EMCRT48D50
FW121
am 12A/500V
Z00-6
3kW
6.6A
EMCRT48D50
FW121
am 12A/500V
Z00-10
4kW
8.5A
EMCRT48D50
FW121
am 12A/500V
Z00-10
5.5kW
12A
EMCRT48D75
FW121
am 20A/500V
Z00-16
7.5kW
16A
EMCRT48D75
FW121
am 32A/500V
Z00-16
CONTROL WIRING
Number of Wires
1
Solid
(no ferrule)
Screwdriver
Type
2
Fine Stranded
(with ferrule)
Solid
(no ferrule)
Fine Stranded
(with ferrule)
Recommended
Torque
N.m
AWG18…AWG14 AWG18…AWG14 AWG18…AWG14 AWG18…AWG14
Pozidriv 2
1.2
Screwdriver
Type
Recommended
Torque
POWER WIRING
Number of Wires
1
Solid
(no ferrule)
2
Fine Stranded
(with ferrule)
Solid
(no ferrule)
Fine Stranded
(with ferrule)
N.m
AWG16…AWG8
APPLICATION WITH ONE PHASE MOTOR
The EMCRT relay, initially developed to reverse threephase asynchronous motors, can be used for reversing single phase motors. This relay has four power
switches, a reversing temporization and a lock in case
of simultaneous controls. If you need large quantities for
single-phase use, please contact us. We can simplify the
product because only two switches of four are used.
AWG16…AWG10
Pozidriv 2
1.8
Main voltage
L
N
Reverse
Forward
1L1
+B1 –A2/B2
R
AWG16…AWG10
+A1
F
AWG16…AWG8
3L2
5L3
1L1
3L2
2T1
4T2
5L3
Solid State
Motor Reverser
2T1
4T2
6T3
6T3
C
M
EMCRT Page Specifications are subject to change without notice
© 2005 TELEDYNE RELAYS
EMCRT\102005\Q1