11-42 11-58 A two-stage compression refrigeration system with refrigerant-134a as the working fluid is considered. The fraction of the refrigerant that evaporates as it is throttled to the flash chamber, the rate of heat removed from the refrigerated space, and the COP are to be determined. Assumptions 1 Steady operating conditions exist. 2 Kinetic and potential energy changes are negligible. 3 The flash chamber is adiabatic. Analysis (a) The enthalpies of the refrigerant at several states are determined from the refrigerant tables (Tables A-11, A12, and A-13) to be h1 234.44 kJ/kg, h2 271.40 kJ/kg h3 262.40 kJ/kg, T h5 127.22 kJ/kg, h6 127.22 kJ/kg h7 81.51 kJ/kg, h8 81.51 kJ/kg The fraction of the refrigerant that evaporates as it is throttled to the flash chamber is simply the quality at state 6, x6 h6 h f h fg 1.4 MPa 4 0.6 MPa 5 2 A 7 127.22 81.51 0.2527 180.90 6 B 8 (b) The enthalpy at state 9 is determined from an energy balance on the mixing chamber: 0.10 MPa 3 9 · QL 1 s E in E out E system 0 (steady) 0 E in E out m h m h e e i i 1h9 x 6 h3 1 x6 h2 h9 0.2527 262.40 1 0.2527 271.40 269.13 kJ/kg P9 0.6 MPa s 9 0.9443 kJ/kg K h9 269.13 kJ/kg also, P4 1.4 MPa h4 287.28 kJ/kg s 4 s 9 0.9443 kJ/kg K Then the rate of heat removed from the refrigerated space and the compressor work input per unit mass of refrigerant flowing through the condenser are m B 1 x 6 m A 1 0.2527 0.25 kg/s 0.1868 kg/s Q L m B h1 h8 0.1868 kg/s 234.44 81.51 kJ/kg 28.57 kW W in W compI,in W compII,in m A h4 h9 m B h2 h1 0.25 kg/s 287.28 269.13 kJ/kg 0.1868 kg/s 271.40 234.44 kJ/kg 11.44 kW (c) The coefficient of performance is determined from COPR Q L W net,in 28.57 kW 2.50 11.44 kW PROPRIETARY MATERIAL. © 2011 The McGraw-Hill Companies, Inc. Limited distribution permitted only to teachers and educators for course preparation. If you are a student using this Manual, you are using it without permission.