WIRING INSTRUCTIONS 120 OR 277V TAP CONNECTION; 12 or 24V INSTALLATION PROCEDURES

advertisement
WIRING INSTRUCTIONS
For Transformers: LVT-150, LVT-300, LVT-300 277V, LVT-300-24, LVT-600-24 and LVT-600-277V-24
INSTALLATION PROCEDURES
• Use #10 wire for 25A circuits; cap off the unused end.
• Under 15 feet, use standard tap; 15 to 40 feet use boost tap.
• Ensure that all wiring connections are tight. For field connections, use
wires suitable for at least 90°C (194°F).
• 130°C Insulation system is used. Allowable temperature rise is 95°C.
• Non-current carrying parts bonded to grounding terminal.
• Properly ground the transformer.
• Flip toggle to reset the magnetic circuit breaker.
• If dimmer is used, must be a magnetic, low-voltage dimmer.
IMPORTANT SAFETY INSTRUCTIONS:
• Read all the instructions before installation. Save instructions for later use.
• Turn off power at fuse or circuit breaker box before installation or before
doing any maintenance work.
• Installing contrary to instructions may cause unsafe conditions.
• Warning: Risk of fire. Use only the type of lamp and maximum wattage
marked on the fixture.
• To avoid hazards to children, account for all parts and properly dispose of
all packing materials.
• Call the Technical Support department at Con-Tech Lighting with any
installation questions: 847.559.5500.
120 OR 277V TAP CONNECTION; 12 or 24V
White Feed
COM PRI
Black Feed
120 OR 277V PRI
TRANSFORMER
X2
Green Ground
Internal
Ground
Screw
BOOST TAP CONNECTION; 12 or 24V
White Feed
COM PRI
TRANSFORMER
120 OR 277V PRI
Green
Striped
Ground
Lead
Circuit
Breaker
X1
X2
Boost Tap
Green Ground
Internal
Ground
Screw
All specifications subject to change without notice.
www.con-techlighting.com
X1
Boost Tap
Black Feed
1-847-559-5500
Circuit
Breaker
Green
Striped
Ground
Lead
This document can be recycled.