3/23/2016 3:28:58 PM NJDCA ELECTRONIC SUBMITTAL STAMP: SEALED: CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: LEGEND GENERAL NOTES 1. THESE GENERAL ELECTRICAL NOTES SHALL APPLY TO ALL E SERIES DRAWINGS, IN COORDINATION WITH DIVISION 26, 27, & 28 SECTIONS, AND FRONT END (DIVISION 0 AND 1) REQUIREMENTS. ALL WORK ASSOCIATED WITH THE E SERIES DRAWINGS SHALL BE COORDINATED WITH ALL OTHER TRADES TO AVOID CONFLICTS. DUPLEX RECEPTACLE - DEVICES SHOWN "DASHED" OR "DARK INK" ON DEMO PLANS ARE TO BE REMOVED UNLESS NOTED OTHERWISE. 2. ALL WORK SHALL BE PERFORMED IN COOPERATION WITH THE UNIVERSITY AND THE ARCHITECT/ENGINEER. THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE CONSTRUCTION SCHEDULE ESTABLISHED BY THE UNIVERSITY, AND SHALL IMMEDIATELY REPORT ANY DELAYS IN MATERIALS RECEIPT INCLUDING CIRCUMSTANCES CAUSING DELAYS. • COMMENCE WORK AFTER PRECONSTRUCTION MEETING AND PROCEED DILIGENTLY AND CONTINUOUSLY TO COMPLETION. • PRIOR TO STARTING WORK, SUBMIT FOR UNIVERSITY'S APPROVAL, A DETAILED SCHEDULE INDICATING ALL WORK THAT MAY AFFECT THE BUILDING AND NEARBY BUILDINGS/STRUCTURES, SUCH AS UTILITY SHUT DOWNS, NOISE GENERATING EQUIPMENT, ETC. • PERFORM WORK IN A MANNER WHICH MINIMIZES NOISE. OPERATIONS IN WHICH NOISE CANNOT BE MINIMIZED SHALL BE SCHEDULED WITH UNIVERSITY. TC TIME CLOCK PC PHOTOCELL F 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: FIRE ALARM STROBE - WALL MOUNT V F V FIRE ALARM STROBE/SPEAKER - CEILING MOUNT EXIT SIGN - SINGLE SIDED S SMOKE DETECTOR EXIT SIGN - DOUBLE SIDED H HEAT DETECTOR EXIT SIGN - TRIANGLES INDICATE DIRECTION ARROWS X X2 X2 FIRE ALARM STROBE/SPEAKER - WALL MOUNT F X1 3. CONTRACT DRAWINGS FOR THE ELECTRICAL WORK ARE DIAGRAMMATIC, INTENDED TO CONVEY THE SCOPE OF WORK AND TO INDICATE THE GENERAL ARRANGEMENT AND APPROXIMATE LOCATION OF EQUIPMENT, PIPING, AND ACCESSORIES. THE INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING AND VERIFYING ALL CONDITIONS, DIMENSIONS, AND LOCATIONS PRIOR TO BIDDING PROJECT. CHECK PROJECT DRAWINGS PRIOR TO INSTALLATION FOR INTERFERENCES WITH OTHER TRADES. SHOULD THE CONTRACTOR FIND SUCH INTERFERENCES, THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING HIS WORK WITH OTHERS. THE UNIVERSITY RESERVES THE RIGHT TO MAKE REASONABLE CHANGES PRIOR TO ROUGH-IN WITHOUT ADDED EXPENSE. DIMENSIONS INDICATED ARE SUBJECT TO VERIFICATION OF EXACT SITE CONDITIONS AT THE TIME OF INSTALLATION. • THE CONTRACTOR SHALL INSTALL ALL CONDUIT, WIRE, EQUIPMENT, LIGHT FIXTURES, ETC. IN A WORKMAN LIKE MANNER WITH QUALIFIED ELECTRICIANS. • ANY DISCREPANCIES BETWEEN THE DRAWINGS AND SPECIFICATIONS SHALL BE REPORTED TO THE UNIVERSITY. IN THE EVENT OF A DISCREPANCY, THE DRAWINGS WILL GOVERN OVER THE SPECIFICATIONS. MANUAL PULL STATION 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com REVISIONS KEY NOTE, REFER TO KEY NOTES ON DRAWING 4. ALL ELECTRICAL WORK SHALL BE INSTALLED TO MEET THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, NEW JERSEY EXISTING BUILDING CODE, INTERNATIONAL BUILDING, FIRE CODE AND NFPA 72. ALL WORK SHALL COMPLY TO ACCORDANCE OF LOCAL, STATE AND FEDERAL REGULATIONS AND OTHER AUTHORITIES HAVING JURISDICTION. DRAWN BY: BFD CHECKED BY: WEF 5. CONTRACTOR IS RESPONSIBLE FOR PAYING FOR ALL FEES ASSOCIATED WITH OBTAINING INSPECTIONS. 9. PROVIDE (FURNISH AND INSTALL) ALL NEW EQUIPMENT AND MATERIALS AS DESCRIBED HEREIN. ANY MATERIAL, OPERATION, METHOD, OR DEVICE MENTIONED, LISTED OR NOTED WITHIN THIS SPECIFICATION SHALL BE FURNISHED BY THIS CONTRACTOR UNLESS SPECIFICALLY MENTIONED AS BEING FURNISHED OR INSTALLED BY OTHERS. • ALL MATERIALS SHALL BE AS SPECIFIED, OR EQUAL, AS APPROVED BY UNIVERSITY. MATERIALS SPECIFIED INDICATE QUALITY INTENT THAT WILL BE USED AS A BASIS FOR REVIEW OF SUBSTITUTES. SEE GENERAL CONDITIONS FOR SUBSTITUTION PROCEDURES. • MATERIALS SHALL BE STORED AT A LOCATION DETERMINED BY THE UNIVERSITY. • DELIVERY OF MATERIALS SHALL BE AS DIRECTED BY THE UNIVERSITY. FIR PU E A ST LL LAR AT M IO N F.A. A/V UNITS 10. THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE COMPLETE AND OPERABLE SYSTEMS, INCLUDING OPERATIONAL PROPERTIES TO THE EXTEND NECESSARY TO LINK MULTIPLE COMPONENTS OF THE SYSTEMS TOGETHER AND TO INTERFACE WITH SYSTEMS PROVIDED BY OTHERS. THE ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL SYSTEMS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE. • THE CONTRACTOR SHALL PROVIDE UNIVERSITY WITH ALL NECESSARY OPERATION AND MAINTENANCE MANUALS, SHOP DRAWINGS, WIRING DIAGRAMS, AND WARRANTY PAPERWORK UPON COMPLETION OF THE PROJECT. • THE CONTRACTOR SHALL REPAIR, ADJUST, OR REPLACE ANY EQUIPMENT, MATERIAL, OR WORKMANSHIP FOUND TO BE DEFECTIVE. 90" MIN. WHERE POSSIBLE 11. THE ELECTRICAL CONTRACTOR SHALL HOLD THE UNIVERSITY, ARCHITECT, AND ENGINEER HARMLESS AGAINST ANY AND ALL CLAIMS ARISING FROM WORK PERFORMED BY THIS CONTRACTOR ON THE SITE. 12. DISCONNECTION OF SERVICES SHALL BE PERFORMED AT A TIME AUTHORIZED BY THE UNIVERSITY. TEMPORARY UTILITIES, IF NEEDED, WILL BE COORDINATED WITH THE UNIVERSITY. 48" 13. CONTRACTOR SHALL MAKE EVERY EFFORT TO PROTECT BUILDING COMPONENTS DURING CONSTRUCTION. A PROTECTION PROPOSAL MUST BE SUBMITTED TO THE UNIVERSITY FOR REVIEW. 14. CONTRACTOR SHALL KEEP SITE FREE OF DEBRIS AND ACCUMULATED REFUSE. SITE SHALL BE BROOM SWEPT AT THE END OF EACH WORKING DAY. 15. FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH THE REQUIREMENTS OF THE LOCAL FIRE MARSHAL CONCERNING FIRE ALARM SYSTEM SHUTDOWN PLANS, PROCEDURES, AND FIRE WATCH PLANS THAT WILL BE IMPLEMENTED FOR SYSTEM INTERRUPTIONS DURING CONSTRUCTION. FLOOR 1 TYPICAL MOUNTING HEIGHTS DETAIL N.T.S. ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS SHEET: E-000 18031.00 6" TO TOP OF DEVICE RAMAPO COLLEGE OF NEW JERSEY CEILING ELECTRICAL LEGEND AND GENERAL NOTES 8. CUTTING AND PATCHING - ALL NOTES BELOW HOLD THE COMMON CONDITION "UNLESS OTHERWISE NOTED". • FOR ALTERATIONS: ALL CUTTING AND PATCHING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR FOR HIS/HER OWN WORK WHETHER DESCRIBED IN THE CONTRACT DOCUMENTS OR NOT. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING CUTTING AND PATCHING REQUIREMENTS WITH OTHER TRADES. • OPENINGS MADE POST-FINISH: IF AN OPENING IS REQUIRED IN A FINISHED SURFACE, AFTER COMPLETION, DUE TO LACK OF COORDINATION OR PROPER SCHEDULE MAINTENANCE, THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ANY CUTTING AND PATCHING REQUIRED TO FINISH SPECIFIC ELECTRICAL WORK AND RESTORE THE FINISHED SURFACE TO PREVIOUS CONDITION. RCNJ No. 201437-01C PHASE 2: ALTERATIONS 7. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER RECOMMENDATIONS. ANY CONFLICTS WITH INSTALLATION AND MANUFACTURER RECOMMENDATIONS SHALL BE REPORTED TO ENGINEER. 505 RAMAPO VALLEY RD. MAHWAH, NY 07430 6. THE ELECTRICAL CONTRACTOR SHALL BE LICENSED IN THE LOCAL JURISDICTION PRIOR TO BIDDING ON PROJECT. CONTRACTOR TO CONTACT CITY/TOWNSHIP TO VERIFY LICENSE TO ENSURE THEY ARE CURRENT. 3/23/2016 3:28:59 PM NJDCA ELECTRONIC SUBMITTAL STAMP: SEALED: CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: GENERAL NOTES 1. THESE GENERAL ELECTRICAL NOTES SHALL APPLY TO ALL E SERIES DRAWINGS, IN COORDINATION WITH DIVISION 26, 27, & 28 SECTIONS, AND FRONT END (DIVISION 0 AND 1) REQUIREMENTS. ALL WORK ASSOCIATED WITH THE E SERIES DRAWINGS SHALL BE COORDINATED WITH ALL OTHER TRADES TO AVOID CONFLICTS. LEGEND 2. ALL WORK SHALL BE PERFORMED IN COOPERATION WITH THE UNIVERSITY AND THE ARCHITECT/ENGINEER. THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE CONSTRUCTION SCHEDULE ESTABLISHED BY THE UNIVERSITY, AND SHALL IMMEDIATELY REPORT ANY DELAYS IN MATERIALS RECEIPT INCLUDING CIRCUMSTANCES CAUSING DELAYS. • COMMENCE WORK AFTER PRECONSTRUCTION MEETING AND PROCEED DILIGENTLY AND CONTINUOUSLY TO COMPLETION. • PRIOR TO STARTING WORK, SUBMIT FOR UNIVERSITY'S APPROVAL, A DETAILED SCHEDULE INDICATING ALL WORK THAT MAY AFFECT THE BUILDING AND NEARBY BUILDINGS/STRUCTURES, SUCH AS UTILITY SHUT DOWNS, NOISE GENERATING EQUIPMENT, ETC. • PERFORM WORK IN A MANNER WHICH MINIMIZES NOISE. OPERATIONS IN WHICH NOISE CANNOT BE MINIMIZED SHALL BE SCHEDULED WITH UNIVERSITY. 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com DUPLEX RECEPTACLE G U G G DUPLEX RECEPTACLE - GFI X2 USB CHARGER-DUPLEX RECEPTACLE - ABOVE COUNTER DUPLEX RECEPTACLE - ABOVE COUNTER, GFI COMBINATION TELE/DATA JACK -PROVIDE CAT. 3 CABLE TO TELEPHONE DEMARC. -PROVIDE CAT. 6a CABLE TO SECOND FLOOR ELECTRICAL ROOM. D D DATA JACK -PROVIDE CAT. 6a CABLE TO SECOND FLOOR ELECTRICAL ROOM FUSED DISCONNECT (POLES, SIZE, FUSE) F MANUAL PULL STATION FIRE ALARM STROBE/SPEAKER - CEILING MOUNT SMOKE DETECTOR F10 5. CONTRACTOR IS RESPONSIBLE FOR PAYING FOR ALL FEES ASSOCIATED WITH OBTAINING INSPECTIONS. REVISIONS FIRE ALARM STROBE - WALL MOUNT V S 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com FIRE ALARM STROBE/SPEAKER - WALL MOUNT F JUNCTION BOX J CEILING MOTION SENSOR - DUAL TECHNOLOGY CORNER MOTION SENSOR - DUAL TECHNOLOGY V (3,30,20) MOTION SENSOR SWITCH M F MANUAL MOTOR STARTER 4. ALL ELECTRICAL WORK SHALL BE INSTALLED TO MEET THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, NEW JERSEY EXISTING BUILDING CODE, INTERNATIONAL BUILDING, FIRE CODE AND NFPA 72. ALL WORK SHALL COMPLY TO ACCORDANCE OF LOCAL, STATE AND FEDERAL REGULATIONS AND OTHER AUTHORITIES HAVING JURISDICTION. ENGINEER: SINGLE POLE LIGHT SWITCH M 3. CONTRACT DRAWINGS FOR THE ELECTRICAL WORK ARE DIAGRAMMATIC, INTENDED TO CONVEY THE SCOPE OF WORK AND TO INDICATE THE GENERAL ARRANGEMENT AND APPROXIMATE LOCATION OF EQUIPMENT, PIPING, AND ACCESSORIES. THE INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING AND VERIFYING ALL CONDITIONS, DIMENSIONS, AND LOCATIONS PRIOR TO BIDDING PROJECT. CHECK PROJECT DRAWINGS PRIOR TO INSTALLATION FOR INTERFERENCES WITH OTHER TRADES. SHOULD THE CONTRACTOR FIND SUCH INTERFERENCES, THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING HIS WORK WITH OTHERS. THE UNIVERSITY RESERVES THE RIGHT TO MAKE REASONABLE CHANGES PRIOR TO ROUGH-IN WITHOUT ADDED EXPENSE. DIMENSIONS INDICATED ARE SUBJECT TO VERIFICATION OF EXACT SITE CONDITIONS AT THE TIME OF INSTALLATION. • THE CONTRACTOR SHALL INSTALL ALL CONDUIT, WIRE, EQUIPMENT, LIGHT FIXTURES, ETC. IN A WORKMAN LIKE MANNER WITH QUALIFIED ELECTRICIANS. • ANY DISCREPANCIES BETWEEN THE DRAWINGS AND SPECIFICATIONS SHALL BE REPORTED TO THE UNIVERSITY. IN THE EVENT OF A DISCREPANCY, THE DRAWINGS WILL GOVERN OVER THE SPECIFICATIONS. EXIT SIGN - TRIANGLES INDICATE DIRECTION ARROWS DRAWN BY: BFD CHECKED BY: WEF LIGHT FIXTURE, REFER TO FIXTURE SCHEDULE 6. THE ELECTRICAL CONTRACTOR SHALL BE LICENSED IN THE LOCAL JURISDICTION PRIOR TO BIDDING ON PROJECT. CONTRACTOR TO CONTACT CITY/TOWNSHIP TO VERIFY LICENSE TO ENSURE THEY ARE CURRENT. X1 EXIT SIGN - SINGLE SIDED 7. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER RECOMMENDATIONS. ANY CONFLICTS WITH INSTALLATION AND MANUFACTURER RECOMMENDATIONS SHALL BE REPORTED TO ENGINEER. X KEY NOTE, REFER TO KEY NOTES ON DRAWING X2 L IG HT SW ITC H 13. CONTRACTOR SHALL MAKE EVERY EFFORT TO PROTECT BUILDING COMPONENTS DURING CONSTRUCTION. A PROTECTION PROPOSAL MUST BE SUBMITTED TO THE UNIVERSITY FOR REVIEW. 14. CONTRACTOR SHALL KEEP SITE FREE OF DEBRIS AND ACCUMULATED REFUSE. SITE SHALL BE BROOM SWEPT AT THE END OF EACH WORKING DAY. TY RE PIC CE AL PT AC LE TY PIC AL DA TA JA DE CK SK PH ON E JA CK 15. FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH THE REQUIREMENTS OF THE LOCAL FIRE MARSHAL CONCERNING FIRE ALARM SYSTEM SHUTDOWN PLANS, PROCEDURES, AND FIRE WATCH PLANS THAT WILL BE IMPLEMENTED FOR SYSTEM INTERRUPTIONS DURING CONSTRUCTION. 48" 18" FLOOR 1 AB CO O V RE UNT E TH CE ER E PT AC LE 12. DISCONNECTION OF SERVICES SHALL BE PERFORMED AT A TIME AUTHORIZED BY THE UNIVERSITY. TEMPORARY UTILITIES, IF NEEDED, WILL BE COORDINATED WITH THE UNIVERSITY. TYPICAL MOUNTING HEIGHTS N.T.S. ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS SHEET: E-001 18031.00 11. THE ELECTRICAL CONTRACTOR SHALL HOLD THE UNIVERSITY, ARCHITECT, AND ENGINEER HARMLESS AGAINST ANY AND ALL CLAIMS ARISING FROM WORK PERFORMED BY THIS CONTRACTOR ON THE SITE. 505 RAMAPO VALLEY RD. MAHWAH, NY 07430 CEILING RAMAPO COLLEGE OF NEW JERSEY 10. THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE COMPLETE AND OPERABLE SYSTEMS, INCLUDING OPERATIONAL PROPERTIES TO THE EXTEND NECESSARY TO LINK MULTIPLE COMPONENTS OF THE SYSTEMS TOGETHER AND TO INTERFACE WITH SYSTEMS PROVIDED BY OTHERS. THE ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL SYSTEMS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE. • THE CONTRACTOR SHALL PROVIDE UNIVERSITY WITH ALL NECESSARY OPERATION AND MAINTENANCE MANUALS, SHOP DRAWINGS, WIRING DIAGRAMS, AND WARRANTY PAPERWORK UPON COMPLETION OF THE PROJECT. • THE CONTRACTOR SHALL REPAIR, ADJUST, OR REPLACE ANY EQUIPMENT, MATERIAL, OR WORKMANSHIP FOUND TO BE DEFECTIVE. ELECTRICAL LEGEND AND GENERAL NOTES 9. PROVIDE (FURNISH AND INSTALL) ALL NEW EQUIPMENT AND MATERIALS AS DESCRIBED HEREIN. ANY MATERIAL, OPERATION, METHOD, OR DEVICE MENTIONED, LISTED OR NOTED WITHIN THIS SPECIFICATION SHALL BE FURNISHED BY THIS CONTRACTOR UNLESS SPECIFICALLY MENTIONED AS BEING FURNISHED OR INSTALLED BY OTHERS. • ALL MATERIALS SHALL BE AS SPECIFIED, OR EQUAL, AS APPROVED BY UNIVERSITY. MATERIALS SPECIFIED INDICATE QUALITY INTENT THAT WILL BE USED AS A BASIS FOR REVIEW OF SUBSTITUTES. SEE GENERAL CONDITIONS FOR SUBSTITUTION PROCEDURES. • MATERIALS SHALL BE STORED AT A LOCATION DETERMINED BY THE UNIVERSITY. • DELIVERY OF MATERIALS SHALL BE AS DIRECTED BY THE UNIVERSITY. RCNJ No. 201437-01C PHASE 2: ALTERATIONS EXIT SIGN - DOUBLE SIDED 8. CUTTING AND PATCHING - ALL NOTES BELOW HOLD THE COMMON CONDITION "UNLESS OTHERWISE NOTED". • FOR ALTERATIONS: ALL CUTTING AND PATCHING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR FOR HIS/HER OWN WORK WHETHER DESCRIBED IN THE CONTRACT DOCUMENTS OR NOT. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING CUTTING AND PATCHING REQUIREMENTS WITH OTHER TRADES. • OPENINGS MADE POST-FINISH: IF AN OPENING IS REQUIRED IN A FINISHED SURFACE, AFTER COMPLETION, DUE TO LACK OF COORDINATION OR PROPER SCHEDULE MAINTENANCE, THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ANY CUTTING AND PATCHING REQUIRED TO FINISH SPECIFIC ELECTRICAL WORK AND RESTORE THE FINISHED SURFACE TO PREVIOUS CONDITION. 3/23/2016 3:29:52 PM NJDCA ELECTRONIC SUBMITTAL STAMP: DEMOLITION GENERAL NOTES 1. 2. 3. E G J N QQ.1 Q.2 Q.3 4. 5. 22 EXISTING EMERGENCY LIGHTING PANEL EPPB GE SPECTRA SERIES 6. 7. 8. 9. B C D KPP3 KPP2 KPP1 21 10. IDENTIFICATION AND/OR ABATEMENT OF HAZARDOUS MATERIALS IS NOT PART OF THIS SCOPE OF WORK. IF ASBESTOS OR OTHER HAZARDOUS MATERIALS ARE ENCOUNTERED, THE CONTRACTOR SHALL NOTIFY THE OWNER IMMEDIATELY. REFER TO SPECIFICATIONS FOR RECYCLING, CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL REQUIREMENTS. OPENING IN THE EXISTING STRUCTURE SMALLER THAN 12" IN ANY DIRECTION ARE NOT IDENTIFIED ON THESE DRAWINGS. SUBCONTRACTORS SHALL BE RESPONSIBLE FOR PROVIDING OPENINGS SMALLER THAN 12" AS REQUIRED FOR INSTALLATION OF THEIR WORK. OPENINGS IN THE EXISTING STRUCTURE SHALL NOT BE MADE WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER. DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE STRUCTURAL INTEGRITY OF THE BUILDING. IF HIDDEN ELEMENTS OR DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY THE ARCHITECT IMMEDIATELY. PROTECT ADJACENT AREAS AND ITEMS "TO REMAIN" DURING DEMOLITION/CONSTRUCTION. REPAIR/REPLACE ITEMS DAMAGED DURING CONSTRUCTION. IF UNANTICIPATED HIDDEN ELEMENTS OR DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY THE OWNERS REPRESENTATIVE IMMEDIATELY. REFER TO CONSULTANT DRAWINGS FOR ADDITIONAL DEMOLITION WORK. REVIEW w/ OWNER TO DETERMINE WHAT, IF ANYTHING, WILL BE REMOVED BY OWNER AND WHAT, IF ANYTHING, IS TO BE SALVAGED & TURNED OVER TO OWNER. DEVICES SHOWN AS "DASHED" OR IN "DARK INK" ARE TO BE REMOVED. ELECTRICAL SUB-CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING DEVICES, DISCONNECTS, STARTERS, RELAYS, AND MISCELLANEOUS COMPONENTS AS REQUIRED. WIRING AND CONDUITS ASSOCIATED WITH REMOVED ITEMS SHALL BE REMOVED BACK TO SOURCE PANEL. DEVICES SHOWN AS "LIGHT INK" ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED. SEALED: CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: EXISTING 120/208V, 3PH, 4W FEDERAL PACIFIC PANEL 20 G G G G G EXISTING ELECTRICAL PANELS J G J G J 19 G G G APPROXIMATE LOCATION OF ELECTRICAL ROOM ON SECOND FLOOR D1 0 0 D2 J G G G 18 D3 G G G J J G GG GFCI G G G G G J 15 G G G G G G J J G G G D3 J J ELECTRICAL SUB-CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING RECEPTACLES, SURFACE BOXES, WIREMOLD, AND CONDUITS. REMOVE CIRCUITRY BACK TO SOURCE PANEL. 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: REMOVE EXISTING HANDICAP DOOR PUSH BUTTON OPERATORS AND STORE FOR REINSTALLATION. DISCONNECT AND REMOVE POWER TO EXISTING DOOR OPERATORS AND DOOR SENSORS, AND REMOVE POWER TO NEAREST HOME RUN JUNCTION BOX, LABEL CIRCUITRY FOR RE-USE. D4 DISCONNECT POWER TO EXISTING CABINET UNIT HEATER AND REMOVE TO NEAREST HOMERUN JUNCTION BOX, LABEL CIRCUITRY FOR RE-USE. D5 CAREFULLY DISCONNECT AND REMOVE EXISTING DUPLEX RECEPTACLE AND DATA JACKS AT A.T.M. LOCATION. STORE DEVICES IN A SAFE PLACE FOR RE-INSTALLATION. REMOVE CONDUIT AND WIRING BACK TO JUNCTION BOX ABOVE GRID CEILING TO ACCOMODATE WALL REMOVEL, LABEL CIRCUITRY FOR RE-USE. REMOVE DATA CABLING AND COIL ABOVE GRID CEILING FOR RE-USE. REFER TO E-110 ELECTRICAL PLAN FOR NEW LOCATION. COORDINATE WORK WITH RAMAPO COLLEGE FACILITY PERSONNEL. 17 D4 J J 16 KEYED NOTES 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com REVISIONS DRAWN BY: BFD CHECKED BY: WEF G G FB G DWR DW 10.9 10.8 FB G J 11 D5 G G G D G FB G D G U U U D U U 10.2 10 U D D D U U U U D U U D B.7 U D U U D A.4 U 9 U U 8 U D U U D D U U D U U U U 6 5 U D D D U D U U U U D D U D U U U U U U D D D U D2 7 U U U 7.1 D U REMOVE ALL SURFACE WIREMOLD FEEDING DEVICES (TYPICAL) U U D U 4 U D1 U D D U D1 3 U U (TYPICAL) 2.9 U D D U U 2.1 1.9 2 1 A F H I K L M O ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS 1 ELECTRICAL DEMO PLAN - FF1 1/8" = 1'-0" SHEET: ED-100 18031.00 G G J GG G EXISTING ELECTRICAL PANELS 12 JJ 505 RAMAPO VALLEY RD. MAHWAH, NY 07430 D G G G RCNJ No. 201437-01C PHASE 2: ALTERATIONS G G RAMAPO COLLEGE OF NEW JERSEY G FB G 13 ELECTRICAL DEMOLITION - FIRST FLOOR 14 10.3 G G 3/23/2016 3:30:20 PM NJDCA ELECTRONIC SUBMITTAL STAMP: DEMOLITION GENERAL NOTES 1. E G J N QQ.1 Q.2 Q.3 22 EXISTING EMERGENCY LIGHTING PANEL EPPB GE SPECTRA SERIES B C D EXISTING ELECTRICAL PANELS KPP2 KPP3 KPP1 21 EXISTING 120/208V, 3PH, 4W FEDERAL PACIFIC PANEL 20 F V 19 APPROXIMATE LOCATION OF ELECTRICAL ROOM ON SECOND FLOOR FIRE F ALARM PANEL IS ALSO LOCATED V HERE) IDENTIFICATION AND/OR ABATEMENT OF HAZARDOUS MATERIALS IS NOT PART OF THIS SCOPE OF WORK. IF ASBESTOS OR OTHER HAZARDOUS MATERIALS ARE ENCOUNTERED, THE CONTRACTOR SHALL NOTIFY THE OWNER IMMEDIATELY. 2. REFER TO SPECIFICATIONS FOR RECYCLING, CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL REQUIREMENTS. 3. OPENING IN THE EXISTING STRUCTURE SMALLER THAN 12" IN ANY DIRECTION ARE NOT IDENTIFIED ON THESE DRAWINGS. SUBCONTRACTORS SHALL BE RESPONSIBLE FOR PROVIDING OPENINGS SMALLER THAN 12" AS REQUIRED FOR INSTALLATION OF THEIR WORK. 4. OPENINGS IN THE EXISTING STRUCTURE SHALL NOT BE MADE WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER. 5. DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE STRUCTURAL INTEGRITY OF THE BUILDING. IF HIDDEN ELEMENTS OR DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY THE ARCHITECT IMMEDIATELY. 6. PROTECT ADJACENT AREAS AND ITEMS "TO REMAIN" DURING DEMOLITION/CONSTRUCTION. REPAIR/REPLACE ITEMS DAMAGED DURING CONSTRUCTION. 7. IF UNANTICIPATED HIDDEN ELEMENTS OR DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY THE OWNERS REPRESENTATIVE IMMEDIATELY. REFER TO CONSULTANT DRAWINGS FOR ADDITIONAL DEMOLITION WORK. 8. REVIEW w/ OWNER TO DETERMINE WHAT, IF ANYTHING, WILL BE REMOVED BY OWNER AND WHAT, IF ANYTHING, IS TO BE SALVAGED & TURNED OVER TO OWNER. 9. DEVICES SHOWN "DASHED" OR IN "DARK INK" ARE TO BE REMOVED. ELECTRICAL SUB-CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING DEVICES, DISCONNECTS, STARTERS, RELAYS, AND MISCELLANEOUS COMPONENTS AS REQUIRED. WIRING AND CONDUITS ASSOCIATED WITH REMOVED ITEMS SHALL BE REMOVED BACK TO SOURCE PANEL. 10. DEVICES SHOWN AS "LIGHT INK" ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED. SEALED: CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: H D V D F V H D D F EXISTING FIRE ALARM ANNUNCIATOR TO REMAIN. 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com 18 ENGINEER: S S KEYED NOTES 17 H D1 H D6 D6 16 15 D H D2 REMOVE EXISTING FIRE ALARM DETECTORS, PULL STATIONS AND AUDIBLE/VISUAL DEVICES. REMOVE FIRE ALARM ANNUNCIATION AND NOTIFICATION CONDUIT & CIRCUITRY BACK TO NEAREST HOME-RUN JUNCTION BOX AT CEILING FOR REUSE. D3 REMOVE EXISTING SURFACE WIREMOLD FEEDING DEVICES SUCH AS SWITCHES, FIRE ALARM PULL STATIONS, AND AUDIBLE/VISUAL DEVICES MOUNTED ON OR IN WALLS BEING REMOVED. D4 REMOVE AND STORE EXISTING EXIT SIGN FOR REINSTALLATION. D5 REMOVE AND STORE FIRE ALARM DEVICE FOR REINSTALLATION. D6 REMOVE LIGHT FIXTURE. H F D ELECTRICAL SUB-CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES, OCCUPANCY SENSORS, AND SWITCHES. REMOVE EXISTING CONDUIT & CIRCUITRY BACK TO NEAREST HOME-RUN JUNCTION BOX AT CEILING. D4 REVISIONS V H H F 13 V D 3 EXISTING ELECTRICAL PANELS 11 10.9 10.8 3D H S DWR DW S 12 14 10.3 D H F H D S D S H A.4 B.7 9 S S F K D F M M S 8 10.2 10 S (TYPICAL) D1 F F (TYPICAL) D1 D 7 S 7.1 D D4 D D D5 S S MULTIPLE EXISTING TRACK LIGHTS (TO BE REMOVED) (TYPICAL) D1 F 6 5 D3 D2 D1 (TYPICAL) D2 4 S D S S S D4 D D (TYPICAL) D1 D5 K CHECKED BY: WEF 2 1 S D1 A BFD F M 2.1 1.9 3 S 2.9 F FF F DRAWN BY: (TYPICAL) F H I K L M O ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS 1 LIGHTING DEMO PLAN - FF1 1/8" = 1'-0" SHEET: ED-101 18031.00 D5 RCNJ No. 201437-01C PHASE 2: ALTERATIONS F RAMAPO COLLEGE OF NEW JERSEY RPK V V D F H FF LIGHTING DEMOLITION - FIRST FLOOR EXISTING ELECTRICAL D PANEL 505 RAMAPO VALLEY RD. MAHWAH, NY 07430 K V 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com 3/23/2016 3:30:21 PM NJDCA ELECTRONIC SUBMITTAL STAMP: DEMOLITION GENERAL NOTES 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. IDENTIFICATION AND/OR ABATEMENT OF HAZARDOUS MATERIALS IS NOT PART OF THIS SCOPE OF WORK. IF ASBESTOS OR OTHER HAZARDOUS MATERIALS ARE ENCOUNTERED, THE CONTRACTOR SHALL NOTIFY THE OWNER IMMEDIATELY. REFER TO SPECIFICATIONS FOR RECYCLING, CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL REQUIREMENTS. OPENING IN THE EXISTING STRUCTURE SMALLER THAN 12" IN ANY DIRECTION ARE NOT IDENTIFIED ON THESE DRAWINGS. SUBCONTRACTORS SHALL BE RESPONSIBLE FOR PROVIDING OPENINGS SMALLER THAN 12" AS REQUIRED FOR INSTALLATION OF THEIR WORK. OPENINGS IN THE EXISTING STRUCTURE SHALL NOT BE MADE WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER. DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE STRUCTURAL INTEGRITY OF THE BUILDING. PROTECT ADJACENT AREAS AND ITEMS "TO REMAIN" DURING DEMOLITION/CONSTRUCTION. REPAIR/REPLACE ITEMS DAMAGED DURING CONSTRUCTION. IF UNANTICIPATED HIDDEN ELEMENTS OR DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY THE OWNERS REPRESENTATIVE IMMEDIATELY. REFER TO CONSULTANT DRAWINGS FOR ADDITIONAL DEMOLITION WORK. REVIEW w/ OWNER TO DETERMINE WHAT, IF ANYTHING, WILL BE REMOVED BY OWNER AND WHAT, IF ANYTHING, IS TO BE SALVAGED & TURNED OVER TO OWNER. DEVICES SHOWN AS "DASHED" OR IN "DARK INK" ARE TO BE REMOVED. ELECTRICAL SUB-CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING DEVICES, DISCONNECTS, STARTERS, RELAYS, AND MISCELLANEOUS COMPONENTS AS REQUIRED. WIRING AND CONDUITS ASSOCIATED WITH REMOVED ITEMS SHALL BE REMOVED BACK TO SOURCE PANEL. DEVICES SHOWN AS "LIGHT INK" ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED. SEALED: CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: KEYED NOTES D1 D2 N Q N D3 DISCONNECT POWER TO EXISTING HAND DRYERS AND DRINKING FOUNTAIN RECEPTACLE. REMOVE JUNCTION BOXES, RECEPTACLE AND ASSOCIATED CONDUIT AND WIRING TO NEAREST HOMERUN JUNCTION BOX ABOVE CEILING. COIL WIRING AND LABEL CIRCUITS FOR RE-USE. DISCONNECT POWER TO EXISTING LIGHT FIXTURES AND OCCUPANCY SENSORS. REMOVE LIGHT FIXTURES AND ASSOCIATED CONDUIT AND WIRING TO NEAREST HOMERUN JUNCTION BOX ABOVE CEILING. COIL WIRING AND LABEL CIRCUITS FOR RE-USE. CAREFULLY DISCONNECT AND REMOVE FIRE ALARM DEVICES. REMOVE ASSOCIATED CONDUIT AND WIRING TO NEAREST HOMERUN JUNCTION BOX ABOVE CEILING. COIL WIRING AND LABEL CIRCUITS FOR RE-USE. STORE FIRE ALARM DEVICES IN A SAFE LOCATION FOR REINSTALLATION. 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com REVISIONS J 19 19 BFD CHECKED BY: WEF D2 D F V D2 F 18 V D2 S D3 J S D2 17 G 17 J F V D1 G G G 1 ELECTRICAL DEMO PLAN - FF1 - RESTROOMS 15 0 4 8 2 12 1/4" = 1'-0" LIGHTING DEMO PLAN - FF1 - BATHROOMS 0 4 8 12 1/4" = 1'-0" NORTH NORTH RCNJ No. 201437-01C PHASE 2: ALTERATIONS 18 D1 D RAMAPO COLLEGE OF NEW JERSEY D1 D3 ELECTRICAL DEMOLITION TOILET ROOMS D2 ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS SHEET: ED-110 18031.00 D2 DRAWN BY: 505 RAMAPO VALLEY RD. MAHWAH, NY 07430 J 3/23/2016 3:30:21 PM NJDCA ELECTRONIC SUBMITTAL STAMP: EXISTING EQUIPMENT SCHEDULE DESSERT EQ16 GRILL EQ3 EQ4 EQ6 EQ7 HOMETOWN EQ5 EQ8 EQ9 MEDITERRANEAN EQ1 EQ2 PIZZA EQ10 EQ11 EQ12 SALAD EQ17 EQ18 SANDWICH EQ19 EQ20 WOK EQ14 EQ15 EQ21 EQ22 EQ23 BREAKFAST EQ13 DEMOLITION EXISTING COLD WELL EXISTING HOT WELL EXISTING HOT WELL EXISTING FRYER EXISTING CONVECTION OVEN EXISTING HOT WELL EXISTING REFRIDGERATOR EXISTING WALL MOUNTED SINK GENERAL NOTES 1. 2. 3. EXISTING HOT WELL EXISTING HOT WELL EXISTING IMPINGER EXISTING PAN RACK EXISTING PIZZA MAKE TABLE 4. 5. EXISTING COLD WELL EXISTING COLD WELL EXISTING COLD WELL EXISTING HAND SINK EXISTING HOT WELL EXISTING HOT WELL EXISTING SINK EXISTING UNDERCOUNTER REFRIDGERATOR EXISTING UNDERCOUNTER REFRIDGERATOR 6. 7. 8. EXISTING HOT WELL 9. B C 10. IDENTIFICATION AND/OR ABATEMENT OF HAZARDOUS MATERIALS IS NOT PART OF THIS SCOPE OF WORK. IF ASBESTOS OR OTHER HAZARDOUS MATERIALS ARE ENCOUNTERED, THE CONTRACTOR SHALL NOTIFY THE OWNER IMMEDIATELY. REFER TO SPECIFICATIONS FOR RECYCLING, CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL REQUIREMENTS. OPENING IN THE EXISTING STRUCTURE SMALLER THAN 12" IN ANY DIRECTION ARE NOT IDENTIFIED ON THESE DRAWINGS. SUBCONTRACTORS SHALL BE RESPONSIBLE FOR PROVIDING OPENINGS SMALLER THAN 12" AS REQUIRED FOR INSTALLATION OF THEIR WORK. OPENINGS IN THE EXISTING STRUCTURE SHALL NOT BE MADE WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER. DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE STRUCTURAL INTEGRITY OF THE BUILDING. IF HIDDEN ELEMENTS OR DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY THE ARCHITECT IMMEDIATELY. PROTECT ADJACENT AREAS AND ITEMS "TO REMAIN" DURING DEMOLITION/CONSTRUCTION. REPAIR/REPLACE ITEMS DAMAGED DURING CONSTRUCTION. IF UNANTICIPATED HIDDEN ELEMENTS OR DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY THE OWNERS REPRESENTATIVE IMMEDIATELY. REFER TO CONSULTANT DRAWINGS FOR ADDITIONAL DEMOLITION WORK. REVIEW w/ OWNER TO DETERMINE WHAT, IF ANYTHING, WILL BE REMOVED BY OWNER AND WHAT, IF ANYTHING, IS TO BE SALVAGED & TURNED OVER TO OWNER. DEVICES SHOWN AS "DASHED" OR IN "DARK INK" ARE TO BE REMOVED. ELECTRICAL SUB-CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING DEVICES, DISCONNECTS, STARTERS, RELAYS, AND MISCELLANEOUS COMPONENTS AS REQUIRED. WIRING AND CONDUITS ASSOCIATED WITH REMOVED ITEMS SHALL BE REMOVED BACK TO SOURCE PANEL. DEVICES SHOWN AS "LIGHT INK" ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED. SEALED: CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: KEYED NOTES D1 19 D2 DISCONNECT POWER TO KITCHEN WOK EQUIPMENT EQ14, EQ-15, EQ-22 & EQ-23 TO ACCOMODATE WOK COUNTER/MILLWORK RENOVATION. REFER TO DRAWING E-113 ELECTRICAL PLAN - SERVERY FOR REINSTALLATION. EXISTING EQUIPMENT IS FED FROM CONDUIT AND WIRING IN FLOOR SLAB. DISCONNECT AND REMOVE POWER TO EXISTING KITCHEN EQUIPMENT EQ-13 AND EQ-16. REMOVE CONDUIT AND WIRING TO NEAREST HOMERUN JUNCTION BOX. REFER TO DRAWING E-113 ELECTRICAL PLAN - SERVERY FOR NEW EQUIPMENT LOCATIONS. 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com REVISIONS EQ12 EQ11 EQ10 EQ-13 EQ21 D1 EQ22 D2 Author CHECKED BY: Checker EQ9 17 16 EQ5 15 EQ15 EQ4 EQ7 14 EQ16 EQ3 EQ6 EQ17 EQ20 EQ2 12 11 EQ19 EQ18 RAMAPO COLLEGE OF NEW JERSEY D1 ELECTRICAL DEMOLITION SERVERY - ALTERNATE #1 D1 RCNJ No. 201437-01C PHASE 2: ALTERATIONS EQ8 EQ23 G EQ1 A 1 ELECTRICAL DEMO PLAN - FF1 - SERVERY 0 4 8 12 1/4" = 1'-0" NORTH ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS SHEET: ADD/ALT 1 ED-111 18031.00 EQ14 DRAWN BY: 505 RAMAPO VALLEY RD. MAHWAH, NY 07430 EQ-16 3/23/2016 3:29:04 PM NJDCA ELECTRONIC SUBMITTAL STAMP: SEALED: B C D E G J N QQ.1 Q.2 Q.3 CABIN TE 0 NA1D A EA B R KR0 , F N 50 D AT B T E R 0 0 CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. 18 DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: 17 KEYED NOTES 16 15 E1. CONNECT TO EXISTING UNDERGROUND EXTERIOR LIGHTING CIRCUITRY/CONDUIT THAT FEEDS BLDG. MOUNTED COLUMN LIGHTS (VIA TIME CLOCK & PHOTOCELL). EXTEND CIRCUIT USING (2) #12, #10G IN 3/4" RGS CONDUIT TO FEED NEW COLUMN LIGHT POLE (FIXTURE TYPE "S1") LOCATIONS SHOWN. REFER TO ELECTRICAL DETAIL SHEET E-310 FOR LIGHT FIXTURE SCHEDULE, TRENCH DETAIL AND LIGHT POLE FOUNDATION DETAIL. 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: 14 10.3 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com 13 CABINET BREA , KR01050F NA DAND BATTER 00 M MH RY TA 2 NI 9.9 SA M 30 RI 3 12 11 00 ND BATTER A NA 01050F BREAD KR 10.9 10.8 3D B.7 7 MH M 3 OR 9.9 ST M 30 RI S1 AIN DR 44 CH 08. EN 3 TR ATE GR UE S1 6 5 UE 4 G 3 UE 2.9 BUILDING LINE BELOW T LE IN S1 S1 T LE IN S1 UE S1 2 1 LP I K L M O REFER TO LANDSCAPE DRAWINGS FOR EXACT LOCATIONS. COORDINATE WITH OTHER TRADES AND EXISTING UNDERGROUND UTILITIES. (TYPICAL) T UL VA H TY ILI UT T LE IN ABOVE GRO UND F LP T LE IN A UE UE STEAM PIPE S WOOD FEN CE WOOD FEN CE E ON PH 5 LE 7.7 TE M 30 RI ABOVE G R O U N D STEAM PIPE S MH WOOD FEN CE MH ISSUED: 3.24.2016 S GA TY ILI UT 0 E ON PH 5 LE 9.9 TE M 30 RI AIN DR 37 CH 08. EN 3 TR ATE GR S1 RCNJ No. 201437-01C PHASE 2: ALTERATIONS 7.1 RAMAPO COLLEGE OF NEW JERSEY UE E1 X BO 20' FROM E X I S T IN G WOOD F E N C E L O CATION S GA GV E LIN PE PI ER RK MA SITE ELECTRICAL PLAN WEF ELECTRICAL SITE PLAN 9 1 CHECKED BY: 10.2 10 8 2.1 1.9 BFD LP A.4 DRAWN BY: DESCRIPTION: BID DOCUMENTS 8 16 SHEET: 24 1/8" = 1'-0" NORTH E-050 18031.00 BIN ET, 505 RAMAPO VALLEY RD. MAHWAH, NY 07430 CA REVISIONS E LIN PE PI ER RK MA 3/23/2016 3:29:06 PM NJDCA ELECTRONIC SUBMITTAL STAMP: GENERAL NOTES 1. E G J N QQ.1 DEVICES SHOWN AS LIGHT OR SHADED ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED. Q.2 Q.3 SEALED: 22 CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: B C D KPP3 KPP2 KPP1 21 KEYED NOTES 19 J 0 0 18 PPP-1 PPP-2 J LPK 17 G J 16 15 E2. PROVIDE (2) 1" RGS CONDUITS UNDER SLAB WITH PULL STRING STUBBING UP WITHIN STUD WALL AT LOCATION SHOWN FOR FUTURE POWER & LIGHTING. CONDUITS WILL BE EXTENDED TO DEVICE LOCATIONS DURING INTERIOR FINISHES PHASE. E3. PROVIDE (2) 1" RGS CONDUITS UNDER SLAB WITH PULL STRING STUBBING UP WITHIN STUD WALL AT LOCATION SHOWN FOR FUTURE POWER & DATA. CONDUITS WILL BE EXTENDED TO DEVICE LOCATIONS DURING INTERIOR FINISHES PHASE. E4. PROVIDE (3) 3/4" RGS CONDUITS WITH PULL STRING UNDER SLAB STUBBING UP WITHIN STUD WALL AT LOCATION SHOWN. CONDUITS AT VESTIBULE END SHALL RISE UP WITHIN MASONRY COLUMN FOR FUTURE POWER (VESTIBULE HVAC CEILING CASSETTE UNIT), VESTIBULE LIGHTS & FIRE ALARM DEVICES. PROVIDE DEVICE BOXES FOR FIRE ALARM DEVICES AND PENETRATE MASONRY WALL ABOVE VESTIBULE CEILING FOR LIGHTS AND HVAC POWER. 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com REVISIONS DRAWN BY: BFD CHECKED BY: WEF 14 10.3 RPK RCNJ No. 201437-01C PHASE 2: ALTERATIONS D 13 J DWR DW 11 CA ND BATTER A NA 01050F BREAD KR BIN ET, 10.9 10.8 E4 U U U D U U 10.2 10 U D D D U U U U D U U D B.7 U D U U D A.4 U 9 U U 8 U D U U WAP D D D U 7.1 U U U U U D U U U U 6 5 U D D D U U D U D U U D D U U U U U U D D D U E1 U 7 RAMAPO COLLEGE OF NEW JERSEY 00 ELECTRICAL PLAN 12 U U D U U 4 U D D U 3 U U 2.9 U D D U U 2.1 1.9 E2 2 1 E3 A F H I K L M O ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS 1 ELECTRICAL PLAN - FF1 PH2 1/8" = 1'-0" SHEET: E-100 18031.00 J E1. SAWCUT FLOOR AND PROVIDE (2) 1" RGS CONDUITS WITH PULL STRING FROM NEARBY WALL (GOES TO DECK) TO EACH LOCATION SHOWN FOR FUTURE POWER & DATA AT SEATING/SHORT WALLS. CONCEAL CONDUITS IN WALL GOING TO DECK AND SWEEP OUT CLOSE TO BOTTOM OF STRUCTURE. SAWCUT AREA INDICATED BY SHADING. 505 RAMAPO VALLEY RD. MAHWAH, NY 07430 20 3/23/2016 3:29:11 PM NJDCA ELECTRONIC SUBMITTAL STAMP: GENERAL NOTES 1. 2. 3. 4. 5. E G J N QQ.1 Q.2 Q.3 6. 22 7. 8. EXISTING EMERGENCY LIGHTING PANEL EPPB GE SPECTRA SERIES 9. EPPB 10. ERP-B 11. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL MATERIAL AND EQUIPMENT IN ACCORDANCE WITH THE CURRENT N.E.C. (NATIONAL ELECTRICAL CODE). ALL WORK SHALL BE INSTALLED NEAT AND WORKMANLIKE COMPLYING WITH THE STANDARDS OF N.E.C.. THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL CONDITIONS, LOCATIONS, DIMENSIONS, AND COUNTS AS SHOWN AND NOTED ON THE DRAWINGS FOR THIS WORK PRIOR TO BIDDING. NO ADDITIONAL COST WILL BE ISSUED FOR FAILURE TO COMPLY WITH THIS REQUIREMENT. THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIAL, AND SUPERVISION NECESSARY TO ACCOMPLISH THE WORK AS SHOWN AND NOTED ON THE DRAWINGS. ANY DEVIATION FROM THE DRAWINGS SHALL BE APPROVED BY THE OWNER. THE ELECTRICAL CONTRACTOR SHALL DO ALL CUTTING AND PATCHING OF THE BUILDING MATERIALS REQUIRED FOR THE INSTALLATION OF HIS WORK. ALL FIRE RATED WALLS, FLOORS, OR CEILINGS SHALL BE SEALED TO MAINTAIN THE FIRE RATING. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL OF ALL TOOLS, DEBRIS, AND GENERAL CLEAN UP FROM HIS WORK. ALL WORK SHALL BE COORDINATED WITH THE OTHER TRADES. THE ELECTRICAL CONTRACTOR SHALL MAKE ALL NECESSARY TESTS TO INSURE THAT THE ENTIRE INSTALLATION IS FREE FROM IMPROPER GROUNDS AND FROM SHORTED AND/OR OPEN CIRCUITS. VOLTAGE AND CURRENT TESTS SHALL BE MADE BEFORE ANY MOTORS ARE PLACED IN OPERATION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND PAYING FOR ALL REQUIRED PERMITS. THE ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL WORK AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER ACCEPTANCE OF THE WORK AND MATERIALS. ALL ELECTRICAL EQUIPMENT AND DEVICES SHALL BE LABELED WITH 1/2" DYNO TAPE FOR THE SOURCE AND CONTROL LOCATION. SEALED: CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: D 21 20 19 0 0 18 PPP-1 PPP-2 15 E4. PROVIDE RECEPTACLES AND DATA DEVICES AS SHOWN. REUSE EXISTING AREA RECEPTACLE CIRCUIT AND MODIFY AND EXTEND TO NEW LOCATIONS AS SHOWN. PROVIDE ALL CONDUIT, MC CABLE AND WIRING REQUIRED FOR A FULLY FUNCTIONAL INSTALLATION. J 1 E-112 RPK 14 10.3 D 13 J D E1 12 DWR DW 11 00 CA BIN ET, ND BATTER A NA 01050F BREAD KR 10.9 10.8 E4 J G RESIDENTIAL SERVERY 138 J E2 E5 UPPER RESIDENTIAL DINING 139 ERP-B-1,3 U U U D U U U D D D U U U U D U U D B.7 CEILING UNIT HEATER CUH-1 U D U U A.4 D D U D U 72" U J E3 72" D 72" U D U 7.1 WAP D D E5 D U E2 U 8 U U U D D U U U U U D U U D D U E5 U D U U 6 5 U D D D U U U D U U D U D U D U U U U E6 U 4 E4 U U U LOWER RESIDENTIAL DINING 140 D D U U U D UPPER LOUNGE 137 7 U U E5 10.2 10 9 E6 72" E2. PROVIDE NEW JUNCTION BOXES ABOVE CEILING FOR NEW MOTOR OPERATED DOORS. MODIFY AND EXTEND EXISTING CIRCUITRY TO NEW LOCATION SHOWN. PROVIDE ALL CONDUIT, MC CABLE AND WIRING REQUIRED FOR A FULLY FUNCTIONAL INSTALLATION. PROVIDE WIRING AND CONNECTIONS TO DOOR OPERATOR PUSH BUTTONS. COORDINATE LOCATIONS AND INSTALLATION IN FIELD. 17 E2 16 E1. RE-INSTALL RECEPTACLE AND DATA JACKS FOR A.T.M. AT LOCATION SHOWN. MODIFY AND EXTEND CIRCUITRY AND DATA CABLES TO NEW LOCATION. PROVIDE NEW CONDUIT, MC CABLE, WIRING AND DATA CABLING AS REQUIRED FOR A FULLY FUNCTIONAL INSTALLATION. E3. PROVIDE 208V, 2-POLE TOGGLE SWITCH DISCONNECT AND CONNECTION TO NEW CEILING UNIT HEATER CUH-1. RECESS TOGGLE DISCONNECT IN GYP. CEILING AND PROVIDE FLUSH FACEPLATE FOR A CLEAN INSTALLATION. PROVIDE A 2-POLE 20A CIRCUIT BREAKER IN EXISTING GE PANELBOARD ERP-B AND CIRCUIT USING 3/4" EMT CONDUIT AND (3) #10, #10G. COORDINATE EXACT LOCATION AND INSTALLATION IN FIELD. LPK J KEYED NOTES 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com REVISIONS DRAWN BY: BFD CHECKED BY: WEF E5. PROVIDE RECEPTACLES AND DATA DEVICES AS SHOWN. PROVIDE 3/4" CONDUIT, MC CABLE AND #12 WIRING AND CIRCUIT TO NEAREST AVAILABLE 120/208V PANEL WITH SPACE (PPP-1, PPP-2, LPK, DWR) VERIFY AVAILABLE SPACE IN PANELBOARDS PRIOR TO INSTALLATION. PROVIDE 20A, 1-POLE CIRCUIT BREAKER COMPATIBLE WITH EXISTING PANEL FOR EACH CIRCUIT SHOWN. E6. E.C. SHALL RUN ALL DATA CABLING TO CAMPUS I.T. DATA RACK LOCATED IN THE SECOND FLOOR ELECTRICAL ROOM. PROVIDE 10' OF LOOSE COILED CABLE AT DATA RACK FOR TERMINATION BY CAMPUS I.T. PERSONNEL. PROVIDE J-HOOKS FROM DATA JACK LOCATIONS TO THIS ROOM. TAKE SPECIAL CARE TO ROUTE CABLING AND J-HOOKS ABOVE CEILING ELEMENTS TO LIMIT VISIBLE SECTIONS FROM PUBLIC VIEW. WHERE CABLING AND J-HOOKS MUST BRIDGE SMALL GAPS BETWEEN CEILING ELEMENTS, PAINT J-HOOKS TO MATCH OTHER EXPOSED BUILDING MATERIALS. ALSO TAKE SPECIAL CARE ON THE SECOND FLOOR AS THE CEILINGS IN THIS AREA ARE NOT BEING REPLACED. E.C. SHALL BE RESPONSIBLE FOR REPLACEMENT OF BROKEN TILES AND ANY TEMPORARY REMOVAL/RE-INSTALLATION OF EXISTING LIGHTS OR DEVICES AS REQUIRED FOR A COMPLETE AND FULLY FUNCTIONAL INSTALLATION. COORDINATE INSTALLATION WITH CAMPUS I.T. DEPARTMENT PERSONNEL. E7. PROVIDE JUNCTION BOX AND CONNECTION AT DOOR FOR DOOR ALARM. PROVIDE 3/4" CONDUIT, MC CABLE AND #12 WIRING AND CIRCUIT TO NEAREST AVAILABLE 120/208V PANEL WITH SPACE (PPP-1, PPP-2, LPK, DWR) VERIFY AVAILABLE SPACE IN PANELBOARDS PRIOR TO INSTALLATION. COORDINATE LOCATION AND INSTALLATION WITH ARCHITECT AND CAMPUS PERSONNEL. PROVIDE 20A, 1-POLE CIRCUIT BREAKER COMPATIBLE WITH EXISTING PANEL FOR CIRCUIT FEED. U D D U 3 J D 72" E6 U E7 D D E6 72" U 72" D E5 72" U U 2.9 U LOWER LOUNGE 136 2.1 1.9 2 1 A F H I K L M ISSUED: 3.24.2016 O DESCRIPTION: BID DOCUMENTS 1 ELECTRICAL PLAN - FF1 0 8 16 24 1/8" = 1'-0" SHEET: NORTH E-110 18031.00 EXISTING 120/208V, 3PH, 4W FEDERAL PACIFIC PANEL 505 RAMAPO VALLEY RD. MAHWAH, NY 07430 KPP2 KPP1 RCNJ No. 201437-01C PHASE 2: ALTERATIONS KPP3 RAMAPO COLLEGE OF NEW JERSEY C ELECTRICAL ALTERATIONS FIRST FLOOR B 3/23/2016 3:29:12 PM NJDCA ELECTRONIC SUBMITTAL STAMP: SEALED: E G J N QQ.1 CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. Q.2 Q.3 DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: 22 KEYED NOTES E1. DISCONNECT POWER TO EXISTING 1HP, 480V, 3PH KITCHEN EXHAUST FAN (EF-6, OVER WOK) AND RECONNECT AFTER IT HAS BEEN REPLACED. LOCATE EXISTING DISCONNECT AND REPLACE FUSES WITH 10A SIZE AS REQUIRED FOR NEW 5HP, 480V, 3PH FAN. COORDINATE ALL WORK. EXISTING ELECTRICAL PANEL "AC-1" 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: EXISTING EMERGENCY LIGHT POWER PANEL "EPP-A" B C D 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com ELECTRICAL ROOM 21 EXISTING KITCHEN EXHAUST FAN EF-6 (OVER WOK) ON ROOF ABOVE REVISIONS 20 EXISTING NOTIFIER FIRE ALARM PANEL 19 DRAWN BY: BFD CHECKED BY: WEF 18 13 DN 12 11 10.9 10.8 10.2 A 1 ELECTRICAL PLAN - FF2 F H I K M 0 8 16 24 1/8" = 1'-0" NORTH ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS SHEET: E-111 18031.00 14 10.3 RAMAPO COLLEGE OF NEW JERSEY 15 ELECTRICAL ALTERATIONS SECOND FLOOR 16 RCNJ No. 201437-01C PHASE 2: ALTERATIONS 17 505 RAMAPO VALLEY RD. MAHWAH, NY 07430 E1 3/23/2016 3:29:13 PM NJDCA ELECTRONIC SUBMITTAL STAMP: SEALED: CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: KEYED NOTES E1. MODIFY AND EXTEND EXISTING HAND DRYER CONDUIT AND CIRCUITRY TO NEW LOCATIONS SHOWN. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT IN FIELD. N 20 20 E3. MODIFY AND EXTEND EXISTING DRINKING FOUNTAIN CONDUIT AND CIRCUITRY TO NEW LOCATION SHOWN. PROVIDE NEW GFCI OUTLET. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT IN FIELD. 19 E4. INSTALL NEW LIGHT FIXTURES AND DUAL TECHNOLOGY OCCUPANCY SENSORS AND CONNECT TO EXISTING CIRCUITRY. CONNECT EMERGENCY FIXTURES DENOTED WITH "E" TO EXISTING EMERGENCY CIRCUIT. LINK OCCUPANCY SENSORS TOGETHER IN EACH BATHROOM TO WORK TO CONTROL AS A SINGLE SPACE. THE EMERGENCY FIXTURES SHALL ALSO BE TIED TO SAID OCCUPANCY SENSORS VIA AN EMERGENCY LIGHTING CONTROL UNIT WITH SWITCHED INPUT. PROVIDE NEW CONDUIT, WIRING AND MC CABLE AS REQUIRED TO FURNISH A FULLY FUNCTIONAL INSTALLATION. F2 19 F2 E4 (TYPICAL) 18 J F F2 E V J F2 S F2 E2 F1 D E5 E E4 F2 F1 (TYPICAL) F F1 E1 17 S V REUSE EXISTING NORMAL & EMERGENCY F1 LIGHTING CIRCUITS F1 F2 E5 F1 F2 17 E F2 F1 J D D E1 E F2 E F2 E J G D G E3 1 ELECTRICAL PLAN - FF1 - RESTROOMS 1/4" = 1'-0" 2 LIGHTING PLAN - FF1 - BATHROOMS 1/4" = 1'-0" REUSE EXISTING NORMAL & EMERGENCY LIGHTING CIRCUITS 15 H G G 15 CHECKED BY: WEF ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS SHEET: E-112 18031.00 E J J E2 BFD 505 RAMAPO VALLEY RD. MAHWAH, NY 07430 F2 F2 DRAWN BY: RCNJ No. 201437-01C PHASE 2: ALTERATIONS E F1 REVISIONS E5. REINSTALL EXISTING FIRE ALARM DEVICES AND CONNECT TO EXISTING CIRCUITRY. PROVIDE NEW CONDUIT, WIRING AND MC CABLE AS REQUIRED TO FURNISH A FULLY FUNCTIONAL INSTALLATION. D F2 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com RAMAPO COLLEGE OF NEW JERSEY F1 ENGINEER: ELECTRICAL/ LIGHTING ALTERATIONS - TOILET ROOMS N E2. MODIFY AND EXTEND UNUSED EXISTING HAND DRYER CONDUIT AND CIRCUITRY TO FEED NEW SINK, URINAL AND TOILET AUTOMATIC FLUSH VALVE TRANSFORMERS. PROVIDE CONDUIT AND LOW VOLTAGE WIRING FROM TRANSFORMER LOCATIONS TO EACH SINK, URINAL AND TOILET AUTOMATIC FLUSH VALVE LOCATION. COORDINATE EXACT LOCATIONS IN FIELD. CONCEAL ALL CONDUIT AND WIRING WITHIN WALLS AND ABOVE CEILING. PROVIDE A FULLY FUNCTIONAL INSTALLATION. 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com EXISTING EQUIPMENT SCHEDULE KITCHEN EQUIPMENT SCHEDULE Electrical Connection Height Cold Water (in) Cold Water Conn. Height(in) Hot Water (in) Hot Water Conn. Height(in) Indirect Waste Size Direct Waste Size Direct Waste Conn. Height(in) Gas Conn. Gas Size(in) Height (in) Gas MBTU ItemNo Quantity Category Mfr Model Voltage Phase Amps Cycle Hp 1 1 Sandwich / Salad Preparation Refrigerator Continental Refrig SW72-30M-FB 115 1 60 2 1 Range, 36", 6 Open Burners Vulcan 36S-6B 3/4" 215.0 3 1 Charbroiler Vulcan VACB36 3/4" 102.0 4 1 Countertop Griddle Vulcan 948RX 120 1 1.0 60 3/4" 108.0 5 1 Equipment Stand, Refrigerated Base Vulcan ARS84 115 1 12.0 60 6 1 Carving Station / Shelf Hatco DCSB400-3624-2 120 1 10.83 60 7 1 Fryer Vulcan LG500 8 1 Work Table Advance Tabco KSS-305 9 1 Dual Temp Food Well, Drop-In Wells HRCP-7300 115 1 5.6 60 Wells HRCP-7300 208/240 1 14.4/16.7 60 1 7.6 Kw 1/2 1.3 Connection Type NEMA Cord & Plug 5-15P Cord & Plug 5-15P Cord & Plug 5-15P Cord & Plug 5-15P 3/4" 1/3 3.8/5.0 Drop-In Sink Advance Tabco DI-1-2012 11 1 Microwave Oven ACP RCS10TS 120 1 12 1 Conveyor Toaster Adcraft CVYT-120 120 1 13 1 Reach-In Freezer True STG1F-1S 115 1 6.8 60 1/2 Cord & Plug 5-15P 14 1 Reach-In Refrigerator True STG1R-1S 115 1 4.8 60 1/3 Cord & Plug 5-15P 15 1 Heated Shelf Food Warmer Hatco GRS-72-L 120 1 5-15P 1-1/2" 15 60 1 60 1.7 5-15P 1.45 Cord & Plug 0.45 Direct Spare Number 2 Drop-In Hot Well Wells SS-10 120 1 3.75 60 18 1 Display Freezer Entree OFL-40 115 1 1.0 60 19 1 Dipper Well AllPoints 56-1462 20 1 L-Shaped Work Table Advance Tabco KTMS-307 Advance Tabco TA-11A-2 Hatco DL-775-CL Hatco DL-SWITCH-16AMP Beverage Air UCR60A 1 4 Decorative Lamp 4 1 Reach-In Undercounter Refrigerator 1/8 5-15P Cord & Plug EXISTING COLD WELL GENERAL NOTES EXISTING HOT WELL EXISTING HOT WELL EXISTING FRYER EXISTING CONVECTION OVEN 1. 2. EXISTING HOT WELL EXISTING REFRIDGERATOR EXISTING WALL MOUNTED SINK EXISTING HOT WELL EXISTING HOT WELL PROVIDE ALL CONDUIT, WIRING, HANGERS, SUPPORTS, AND MISCELANEOUS COMPONENTS REQUIRED TO FURNISH A FULLY OPERATIONAL INSTALLATION. EXISTING POWER FEEDS TO WOK AND SERVER LINE ISLANDS IS IN OR UNDER THE EXISTING SLAB. COORDINATE ALTERATION WORK TO RE-USE EXISTING FLOOR PENETRATIONS AND IN SLAB CONDUIT WHERE POSSIBLE. COORDINATE EXISTING CONDUIT FLOOR PENETRATIONS AND EQUIPMENT FEEDS WITH ARCHITECT AND NEW CASEWORK. EXISTING IMPINGER EXISTING PAN RACK EXISTING PIZZA MAKE TABLE SEALED: EXISTING COLD WELL EXISTING COLD WELL EXISTING COLD WELL EXISTING HAND SINK EXISTING HOT WELL EXISTING HOT WELL EXISTING SINK EXISTING UNDERCOUNTER REFRIDGERATOR EXISTING UNDERCOUNTER REFRIDGERATOR EXISTING HOT WELL CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. (2) 1-1/2" 1 120 2.08 60 .25 DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. Direct ARCHITECT: 16.0 115 1 8.2 60 1/4 KEYED NOTES B C D E E1. MODIFY AND EXTEND EXISTING POWER AND CIRCUITRY AS REQUIRED TO RE-CONNECT POWER TO EXISTING KITCHEN WOK EQUIPMENT EQ-14, EQ-15, EQ-22 & EQ-23. 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: E2. MODIFY AND EXTEND EXISTING POWER AND CIRCUITRY AS REQUIRED TO RE-CONNECT POWER TO EXISTING RE-LOCATED KITCHEN EQUIPMENT EQ-13 AND EQ-16. E3. DISCONNECT POWER TO EXISTING 208V INDUCTION RANGES. MODIFY AND EXTEND (1) EXISTING CIRCUIT FOR CONNECTION TO NEW SANDWICH/SALAD PREP REFRIGERATOR. REMOVE OTHER CIRCUIT BACK TO SOURCE PANEL PPP-2 AND RE-LABEL CIRCUIT BREAKER SPARE. E12 19 11 E13 E2 12 10 E4. COUNTERTOP GRIDDLE: PROVIDE NEW 120V, 5-20R RECEPTACLE. PROVIDE A 1-POLE, 20A CIRCUIT BREAKER IN EXISTING PANEL PPP-2 AND (2) #12, #12G IN 3/4" CONDUIT TO FEED NEW EQUIPMENT. CONCEAL CONDUIT IN WALL AND ABOVE CEILING TO MINIMIZE VISIBILITY. IN EXPOSED CEILING AREA, PAINT TO MATCH EXISTING FINISH. COORDINATE INSTALLATION AND LOCATION OF EQUIPMENT IN FIELD. EQ13 EQ12 EQ11 EQ21 EQ22 EQ10 E5. DUAL TEMP DROP IN FOOD WELLS: PROVIDE A 1-POLE, 20A CIRCUIT BREAKER IN EXISTING PANEL PPP-1 OR PPP-2 AND (2) # 12, #12G IN 3/4" CONDUIT TO FEED NEW 120V FOOD WELL. PROVIDE A 2-POLE, 20A CIRCUIT BREAKER IN EXISTING PANEL PPP-1 OR PPP-2 AND (3) #12, #12G IN 3/4" CONDUIT TO FEED NEW 208V FOOD WELL. USE EXSITNG IN SLAB CONDUITS OR PROVIDE NEW FEED FROM NEW WALL AND INSIDE CASEWORK. CONCEAL CONDUIT IN WALL, CASEWORK, AND ABOVE CEILING TO MINIMIZE VISIBILITY. IN EXPOSED CEILING AREA, PAINT TO MATCH EXISTING FINISH. COORDINATE INSTALLATION AND LOCATION OF EQUIPMENT IN FIELD. 8 E15 E1 5-20R 13 E10 G 5-20R 14 PPP-1 20 E6. DISCONNECT POWER TO ACCOMMODATE REMOVAL OF EXISTING HOT WELLS. CONNECT (1) EXISTING 120V CIRCUIT TO NEW REPLACEMENT HOT WELLS (3.75A EA.). MODIFY AND EXTEND SECOND EXISTING CIRCUIT TO FEED NEW DISPLAY FREEZER (1A, 5-15P). PROVIDE NEW 5-20R RECEPTACLE FOR DISPLAY FREEZER. LPK EQ9 17 E1 E7. EQUIPMENT STAND, REFRIGERATED BASE: PROVIDE NEW 120V, 5-20R RECEPTACLE. PROVIDE A 1-POLE, 20A CIRCUIT BREAKER IN EXISTING PANEL PPP-2 AND (2) #12, #12G IN 3/4" CONDUIT TO FEED NEW EQUIPMENT. CONCEAL CONDUIT IN WALL AND ABOVE CEILING TO MINIMIZE VISIBILITY. IN EXPOSED CEILING AREA, PAINT TO MATCH EXISTING FINISH. COORDINATE INSTALLATION AND LOCATION OF EQUIPMENT IN FIELD. EQ8 EQ15 EQ23 9 E1 E9 EXISTING SERVERY ELECTRICAL PANELS 6 E5 8 16 E8. RE-USE EXISTING RECEPTACLE TO POWER NEW REACH-IN UNDERCOUNTER REFRIGERATOR. MODIFY AND EXTEND LOCATION AS REQUIRED. COORDINATE INSTALLATION AND LOCATION OF EQUIPMENT IN FIELD. 15 E9. REMOVE EXISTING 208V CIRCUIT AND RECEPTACLE TO FEED A NEW 120V CARVING STATION (5-15P). PROVIDE A 5-20R RECEPTACLE AND MODIFY EXISTING WIRING AS REQUIRED. FIELD VERIFY AND REPLACE EXISTING CIRCUIT 2-POLE BREAKER WITH (2) NEW 20A/1P CIRCUIT BREAKERS, REUSE (1) FOR 120V CARVING STATION. RE-USE EXSTING IN SLAB CONDUIT FOR POWER FEED. PROVIDE NEW #12 WIRING AND COORDINATE INSTALLATION AND LOCATION OF EQUIPMENT IN FIELD. 5-20R 4 5 5-20R E4 3 E10. RE-USE EXISTING RECEPTACLE TO POWER NEW HEATED SHELF FOOD WARMER. MODIFY AND EXTEND LOCATION AS REQUIRED. COORDINATE INSTALLATION AND LOCATION OF EQUIPMENT IN FIELD. E7 E11. MICROWAVE OVEN: PROVIDE A 1-POLE, 20A CIRCUIT BREAKER IN EXISTING PANEL PPP-1 OR PPP-2 AND (2) #12, # 12G IN 3/4" CONDUIT TO FEED NEW 120V, 20A DUPLEX RECEPTACLE. CONCEAL CONDUIT IN WALL AND ABOVE CEILING TO MINIMIZE VISIBILITY. IN EXPOSED CEILING AREA, PAINT TO MATCH EXISTING FINISH. COORDINATE INSTALLATION AND LOCATION OF EQUIPMENT IN FIELD. EQ4 EQ7 14 7 EQ16 E12. CONVEYOR TOASTER: PROVIDE A 1-POLE, 20A CIRCUIT BREAKER IN EXISTING PANEL PPP-1 OR PPP-2 AND (2) #12, # 12G IN 3/4" CONDUIT TO FEED NEW 120V, 20A DUPLEX RECEPTACLE. CONCEAL CONDUIT IN WALL AND ABOVE CEILING TO MINIMIZE VISIBILITY. IN EXPOSED CEILING AREA, PAINT TO MATCH EXISTING FINISH. COORDINATE INSTALLATION AND LOCATION OF EQUIPMENT IN FIELD. (TYPICAL FOR 2 LOCATIONS) EQ6 EQ3 E2 13 2 E13. REACH IN FREEZER AND REACH IN REFRIGERATOR: PROVIDE A 1-POLE, 20A CIRCUIT BREAKER IN EXISTING PANEL PPP-1 OR PPP-2 AND (2) #12, #12G IN 3/4" CONDUIT TO FEED NEW 120V, 20A DUPLEX RECEPTACLE. CONCEAL CONDUIT IN WALL AND ABOVE CEILING TO MINIMIZE VISIBILITY. IN EXPOSED CEILING AREA, PAINT TO MATCH EXISTING FINISH. COORDINATE INSTALLATION AND LOCATION OF EQUIPMENT IN FIELD. (TYPICAL FOR EACH PIECE OF EQUIPMENT) E8 EQ17 18 E6 22 EQ20 EQ2 19 12 17 BFD CHECKED BY: WEF E14. RE-USE EXISTING RECEPTACLE CIRCUIT TO POWER NEW RECEPTACLES. MODIFY & EXTEND CIRCUITRY AS REQUIRED. PROVIDE CONDUIT, MC CABLE AND #12 WIRING REQUIRED TO FURNISH A FULLY FUNCTIONAL INSTALLATION. 11 EQ18 17 DRAWN BY: PPP-2 E14 EQ14 REVISIONS E15. PROVIDE A 1-POLE, 20A CIRCUIT BREAKER IN EXISTING PANEL PPP-1 OR PPP-2 AND (2) #12, #12G IN 3/4" CONDUIT TO FEED NEW 120V, HEAT LAMPS (EQUIPMENT #21) AND CONTROL SWITCH. INSTALL CONTROL SWITCH AT SERVER STATION, COORDINATE EXACT LOCATION IN FIELD. CONCEAL CONDUIT IN WALL AND ABOVE CEILING TO MINIMIZE VISIBILITY. IN EXPOSED CEILING AREA, PAINT TO MATCH EXISTING FINISH. COORDINATE INSTALLATION AND LOCATION OF EQUIPMENT IN FIELD. EQ1 EQ19 G 1 E3 ISSUED: 3.24.2016 A 1 DESCRIPTION: BID DOCUMENTS ELECTRICAL PLAN - FF1 - SERVERY 1/4" = 1'-0" SHEET: ADD/ALT 1 E-113 18031.00 12 5-20R 505 RAMAPO VALLEY RD. MAHWAH, NY 07430 5-20R RCNJ No. 201437-01C PHASE 2: ALTERATIONS 5-20R 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com RAMAPO COLLEGE OF NEW JERSEY E11 ELECTRICAL ALTERATIONS SERVERY - ALTERNATE #1 E12 G 22 5-15P Cord & Plug 60 17 21 150.0 Direct 1 16 DESSERT EQ16 GRILL EQ3 EQ4 EQ6 EQ7 HOMETOWN EQ5 EQ8 EQ9 MEDITERRANEAN EQ1 EQ2 PIZZA EQ10 EQ11 EQ12 SALAD EQ17 EQ18 SANDWICH EQ19 EQ20 WOK EQ14 EQ15 EQ21 EQ22 EQ23 BREAKFAST EQ13 Direct 10 G 3/23/2016 3:29:15 PM NJDCA ELECTRONIC SUBMITTAL STAMP: 3/23/2016 3:29:25 PM NJDCA ELECTRONIC SUBMITTAL STAMP: GENERAL NOTES 1. E G J N QQ.1 DEVICES SHOWN AS LIGHT OR SHADED ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED. Q.2 Q.3 SEALED: B C D KPP2 KPP3 TC 21 KPP1 E1 20 F CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. V 19 DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: H D F F V D V 18 H F V D D S KEYED NOTES S F 17 E1. PROVIDE 2-CHANNEL TIME CLOCK IN ELECTRICAL ROOM FOR CONTROL OF NEW EXTERIOR COLUMN LIGHTS IN ELECTRICAL ROOM. COORDINATE EXACT LOCATION IN FIELD. BASIS OF DESIGN: INTERMATIC ET90215C. H F H H V X1 16 X2 E3. PROVIDE 3/4" RGS CONDUIT WITH #12 WIRE FROM TIME CLOCK AND PHOTOCELL TO COLUMN LIGHT LOCATIONS. REFER TO ARCHITECTURAL FLOOR & ELEVATION PLANS FOR LOCTIONS. COLUMN SPECIFIED IN A-SERIES DRAWINGS, WIRED & INSTALELD PER DIVISION 26. CONDUIT AND WIRING CONNECTIONS TO THE POWER SOURCE WILL BE PROVIDED IN FUTURE PHASE. CONTROLS SHALL BE: PHOTOCELL "ON", TIME CLOCK "OFF". PROVIDE ALL CONDUIT, BOXES, WIRING, TRENCHING & SAWCUTTING, & MISCELLANEOUS HARDWARE REQUIRED FOR LIGHT LOCATIONS SHOWN. H H F D V S E4 H D V H F 13 V D 3 S UG 12 DWR DW S 11 REVISIONS E4. CONDUITS SHALL RUN FROM PHOTOCELL TO TIMECLOCK. FROM TIMECLOCK, CONDUITS SHALL RUN TO TWO INTERIOR COLUMNS (ONE AT VESTIBULE/SEATING EXPANSION, ONE AT RESIDENTIAL DINING EXPANSION), THEN CONTINUE IN SERIES TO REMAINING COLUMNS. DRAWN BY: BFD E5. REINSTALL EXIT SIGN REMOVED DURING DEMOLITION. CHECKED BY: WEF/PP E6. REINSTALL FIRE ALARM DEVICES REMOVED DURING DEMOLITION. 10.9 10.8 3D H S D E3 H H F RCNJ No. 201437-01C PHASE 2: ALTERATIONS H S S F F 9 S S F 8 10.2 10 D UG S E3 X1 S UG S S E6 F F F D 7 S 7.1 E3 E3 S D E3 S S S S S UG UG UG S X1 6 5 E5 F F E3 E6 X1 E3 4 S S D S S E3 E5 UG S S UG E4 S F S S E3 D H UG UG 3 S 2.9 FF X1 S E3 E3 E3 E3 S F F 2.1 1.9 S PC X1 UG UG RAMAPO COLLEGE OF NEW JERSEY H X1 B.7 LIGHTING - FIRST FLOOR H X1 A.4 UG S S 2 1 E2 A F H I K L M O ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS 1 LIGHTING PLAN - FF1 PH2 1/8" = 1'-0" SHEET: E-200 18031.00 V H D 14 10.3 F RPK 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com 505 RAMAPO VALLEY RD. MAHWAH, NY 07430 F ENGINEER: E2. PROVIDE LIGHTING PHOTOCELL FOR CONTROL OF EXTERIOR COLUMN LIGHTS IN CONJUNCTION WITH NEW TIME CLOCK. MOUNT PHOTOCELL ON OUTSIDE FACE OF ROOF CANOPY, FLUSH MOUNTED AT 21'-0" AFF. 15 D 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com 3/23/2016 3:29:41 PM NJDCA ELECTRONIC SUBMITTAL STAMP: GENERAL NOTES 1. 2. 3. 4. E G J N QQ.1 Q.2 Q.3 5. EMERGENCY LIGHTING PANEL (ALSO ONE ON THE SECOND FLOOR ELEC/MECH. ROOM ABOVE) 6. 7. EPPB B C 8. TIME CLOCK LOCATION: CONNECT SITE COLUMN LIGHTS TO TIME CLOCK VIA PHOTOCELL. OPERATION SHALL BE PHOTOCELL "ON", TIME CLOCK "OFF" UNLESS DIRECTED OTHERWISE BY CAMPUS PERSONNEL. D 9. 10. 11. TC IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL MATERIAL AND EQUIPMENT IN ACCORDANCE WITH THE CURRENT N.E.C. (NATIONAL ELECTRICAL CODE). ALL WORK SHALL BE INSTALLED NEAT AND WORKMANLIKE COMPLYING WITH THE STANDARDS OF N.E.C.. THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL CONDITIONS, LOCATIONS, DIMENSIONS, AND COUNTS AS SHOWN AND NOTED ON THE DRAWINGS FOR THIS WORK PRIOR TO BIDDING. NO ADDITIONAL COST WILL BE ISSUED FOR FAILURE TO COMPLY WITH THIS REQUIREMENT. THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIAL, AND SUPERVISION NECESSARY TO ACCOMPLISH THE WORK AS SHOWN AND NOTED ON THE DRAWINGS. ANY DEVIATION FROM THE DRAWINGS SHALL BE APPROVED BY THE OWNER. THE ELECTRICAL CONTRACTOR SHALL DO ALL CUTTING AND PATCHING OF THE BUILDING MATERIALS REQUIRED FOR THE INSTALLATION OF HIS WORK. ALL FIRE RATED WALLS, FLOORS, OR CEILINGS SHALL BE SEALED TO MAINTAIN THE FIRE RATING. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL OF ALL TOOLS, DEBRIS, AND GENERAL CLEAN UP FROM HIS WORK. ALL WORK SHALL BE COORDINATED WITH THE OTHER TRADES. THE ELECTRICAL CONTRACTOR SHALL MAKE ALL NECESSARY TESTS TO INSURE THAT THE ENTIRE INSTALLATION IS FREE FROM IMPROPER GROUNDS AND FROM SHORTED AND/OR OPEN CIRCUITS. VOLTAGE AND CURRENT TESTS SHALL BE MADE BEFORE ANY MOTORS ARE PLACED IN OPERATION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND PAYING FOR ALL REQUIRED PERMITS. THE ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL WORK AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER ACCEPTANCE OF THE WORK AND MATERIALS. ALL ELECTRICAL EQUIPMENT AND DEVICES SHALL BE LABELED WITH 1/2" DYNO TAPE FOR THE SOURCE AND CONTROL LOCATION. 21 SEALED: CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: E8 20 F V 19 KEYED NOTES E1. REPLACE (3) EXISTING 1'X4' SURFACE MOUNT FIXTURES WITH NEW LED FIXTURE, BASIS OF DESIGN: LITHONIA LBL4 30L EZ1 LP835. TURN EXISTING FLUORESCENT FIXTURES OVER TO CAMPUS PERSONNEL. RE-USE EXISTING CIRCUITRY. H F V H M LPK E2. PROVIDE NEW FIXTURES AND CORNER MOUNT OCCUPANCY SENSOR AS SHOWN. CONNECT TO EXISTING NORMAL AND EMERGENCY POWER CIRCUITS. FIXTURES DENOTED WITH AN "E" SHALL BE ON EMERGENCY CIRCUIT. PROVIDE EMERGENCY LIGHTING CONTROL UNITS TO ALLOW EMERGENCY FIXTURES TO BE SWITCHED WITH OTHER NEARBY "NORMAL POWER" AREA LIGHTING. PROVIDE ALL CONDUIT, WHIPS AND WIRING REQUIRED FOR A FULLY FUNCTIONAL INSTALLATION. F D 17 F2 E F2 H F H H V F2 E EXISTING VESTIBULE 132 F2 16 D H 14 10.3 F V V F4 H H F 13 V D 3 F4 S E1 E5. PROVIDE NEW FIXTURES AND OCCUPANCY SENSORS AS SHOWN. CONNECT TO EXISTING NORMAL AND EMERGENCY POWER CIRCUITS. FIXTURES DENOTED WITH AN "E" SHALL BE ON EMERGENCY CIRCUIT. OCCUPANCY SENSORS SHALL BE LINKED TOGETHER FOR CONTROL AS A SINGLE SPACE. PROVIDE EMERGENCY LIGHTING CONTROL UNITS TO ALLOW EMERGENCY FIXTURES TO BE SWITCHED WITH OTHER NEARBY "NORMAL POWER" AREA LIGHTING. PROVIDE ALL CONDUIT, WHIPS AND WIRING REQUIRED FOR A FULLY FUNCTIONAL INSTALLATION. PAINT ALL CONDUIT/WHIPS VISIBLE TO PUBLIC TO MATCH OTHER EXPOSED BUILDING ELEMENTS. E2 F4 F6 F6 S DW 11 F6 M E F2 H F F1 E3 H S F6 F6 F6 E F6 E7 E F4 E F4 F4 F17 F17 NEW VESTIBULE 141 F2 E 10.2 10 F F F4 MOUNT AT 7'-0" AFF (TYPICAL) B.7 E5 F2 M A.4 EXISTING DINING AREA 277V LIGHTING PANEL H H F6 E F4 E2 S E F6 F6 F6 E7. PROVIDE NEW FIXTURES AND SWITCH AS SHOWN. CONNECT TO NEAREST 120V TRACK LIGHTING CIRCUIT. PROVIDE ALL CONDUIT, WHIPS AND WIRING REQUIRED FOR A FULLY FUNCTIONAL INSTALLATION. PAINT ALL CONDUIT/WHIPS VISIBLE TO PUBLIC TO MATCH OTHER EXPOSED BUILDING ELEMENTS. 9 S D F10 F10 S UPPER LOUNGE 137 F6 E F4 E4 F10 F10 E LOWER RESIDENTIAL DINING 140 E (TYPICAL) F F11 F4 CIRCUIT TO SECOND SWITCH F6 E F4 F7 F4 F4 F4 F4 E E F4 F4 D E5 F4 F4 E F S D H F8 F8 F9 F8 F9 F6 A WEF F11 F11 F8 E F8 F11 F6 F11 F6 E F11 F11 F11 F11 PC MOUNT F9 FIXTURES AT 8'-6" AFF TO BOTTOM OF FIXTURE CHECKED BY: E4 S F9 E 2 1 M 2.1 1.9 E F F F9 E F8 F9 LOWER LOUNGE 136 F6 F6 F6 F4 S F9 F9 F4 S F4 3 FF E 2.9 F7 E F4 S S F8 MOUNT F7 FIXTURES AT 8'-0" AFF TO BOTTOM OF FIXTURE F7 F7 F4 S F4 S F8 4 D S F4 S F4 6 5 F S F4 F7 D F6 F5 F8 F7 F7 F4 E D F6 S F4 MOUNT AT 8'-0" AFF TO BOTTOM OF FIXTURE E S S F8 F4 F4 MOUNT AT 6'-0" AFF (TYPICAL) S F4 7 E S F4 E5 D S F8 F F10 E E8. PROVIDE 20A, 1-POLE CIRCUIT BREAKER IN NEARBY 277V PANEL EPPB AND CONDUIT & CIRCUITRY TO TIME CLOCK FOR EXTERIOR BUILDING AND COLUMN POLE LIGHTS. PROVIDE ALL CONDUIT, MC CABLE AND #12 WIRING REQUIRED FOR A FULLY FUNCTIONAL INSTALLATION. F7 F10 F4 F4 F7 E F3 S F F TO THIRD SWITCH D F7 F6 MOUNT AT 10'-6" AFF TO BOTTOM OF FIXTURE F4 E6 F10 S S E 7.1 F10 S F10 F4 E F4 S F10 F4 S MOUNT F4 FIXTURES IN LOWER DINING AT 10-0"" AFF TO BOTTOM OF FIXTURE S 8 E F6 F E6. RE-USE EXISTING AREA EMERGENCY LIGHTING CIRCUIT FOR NEW EMERGENCY FIXTURES. PROVIDE ALL CONDUIT, WHIPS AND WIRING AS REQUIRED TO CIRCUIT AS SHOWN ON DRAWING. PROVIDE EMERGENCY LIGHTING CONTROL UNITS TO ALLOW EMERGENCY FIXTURES TO BE SWITCHED WITH OTHER NEARBY "NORMAL POWER" AREA LIGHTING. PAINT ALL CONDUIT/WHIPS VISIBLE TO PUBLIC TO MATCH OTHER EXPOSED BUILDING ELEMENTS. F2 S S F6 E F2 F2 S UPPER RESIDENTIAL DINING 139 H 3D H S D MOUNT F6 FIXTURES AT 9'-0" AFF (TYPICAL) 10.9 10.8 BFD MOUNT F11 FIXTURES AT 7'-6" AFF TO BOTTOM OF FIXTURE MOUNT F8 FIXTURES AT 8'-0" AFF TO BOTTOM OF FIXTURE F H I K L M O ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS 1 LIGHTING PLAN - FF1 SHEET: 0 8 16 24 1/8" = 1'-0" NORTH E-210 18031.00 H F DRAWN BY: 505 RAMAPO VALLEY RD. MAHWAH, NY 07430 S F4 2 E-112 E4. PROVIDE NEW FIXTURES AND OCCUPANCY SENSORS AS SHOWN. CONNECT TO ADJACENT DINING AREA LIGHTING CIRCUIT. FIXTURES DENOTED WITH AN "E" SHALL BE CONNECTED TO THE EXISTNG EMERGENCY LIGHTING CIRCUITRY. OCCUPANCY SENSORS SHALL BE LINKED TOGETHER FOR CONTROL AS A SINGLE SPACE. PROVIDE EMERGENCY LIGHTING CONTROL UNITS TO ALLOW EMERGENCY FIXTURES TO BE SWITCHED WITH OTHER NEARBY "NORMAL POWER" AREA LIGHTING. PROVIDE ALL CONDUIT, WHIPS AND WIRING REQUIRED FOR A FULLY FUNCTIONAL INSTALLATION. PAINT ALL CONDUIT/WHIPS VISIBLE TO PUBLIC TO MATCH OTHER EXPOSED BUILDING ELEMENTS. MOUNT AT 7'-0" AFF TO BOTTOM (TYPICAL) RCNJ No. 201437-01C PHASE 2: ALTERATIONS V RAMAPO COLLEGE OF NEW JERSEY H F D 12 REVISIONS F4 D D 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com E3. PROVIDE NEW EMERGENCY FIXTURE ON UPPER COLUMN SECTION. BASIS OF DESIGN: LITHONIA AFN B EXT FWD. CONNECT TO VESTIBULE LIGHTING CIRCUITRY. PROVIDE ALL CONDUIT AND WIRING REQUIRED FOR A FULLY FUNCTIONAL INSTALLATION. COORDINATE LOCATION AND INSTALLATION IN THE FIELD. 15 M E2 ENGINEER: LIGHTING ALTERATIONS - FIRST FLOOR EXISTING SERVERY AREA 120V LIGHTING PANEL 18 D 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com 3/23/2016 3:29:49 PM NJDCA ELECTRONIC SUBMITTAL STAMP: SERVERY LIGHT FIXTURE SCHEDULE Type Mark F1 F2 F12 F13 F14 F15 F16 F18 Description Manufacturer 4" LED Recessed Downlight 6LW - New Construction or Remodel 6" LED Recessed Downlight Decorative Milk Can Fixture Decorative Milk Can Fixture Decorative Shade Fixture Decorative Shade Fixture Decorative Shade Fixture LED Track Head Cooper Industries, Inc. . Cooper Lighting Hi-Lite Manufacturing Hi-Lite Manufacturing Hi-Lite Manufacturing Hi-Lite Manufacturing Hi-Lite Manufacturing CooperLighting Industries, Inc. Philips GENERAL NOTES Model Lamp LD4A1300D010TE ERWA13930 4LWO WH LD620 AND LD6R20 LD6A20D010TE ERW6A20830 6LWO WH H-2046 ST1/8 STC H-7106 ST1/8 STC H-15006 ST1/8 STC H-16006 ST1/8 STC H-19006 ST1/8 STC . 9030N LR F BK Voltage LED 2 LED LED LED LED LED LED LED 120 120/277 120/277 120 120 120 120 120 120 Mounting Comments Recessed Recessed Pendant Pendant Pendant Pendant Pendant Existing Track 1. 2. Finish Selection by Architect, Provide Philips 100W EQUIV. LED A19 Finish Selection by Architect, Provide Philips 100W EQUIV. LED A19 Finish Selection by Architect, Provide Philips 100W EQUIV. LED A19 Finish Selection by Architect, Provide Philips 100W EQUIV. LED A19 Finish Selection by Architect, Provide Philips 100W EQUIV. LED A19 Fixture must be compatible with existing Lightolier line voltage track 3. 4. 5. B C 6. 7. 8. 9. 19 10. F2 F2 F2 11. F2 12. DEVICES SHOWN AS LIGHT OR SHADED ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL MATERIAL AND EQUIPMENT IN ACCORDANCE WITH THE CURRENT N.E.C. (NATIONAL ELECTRICAL CODE). ALL WORK SHALL BE INSTALLED NEAT AND WORKMANLIKE COMPLYING WITH THE STANDARDS OF N.E.C.. THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL CONDITIONS, LOCATIONS, DIMENSIONS, AND COUNTS AS SHOWN AND NOTED ON THE DRAWINGS FOR THIS WORK PRIOR TO BIDDING. NO ADDITIONAL COST WILL BE ISSUED FOR FAILURE TO COMPLY WITH THIS REQUIREMENT. THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIAL, AND SUPERVISION NECESSARY TO ACCOMPLISH THE WORK AS SHOWN AND NOTED ON THE DRAWINGS. ANY DEVIATION FROM THE DRAWINGS SHALL BE APPROVED BY THE OWNER. THE ELECTRICAL CONTRACTOR SHALL DO ALL CUTTING AND PATCHING OF THE BUILDING MATERIALS REQUIRED FOR THE INSTALLATION OF HIS WORK. ALL FIRE RATED WALLS, FLOORS, OR CEILINGS SHALL BE SEALED TO MAINTAIN THE FIRE RATING. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL OF ALL TOOLS, DEBRIS, AND GENERAL CLEAN UP FROM HIS WORK. ALL WORK SHALL BE COORDINATED WITH THE OTHER TRADES. THE ELECTRICAL CONTRACTOR SHALL MAKE ALL NECESSARY TESTS TO INSURE THAT THE ENTIRE INSTALLATION IS FREE FROM IMPROPER GROUNDS AND FROM SHORTED AND/OR OPEN CIRCUITS. VOLTAGE AND CURRENT TESTS SHALL BE MADE BEFORE ANY MOTORS ARE PLACED IN OPERATION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND PAYING FOR ALL REQUIRED PERMITS. THE ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL WORK AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER ACCEPTANCE OF THE WORK AND MATERIALS. ALL ELECTRICAL EQUIPMENT AND DEVICES SHALL BE LABELED WITH 1/2" DYNO TAPE FOR THE SOURCE AND CONTROL LOCATION. SEALED: CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: M E1 F1 E1 DEMO KEYED NOTES (TYPICAL) F1 F1 D1. DISCONNECT AND REMOVE EXISTING PENDANT FIXTURES OVER WOK AREA. REMOVE CONDUIT, WHIPS AND CIRCUITRY TO NEAREST HOMERUN JUNCTION BOX. LABEL CIRCUITRY FOR RE-USE. F1 F1 17 MOUNT AT 6'-0" AFF TO BOTTOM OF FIXTURE (TYPICAL) F12 F1 EXISTING SERVERY AREA 120V LIGHTING PANEL E2 F15 (TYPICAL) F12 D1 (TYPICAL) F13 MOUNT AT 6'-0" AFF TO BOTTOM OF FIXTURE (TYPICAL) D2 F14 F13 LPK 17 E1 D2 16 F15 F15 15 F16 F14 F16 D3 (TYPICAL) F13 D2 11 F12 14 D2 12 F15 F13 F16 D2 13 F12 F13 F16 F12 D2 12 F15 11 D2 E2 H D2 S H A.4 WEF B.7 A.4 B.7 A A 1 LIGHTING DEMO PLAN - SERVERY 0 8 16 2 24 1/8" = 1'-0" LIGHTING PLAN - FF1 - SERVERY 0 4 8 ISSUED: 3.24.2016 12 DESCRIPTION: 1/4" = 1'-0" NORTH NORTH BID DOCUMENTS SHEET: ADD/ALT 1 E-211 18031.00 E2. PROVIDE NEW TRACK LIGHT FIXTURES COMPATIBLE WITH EXISTING BLACK LIGHTOLIER LINE VOLTAGE TRACK SYSTEM. REFER TO LIGHT FIXTURE SCHEDULE FOR BASIS OF DESIGN FIXTURE. FIELD VERIFY QUANTITY AND LOCATIONS OF TRACK LIGHTS PRIOR TO REMOVALS OF EXISTING TRACK HEADS. QUANTITY AND LOCATIONS SHOWN ARE APPROXIMATE. CHECKED BY: 505 RAMAPO VALLEY RD. MAHWAH, NY 07430 F18 (TYPICAL) BFD RCNJ No. 201437-01C PHASE 2: ALTERATIONS D DRAWN BY: RAMAPO COLLEGE OF NEW JERSEY 15 E1. PROVIDE NEW FIXTURES SHOWN AND CONNECT TO EXISTING SERVER LINE LIGHTING CIRCUIT. RE-USE EXISTING HOME-RUN CONDUITS WHERE PRACTICAL AND PROVIDE NEW AS REQUIRED. PROVIDE ALL CONDUIT, WHIPS AND WIRING AS REQUIRED TO CIRCUIT AS SHOWN ON DRAWING. PROVIDE ALL CONNECTIONS TO LIGHT FIXTURES, SWITCHES AND OCCUPANCY SENSORS AS REQUIRED FOR A COMPLETE AND FULLY FUNCTIONAL SYSTEM. PAINT ALL CONDUIT/WHIPS VISIBLE TO PUBLIC TO MATCH OTHER EXPOSED BUILDING ELEMENTS. EXISTING SWITCHES SHALL BE RE-USED. ONE SWITCH SHALL CONTROL THE EXISTING TRACK LIGHTING, THE OTHER SWITCH SHALL CONTROL THE WOK AREA AND SERVER LINE PENDANT LIGHTING. LIGHTING ALTERATIONS SERVERY - ALTERNATE #1 16 F15 19 REVISIONS F13 F14 C 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com KEYED NOTES F13 F14 B D3. REMOVE EXISTING TRACK HEADS FROM EXISTING BLACK LINE VOLTAGE LIGHTOLIER TRACK SYSTEMS AND TURN OVER TO CAMPUS PERSONNEL. EXISTING TRACK SYSTEM TO REMAIN. TAKE QUANTITY OF FIXTURES REMOVED FOR REPLACEMENT. F12 F16 F1 ENGINEER: D2. DISCONNECT AND REMOVE EXISTING JUNO TRACK LIGHTING AND PENDANT FIXTURES AT SERVER LINES. REMOVE CONDUIT, WHIPS AND CIRCUITRY TO NEAREST HOMERUN JUNCTION BOX. LABEL CIRCUITRY FOR RE-USE. MOUNT AT 6'-0" AFF TO BOTTOM OF FIXTURE (TYPICAL) F15 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com 3/23/2016 3:29:49 PM NJDCA ELECTRONIC SUBMITTAL STAMP: SEALED: LIGHT FIXTURE SCHEDULE Type Mark Manufacturer 4" LED Recessed Downlight 6" LED Recessed Downlight 6LW - New Construction or Remodel Decorative Drum Fixture Decorative Lensed Lowbay with Uplight Decorative Drum Fixture 6" LED Cylinder - Rigid Stem Mount LED Linear Architectural Suspended Fixture Decorative Period Jelly Jar Fixture Decorative Angled Shade Light Decorative Surface Jelly Jar Fixture Decorative Bell Shade Fixture Decorative Shade Fixture LED Column Light Pole Architectural Edge Lit Exit Sign 2-Sided Architectural Edge Lit Exit Sign Model Cooper Industries, Inc. . Cooper Lighting Barbican Lighting Hi-Lite Manufacturing Barbican Lighting Juno Lighting Group by Schneider Electric Cooper Lighting Tech Lighting Hi-Lite Manufacturing Hi-Lite Manufacturing Hi-Lite Manufacturing Hi-Lite Manufacturing Hi-Lite Manufacturing Selux Corporation Lithonia Lighting Lithonia Lighting LD4A1300D010TE ERWA13930 4LWO WH LD6A20D010TE ERW6A20830 6LWO WH LD620 AND LD6R20 16-5048-LF-__-24-ACB-HTO-NT-RAL-277V H-23638 16-0448-LF-__-24-ACB-HTO-NT-RAL-277V . LSR6A-15-D010TE-MB-ERCW6A-15830-6LWO-WH 700LSKNOX LED277 H-MCGUS-6S H-18110 H-LCGU-FB H-1214 H-EMC-06 CCCL-10-4-4L35-30-__-277 EDG 1 R EL EDG 2 RMR EL Lamp LED 2 LED LED DO NOT 42W CFLUSE LED LED LED 18W CFL 18W CFL 18W CFL 18W CFL LED LED LED LED Voltage 277 120/277 120/277 Mounting Comments Recessed Recessed Finish Selection by Architect. Finish Selection by Architect, Provide Rigid Stem Mount Finish Selection by Architect. Provide Rigid Stem, Finish Selection by Architect Finish Selection by Architect Provide Rigid Stem, Finish and Lens Selection by Architect Provide with B-6 Wall Bracket Mount, Finish Selection by Architect Finish and Lens Selection by Architect Provide Rigid Stem, Finish and Lens Selection by Architect Provide Rigid Stem & 60W Equiv. LED A19 bulb, 800 Lumens Min., Finish Selection by Architect Finish Selection by Architect . 277 120/277 277 120/277 120/277 120/277 120/277 120 277 120/277 120/277 Pendant Suspended Pendant Wall - Arm Wall Pendant Pendant Pole Surface Surface CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com 3' MIN. FROM EDGE OF CURB PROVIDE TOP SURFACE TO MATCH ADJACENT AREAS (TOPSOIL AND SEED, CONCRETE, PAVEMENT, ETC..) 1" PVC CONDUIT W/POWER & GROUND CONDUCTORS DETECTABLE MARKING TAPE EXOTHERMIC WELD 12" MIN. 3" MIN. 3" MIN. 3/4" X 10'-0" COPPER CLAD GROUNDING ROD CONDUIT COUPLING (TYP.) RIGID SCHED. 80 PVC CONDUIT (SIZED AS PER DRAWINGS) RIGID STEEL CONDUIT SWEEP CLEAN SAND 24" MIN. BACKFILL IN 8" LIFT AND COMPACT TO 95% MODIFIED PROCTOR 1 LIGHT POLE FOUNDATION DETAIL 12" = 1'-0" (4)-#7 VERTICAL BARS SPACED EQUALLY 4" MIN. COORDINATE BOLT REQUIREMENTS AND PATTERN W/POLE AND SHOP DRAWINGS #3 TIES AT 12" O/C W/3" MIN. COVER FOUNDATION TO BE PLACED IN UNDISTURBED SOIL NOTE: ALL WORK SHOW SHALL BE PERFORMED BY THE E.C. 2 TRENCH DETAIL N.T.S. 1'-6" MIN. BACKFILL MATERIAL. SUITABLE NATIVE BACKFILL COMPACTED TO 90% MODIFIED PROCTOR 1'-0" MIN. 6" CU. GND. 24" MIN. PVC CONDUIT WITH GROUND CONDUCTOR 3/4" DIA. GALV. HEADED AND PARTIALLY THREADED ANCHOR RODS, MIN. 36" LONG (TYP.) 12" MIN. FINISHED GRADE ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS SHEET: E-310 18031.00 OBTAIN BASE PLATE BOLT PATTERN FROM MANUFACTURER WEF 505 RAMAPO VALLEY RD. MAHWAH, NY 07430 TO POLE GROUND STUD CHECKED BY: RCNJ No. 201437-01C PHASE 2: ALTERATIONS BOLT CAP BFD RAMAPO COLLEGE OF NEW JERSEY TO POLE CIRCUIT DRAWN BY: ELECTRICAL DETAILS & SCHEDULES CONDUIT WITH BONDING BUSHING 4" MIN. COORDINATE REVEAL HEIGHT IN FIELD REVISIONS 4 FEET F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F17 S1 X1 X2 Description