NJDCA ELECTRONIC SUBMITTAL STAMP:
SEALED:
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
LEGEND
GENERAL NOTES
1. THESE GENERAL ELECTRICAL NOTES SHALL APPLY TO ALL E SERIES DRAWINGS, IN COORDINATION WITH DIVISION 26,
27, & 28 SECTIONS, AND FRONT END (DIVISION 0 AND 1) REQUIREMENTS. ALL WORK ASSOCIATED WITH THE E SERIES
DRAWINGS SHALL BE COORDINATED WITH ALL OTHER TRADES TO AVOID CONFLICTS.
DUPLEX RECEPTACLE - DEVICES
SHOWN "DASHED" OR "DARK INK" ON
DEMO PLANS ARE TO BE REMOVED
UNLESS NOTED OTHERWISE.
2. ALL WORK SHALL BE PERFORMED IN COOPERATION WITH THE UNIVERSITY AND THE ARCHITECT/ENGINEER. THE
CONTRACTOR SHALL COORDINATE ALL WORK WITH THE CONSTRUCTION SCHEDULE ESTABLISHED BY THE UNIVERSITY,
AND SHALL IMMEDIATELY REPORT ANY DELAYS IN MATERIALS RECEIPT INCLUDING CIRCUMSTANCES CAUSING DELAYS.
•
COMMENCE WORK AFTER PRECONSTRUCTION MEETING AND PROCEED DILIGENTLY AND CONTINUOUSLY TO
COMPLETION.
•
PRIOR TO STARTING WORK, SUBMIT FOR UNIVERSITY'S APPROVAL, A DETAILED SCHEDULE INDICATING ALL
WORK THAT MAY AFFECT THE BUILDING AND NEARBY BUILDINGS/STRUCTURES, SUCH AS UTILITY SHUT DOWNS,
NOISE GENERATING EQUIPMENT, ETC.
•
PERFORM WORK IN A MANNER WHICH MINIMIZES NOISE. OPERATIONS IN WHICH NOISE CANNOT BE MINIMIZED
SHALL BE SCHEDULED WITH UNIVERSITY.
TC
TIME CLOCK
PC
PHOTOCELL
F
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
ENGINEER:
FIRE ALARM STROBE - WALL MOUNT
V
F
V
FIRE ALARM STROBE/SPEAKER - CEILING MOUNT
EXIT SIGN - SINGLE SIDED
S
SMOKE DETECTOR
EXIT SIGN - DOUBLE SIDED
H
HEAT DETECTOR
EXIT SIGN - TRIANGLES INDICATE DIRECTION
ARROWS
X
X2
X2
FIRE ALARM STROBE/SPEAKER - WALL MOUNT
F
X1
3. CONTRACT DRAWINGS FOR THE ELECTRICAL WORK ARE DIAGRAMMATIC, INTENDED TO CONVEY THE SCOPE OF
WORK AND TO INDICATE THE GENERAL ARRANGEMENT AND APPROXIMATE LOCATION OF EQUIPMENT, PIPING, AND
ACCESSORIES. THE INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING AND VERIFYING ALL
CONDITIONS, DIMENSIONS, AND LOCATIONS PRIOR TO BIDDING PROJECT. CHECK PROJECT DRAWINGS PRIOR TO
INSTALLATION FOR INTERFERENCES WITH OTHER TRADES. SHOULD THE CONTRACTOR FIND SUCH INTERFERENCES, THE
CONTRACTOR IS RESPONSIBLE FOR COORDINATING HIS WORK WITH OTHERS. THE UNIVERSITY RESERVES THE RIGHT TO
MAKE REASONABLE CHANGES PRIOR TO ROUGH-IN WITHOUT ADDED EXPENSE. DIMENSIONS INDICATED ARE SUBJECT
TO VERIFICATION OF EXACT SITE CONDITIONS AT THE TIME OF INSTALLATION.
•
THE CONTRACTOR SHALL INSTALL ALL CONDUIT, WIRE, EQUIPMENT, LIGHT FIXTURES, ETC. IN A WORKMAN LIKE
MANNER WITH QUALIFIED ELECTRICIANS.
•
ANY DISCREPANCIES BETWEEN THE DRAWINGS AND SPECIFICATIONS SHALL BE REPORTED TO THE UNIVERSITY.
IN THE EVENT OF A DISCREPANCY, THE DRAWINGS WILL GOVERN OVER THE SPECIFICATIONS.
MANUAL PULL STATION
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
REVISIONS
KEY NOTE, REFER TO KEY NOTES ON DRAWING
4. ALL ELECTRICAL WORK SHALL BE INSTALLED TO MEET THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE,
NEW JERSEY EXISTING BUILDING CODE, INTERNATIONAL BUILDING, FIRE CODE AND NFPA 72. ALL WORK SHALL
COMPLY TO ACCORDANCE OF LOCAL, STATE AND FEDERAL REGULATIONS AND OTHER AUTHORITIES HAVING
JURISDICTION.
DRAWN BY:
BFD
CHECKED BY:
WEF
5. CONTRACTOR IS RESPONSIBLE FOR PAYING FOR ALL FEES ASSOCIATED WITH OBTAINING INSPECTIONS.
9. PROVIDE (FURNISH AND INSTALL) ALL NEW EQUIPMENT AND MATERIALS AS DESCRIBED HEREIN. ANY MATERIAL,
OPERATION, METHOD, OR DEVICE MENTIONED, LISTED OR NOTED WITHIN THIS SPECIFICATION SHALL BE FURNISHED BY
THIS CONTRACTOR UNLESS SPECIFICALLY MENTIONED AS BEING FURNISHED OR INSTALLED BY OTHERS.
•
ALL MATERIALS SHALL BE AS SPECIFIED, OR EQUAL, AS APPROVED BY UNIVERSITY. MATERIALS SPECIFIED
INDICATE QUALITY INTENT THAT WILL BE USED AS A BASIS FOR REVIEW OF SUBSTITUTES. SEE GENERAL
CONDITIONS FOR SUBSTITUTION PROCEDURES.
•
MATERIALS SHALL BE STORED AT A LOCATION DETERMINED BY THE UNIVERSITY.
•
DELIVERY OF MATERIALS SHALL BE AS DIRECTED BY THE UNIVERSITY.
FIR
PU E A
ST LL LAR
AT
M
IO
N
F.A.
A/V
UNITS
10. THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE COMPLETE AND OPERABLE SYSTEMS, INCLUDING
OPERATIONAL PROPERTIES TO THE EXTEND NECESSARY TO LINK MULTIPLE COMPONENTS OF THE SYSTEMS TOGETHER
AND TO INTERFACE WITH SYSTEMS PROVIDED BY OTHERS. THE ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL
SYSTEMS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE.
•
THE CONTRACTOR SHALL PROVIDE UNIVERSITY WITH ALL NECESSARY OPERATION AND MAINTENANCE
MANUALS, SHOP DRAWINGS, WIRING DIAGRAMS, AND WARRANTY PAPERWORK UPON COMPLETION OF THE
PROJECT.
•
THE CONTRACTOR SHALL REPAIR, ADJUST, OR REPLACE ANY EQUIPMENT, MATERIAL, OR WORKMANSHIP
FOUND TO BE DEFECTIVE.
90" MIN.
WHERE
POSSIBLE
11. THE ELECTRICAL CONTRACTOR SHALL HOLD THE UNIVERSITY, ARCHITECT, AND ENGINEER HARMLESS AGAINST ANY
AND ALL CLAIMS ARISING FROM WORK PERFORMED BY THIS CONTRACTOR ON THE SITE.
12. DISCONNECTION OF SERVICES SHALL BE PERFORMED AT A TIME AUTHORIZED BY THE UNIVERSITY. TEMPORARY
UTILITIES, IF NEEDED, WILL BE COORDINATED WITH THE UNIVERSITY.
48"
13. CONTRACTOR SHALL MAKE EVERY EFFORT TO PROTECT BUILDING COMPONENTS DURING CONSTRUCTION. A
PROTECTION PROPOSAL MUST BE SUBMITTED TO THE UNIVERSITY FOR REVIEW.
14. CONTRACTOR SHALL KEEP SITE FREE OF DEBRIS AND ACCUMULATED REFUSE. SITE SHALL BE BROOM SWEPT AT
THE END OF EACH WORKING DAY.
15. FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH THE REQUIREMENTS OF THE LOCAL FIRE
MARSHAL CONCERNING FIRE ALARM SYSTEM SHUTDOWN PLANS, PROCEDURES, AND FIRE WATCH PLANS THAT WILL BE
IMPLEMENTED FOR SYSTEM INTERRUPTIONS DURING CONSTRUCTION.
FLOOR
1
TYPICAL MOUNTING HEIGHTS DETAIL
N.T.S.
ISSUED:
3.24.2016
DESCRIPTION:
BID DOCUMENTS
SHEET:
E-000
18031.00
6" TO TOP OF DEVICE
RAMAPO COLLEGE
OF NEW JERSEY
CEILING
ELECTRICAL LEGEND AND
GENERAL NOTES
8. CUTTING AND PATCHING - ALL NOTES BELOW HOLD THE COMMON CONDITION "UNLESS OTHERWISE NOTED".
•
FOR ALTERATIONS: ALL CUTTING AND PATCHING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR FOR
HIS/HER OWN WORK WHETHER DESCRIBED IN THE CONTRACT DOCUMENTS OR NOT. THE CONTRACTOR SHALL
BE RESPONSIBLE FOR COORDINATING CUTTING AND PATCHING REQUIREMENTS WITH OTHER TRADES.
•
OPENINGS MADE POST-FINISH: IF AN OPENING IS REQUIRED IN A FINISHED SURFACE, AFTER COMPLETION,
DUE TO LACK OF COORDINATION OR PROPER SCHEDULE MAINTENANCE, THE ELECTRICAL CONTRACTOR
SHALL BE RESPONSIBLE FOR ANY CUTTING AND PATCHING REQUIRED TO FINISH SPECIFIC ELECTRICAL WORK
AND RESTORE THE FINISHED SURFACE TO PREVIOUS CONDITION.
RCNJ No. 201437-01C
PHASE 2: ALTERATIONS
7. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER RECOMMENDATIONS. ANY CONFLICTS WITH
INSTALLATION AND MANUFACTURER RECOMMENDATIONS SHALL BE REPORTED TO ENGINEER.
505 RAMAPO VALLEY RD.
MAHWAH, NY 07430
6. THE ELECTRICAL CONTRACTOR SHALL BE LICENSED IN THE LOCAL JURISDICTION PRIOR TO BIDDING ON PROJECT.
CONTRACTOR TO CONTACT CITY/TOWNSHIP TO VERIFY LICENSE TO ENSURE THEY ARE CURRENT.
3/23/2016 3:28:59 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
SEALED:
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
GENERAL NOTES
1. THESE GENERAL ELECTRICAL NOTES SHALL APPLY TO ALL E SERIES DRAWINGS, IN COORDINATION WITH DIVISION 26,
27, & 28 SECTIONS, AND FRONT END (DIVISION 0 AND 1) REQUIREMENTS. ALL WORK ASSOCIATED WITH THE E SERIES
DRAWINGS SHALL BE COORDINATED WITH ALL OTHER TRADES TO AVOID CONFLICTS.
LEGEND
2. ALL WORK SHALL BE PERFORMED IN COOPERATION WITH THE UNIVERSITY AND THE ARCHITECT/ENGINEER. THE
CONTRACTOR SHALL COORDINATE ALL WORK WITH THE CONSTRUCTION SCHEDULE ESTABLISHED BY THE UNIVERSITY,
AND SHALL IMMEDIATELY REPORT ANY DELAYS IN MATERIALS RECEIPT INCLUDING CIRCUMSTANCES CAUSING DELAYS.
•
COMMENCE WORK AFTER PRECONSTRUCTION MEETING AND PROCEED DILIGENTLY AND CONTINUOUSLY TO
COMPLETION.
•
PRIOR TO STARTING WORK, SUBMIT FOR UNIVERSITY'S APPROVAL, A DETAILED SCHEDULE INDICATING ALL
WORK THAT MAY AFFECT THE BUILDING AND NEARBY BUILDINGS/STRUCTURES, SUCH AS UTILITY SHUT DOWNS,
NOISE GENERATING EQUIPMENT, ETC.
•
PERFORM WORK IN A MANNER WHICH MINIMIZES NOISE. OPERATIONS IN WHICH NOISE CANNOT BE MINIMIZED
SHALL BE SCHEDULED WITH UNIVERSITY.
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
DUPLEX RECEPTACLE
G
U
G
G
DUPLEX RECEPTACLE - GFI
X2
USB CHARGER-DUPLEX RECEPTACLE - ABOVE
COUNTER
DUPLEX RECEPTACLE - ABOVE COUNTER, GFI
COMBINATION TELE/DATA JACK
-PROVIDE CAT. 3 CABLE TO TELEPHONE DEMARC.
-PROVIDE CAT. 6a CABLE TO SECOND FLOOR
ELECTRICAL ROOM.
D
D
DATA JACK
-PROVIDE CAT. 6a CABLE TO SECOND FLOOR
ELECTRICAL ROOM
FUSED DISCONNECT (POLES, SIZE, FUSE)
F
MANUAL PULL STATION
FIRE ALARM STROBE/SPEAKER - CEILING MOUNT
SMOKE DETECTOR
F10
5. CONTRACTOR IS RESPONSIBLE FOR PAYING FOR ALL FEES ASSOCIATED WITH OBTAINING INSPECTIONS.
REVISIONS
FIRE ALARM STROBE - WALL MOUNT
V
S
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
FIRE ALARM STROBE/SPEAKER - WALL MOUNT
F
JUNCTION BOX
J
CEILING MOTION SENSOR - DUAL TECHNOLOGY
CORNER MOTION SENSOR - DUAL TECHNOLOGY
V
(3,30,20)
MOTION SENSOR SWITCH
M
F
MANUAL MOTOR STARTER
4. ALL ELECTRICAL WORK SHALL BE INSTALLED TO MEET THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE,
NEW JERSEY EXISTING BUILDING CODE, INTERNATIONAL BUILDING, FIRE CODE AND NFPA 72. ALL WORK SHALL
COMPLY TO ACCORDANCE OF LOCAL, STATE AND FEDERAL REGULATIONS AND OTHER AUTHORITIES HAVING
JURISDICTION.
ENGINEER:
SINGLE POLE LIGHT SWITCH
M
3. CONTRACT DRAWINGS FOR THE ELECTRICAL WORK ARE DIAGRAMMATIC, INTENDED TO CONVEY THE SCOPE OF
WORK AND TO INDICATE THE GENERAL ARRANGEMENT AND APPROXIMATE LOCATION OF EQUIPMENT, PIPING, AND
ACCESSORIES. THE INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING AND VERIFYING ALL
CONDITIONS, DIMENSIONS, AND LOCATIONS PRIOR TO BIDDING PROJECT. CHECK PROJECT DRAWINGS PRIOR TO
INSTALLATION FOR INTERFERENCES WITH OTHER TRADES. SHOULD THE CONTRACTOR FIND SUCH INTERFERENCES, THE
CONTRACTOR IS RESPONSIBLE FOR COORDINATING HIS WORK WITH OTHERS. THE UNIVERSITY RESERVES THE RIGHT TO
MAKE REASONABLE CHANGES PRIOR TO ROUGH-IN WITHOUT ADDED EXPENSE. DIMENSIONS INDICATED ARE SUBJECT
TO VERIFICATION OF EXACT SITE CONDITIONS AT THE TIME OF INSTALLATION.
•
THE CONTRACTOR SHALL INSTALL ALL CONDUIT, WIRE, EQUIPMENT, LIGHT FIXTURES, ETC. IN A WORKMAN LIKE
MANNER WITH QUALIFIED ELECTRICIANS.
•
ANY DISCREPANCIES BETWEEN THE DRAWINGS AND SPECIFICATIONS SHALL BE REPORTED TO THE UNIVERSITY.
IN THE EVENT OF A DISCREPANCY, THE DRAWINGS WILL GOVERN OVER THE SPECIFICATIONS.
EXIT SIGN - TRIANGLES INDICATE DIRECTION
ARROWS
DRAWN BY:
BFD
CHECKED BY:
WEF
LIGHT FIXTURE, REFER TO FIXTURE SCHEDULE
6. THE ELECTRICAL CONTRACTOR SHALL BE LICENSED IN THE LOCAL JURISDICTION PRIOR TO BIDDING ON PROJECT.
CONTRACTOR TO CONTACT CITY/TOWNSHIP TO VERIFY LICENSE TO ENSURE THEY ARE CURRENT.
X1
EXIT SIGN - SINGLE SIDED
7. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER RECOMMENDATIONS. ANY CONFLICTS WITH
INSTALLATION AND MANUFACTURER RECOMMENDATIONS SHALL BE REPORTED TO ENGINEER.
X
KEY NOTE, REFER TO KEY NOTES ON DRAWING
X2
L IG
HT
SW
ITC
H
13. CONTRACTOR SHALL MAKE EVERY EFFORT TO PROTECT BUILDING COMPONENTS DURING CONSTRUCTION. A
PROTECTION PROPOSAL MUST BE SUBMITTED TO THE UNIVERSITY FOR REVIEW.
14. CONTRACTOR SHALL KEEP SITE FREE OF DEBRIS AND ACCUMULATED REFUSE. SITE SHALL BE BROOM SWEPT AT
THE END OF EACH WORKING DAY.
TY
RE PIC
CE AL
PT
AC
LE
TY
PIC
AL
DA
TA
JA
DE
CK
SK
PH
ON
E
JA
CK
15. FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH THE REQUIREMENTS OF THE LOCAL FIRE
MARSHAL CONCERNING FIRE ALARM SYSTEM SHUTDOWN PLANS, PROCEDURES, AND FIRE WATCH PLANS THAT WILL BE
IMPLEMENTED FOR SYSTEM INTERRUPTIONS DURING CONSTRUCTION.
48"
18"
FLOOR
1
AB
CO O V
RE UNT E TH
CE ER E
PT
AC
LE
12. DISCONNECTION OF SERVICES SHALL BE PERFORMED AT A TIME AUTHORIZED BY THE UNIVERSITY. TEMPORARY
UTILITIES, IF NEEDED, WILL BE COORDINATED WITH THE UNIVERSITY.
TYPICAL MOUNTING HEIGHTS
N.T.S.
ISSUED:
3.24.2016
DESCRIPTION:
BID DOCUMENTS
SHEET:
E-001
18031.00
11. THE ELECTRICAL CONTRACTOR SHALL HOLD THE UNIVERSITY, ARCHITECT, AND ENGINEER HARMLESS AGAINST ANY
AND ALL CLAIMS ARISING FROM WORK PERFORMED BY THIS CONTRACTOR ON THE SITE.
505 RAMAPO VALLEY RD.
MAHWAH, NY 07430
CEILING
RAMAPO COLLEGE
OF NEW JERSEY
10. THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE COMPLETE AND OPERABLE SYSTEMS, INCLUDING
OPERATIONAL PROPERTIES TO THE EXTEND NECESSARY TO LINK MULTIPLE COMPONENTS OF THE SYSTEMS TOGETHER
AND TO INTERFACE WITH SYSTEMS PROVIDED BY OTHERS. THE ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL
SYSTEMS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE.
•
THE CONTRACTOR SHALL PROVIDE UNIVERSITY WITH ALL NECESSARY OPERATION AND MAINTENANCE
MANUALS, SHOP DRAWINGS, WIRING DIAGRAMS, AND WARRANTY PAPERWORK UPON COMPLETION OF THE
PROJECT.
•
THE CONTRACTOR SHALL REPAIR, ADJUST, OR REPLACE ANY EQUIPMENT, MATERIAL, OR WORKMANSHIP
FOUND TO BE DEFECTIVE.
ELECTRICAL LEGEND AND
GENERAL NOTES
9. PROVIDE (FURNISH AND INSTALL) ALL NEW EQUIPMENT AND MATERIALS AS DESCRIBED HEREIN. ANY MATERIAL,
OPERATION, METHOD, OR DEVICE MENTIONED, LISTED OR NOTED WITHIN THIS SPECIFICATION SHALL BE FURNISHED BY
THIS CONTRACTOR UNLESS SPECIFICALLY MENTIONED AS BEING FURNISHED OR INSTALLED BY OTHERS.
•
ALL MATERIALS SHALL BE AS SPECIFIED, OR EQUAL, AS APPROVED BY UNIVERSITY. MATERIALS SPECIFIED
INDICATE QUALITY INTENT THAT WILL BE USED AS A BASIS FOR REVIEW OF SUBSTITUTES. SEE GENERAL
CONDITIONS FOR SUBSTITUTION PROCEDURES.
•
MATERIALS SHALL BE STORED AT A LOCATION DETERMINED BY THE UNIVERSITY.
•
DELIVERY OF MATERIALS SHALL BE AS DIRECTED BY THE UNIVERSITY.
RCNJ No. 201437-01C
PHASE 2: ALTERATIONS
EXIT SIGN - DOUBLE SIDED
8. CUTTING AND PATCHING - ALL NOTES BELOW HOLD THE COMMON CONDITION "UNLESS OTHERWISE NOTED".
•
FOR ALTERATIONS: ALL CUTTING AND PATCHING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR FOR
HIS/HER OWN WORK WHETHER DESCRIBED IN THE CONTRACT DOCUMENTS OR NOT. THE CONTRACTOR SHALL
BE RESPONSIBLE FOR COORDINATING CUTTING AND PATCHING REQUIREMENTS WITH OTHER TRADES.
•
OPENINGS MADE POST-FINISH: IF AN OPENING IS REQUIRED IN A FINISHED SURFACE, AFTER COMPLETION,
DUE TO LACK OF COORDINATION OR PROPER SCHEDULE MAINTENANCE, THE ELECTRICAL CONTRACTOR
SHALL BE RESPONSIBLE FOR ANY CUTTING AND PATCHING REQUIRED TO FINISH SPECIFIC ELECTRICAL WORK
AND RESTORE THE FINISHED SURFACE TO PREVIOUS CONDITION.
3/23/2016 3:29:52 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
DEMOLITION
GENERAL NOTES
1.
2.
3.
E
G
J
N
QQ.1
Q.2
Q.3
4.
5.
22
EXISTING EMERGENCY
LIGHTING PANEL EPPB
GE SPECTRA SERIES
6.
7.
8.
9.
B
C
D
KPP3
KPP2
KPP1
21
10.
IDENTIFICATION AND/OR ABATEMENT OF
HAZARDOUS MATERIALS IS NOT PART OF THIS SCOPE
OF WORK. IF ASBESTOS OR OTHER HAZARDOUS
MATERIALS ARE ENCOUNTERED, THE CONTRACTOR
SHALL NOTIFY THE OWNER IMMEDIATELY.
REFER TO SPECIFICATIONS FOR RECYCLING,
CONSTRUCTION WASTE MANAGEMENT AND
DISPOSAL REQUIREMENTS.
OPENING IN THE EXISTING STRUCTURE SMALLER
THAN 12" IN ANY DIRECTION ARE NOT IDENTIFIED
ON THESE DRAWINGS. SUBCONTRACTORS SHALL BE
RESPONSIBLE FOR PROVIDING OPENINGS SMALLER
THAN 12" AS REQUIRED FOR INSTALLATION OF THEIR
WORK.
OPENINGS IN THE EXISTING STRUCTURE SHALL NOT
BE MADE WITHOUT PRIOR APPROVAL OF THE
STRUCTURAL ENGINEER.
DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE
STRUCTURAL INTEGRITY OF THE BUILDING. IF
HIDDEN ELEMENTS OR DETERIORATED ELEMENTS ARE
ENCOUNTERED, NOTIFY THE ARCHITECT
IMMEDIATELY.
PROTECT ADJACENT AREAS AND ITEMS "TO
REMAIN" DURING DEMOLITION/CONSTRUCTION.
REPAIR/REPLACE ITEMS DAMAGED DURING
CONSTRUCTION.
IF UNANTICIPATED HIDDEN ELEMENTS OR
DETERIORATED ELEMENTS ARE ENCOUNTERED,
NOTIFY THE OWNERS REPRESENTATIVE IMMEDIATELY.
REFER TO CONSULTANT DRAWINGS FOR
ADDITIONAL DEMOLITION WORK.
REVIEW w/ OWNER TO DETERMINE WHAT, IF
ANYTHING, WILL BE REMOVED BY OWNER AND
WHAT, IF ANYTHING, IS TO BE SALVAGED & TURNED
OVER TO OWNER.
DEVICES SHOWN AS "DASHED" OR IN "DARK INK" ARE
TO BE REMOVED. ELECTRICAL SUB-CONTRACTOR
SHALL DISCONNECT AND REMOVE EXISTING
DEVICES, DISCONNECTS, STARTERS, RELAYS, AND
MISCELLANEOUS COMPONENTS AS REQUIRED.
WIRING AND CONDUITS ASSOCIATED WITH
REMOVED ITEMS SHALL BE REMOVED BACK TO
SOURCE PANEL.
DEVICES SHOWN AS "LIGHT INK" ARE EXISTING TO
REMAIN UNLESS OTHERWISE NOTED.
SEALED:
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
EXISTING 120/208V, 3PH, 4W
FEDERAL PACIFIC PANEL
20
G
G
G
G
G
EXISTING
ELECTRICAL
PANELS
J
G
J
G
J
19
G
G
G
APPROXIMATE
LOCATION OF
ELECTRICAL ROOM
ON SECOND FLOOR
D1
0
0
D2
J
G
G
G
18
D3
G
G G
J
J
G
GG
GFCI
G
G
G
G
G
J
15
G
G
G
G
G
G
J
J
G
G G
D3
J
J
ELECTRICAL SUB-CONTRACTOR SHALL DISCONNECT AND
REMOVE EXISTING RECEPTACLES, SURFACE BOXES,
WIREMOLD, AND CONDUITS. REMOVE CIRCUITRY BACK TO
SOURCE PANEL.
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
ENGINEER:
REMOVE EXISTING HANDICAP DOOR PUSH BUTTON
OPERATORS AND STORE FOR REINSTALLATION.
DISCONNECT AND REMOVE POWER TO EXISTING DOOR
OPERATORS AND DOOR SENSORS, AND REMOVE POWER TO
NEAREST HOME RUN JUNCTION BOX, LABEL CIRCUITRY FOR
RE-USE.
D4
DISCONNECT POWER TO EXISTING CABINET UNIT HEATER
AND REMOVE TO NEAREST HOMERUN JUNCTION BOX,
LABEL CIRCUITRY FOR RE-USE.
D5
CAREFULLY DISCONNECT AND REMOVE EXISTING DUPLEX
RECEPTACLE AND DATA JACKS AT A.T.M. LOCATION. STORE
DEVICES IN A SAFE PLACE FOR RE-INSTALLATION. REMOVE
CONDUIT AND WIRING BACK TO JUNCTION BOX ABOVE
GRID CEILING TO ACCOMODATE WALL REMOVEL, LABEL
CIRCUITRY FOR RE-USE. REMOVE DATA CABLING AND COIL
ABOVE GRID CEILING FOR RE-USE. REFER TO E-110
ELECTRICAL PLAN FOR NEW LOCATION. COORDINATE
WORK WITH RAMAPO COLLEGE FACILITY PERSONNEL.
17
D4
J
J
16
KEYED NOTES
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
REVISIONS
DRAWN BY:
BFD
CHECKED BY:
WEF
G
G
FB
G
DWR DW
10.9
10.8
FB
G
J
11
D5
G
G
G
D
G
FB
G
D
G
U
U
U
D
U
U
10.2
10
U
D
D
D
U
U
U
U
D
U
U
D
B.7
U
D
U
U
D
A.4
U
9
U
U
8
U
D
U
U
D
D
U
U
D
U
U
U
U
6
5
U
D
D
D
U
D
U
U
U
U
D
D
U
D
U
U
U
U
U
U
D
D
D
U
D2
7
U
U
U
7.1
D
U
REMOVE ALL
SURFACE WIREMOLD
FEEDING DEVICES
(TYPICAL)
U
U
D
U
4
U
D1
U
D
D
U
D1
3
U
U
(TYPICAL)
2.9
U
D
D
U
U
2.1
1.9
2
1
A
F
H
I
K
L
M
O
ISSUED:
3.24.2016
DESCRIPTION:
BID DOCUMENTS
1
ELECTRICAL DEMO PLAN - FF1
1/8" = 1'-0"
SHEET:
ED-100
18031.00
G
G
J
GG
G
EXISTING
ELECTRICAL
PANELS
12
JJ
505 RAMAPO VALLEY RD.
MAHWAH, NY 07430
D
G
G
G
RCNJ No. 201437-01C
PHASE 2: ALTERATIONS
G
G
RAMAPO COLLEGE
OF NEW JERSEY
G
FB
G
13
ELECTRICAL DEMOLITION - FIRST
FLOOR
14
10.3
G
G
3/23/2016 3:30:20 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
DEMOLITION
GENERAL NOTES
1.
E
G
J
N
QQ.1
Q.2
Q.3
22
EXISTING EMERGENCY
LIGHTING PANEL EPPB
GE SPECTRA SERIES
B
C
D
EXISTING
ELECTRICAL
PANELS
KPP2
KPP3
KPP1
21
EXISTING 120/208V, 3PH, 4W
FEDERAL PACIFIC PANEL
20
F
V
19
APPROXIMATE
LOCATION OF
ELECTRICAL ROOM
ON SECOND FLOOR
FIRE
F ALARM PANEL
IS ALSO
LOCATED
V
HERE)
IDENTIFICATION AND/OR ABATEMENT OF
HAZARDOUS MATERIALS IS NOT PART OF THIS
SCOPE OF WORK. IF ASBESTOS OR OTHER
HAZARDOUS MATERIALS ARE ENCOUNTERED, THE
CONTRACTOR SHALL NOTIFY THE OWNER
IMMEDIATELY.
2.
REFER TO SPECIFICATIONS FOR RECYCLING,
CONSTRUCTION WASTE MANAGEMENT AND
DISPOSAL REQUIREMENTS.
3.
OPENING IN THE EXISTING STRUCTURE SMALLER
THAN 12" IN ANY DIRECTION ARE NOT IDENTIFIED
ON THESE DRAWINGS. SUBCONTRACTORS SHALL
BE RESPONSIBLE FOR PROVIDING OPENINGS
SMALLER THAN 12" AS REQUIRED FOR
INSTALLATION OF THEIR WORK.
4.
OPENINGS IN THE EXISTING STRUCTURE SHALL NOT
BE MADE WITHOUT PRIOR APPROVAL OF THE
STRUCTURAL ENGINEER.
5.
DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE
STRUCTURAL INTEGRITY OF THE BUILDING. IF
HIDDEN ELEMENTS OR DETERIORATED ELEMENTS
ARE ENCOUNTERED, NOTIFY THE ARCHITECT
IMMEDIATELY.
6.
PROTECT ADJACENT AREAS AND ITEMS "TO
REMAIN" DURING DEMOLITION/CONSTRUCTION.
REPAIR/REPLACE ITEMS DAMAGED DURING
CONSTRUCTION.
7.
IF UNANTICIPATED HIDDEN ELEMENTS OR
DETERIORATED ELEMENTS ARE ENCOUNTERED,
NOTIFY THE OWNERS REPRESENTATIVE
IMMEDIATELY.
REFER TO CONSULTANT DRAWINGS FOR
ADDITIONAL
DEMOLITION WORK.
8.
REVIEW w/ OWNER TO DETERMINE WHAT, IF
ANYTHING, WILL BE REMOVED BY OWNER AND
WHAT, IF ANYTHING, IS TO BE SALVAGED &
TURNED
OVER TO OWNER.
9.
DEVICES SHOWN "DASHED" OR IN "DARK INK" ARE
TO
BE REMOVED. ELECTRICAL SUB-CONTRACTOR
SHALL DISCONNECT AND REMOVE EXISTING
DEVICES, DISCONNECTS, STARTERS, RELAYS, AND
MISCELLANEOUS COMPONENTS AS REQUIRED.
WIRING AND CONDUITS
ASSOCIATED WITH
REMOVED ITEMS SHALL BE REMOVED BACK TO
SOURCE PANEL.
10.
DEVICES SHOWN AS "LIGHT INK" ARE EXISTING TO
REMAIN UNLESS OTHERWISE NOTED.
SEALED:
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
H
D
V
D
F
V
H
D
D
F
EXISTING FIRE
ALARM
ANNUNCIATOR
TO REMAIN.
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
18
ENGINEER:
S
S
KEYED NOTES
17
H
D1
H
D6
D6
16
15
D
H
D2
REMOVE EXISTING FIRE ALARM DETECTORS, PULL
STATIONS AND AUDIBLE/VISUAL DEVICES. REMOVE
FIRE ALARM ANNUNCIATION AND NOTIFICATION
CONDUIT & CIRCUITRY BACK TO NEAREST HOME-RUN
JUNCTION BOX AT CEILING FOR REUSE.
D3
REMOVE EXISTING SURFACE WIREMOLD FEEDING
DEVICES SUCH AS SWITCHES, FIRE ALARM PULL
STATIONS, AND AUDIBLE/VISUAL DEVICES MOUNTED
ON OR IN WALLS BEING REMOVED.
D4
REMOVE AND STORE EXISTING EXIT SIGN FOR
REINSTALLATION.
D5
REMOVE AND STORE FIRE ALARM DEVICE FOR
REINSTALLATION.
D6
REMOVE LIGHT FIXTURE.
H
F
D
ELECTRICAL SUB-CONTRACTOR SHALL DISCONNECT
AND REMOVE EXISTING LIGHT FIXTURES, OCCUPANCY
SENSORS, AND SWITCHES. REMOVE EXISTING CONDUIT
& CIRCUITRY BACK TO NEAREST HOME-RUN JUNCTION
BOX AT CEILING.
D4
REVISIONS
V
H
H
F
13
V
D
3
EXISTING
ELECTRICAL
PANELS
11
10.9
10.8
3D
H
S
DWR DW
S
12
14
10.3
D
H
F
H
D
S
D
S
H
A.4
B.7
9
S
S
F
K
D
F
M
M
S
8
10.2
10
S
(TYPICAL)
D1
F F
(TYPICAL)
D1
D
7
S
7.1
D
D4
D
D
D5
S
S
MULTIPLE
EXISTING TRACK
LIGHTS (TO BE
REMOVED)
(TYPICAL)
D1
F
6
5
D3
D2
D1
(TYPICAL) D2
4
S
D
S
S
S
D4
D
D
(TYPICAL) D1
D5
K
CHECKED BY:
WEF
2
1
S
D1
A
BFD
F
M
2.1
1.9
3
S
2.9
F
FF
F
DRAWN BY:
(TYPICAL)
F
H
I
K
L
M
O
ISSUED:
3.24.2016
DESCRIPTION:
BID DOCUMENTS
1
LIGHTING DEMO PLAN - FF1
1/8" = 1'-0"
SHEET:
ED-101
18031.00
D5
RCNJ No. 201437-01C
PHASE 2: ALTERATIONS
F
RAMAPO COLLEGE
OF NEW JERSEY
RPK
V
V
D
F
H
FF
LIGHTING DEMOLITION - FIRST
FLOOR
EXISTING
ELECTRICAL
D
PANEL
505 RAMAPO VALLEY RD.
MAHWAH, NY 07430
K
V
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
3/23/2016 3:30:21 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
DEMOLITION
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
IDENTIFICATION AND/OR ABATEMENT OF HAZARDOUS
MATERIALS IS NOT PART OF THIS SCOPE OF WORK. IF
ASBESTOS OR OTHER HAZARDOUS MATERIALS ARE
ENCOUNTERED, THE CONTRACTOR SHALL NOTIFY THE
OWNER IMMEDIATELY.
REFER TO SPECIFICATIONS FOR RECYCLING,
CONSTRUCTION WASTE MANAGEMENT AND
DISPOSAL REQUIREMENTS.
OPENING IN THE EXISTING STRUCTURE SMALLER THAN
12" IN ANY DIRECTION ARE NOT IDENTIFIED ON THESE
DRAWINGS. SUBCONTRACTORS SHALL BE
RESPONSIBLE FOR PROVIDING OPENINGS SMALLER
THAN 12" AS REQUIRED FOR INSTALLATION OF THEIR
WORK.
OPENINGS IN THE EXISTING STRUCTURE SHALL NOT BE
MADE WITHOUT PRIOR APPROVAL OF THE
STRUCTURAL ENGINEER.
DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE
STRUCTURAL INTEGRITY OF THE BUILDING.
PROTECT ADJACENT AREAS AND ITEMS "TO REMAIN"
DURING DEMOLITION/CONSTRUCTION.
REPAIR/REPLACE ITEMS DAMAGED DURING
CONSTRUCTION.
IF UNANTICIPATED HIDDEN ELEMENTS OR
DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY
THE OWNERS REPRESENTATIVE IMMEDIATELY.
REFER TO CONSULTANT DRAWINGS FOR ADDITIONAL
DEMOLITION WORK.
REVIEW w/ OWNER TO DETERMINE WHAT, IF
ANYTHING, WILL BE REMOVED BY OWNER AND
WHAT, IF ANYTHING, IS TO BE SALVAGED & TURNED
OVER TO OWNER.
DEVICES SHOWN AS "DASHED" OR IN "DARK INK" ARE
TO BE REMOVED. ELECTRICAL SUB-CONTRACTOR
SHALL DISCONNECT AND REMOVE EXISTING
DEVICES, DISCONNECTS, STARTERS, RELAYS, AND
MISCELLANEOUS COMPONENTS AS REQUIRED.
WIRING AND CONDUITS ASSOCIATED WITH
REMOVED ITEMS SHALL BE REMOVED BACK TO
SOURCE PANEL.
DEVICES SHOWN AS "LIGHT INK" ARE EXISTING TO
REMAIN UNLESS OTHERWISE NOTED.
SEALED:
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
KEYED NOTES
D1
D2
N
Q
N
D3
DISCONNECT POWER TO EXISTING HAND DRYERS AND
DRINKING FOUNTAIN RECEPTACLE. REMOVE JUNCTION
BOXES, RECEPTACLE AND ASSOCIATED CONDUIT AND
WIRING TO NEAREST HOMERUN JUNCTION BOX ABOVE
CEILING. COIL WIRING AND LABEL CIRCUITS FOR RE-USE.
DISCONNECT POWER TO EXISTING LIGHT FIXTURES AND
OCCUPANCY SENSORS. REMOVE LIGHT FIXTURES AND
ASSOCIATED CONDUIT AND WIRING TO NEAREST
HOMERUN JUNCTION BOX ABOVE CEILING. COIL WIRING
AND LABEL CIRCUITS FOR RE-USE.
CAREFULLY DISCONNECT AND REMOVE FIRE ALARM
DEVICES. REMOVE ASSOCIATED CONDUIT AND WIRING
TO NEAREST HOMERUN JUNCTION BOX ABOVE CEILING.
COIL WIRING AND LABEL CIRCUITS FOR RE-USE. STORE
FIRE ALARM DEVICES IN A SAFE LOCATION FOR REINSTALLATION.
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
ENGINEER:
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
REVISIONS
J
19
19
BFD
CHECKED BY:
WEF
D2
D
F
V
D2
F
18
V
D2
S
D3
J
S
D2
17
G
17
J
F
V
D1
G
G
G
1
ELECTRICAL DEMO PLAN - FF1 - RESTROOMS
15
0
4
8
2
12
1/4" = 1'-0"
LIGHTING DEMO PLAN - FF1 - BATHROOMS
0
4
8
12
1/4" = 1'-0"
NORTH
NORTH
RCNJ No. 201437-01C
PHASE 2: ALTERATIONS
18
D1
D
RAMAPO COLLEGE
OF NEW JERSEY
D1
D3
ELECTRICAL DEMOLITION TOILET ROOMS
D2
ISSUED:
3.24.2016
DESCRIPTION:
BID DOCUMENTS
SHEET:
ED-110
18031.00
D2
DRAWN BY:
505 RAMAPO VALLEY RD.
MAHWAH, NY 07430
J
3/23/2016 3:30:21 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
EXISTING EQUIPMENT SCHEDULE
DESSERT
EQ16
GRILL
EQ3
EQ4
EQ6
EQ7
HOMETOWN
EQ5
EQ8
EQ9
MEDITERRANEAN
EQ1
EQ2
PIZZA
EQ10
EQ11
EQ12
SALAD
EQ17
EQ18
SANDWICH
EQ19
EQ20
WOK
EQ14
EQ15
EQ21
EQ22
EQ23
BREAKFAST
EQ13
DEMOLITION
EXISTING COLD WELL
EXISTING HOT WELL
EXISTING HOT WELL
EXISTING FRYER
EXISTING CONVECTION OVEN
EXISTING HOT WELL
EXISTING REFRIDGERATOR
EXISTING WALL MOUNTED SINK
GENERAL NOTES
1.
2.
3.
EXISTING HOT WELL
EXISTING HOT WELL
EXISTING IMPINGER
EXISTING PAN RACK
EXISTING PIZZA MAKE TABLE
4.
5.
EXISTING COLD WELL
EXISTING COLD WELL
EXISTING COLD WELL
EXISTING HAND SINK
EXISTING HOT WELL
EXISTING HOT WELL
EXISTING SINK
EXISTING UNDERCOUNTER REFRIDGERATOR
EXISTING UNDERCOUNTER REFRIDGERATOR
6.
7.
8.
EXISTING HOT WELL
9.
B
C
10.
IDENTIFICATION AND/OR ABATEMENT OF
HAZARDOUS MATERIALS IS NOT PART OF THIS SCOPE
OF WORK. IF ASBESTOS OR OTHER HAZARDOUS
MATERIALS ARE ENCOUNTERED, THE CONTRACTOR
SHALL NOTIFY THE OWNER IMMEDIATELY.
REFER TO SPECIFICATIONS FOR RECYCLING,
CONSTRUCTION WASTE MANAGEMENT AND
DISPOSAL REQUIREMENTS.
OPENING IN THE EXISTING STRUCTURE SMALLER
THAN 12" IN ANY DIRECTION ARE NOT IDENTIFIED
ON THESE DRAWINGS. SUBCONTRACTORS SHALL BE
RESPONSIBLE FOR PROVIDING OPENINGS SMALLER
THAN 12" AS REQUIRED FOR INSTALLATION OF THEIR
WORK.
OPENINGS IN THE EXISTING STRUCTURE SHALL NOT
BE MADE WITHOUT PRIOR APPROVAL OF THE
STRUCTURAL ENGINEER.
DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE
STRUCTURAL INTEGRITY OF THE BUILDING. IF
HIDDEN ELEMENTS OR DETERIORATED ELEMENTS ARE
ENCOUNTERED, NOTIFY THE ARCHITECT
IMMEDIATELY.
PROTECT ADJACENT AREAS AND ITEMS "TO
REMAIN" DURING DEMOLITION/CONSTRUCTION.
REPAIR/REPLACE ITEMS DAMAGED DURING
CONSTRUCTION.
IF UNANTICIPATED HIDDEN ELEMENTS OR
DETERIORATED ELEMENTS ARE ENCOUNTERED,
NOTIFY THE OWNERS REPRESENTATIVE IMMEDIATELY.
REFER TO CONSULTANT DRAWINGS FOR
ADDITIONAL DEMOLITION WORK.
REVIEW w/ OWNER TO DETERMINE WHAT, IF
ANYTHING, WILL BE REMOVED BY OWNER AND
WHAT, IF ANYTHING, IS TO BE SALVAGED & TURNED
OVER TO OWNER.
DEVICES SHOWN AS "DASHED" OR IN "DARK INK" ARE
TO BE REMOVED. ELECTRICAL SUB-CONTRACTOR
SHALL DISCONNECT AND REMOVE EXISTING
DEVICES, DISCONNECTS, STARTERS, RELAYS, AND
MISCELLANEOUS COMPONENTS AS REQUIRED.
WIRING AND CONDUITS ASSOCIATED WITH
REMOVED ITEMS SHALL BE REMOVED BACK TO
SOURCE PANEL.
DEVICES SHOWN AS "LIGHT INK" ARE EXISTING TO
REMAIN UNLESS OTHERWISE NOTED.
SEALED:
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
KEYED NOTES
D1
19
D2
DISCONNECT POWER TO KITCHEN WOK EQUIPMENT EQ14, EQ-15, EQ-22 & EQ-23 TO ACCOMODATE WOK
COUNTER/MILLWORK RENOVATION. REFER TO
DRAWING E-113 ELECTRICAL PLAN - SERVERY FOR REINSTALLATION. EXISTING EQUIPMENT IS FED FROM
CONDUIT AND WIRING IN FLOOR SLAB.
DISCONNECT AND REMOVE POWER TO EXISTING KITCHEN
EQUIPMENT EQ-13 AND EQ-16. REMOVE CONDUIT AND
WIRING TO NEAREST HOMERUN JUNCTION BOX. REFER TO
DRAWING E-113 ELECTRICAL PLAN - SERVERY FOR NEW
EQUIPMENT LOCATIONS.
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
ENGINEER:
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
REVISIONS
EQ12
EQ11
EQ10
EQ-13
EQ21
D1
EQ22
D2
Author
CHECKED BY:
Checker
EQ9
17
16
EQ5
15
EQ15
EQ4
EQ7
14
EQ16
EQ3
EQ6
EQ17
EQ20
EQ2
12
11
EQ19
EQ18
RAMAPO COLLEGE
OF NEW JERSEY
D1
ELECTRICAL DEMOLITION SERVERY - ALTERNATE #1
D1
RCNJ No. 201437-01C
PHASE 2: ALTERATIONS
EQ8
EQ23
G
EQ1
A
1
ELECTRICAL DEMO PLAN - FF1 - SERVERY
0
4
8
12
1/4" = 1'-0"
NORTH
ISSUED:
3.24.2016
DESCRIPTION:
BID DOCUMENTS
SHEET:
ADD/ALT 1
ED-111
18031.00
EQ14
DRAWN BY:
505 RAMAPO VALLEY RD.
MAHWAH, NY 07430
EQ-16
3/23/2016 3:29:04 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
SEALED:
B
C
D
E
G
J
N
QQ.1
Q.2
Q.3
CABIN
TE
0
NA1D A
EA
B
R
KR0
,
F
N
50 D
AT
B
T
E
R
0
0
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
18
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
17
KEYED NOTES
16
15
E1. CONNECT TO EXISTING UNDERGROUND EXTERIOR
LIGHTING CIRCUITRY/CONDUIT THAT FEEDS BLDG. MOUNTED
COLUMN LIGHTS (VIA TIME CLOCK & PHOTOCELL). EXTEND
CIRCUIT USING (2) #12, #10G IN 3/4" RGS CONDUIT TO FEED
NEW COLUMN LIGHT POLE (FIXTURE TYPE "S1") LOCATIONS
SHOWN. REFER TO ELECTRICAL DETAIL SHEET E-310 FOR LIGHT
FIXTURE SCHEDULE, TRENCH DETAIL AND LIGHT POLE
FOUNDATION DETAIL.
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
ENGINEER:
14
10.3
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
13
CABINET BREA
, KR01050F
NA
DAND BATTER
00
M
MH
RY
TA 2
NI 9.9
SA M 30
RI
3
12
11
00
ND BATTER
A
NA
01050F
BREAD
KR
10.9
10.8
3D
B.7
7
MH
M 3
OR 9.9
ST M 30
RI
S1
AIN
DR 44
CH 08.
EN 3
TR ATE
GR
UE
S1
6
5
UE
4
G
3
UE
2.9
BUILDING LINE BELOW
T
LE
IN
S1
S1
T
LE
IN
S1
UE
S1
2
1
LP
I
K
L
M
O
REFER TO LANDSCAPE DRAWINGS
FOR EXACT LOCATIONS.
COORDINATE WITH OTHER TRADES
AND EXISTING UNDERGROUND
UTILITIES. (TYPICAL)
T
UL
VA
H
TY
ILI
UT
T
LE
IN
ABOVE GRO
UND
F
LP
T
LE
IN
A
UE
UE
STEAM PIPE
S
WOOD FEN
CE
WOOD FEN
CE
E
ON
PH 5
LE 7.7
TE M 30
RI
ABOVE
G
R
O
U
N
D
STEAM PIPE
S
MH
WOOD FEN
CE
MH
ISSUED:
3.24.2016
S
GA
TY
ILI
UT
0
E
ON
PH 5
LE 9.9
TE M 30
RI
AIN
DR 37
CH 08.
EN 3
TR ATE
GR
S1
RCNJ No. 201437-01C
PHASE 2: ALTERATIONS
7.1
RAMAPO COLLEGE
OF NEW JERSEY
UE
E1
X
BO
20' FROM
E
X
I
S
T
IN
G
WOOD
F
E
N
C
E
L
O
CATION
S
GA
GV
E
LIN
PE
PI
ER
RK
MA
SITE ELECTRICAL PLAN
WEF
ELECTRICAL SITE PLAN
9
1
CHECKED BY:
10.2
10
8
2.1
1.9
BFD
LP
A.4
DRAWN BY:
DESCRIPTION:
BID DOCUMENTS
8
16
SHEET:
24
1/8" = 1'-0"
NORTH
E-050
18031.00
BIN ET,
505 RAMAPO VALLEY RD.
MAHWAH, NY 07430
CA
REVISIONS
E
LIN
PE
PI
ER
RK
MA
3/23/2016 3:29:06 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
GENERAL NOTES
1.
E
G
J
N
QQ.1
DEVICES SHOWN AS LIGHT OR SHADED ARE
EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
Q.2
Q.3
SEALED:
22
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
B
C
D
KPP3
KPP2
KPP1
21
KEYED NOTES
19
J
0
0
18
PPP-1
PPP-2
J
LPK
17
G
J
16
15
E2. PROVIDE (2) 1" RGS CONDUITS UNDER SLAB WITH PULL
STRING STUBBING UP WITHIN STUD WALL AT LOCATION
SHOWN FOR FUTURE POWER & LIGHTING. CONDUITS WILL BE
EXTENDED TO DEVICE LOCATIONS DURING INTERIOR FINISHES
PHASE.
E3. PROVIDE (2) 1" RGS CONDUITS UNDER SLAB WITH PULL
STRING STUBBING UP WITHIN STUD WALL AT LOCATION
SHOWN FOR FUTURE POWER & DATA. CONDUITS WILL BE
EXTENDED TO DEVICE LOCATIONS DURING INTERIOR FINISHES
PHASE.
E4. PROVIDE (3) 3/4" RGS CONDUITS WITH PULL STRING UNDER
SLAB STUBBING UP WITHIN STUD WALL AT LOCATION SHOWN.
CONDUITS AT VESTIBULE END SHALL RISE UP WITHIN MASONRY
COLUMN FOR FUTURE POWER (VESTIBULE HVAC CEILING
CASSETTE UNIT), VESTIBULE LIGHTS & FIRE ALARM DEVICES.
PROVIDE DEVICE BOXES FOR FIRE ALARM DEVICES AND
PENETRATE MASONRY WALL ABOVE VESTIBULE CEILING FOR
LIGHTS AND HVAC POWER.
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
ENGINEER:
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
REVISIONS
DRAWN BY:
BFD
CHECKED BY:
WEF
14
10.3
RPK
RCNJ No. 201437-01C
PHASE 2: ALTERATIONS
D
13
J
DWR DW
11
CA
ND BATTER
A
NA
01050F
BREAD
KR
BIN ET,
10.9
10.8
E4
U
U
U
D
U
U
10.2
10
U
D
D
D
U
U
U
U
D
U
U
D
B.7
U
D
U
U
D
A.4
U
9
U
U
8
U
D
U
U
WAP
D
D
D
U
7.1
U
U
U
U
U
D
U
U
U
U
6
5
U
D
D
D
U
U
D
U
D
U
U
D
D
U
U
U
U
U
U
D
D
D
U
E1
U
7
RAMAPO COLLEGE
OF NEW JERSEY
00
ELECTRICAL PLAN
12
U
U
D
U
U
4
U
D
D
U
3
U
U
2.9
U
D
D
U
U
2.1
1.9
E2
2
1
E3
A
F
H
I
K
L
M
O
ISSUED:
3.24.2016
DESCRIPTION:
BID DOCUMENTS
1
ELECTRICAL PLAN - FF1 PH2
1/8" = 1'-0"
SHEET:
E-100
18031.00
J
E1. SAWCUT FLOOR AND PROVIDE (2) 1" RGS CONDUITS WITH
PULL STRING FROM NEARBY WALL (GOES TO DECK) TO EACH
LOCATION SHOWN FOR FUTURE POWER & DATA AT
SEATING/SHORT WALLS. CONCEAL CONDUITS IN WALL
GOING TO DECK AND SWEEP OUT CLOSE TO BOTTOM OF
STRUCTURE. SAWCUT AREA INDICATED BY SHADING.
505 RAMAPO VALLEY RD.
MAHWAH, NY 07430
20
3/23/2016 3:29:11 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
GENERAL NOTES
1.
2.
3.
4.
5.
E
G
J
N
QQ.1
Q.2
Q.3
6.
22
7.
8.
EXISTING EMERGENCY
LIGHTING PANEL EPPB
GE SPECTRA SERIES
9.
EPPB
10.
ERP-B
11.
IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL
MATERIAL AND EQUIPMENT IN ACCORDANCE WITH THE
CURRENT N.E.C. (NATIONAL ELECTRICAL CODE).
ALL WORK SHALL BE INSTALLED NEAT AND WORKMANLIKE
COMPLYING WITH THE STANDARDS OF N.E.C..
THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL
CONDITIONS, LOCATIONS, DIMENSIONS, AND COUNTS AS
SHOWN AND NOTED ON THE DRAWINGS FOR THIS WORK
PRIOR TO BIDDING. NO ADDITIONAL COST WILL BE ISSUED
FOR FAILURE TO COMPLY WITH THIS REQUIREMENT.
THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIAL,
AND SUPERVISION NECESSARY TO ACCOMPLISH THE WORK
AS SHOWN AND NOTED ON THE DRAWINGS. ANY
DEVIATION FROM THE DRAWINGS SHALL BE APPROVED BY
THE OWNER.
THE ELECTRICAL CONTRACTOR SHALL DO ALL CUTTING AND
PATCHING OF THE BUILDING MATERIALS REQUIRED FOR THE
INSTALLATION OF HIS WORK. ALL FIRE RATED WALLS, FLOORS,
OR CEILINGS SHALL BE SEALED TO MAINTAIN THE FIRE
RATING.
THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR THE
REMOVAL OF ALL TOOLS, DEBRIS, AND GENERAL CLEAN UP
FROM HIS WORK.
ALL WORK SHALL BE COORDINATED WITH THE OTHER
TRADES.
THE ELECTRICAL CONTRACTOR SHALL MAKE ALL NECESSARY
TESTS TO INSURE THAT THE ENTIRE INSTALLATION IS FREE FROM
IMPROPER GROUNDS AND FROM SHORTED AND/OR OPEN
CIRCUITS. VOLTAGE AND CURRENT TESTS SHALL BE MADE
BEFORE ANY MOTORS ARE PLACED IN OPERATION.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING
AND PAYING FOR ALL REQUIRED PERMITS.
THE ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL
WORK AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER
ACCEPTANCE OF THE WORK AND MATERIALS.
ALL ELECTRICAL EQUIPMENT AND DEVICES SHALL BE LABELED
WITH 1/2" DYNO TAPE FOR THE SOURCE AND CONTROL
LOCATION.
SEALED:
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
D
21
20
19
0
0
18
PPP-1
PPP-2
15
E4. PROVIDE RECEPTACLES AND DATA DEVICES AS SHOWN. REUSE EXISTING AREA RECEPTACLE CIRCUIT AND MODIFY AND
EXTEND TO NEW LOCATIONS AS SHOWN. PROVIDE ALL
CONDUIT, MC CABLE AND WIRING REQUIRED FOR A FULLY
FUNCTIONAL INSTALLATION.
J
1
E-112
RPK
14
10.3
D
13
J
D
E1
12
DWR DW
11
00
CA
BIN ET,
ND BATTER
A
NA
01050F
BREAD
KR
10.9
10.8
E4
J
G
RESIDENTIAL SERVERY
138
J
E2
E5
UPPER RESIDENTIAL
DINING
139
ERP-B-1,3
U
U
U
D
U
U
U
D
D
D
U
U
U
U
D
U
U
D
B.7
CEILING UNIT
HEATER CUH-1
U
D
U
U
A.4
D
D
U
D
U
72"
U
J
E3
72"
D
72"
U
D
U
7.1
WAP
D
D
E5
D
U
E2
U
8
U
U
U
D
D
U
U
U
U
U
D
U
U
D
D
U
E5
U
D
U
U
6
5
U
D
D
D
U
U
U
D
U
U
D
U
D
U
D
U
U
U
U
E6
U
4
E4
U
U
U
LOWER RESIDENTIAL
DINING
140
D
D
U
U
U
D
UPPER LOUNGE
137
7
U
U
E5
10.2
10
9
E6
72"
E2. PROVIDE NEW JUNCTION BOXES ABOVE CEILING FOR NEW
MOTOR OPERATED DOORS. MODIFY AND EXTEND EXISTING
CIRCUITRY TO NEW LOCATION SHOWN. PROVIDE ALL
CONDUIT, MC CABLE AND WIRING REQUIRED FOR A FULLY
FUNCTIONAL INSTALLATION. PROVIDE WIRING AND
CONNECTIONS TO DOOR OPERATOR PUSH BUTTONS.
COORDINATE LOCATIONS AND INSTALLATION IN FIELD.
17
E2
16
E1. RE-INSTALL RECEPTACLE AND DATA JACKS FOR A.T.M. AT
LOCATION SHOWN. MODIFY AND EXTEND CIRCUITRY AND
DATA CABLES TO NEW LOCATION. PROVIDE NEW CONDUIT,
MC CABLE, WIRING AND DATA CABLING AS REQUIRED FOR A
FULLY FUNCTIONAL INSTALLATION.
E3. PROVIDE 208V, 2-POLE TOGGLE SWITCH DISCONNECT AND
CONNECTION TO NEW CEILING UNIT HEATER CUH-1. RECESS
TOGGLE DISCONNECT IN GYP. CEILING AND PROVIDE FLUSH
FACEPLATE FOR A CLEAN INSTALLATION. PROVIDE A 2-POLE
20A CIRCUIT BREAKER IN EXISTING GE PANELBOARD ERP-B AND
CIRCUIT USING 3/4" EMT CONDUIT AND (3) #10, #10G.
COORDINATE EXACT LOCATION AND INSTALLATION IN FIELD.
LPK
J
KEYED NOTES
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
ENGINEER:
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
REVISIONS
DRAWN BY:
BFD
CHECKED BY:
WEF
E5. PROVIDE RECEPTACLES AND DATA DEVICES AS SHOWN.
PROVIDE 3/4" CONDUIT, MC CABLE AND #12 WIRING AND
CIRCUIT TO NEAREST AVAILABLE 120/208V PANEL WITH SPACE
(PPP-1, PPP-2, LPK, DWR) VERIFY AVAILABLE SPACE IN
PANELBOARDS PRIOR TO INSTALLATION. PROVIDE 20A, 1-POLE
CIRCUIT BREAKER COMPATIBLE WITH EXISTING PANEL FOR
EACH CIRCUIT SHOWN.
E6. E.C. SHALL RUN ALL DATA CABLING TO CAMPUS I.T. DATA
RACK LOCATED IN THE SECOND FLOOR ELECTRICAL ROOM.
PROVIDE 10' OF LOOSE COILED CABLE AT DATA RACK FOR
TERMINATION BY CAMPUS I.T. PERSONNEL. PROVIDE J-HOOKS
FROM DATA JACK LOCATIONS TO THIS ROOM. TAKE SPECIAL
CARE TO ROUTE CABLING AND J-HOOKS ABOVE CEILING
ELEMENTS TO LIMIT VISIBLE SECTIONS FROM PUBLIC VIEW.
WHERE CABLING AND J-HOOKS MUST BRIDGE SMALL GAPS
BETWEEN CEILING ELEMENTS, PAINT J-HOOKS TO MATCH OTHER
EXPOSED BUILDING MATERIALS. ALSO TAKE SPECIAL CARE ON
THE SECOND FLOOR AS THE CEILINGS IN THIS AREA ARE NOT
BEING REPLACED. E.C. SHALL BE RESPONSIBLE FOR
REPLACEMENT OF BROKEN TILES AND ANY TEMPORARY
REMOVAL/RE-INSTALLATION OF EXISTING LIGHTS OR DEVICES
AS REQUIRED FOR A COMPLETE AND FULLY FUNCTIONAL
INSTALLATION. COORDINATE INSTALLATION WITH CAMPUS I.T.
DEPARTMENT PERSONNEL.
E7. PROVIDE JUNCTION BOX AND CONNECTION AT DOOR
FOR DOOR ALARM. PROVIDE 3/4" CONDUIT, MC CABLE AND
#12 WIRING AND CIRCUIT TO NEAREST AVAILABLE 120/208V
PANEL WITH SPACE (PPP-1, PPP-2, LPK, DWR) VERIFY AVAILABLE
SPACE IN PANELBOARDS PRIOR TO INSTALLATION.
COORDINATE LOCATION AND INSTALLATION WITH ARCHITECT
AND CAMPUS PERSONNEL. PROVIDE 20A, 1-POLE CIRCUIT
BREAKER COMPATIBLE WITH EXISTING PANEL FOR CIRCUIT FEED.
U
D
D
U
3
J
D
72"
E6
U
E7
D
D
E6
72"
U
72"
D
E5
72"
U
U
2.9
U
LOWER LOUNGE
136
2.1
1.9
2
1
A
F
H
I
K
L
M
ISSUED:
3.24.2016
O
DESCRIPTION:
BID DOCUMENTS
1
ELECTRICAL PLAN - FF1
0
8
16
24
1/8" = 1'-0"
SHEET:
NORTH
E-110
18031.00
EXISTING 120/208V, 3PH, 4W
FEDERAL PACIFIC PANEL
505 RAMAPO VALLEY RD.
MAHWAH, NY 07430
KPP2
KPP1
RCNJ No. 201437-01C
PHASE 2: ALTERATIONS
KPP3
RAMAPO COLLEGE
OF NEW JERSEY
C
ELECTRICAL ALTERATIONS FIRST FLOOR
B
3/23/2016 3:29:12 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
SEALED:
E
G
J
N
QQ.1
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
Q.2
Q.3
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
22
KEYED NOTES
E1. DISCONNECT POWER TO EXISTING 1HP, 480V, 3PH
KITCHEN EXHAUST FAN (EF-6, OVER WOK) AND RECONNECT AFTER IT HAS BEEN REPLACED. LOCATE EXISTING
DISCONNECT AND REPLACE FUSES WITH 10A SIZE AS
REQUIRED FOR NEW 5HP, 480V, 3PH FAN. COORDINATE ALL
WORK.
EXISTING ELECTRICAL
PANEL "AC-1"
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
ENGINEER:
EXISTING EMERGENCY LIGHT
POWER PANEL "EPP-A"
B
C
D
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
ELECTRICAL ROOM
21
EXISTING KITCHEN EXHAUST
FAN EF-6 (OVER WOK) ON
ROOF ABOVE
REVISIONS
20
EXISTING NOTIFIER
FIRE ALARM PANEL
19
DRAWN BY:
BFD
CHECKED BY:
WEF
18
13
DN
12
11
10.9
10.8
10.2
A
1
ELECTRICAL PLAN - FF2
F
H
I
K
M
0
8
16
24
1/8" = 1'-0"
NORTH
ISSUED:
3.24.2016
DESCRIPTION:
BID DOCUMENTS
SHEET:
E-111
18031.00
14
10.3
RAMAPO COLLEGE
OF NEW JERSEY
15
ELECTRICAL ALTERATIONS SECOND FLOOR
16
RCNJ No. 201437-01C
PHASE 2: ALTERATIONS
17
505 RAMAPO VALLEY RD.
MAHWAH, NY 07430
E1
3/23/2016 3:29:13 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
SEALED:
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
KEYED NOTES
E1. MODIFY AND EXTEND EXISTING HAND DRYER CONDUIT AND
CIRCUITRY TO NEW LOCATIONS SHOWN. COORDINATE EXACT
LOCATION AND MOUNTING HEIGHT IN FIELD.
N
20
20
E3. MODIFY AND EXTEND EXISTING DRINKING FOUNTAIN
CONDUIT AND CIRCUITRY TO NEW LOCATION SHOWN.
PROVIDE NEW GFCI OUTLET. COORDINATE EXACT LOCATION
AND MOUNTING HEIGHT IN FIELD.
19
E4. INSTALL NEW LIGHT FIXTURES AND DUAL TECHNOLOGY
OCCUPANCY SENSORS AND CONNECT TO EXISTING
CIRCUITRY. CONNECT EMERGENCY FIXTURES DENOTED WITH "E"
TO EXISTING EMERGENCY CIRCUIT. LINK OCCUPANCY
SENSORS TOGETHER IN EACH BATHROOM TO WORK TO
CONTROL AS A SINGLE SPACE. THE EMERGENCY FIXTURES
SHALL ALSO BE TIED TO SAID OCCUPANCY SENSORS VIA AN
EMERGENCY LIGHTING CONTROL UNIT WITH SWITCHED INPUT.
PROVIDE NEW CONDUIT, WIRING AND MC CABLE AS
REQUIRED TO FURNISH A FULLY FUNCTIONAL INSTALLATION.
F2
19
F2
E4
(TYPICAL)
18
J
F
F2 E
V
J
F2
S
F2
E2
F1
D
E5
E
E4
F2
F1
(TYPICAL)
F
F1
E1
17
S
V
REUSE EXISTING
NORMAL &
EMERGENCY
F1 LIGHTING
CIRCUITS
F1
F2
E5
F1
F2
17
E
F2
F1
J
D
D
E1
E
F2
E
F2
E
J
G
D
G
E3
1
ELECTRICAL PLAN - FF1 - RESTROOMS
1/4" = 1'-0"
2
LIGHTING PLAN - FF1 - BATHROOMS
1/4" = 1'-0"
REUSE EXISTING
NORMAL &
EMERGENCY
LIGHTING
CIRCUITS
15
H
G
G
15
CHECKED BY:
WEF
ISSUED:
3.24.2016
DESCRIPTION:
BID DOCUMENTS
SHEET:
E-112
18031.00
E
J J
E2
BFD
505 RAMAPO VALLEY RD.
MAHWAH, NY 07430
F2
F2
DRAWN BY:
RCNJ No. 201437-01C
PHASE 2: ALTERATIONS
E
F1
REVISIONS
E5. REINSTALL EXISTING FIRE ALARM DEVICES AND CONNECT
TO EXISTING CIRCUITRY. PROVIDE NEW CONDUIT, WIRING AND
MC CABLE AS REQUIRED TO FURNISH A FULLY FUNCTIONAL
INSTALLATION.
D
F2
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
RAMAPO COLLEGE
OF NEW JERSEY
F1
ENGINEER:
ELECTRICAL/ LIGHTING
ALTERATIONS - TOILET ROOMS
N
E2. MODIFY AND EXTEND UNUSED EXISTING HAND DRYER
CONDUIT AND CIRCUITRY TO FEED NEW SINK, URINAL AND
TOILET AUTOMATIC FLUSH VALVE TRANSFORMERS. PROVIDE
CONDUIT AND LOW VOLTAGE WIRING FROM TRANSFORMER
LOCATIONS TO EACH SINK, URINAL AND TOILET AUTOMATIC
FLUSH VALVE LOCATION. COORDINATE EXACT LOCATIONS IN
FIELD. CONCEAL ALL CONDUIT AND WIRING WITHIN WALLS
AND ABOVE CEILING. PROVIDE A FULLY FUNCTIONAL
INSTALLATION.
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
EXISTING EQUIPMENT SCHEDULE
KITCHEN EQUIPMENT SCHEDULE
Electrical
Connection
Height
Cold
Water
(in)
Cold Water
Conn.
Height(in)
Hot
Water
(in)
Hot Water
Conn.
Height(in)
Indirect
Waste
Size
Direct
Waste
Size
Direct
Waste
Conn.
Height(in)
Gas Conn.
Gas Size(in) Height (in)
Gas MBTU
ItemNo
Quantity
Category
Mfr
Model
Voltage
Phase Amps
Cycle Hp
1
1
Sandwich / Salad Preparation Refrigerator
Continental Refrig
SW72-30M-FB
115
1
60
2
1
Range, 36", 6 Open Burners
Vulcan
36S-6B
3/4"
215.0
3
1
Charbroiler
Vulcan
VACB36
3/4"
102.0
4
1
Countertop Griddle
Vulcan
948RX
120
1
1.0
60
3/4"
108.0
5
1
Equipment Stand, Refrigerated Base
Vulcan
ARS84
115
1
12.0
60
6
1
Carving Station / Shelf
Hatco
DCSB400-3624-2
120
1
10.83
60
7
1
Fryer
Vulcan
LG500
8
1
Work Table
Advance Tabco
KSS-305
9
1
Dual Temp Food Well, Drop-In
Wells
HRCP-7300
115
1
5.6
60
Wells
HRCP-7300
208/240
1
14.4/16.7
60
1
7.6
Kw
1/2
1.3
Connection Type
NEMA
Cord & Plug
5-15P
Cord & Plug
5-15P
Cord & Plug
5-15P
Cord & Plug
5-15P
3/4"
1/3
3.8/5.0
Drop-In Sink
Advance Tabco
DI-1-2012
11
1
Microwave Oven
ACP
RCS10TS
120
1
12
1
Conveyor Toaster
Adcraft
CVYT-120
120
1
13
1
Reach-In Freezer
True
STG1F-1S
115
1
6.8
60
1/2
Cord & Plug
5-15P
14
1
Reach-In Refrigerator
True
STG1R-1S
115
1
4.8
60
1/3
Cord & Plug
5-15P
15
1
Heated Shelf Food Warmer
Hatco
GRS-72-L
120
1
5-15P
1-1/2"
15
60
1
60
1.7
5-15P
1.45
Cord & Plug
0.45
Direct
Spare Number
2
Drop-In Hot Well
Wells
SS-10
120
1
3.75
60
18
1
Display Freezer
Entree
OFL-40
115
1
1.0
60
19
1
Dipper Well
AllPoints
56-1462
20
1
L-Shaped Work Table
Advance Tabco
KTMS-307
Advance Tabco
TA-11A-2
Hatco
DL-775-CL
Hatco
DL-SWITCH-16AMP
Beverage Air
UCR60A
1
4
Decorative Lamp
4
1
Reach-In Undercounter Refrigerator
1/8
5-15P
Cord & Plug
EXISTING COLD WELL
GENERAL NOTES
EXISTING HOT WELL
EXISTING HOT WELL
EXISTING FRYER
EXISTING CONVECTION OVEN
1.
2.
EXISTING HOT WELL
EXISTING REFRIDGERATOR
EXISTING WALL MOUNTED SINK
EXISTING HOT WELL
EXISTING HOT WELL
PROVIDE ALL CONDUIT, WIRING, HANGERS, SUPPORTS,
AND MISCELANEOUS COMPONENTS REQUIRED TO
FURNISH A FULLY OPERATIONAL INSTALLATION.
EXISTING POWER FEEDS TO WOK AND SERVER LINE
ISLANDS IS IN OR UNDER THE EXISTING SLAB. COORDINATE
ALTERATION WORK TO RE-USE EXISTING FLOOR
PENETRATIONS AND IN SLAB CONDUIT WHERE POSSIBLE.
COORDINATE EXISTING CONDUIT FLOOR PENETRATIONS
AND EQUIPMENT FEEDS WITH ARCHITECT AND NEW
CASEWORK.
EXISTING IMPINGER
EXISTING PAN RACK
EXISTING PIZZA MAKE TABLE
SEALED:
EXISTING COLD WELL
EXISTING COLD WELL
EXISTING COLD WELL
EXISTING HAND SINK
EXISTING HOT WELL
EXISTING HOT WELL
EXISTING SINK
EXISTING UNDERCOUNTER REFRIDGERATOR
EXISTING UNDERCOUNTER REFRIDGERATOR
EXISTING HOT WELL
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
(2) 1-1/2"
1
120
2.08
60
.25
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
Direct
ARCHITECT:
16.0
115
1
8.2
60
1/4
KEYED NOTES
B
C
D
E
E1. MODIFY AND EXTEND EXISTING POWER AND CIRCUITRY AS
REQUIRED TO RE-CONNECT POWER TO EXISTING KITCHEN WOK
EQUIPMENT EQ-14, EQ-15, EQ-22 & EQ-23.
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
ENGINEER:
E2. MODIFY AND EXTEND EXISTING POWER AND CIRCUITRY AS
REQUIRED TO RE-CONNECT POWER TO EXISTING RE-LOCATED
KITCHEN EQUIPMENT EQ-13 AND EQ-16.
E3. DISCONNECT POWER TO EXISTING 208V INDUCTION
RANGES. MODIFY AND EXTEND (1) EXISTING CIRCUIT FOR
CONNECTION TO NEW SANDWICH/SALAD PREP
REFRIGERATOR. REMOVE OTHER CIRCUIT BACK TO SOURCE
PANEL PPP-2 AND RE-LABEL CIRCUIT BREAKER SPARE.
E12
19
11
E13
E2
12
10
E4. COUNTERTOP GRIDDLE: PROVIDE NEW 120V, 5-20R
RECEPTACLE. PROVIDE A 1-POLE, 20A CIRCUIT BREAKER IN
EXISTING PANEL PPP-2 AND (2) #12, #12G IN 3/4" CONDUIT TO
FEED NEW EQUIPMENT. CONCEAL CONDUIT IN WALL AND
ABOVE CEILING TO MINIMIZE VISIBILITY. IN EXPOSED CEILING
AREA, PAINT TO MATCH EXISTING FINISH. COORDINATE
INSTALLATION AND LOCATION OF EQUIPMENT IN FIELD.
EQ13
EQ12
EQ11
EQ21 EQ22
EQ10
E5. DUAL TEMP DROP IN FOOD WELLS: PROVIDE A 1-POLE, 20A
CIRCUIT BREAKER IN EXISTING PANEL PPP-1 OR PPP-2 AND (2) #
12, #12G IN 3/4" CONDUIT TO FEED NEW 120V FOOD WELL.
PROVIDE A 2-POLE, 20A CIRCUIT BREAKER IN EXISTING PANEL
PPP-1 OR PPP-2 AND (3) #12, #12G IN 3/4" CONDUIT TO FEED
NEW 208V FOOD WELL. USE EXSITNG IN SLAB CONDUITS OR
PROVIDE NEW FEED FROM NEW WALL AND INSIDE CASEWORK.
CONCEAL CONDUIT IN WALL, CASEWORK, AND ABOVE
CEILING TO MINIMIZE VISIBILITY. IN EXPOSED CEILING AREA,
PAINT TO MATCH EXISTING FINISH. COORDINATE INSTALLATION
AND LOCATION OF EQUIPMENT IN FIELD.
8
E15
E1
5-20R
13
E10
G
5-20R
14
PPP-1
20
E6. DISCONNECT POWER TO ACCOMMODATE REMOVAL OF
EXISTING HOT WELLS. CONNECT (1) EXISTING 120V CIRCUIT TO
NEW REPLACEMENT HOT WELLS (3.75A EA.). MODIFY AND
EXTEND SECOND EXISTING CIRCUIT TO FEED NEW DISPLAY
FREEZER (1A, 5-15P). PROVIDE NEW 5-20R RECEPTACLE FOR
DISPLAY FREEZER.
LPK
EQ9
17
E1
E7. EQUIPMENT STAND, REFRIGERATED BASE: PROVIDE NEW
120V, 5-20R RECEPTACLE. PROVIDE A 1-POLE, 20A CIRCUIT
BREAKER IN EXISTING PANEL PPP-2 AND (2) #12, #12G IN 3/4"
CONDUIT TO FEED NEW EQUIPMENT. CONCEAL CONDUIT IN
WALL AND ABOVE CEILING TO MINIMIZE VISIBILITY. IN EXPOSED
CEILING AREA, PAINT TO MATCH EXISTING FINISH.
COORDINATE INSTALLATION AND LOCATION OF EQUIPMENT IN
FIELD.
EQ8
EQ15
EQ23
9
E1
E9
EXISTING SERVERY
ELECTRICAL PANELS
6
E5
8
16
E8. RE-USE EXISTING RECEPTACLE TO POWER NEW REACH-IN
UNDERCOUNTER REFRIGERATOR. MODIFY AND EXTEND
LOCATION AS REQUIRED. COORDINATE INSTALLATION AND
LOCATION OF EQUIPMENT IN FIELD.
15
E9. REMOVE EXISTING 208V CIRCUIT AND RECEPTACLE TO FEED
A NEW 120V CARVING STATION (5-15P). PROVIDE A 5-20R
RECEPTACLE AND MODIFY EXISTING WIRING AS REQUIRED.
FIELD VERIFY AND REPLACE EXISTING CIRCUIT 2-POLE BREAKER
WITH (2) NEW 20A/1P CIRCUIT BREAKERS, REUSE (1) FOR 120V
CARVING STATION. RE-USE EXSTING IN SLAB CONDUIT FOR
POWER FEED. PROVIDE NEW #12 WIRING AND COORDINATE
INSTALLATION AND LOCATION OF EQUIPMENT IN FIELD.
5-20R
4
5
5-20R
E4
3
E10. RE-USE EXISTING RECEPTACLE TO POWER NEW HEATED
SHELF FOOD WARMER. MODIFY AND EXTEND LOCATION AS
REQUIRED. COORDINATE INSTALLATION AND LOCATION OF
EQUIPMENT IN FIELD.
E7
E11. MICROWAVE OVEN: PROVIDE A 1-POLE, 20A CIRCUIT
BREAKER IN EXISTING PANEL PPP-1 OR PPP-2 AND (2) #12, #
12G IN 3/4" CONDUIT TO FEED NEW 120V, 20A DUPLEX
RECEPTACLE. CONCEAL CONDUIT IN WALL AND ABOVE
CEILING TO MINIMIZE VISIBILITY. IN EXPOSED CEILING AREA,
PAINT TO MATCH EXISTING FINISH. COORDINATE INSTALLATION
AND LOCATION OF EQUIPMENT IN FIELD.
EQ4
EQ7
14
7
EQ16
E12. CONVEYOR TOASTER: PROVIDE A 1-POLE, 20A CIRCUIT
BREAKER IN EXISTING PANEL PPP-1 OR PPP-2 AND (2) #12, #
12G IN 3/4" CONDUIT TO FEED NEW 120V, 20A DUPLEX
RECEPTACLE. CONCEAL CONDUIT IN WALL AND ABOVE
CEILING TO MINIMIZE VISIBILITY. IN EXPOSED CEILING AREA,
PAINT TO MATCH EXISTING FINISH. COORDINATE INSTALLATION
AND LOCATION OF EQUIPMENT IN FIELD. (TYPICAL FOR 2
LOCATIONS)
EQ6
EQ3
E2
13
2
E13. REACH IN FREEZER AND REACH IN REFRIGERATOR:
PROVIDE A 1-POLE, 20A CIRCUIT BREAKER IN EXISTING PANEL
PPP-1 OR PPP-2 AND (2) #12, #12G IN 3/4" CONDUIT TO FEED
NEW 120V, 20A DUPLEX RECEPTACLE. CONCEAL CONDUIT IN
WALL AND ABOVE CEILING TO MINIMIZE VISIBILITY. IN EXPOSED
CEILING AREA, PAINT TO MATCH EXISTING FINISH.
COORDINATE INSTALLATION AND LOCATION OF EQUIPMENT IN
FIELD. (TYPICAL FOR EACH PIECE OF EQUIPMENT)
E8
EQ17
18
E6
22
EQ20
EQ2
19
12
17
BFD
CHECKED BY:
WEF
E14. RE-USE EXISTING RECEPTACLE CIRCUIT TO POWER NEW
RECEPTACLES. MODIFY & EXTEND CIRCUITRY AS REQUIRED.
PROVIDE CONDUIT, MC CABLE AND #12 WIRING REQUIRED TO
FURNISH A FULLY FUNCTIONAL INSTALLATION.
11
EQ18
17
DRAWN BY:
PPP-2
E14
EQ14
REVISIONS
E15. PROVIDE A 1-POLE, 20A CIRCUIT BREAKER IN EXISTING
PANEL PPP-1 OR PPP-2 AND (2) #12, #12G IN 3/4" CONDUIT TO
FEED NEW 120V, HEAT LAMPS (EQUIPMENT #21) AND CONTROL
SWITCH. INSTALL CONTROL SWITCH AT SERVER STATION,
COORDINATE EXACT LOCATION IN FIELD. CONCEAL CONDUIT
IN WALL AND ABOVE CEILING TO MINIMIZE VISIBILITY. IN
EXPOSED CEILING AREA, PAINT TO MATCH EXISTING FINISH.
COORDINATE INSTALLATION AND LOCATION OF EQUIPMENT IN
FIELD.
EQ1
EQ19
G
1
E3
ISSUED:
3.24.2016
A
1
DESCRIPTION:
BID DOCUMENTS
ELECTRICAL PLAN - FF1 - SERVERY
1/4" = 1'-0"
SHEET:
ADD/ALT 1
E-113
18031.00
12
5-20R
505 RAMAPO VALLEY RD.
MAHWAH, NY 07430
5-20R
RCNJ No. 201437-01C
PHASE 2: ALTERATIONS
5-20R
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
RAMAPO COLLEGE
OF NEW JERSEY
E11
ELECTRICAL ALTERATIONS SERVERY - ALTERNATE #1
E12
G
22
5-15P
Cord & Plug
60
17
21
150.0
Direct
1
16
DESSERT
EQ16
GRILL
EQ3
EQ4
EQ6
EQ7
HOMETOWN
EQ5
EQ8
EQ9
MEDITERRANEAN
EQ1
EQ2
PIZZA
EQ10
EQ11
EQ12
SALAD
EQ17
EQ18
SANDWICH
EQ19
EQ20
WOK
EQ14
EQ15
EQ21
EQ22
EQ23
BREAKFAST
EQ13
Direct
10
G
3/23/2016 3:29:15 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
3/23/2016 3:29:25 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
GENERAL NOTES
1.
E
G
J
N
QQ.1
DEVICES SHOWN AS LIGHT OR SHADED ARE
EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
Q.2
Q.3
SEALED:
B
C
D
KPP2
KPP3
TC
21
KPP1
E1
20
F
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
V
19
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
H
D
F
F
V
D
V
18
H
F
V
D
D
S
KEYED NOTES
S
F
17
E1. PROVIDE 2-CHANNEL TIME CLOCK IN ELECTRICAL ROOM
FOR CONTROL OF NEW EXTERIOR COLUMN LIGHTS IN
ELECTRICAL ROOM. COORDINATE EXACT LOCATION IN
FIELD. BASIS OF DESIGN: INTERMATIC ET90215C.
H
F
H
H
V
X1
16
X2
E3. PROVIDE 3/4" RGS CONDUIT WITH #12 WIRE FROM TIME
CLOCK AND PHOTOCELL TO COLUMN LIGHT LOCATIONS.
REFER TO ARCHITECTURAL FLOOR & ELEVATION PLANS FOR
LOCTIONS. COLUMN SPECIFIED IN A-SERIES DRAWINGS,
WIRED & INSTALELD PER DIVISION 26. CONDUIT AND WIRING
CONNECTIONS TO THE POWER SOURCE WILL BE PROVIDED IN
FUTURE PHASE. CONTROLS SHALL BE: PHOTOCELL "ON", TIME
CLOCK "OFF". PROVIDE ALL CONDUIT, BOXES, WIRING,
TRENCHING & SAWCUTTING, & MISCELLANEOUS HARDWARE
REQUIRED FOR LIGHT LOCATIONS SHOWN.
H
H
F
D
V
S
E4
H
D
V
H
F
13
V
D
3
S
UG
12
DWR DW
S
11
REVISIONS
E4. CONDUITS SHALL RUN FROM PHOTOCELL TO TIMECLOCK.
FROM TIMECLOCK, CONDUITS SHALL RUN TO TWO INTERIOR
COLUMNS (ONE AT VESTIBULE/SEATING EXPANSION, ONE AT
RESIDENTIAL DINING EXPANSION), THEN CONTINUE IN SERIES
TO REMAINING COLUMNS.
DRAWN BY:
BFD
E5. REINSTALL EXIT SIGN REMOVED DURING DEMOLITION.
CHECKED BY:
WEF/PP
E6. REINSTALL FIRE ALARM DEVICES REMOVED DURING
DEMOLITION.
10.9
10.8
3D
H
S
D
E3
H
H
F
RCNJ No. 201437-01C
PHASE 2: ALTERATIONS
H
S
S
F F
9
S
S
F
8
10.2
10
D
UG
S
E3
X1
S
UG
S
S
E6
F
F F
D
7
S
7.1
E3
E3
S
D
E3
S
S
S
S
S
UG
UG
UG
S
X1
6
5
E5
F
F
E3
E6
X1
E3
4
S
S
D
S
S
E3
E5
UG
S
S
UG
E4
S
F
S
S
E3
D
H
UG
UG
3
S
2.9
FF
X1
S
E3
E3
E3
E3
S
F F
2.1
1.9
S
PC
X1
UG
UG
RAMAPO COLLEGE
OF NEW JERSEY
H
X1
B.7
LIGHTING - FIRST FLOOR
H
X1
A.4
UG
S
S
2
1
E2
A
F
H
I
K
L
M
O
ISSUED:
3.24.2016
DESCRIPTION:
BID DOCUMENTS
1
LIGHTING PLAN - FF1 PH2
1/8" = 1'-0"
SHEET:
E-200
18031.00
V
H
D
14
10.3
F
RPK
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
505 RAMAPO VALLEY RD.
MAHWAH, NY 07430
F
ENGINEER:
E2. PROVIDE LIGHTING PHOTOCELL FOR CONTROL OF
EXTERIOR COLUMN LIGHTS IN CONJUNCTION WITH NEW TIME
CLOCK. MOUNT PHOTOCELL ON OUTSIDE FACE OF ROOF
CANOPY, FLUSH MOUNTED AT 21'-0" AFF.
15
D
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
3/23/2016 3:29:41 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
GENERAL NOTES
1.
2.
3.
4.
E
G
J
N
QQ.1
Q.2
Q.3
5.
EMERGENCY LIGHTING PANEL
(ALSO ONE ON THE SECOND
FLOOR ELEC/MECH. ROOM
ABOVE)
6.
7.
EPPB
B
C
8.
TIME CLOCK LOCATION:
CONNECT SITE COLUMN
LIGHTS TO TIME CLOCK VIA
PHOTOCELL. OPERATION
SHALL BE PHOTOCELL "ON",
TIME CLOCK "OFF" UNLESS
DIRECTED OTHERWISE BY
CAMPUS PERSONNEL.
D
9.
10.
11.
TC
IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL
MATERIAL AND EQUIPMENT IN ACCORDANCE WITH THE
CURRENT N.E.C. (NATIONAL ELECTRICAL CODE).
ALL WORK SHALL BE INSTALLED NEAT AND WORKMANLIKE
COMPLYING WITH THE STANDARDS OF N.E.C..
THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY
ALL CONDITIONS, LOCATIONS, DIMENSIONS, AND COUNTS
AS SHOWN AND NOTED ON THE DRAWINGS FOR THIS
WORK PRIOR TO BIDDING. NO ADDITIONAL COST WILL BE
ISSUED FOR FAILURE TO COMPLY WITH THIS REQUIREMENT.
THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIAL,
AND SUPERVISION NECESSARY TO ACCOMPLISH THE
WORK AS SHOWN AND NOTED ON THE DRAWINGS. ANY
DEVIATION FROM THE DRAWINGS SHALL BE APPROVED BY
THE OWNER.
THE ELECTRICAL CONTRACTOR SHALL DO ALL CUTTING
AND PATCHING OF THE BUILDING MATERIALS REQUIRED
FOR THE INSTALLATION OF HIS WORK. ALL FIRE RATED
WALLS, FLOORS, OR CEILINGS SHALL BE SEALED TO
MAINTAIN THE FIRE RATING.
THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR THE
REMOVAL OF ALL TOOLS, DEBRIS, AND GENERAL CLEAN
UP FROM HIS WORK.
ALL WORK SHALL BE COORDINATED WITH THE OTHER
TRADES.
THE ELECTRICAL CONTRACTOR SHALL MAKE ALL
NECESSARY TESTS TO INSURE THAT THE ENTIRE INSTALLATION
IS FREE FROM IMPROPER GROUNDS AND FROM SHORTED
AND/OR OPEN CIRCUITS. VOLTAGE AND CURRENT TESTS
SHALL BE MADE BEFORE ANY MOTORS ARE PLACED IN
OPERATION.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING
AND PAYING FOR ALL REQUIRED PERMITS.
THE ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL
WORK AND MATERIALS FOR A PERIOD OF ONE YEAR
AFTER ACCEPTANCE OF THE WORK AND MATERIALS.
ALL ELECTRICAL EQUIPMENT AND DEVICES SHALL BE
LABELED WITH 1/2" DYNO TAPE FOR THE SOURCE AND
CONTROL LOCATION.
21
SEALED:
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
E8
20
F
V
19
KEYED NOTES
E1. REPLACE (3) EXISTING 1'X4' SURFACE MOUNT FIXTURES
WITH NEW LED FIXTURE, BASIS OF DESIGN: LITHONIA LBL4 30L
EZ1 LP835. TURN EXISTING FLUORESCENT FIXTURES OVER TO
CAMPUS PERSONNEL. RE-USE EXISTING CIRCUITRY.
H
F
V
H
M
LPK
E2. PROVIDE NEW FIXTURES AND CORNER MOUNT
OCCUPANCY SENSOR AS SHOWN. CONNECT TO EXISTING
NORMAL AND EMERGENCY POWER CIRCUITS. FIXTURES
DENOTED WITH AN "E" SHALL BE ON EMERGENCY CIRCUIT.
PROVIDE EMERGENCY LIGHTING CONTROL UNITS TO
ALLOW EMERGENCY FIXTURES TO BE SWITCHED WITH OTHER
NEARBY "NORMAL POWER" AREA LIGHTING. PROVIDE ALL
CONDUIT, WHIPS AND WIRING REQUIRED FOR A FULLY
FUNCTIONAL INSTALLATION.
F
D
17
F2 E
F2
H
F
H
H
V
F2 E
EXISTING VESTIBULE
132
F2
16
D
H
14
10.3
F
V
V
F4
H
H
F
13
V
D
3
F4
S
E1
E5. PROVIDE NEW FIXTURES AND OCCUPANCY SENSORS AS
SHOWN. CONNECT TO EXISTING NORMAL AND
EMERGENCY POWER CIRCUITS. FIXTURES DENOTED WITH AN
"E" SHALL BE ON EMERGENCY CIRCUIT. OCCUPANCY
SENSORS SHALL BE LINKED TOGETHER FOR CONTROL AS A
SINGLE SPACE. PROVIDE EMERGENCY LIGHTING CONTROL
UNITS TO ALLOW EMERGENCY FIXTURES TO BE SWITCHED
WITH OTHER NEARBY "NORMAL POWER" AREA LIGHTING.
PROVIDE ALL CONDUIT, WHIPS AND WIRING REQUIRED FOR
A FULLY FUNCTIONAL INSTALLATION. PAINT ALL
CONDUIT/WHIPS VISIBLE TO PUBLIC TO MATCH OTHER
EXPOSED BUILDING ELEMENTS.
E2
F4
F6
F6
S
DW
11
F6
M
E
F2
H
F
F1
E3
H
S
F6
F6
F6 E
F6
E7
E
F4
E
F4
F4
F17
F17
NEW VESTIBULE
141
F2 E
10.2
10
F F
F4
MOUNT AT 7'-0"
AFF (TYPICAL)
B.7
E5
F2
M
A.4
EXISTING DINING AREA
277V LIGHTING PANEL
H
H
F6 E
F4
E2
S
E F6
F6
F6
E7. PROVIDE NEW FIXTURES AND SWITCH AS SHOWN.
CONNECT TO NEAREST 120V TRACK LIGHTING CIRCUIT.
PROVIDE ALL CONDUIT, WHIPS AND WIRING REQUIRED FOR
A FULLY FUNCTIONAL INSTALLATION. PAINT ALL
CONDUIT/WHIPS VISIBLE TO PUBLIC TO MATCH OTHER
EXPOSED BUILDING ELEMENTS.
9
S
D
F10
F10
S
UPPER LOUNGE
137
F6
E
F4
E4
F10
F10
E
LOWER RESIDENTIAL
DINING
140
E
(TYPICAL)
F
F11
F4
CIRCUIT TO
SECOND
SWITCH
F6
E
F4
F7
F4
F4
F4
F4
E
E
F4
F4
D
E5
F4
F4
E
F
S
D
H
F8
F8
F9
F8
F9
F6
A
WEF
F11
F11
F8
E
F8
F11
F6
F11
F6 E
F11 F11
F11
F11
PC
MOUNT F9 FIXTURES AT
8'-6" AFF TO BOTTOM
OF FIXTURE
CHECKED BY:
E4
S
F9
E
2
1
M
2.1
1.9
E
F F
F9
E
F8
F9
LOWER LOUNGE
136
F6
F6
F6
F4
S
F9
F9
F4
S
F4
3
FF
E
2.9
F7
E
F4
S
S
F8
MOUNT F7 FIXTURES AT
8'-0" AFF TO BOTTOM
OF FIXTURE
F7
F7
F4
S
F4
S
F8
4
D
S
F4
S
F4
6
5
F
S
F4
F7
D
F6
F5
F8
F7
F7
F4
E
D
F6
S
F4
MOUNT AT 8'-0"
AFF TO BOTTOM
OF FIXTURE
E
S
S
F8
F4
F4
MOUNT AT
6'-0" AFF
(TYPICAL)
S
F4
7
E
S
F4
E5
D
S
F8
F
F10
E
E8. PROVIDE 20A, 1-POLE CIRCUIT BREAKER IN NEARBY 277V
PANEL EPPB AND CONDUIT & CIRCUITRY TO TIME CLOCK
FOR EXTERIOR BUILDING AND COLUMN POLE LIGHTS.
PROVIDE ALL CONDUIT, MC CABLE AND #12 WIRING
REQUIRED FOR A FULLY FUNCTIONAL INSTALLATION.
F7
F10
F4
F4
F7
E
F3
S
F F
TO THIRD
SWITCH
D
F7
F6
MOUNT AT
10'-6" AFF TO
BOTTOM OF
FIXTURE
F4
E6
F10
S
S
E
7.1
F10
S
F10
F4 E
F4
S
F10
F4
S
MOUNT F4 FIXTURES IN
LOWER DINING AT 10-0""
AFF TO BOTTOM OF
FIXTURE
S
8
E F6
F
E6. RE-USE EXISTING AREA EMERGENCY LIGHTING CIRCUIT
FOR NEW EMERGENCY FIXTURES. PROVIDE ALL CONDUIT,
WHIPS AND WIRING AS REQUIRED TO CIRCUIT AS SHOWN
ON DRAWING. PROVIDE EMERGENCY LIGHTING CONTROL
UNITS TO ALLOW EMERGENCY FIXTURES TO BE SWITCHED
WITH OTHER NEARBY "NORMAL POWER" AREA LIGHTING.
PAINT ALL CONDUIT/WHIPS VISIBLE TO PUBLIC TO MATCH
OTHER EXPOSED BUILDING ELEMENTS.
F2
S
S
F6 E
F2
F2
S
UPPER RESIDENTIAL
DINING
139
H
3D
H
S
D
MOUNT F6
FIXTURES AT 9'-0"
AFF (TYPICAL)
10.9
10.8
BFD
MOUNT F11 FIXTURES
AT 7'-6" AFF TO
BOTTOM OF FIXTURE
MOUNT F8 FIXTURES AT
8'-0" AFF TO BOTTOM
OF FIXTURE
F
H
I
K
L
M
O
ISSUED:
3.24.2016
DESCRIPTION:
BID DOCUMENTS
1
LIGHTING PLAN - FF1
SHEET:
0
8
16
24
1/8" = 1'-0"
NORTH
E-210
18031.00
H
F
DRAWN BY:
505 RAMAPO VALLEY RD.
MAHWAH, NY 07430
S
F4
2
E-112
E4. PROVIDE NEW FIXTURES AND OCCUPANCY SENSORS AS
SHOWN. CONNECT TO ADJACENT DINING AREA LIGHTING
CIRCUIT. FIXTURES DENOTED WITH AN "E" SHALL BE
CONNECTED TO THE EXISTNG EMERGENCY LIGHTING
CIRCUITRY. OCCUPANCY SENSORS SHALL BE LINKED
TOGETHER FOR CONTROL AS A SINGLE SPACE. PROVIDE
EMERGENCY LIGHTING CONTROL UNITS TO ALLOW
EMERGENCY FIXTURES TO BE SWITCHED WITH OTHER
NEARBY "NORMAL POWER" AREA LIGHTING. PROVIDE ALL
CONDUIT, WHIPS AND WIRING REQUIRED FOR A FULLY
FUNCTIONAL INSTALLATION. PAINT ALL CONDUIT/WHIPS
VISIBLE TO PUBLIC TO MATCH OTHER EXPOSED BUILDING
ELEMENTS.
MOUNT AT 7'-0"
AFF TO BOTTOM
(TYPICAL)
RCNJ No. 201437-01C
PHASE 2: ALTERATIONS
V
RAMAPO COLLEGE
OF NEW JERSEY
H
F
D
12
REVISIONS
F4
D
D
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
E3. PROVIDE NEW EMERGENCY FIXTURE ON UPPER
COLUMN SECTION. BASIS OF DESIGN: LITHONIA AFN B EXT
FWD. CONNECT TO VESTIBULE LIGHTING CIRCUITRY.
PROVIDE ALL CONDUIT AND WIRING REQUIRED FOR A
FULLY FUNCTIONAL INSTALLATION. COORDINATE
LOCATION AND INSTALLATION IN THE FIELD.
15
M
E2
ENGINEER:
LIGHTING ALTERATIONS - FIRST
FLOOR
EXISTING SERVERY AREA
120V LIGHTING PANEL
18
D
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
3/23/2016 3:29:49 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
SERVERY LIGHT FIXTURE SCHEDULE
Type Mark
F1
F2
F12
F13
F14
F15
F16
F18
Description
Manufacturer
4" LED Recessed Downlight
6LW
- New
Construction
or Remodel
6"
LED
Recessed
Downlight
Decorative Milk Can Fixture
Decorative Milk Can Fixture
Decorative Shade Fixture
Decorative Shade Fixture
Decorative Shade Fixture
LED Track Head
Cooper Industries, Inc.
. Cooper Lighting
Hi-Lite Manufacturing
Hi-Lite Manufacturing
Hi-Lite Manufacturing
Hi-Lite Manufacturing
Hi-Lite Manufacturing
CooperLighting
Industries, Inc.
Philips
GENERAL NOTES
Model
Lamp
LD4A1300D010TE ERWA13930 4LWO WH
LD620
AND LD6R20
LD6A20D010TE
ERW6A20830 6LWO WH
H-2046 ST1/8 STC
H-7106 ST1/8 STC
H-15006 ST1/8 STC
H-16006 ST1/8 STC
H-19006 ST1/8 STC
. 9030N LR F BK
Voltage
LED
2
LED
LED
LED
LED
LED
LED
LED
120
120/277
120/277
120
120
120
120
120
120
Mounting
Comments
Recessed
Recessed
Pendant
Pendant
Pendant
Pendant
Pendant
Existing Track
1.
2.
Finish Selection by Architect, Provide Philips 100W EQUIV. LED A19
Finish Selection by Architect, Provide Philips 100W EQUIV. LED A19
Finish Selection by Architect, Provide Philips 100W EQUIV. LED A19
Finish Selection by Architect, Provide Philips 100W EQUIV. LED A19
Finish Selection by Architect, Provide Philips 100W EQUIV. LED A19
Fixture must be compatible with existing Lightolier line voltage track
3.
4.
5.
B
C
6.
7.
8.
9.
19
10.
F2
F2
F2
11.
F2
12.
DEVICES SHOWN AS LIGHT OR SHADED ARE EXISTING TO
REMAIN UNLESS OTHERWISE NOTED.
IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO
INSTALL MATERIAL AND EQUIPMENT IN ACCORDANCE
WITH THE CURRENT N.E.C. (NATIONAL ELECTRICAL
CODE).
ALL WORK SHALL BE INSTALLED NEAT AND
WORKMANLIKE COMPLYING WITH THE STANDARDS OF
N.E.C..
THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY
ALL CONDITIONS, LOCATIONS, DIMENSIONS, AND
COUNTS AS SHOWN AND NOTED ON THE DRAWINGS
FOR THIS WORK PRIOR TO BIDDING. NO ADDITIONAL
COST WILL BE ISSUED FOR FAILURE TO COMPLY WITH
THIS REQUIREMENT.
THE CONTRACTOR SHALL PROVIDE ALL LABOR,
MATERIAL, AND SUPERVISION NECESSARY TO
ACCOMPLISH THE WORK AS SHOWN AND NOTED ON
THE DRAWINGS. ANY DEVIATION FROM THE DRAWINGS
SHALL BE APPROVED BY THE OWNER.
THE ELECTRICAL CONTRACTOR SHALL DO ALL CUTTING
AND PATCHING OF THE BUILDING MATERIALS REQUIRED
FOR THE INSTALLATION OF HIS WORK. ALL FIRE RATED
WALLS, FLOORS, OR CEILINGS SHALL BE SEALED TO
MAINTAIN THE FIRE RATING.
THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR THE
REMOVAL OF ALL TOOLS, DEBRIS, AND GENERAL
CLEAN UP FROM HIS WORK.
ALL WORK SHALL BE COORDINATED WITH THE OTHER
TRADES.
THE ELECTRICAL CONTRACTOR SHALL MAKE ALL
NECESSARY TESTS TO INSURE THAT THE ENTIRE
INSTALLATION IS FREE FROM IMPROPER GROUNDS AND
FROM SHORTED AND/OR OPEN CIRCUITS. VOLTAGE
AND CURRENT TESTS SHALL BE MADE BEFORE ANY
MOTORS ARE PLACED IN OPERATION.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR
OBTAINING AND PAYING FOR ALL REQUIRED PERMITS.
THE ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL
WORK AND MATERIALS FOR A PERIOD OF ONE YEAR
AFTER ACCEPTANCE OF THE WORK AND MATERIALS.
ALL ELECTRICAL EQUIPMENT AND DEVICES SHALL BE
LABELED WITH 1/2" DYNO TAPE FOR THE SOURCE AND
CONTROL LOCATION.
SEALED:
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
M
E1
F1
E1
DEMO KEYED NOTES
(TYPICAL)
F1
F1
D1. DISCONNECT AND REMOVE EXISTING PENDANT FIXTURES
OVER WOK AREA. REMOVE CONDUIT, WHIPS AND
CIRCUITRY TO NEAREST HOMERUN JUNCTION BOX. LABEL
CIRCUITRY FOR RE-USE.
F1
F1
17
MOUNT AT 6'-0" AFF TO
BOTTOM OF FIXTURE
(TYPICAL)
F12
F1
EXISTING SERVERY AREA 120V LIGHTING PANEL
E2
F15
(TYPICAL)
F12
D1
(TYPICAL)
F13
MOUNT AT 6'-0" AFF TO
BOTTOM OF FIXTURE
(TYPICAL)
D2
F14
F13
LPK
17
E1
D2
16
F15
F15
15
F16
F14
F16
D3
(TYPICAL)
F13
D2
11
F12
14
D2
12
F15
F13
F16
D2
13
F12
F13
F16
F12
D2
12
F15
11
D2
E2
H
D2
S
H
A.4
WEF
B.7
A.4
B.7
A
A
1
LIGHTING DEMO PLAN - SERVERY
0
8
16
2
24
1/8" = 1'-0"
LIGHTING PLAN - FF1 - SERVERY
0
4
8
ISSUED:
3.24.2016
12
DESCRIPTION:
1/4" = 1'-0"
NORTH
NORTH
BID DOCUMENTS
SHEET:
ADD/ALT 1
E-211
18031.00
E2. PROVIDE NEW TRACK LIGHT FIXTURES COMPATIBLE WITH
EXISTING BLACK LIGHTOLIER LINE VOLTAGE TRACK SYSTEM.
REFER TO LIGHT FIXTURE SCHEDULE FOR BASIS OF DESIGN
FIXTURE. FIELD VERIFY QUANTITY AND LOCATIONS OF TRACK
LIGHTS PRIOR TO REMOVALS OF EXISTING TRACK HEADS.
QUANTITY AND LOCATIONS SHOWN ARE APPROXIMATE.
CHECKED BY:
505 RAMAPO VALLEY RD.
MAHWAH, NY 07430
F18 (TYPICAL)
BFD
RCNJ No. 201437-01C
PHASE 2: ALTERATIONS
D
DRAWN BY:
RAMAPO COLLEGE
OF NEW JERSEY
15
E1. PROVIDE NEW FIXTURES SHOWN AND CONNECT TO
EXISTING SERVER LINE LIGHTING CIRCUIT. RE-USE EXISTING
HOME-RUN CONDUITS WHERE PRACTICAL AND PROVIDE
NEW AS REQUIRED. PROVIDE ALL CONDUIT, WHIPS AND
WIRING AS REQUIRED TO CIRCUIT AS SHOWN ON DRAWING.
PROVIDE ALL CONNECTIONS TO LIGHT FIXTURES, SWITCHES
AND OCCUPANCY SENSORS AS REQUIRED FOR A COMPLETE
AND FULLY FUNCTIONAL SYSTEM. PAINT ALL CONDUIT/WHIPS
VISIBLE TO PUBLIC TO MATCH OTHER EXPOSED BUILDING
ELEMENTS. EXISTING SWITCHES SHALL BE RE-USED. ONE
SWITCH SHALL CONTROL THE EXISTING TRACK LIGHTING, THE
OTHER SWITCH SHALL CONTROL THE WOK AREA AND SERVER
LINE PENDANT LIGHTING.
LIGHTING ALTERATIONS SERVERY - ALTERNATE #1
16
F15
19
REVISIONS
F13
F14
C
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
KEYED NOTES
F13
F14
B
D3. REMOVE EXISTING TRACK HEADS FROM EXISTING BLACK
LINE VOLTAGE LIGHTOLIER TRACK SYSTEMS AND TURN OVER
TO CAMPUS PERSONNEL. EXISTING TRACK SYSTEM TO
REMAIN. TAKE QUANTITY OF FIXTURES REMOVED FOR
REPLACEMENT.
F12
F16
F1
ENGINEER:
D2. DISCONNECT AND REMOVE EXISTING JUNO TRACK
LIGHTING AND PENDANT FIXTURES AT SERVER LINES. REMOVE
CONDUIT, WHIPS AND CIRCUITRY TO NEAREST HOMERUN
JUNCTION BOX. LABEL CIRCUITRY FOR RE-USE.
MOUNT AT 6'-0" AFF TO
BOTTOM OF FIXTURE
(TYPICAL)
F15
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
3/23/2016 3:29:49 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
SEALED:
LIGHT FIXTURE SCHEDULE
Type Mark
Manufacturer
4" LED Recessed Downlight
6" LED
Recessed
Downlight
6LW
- New
Construction
or Remodel
Decorative Drum Fixture
Decorative Lensed Lowbay with Uplight
Decorative Drum Fixture
6" LED Cylinder - Rigid Stem Mount
LED Linear Architectural Suspended Fixture
Decorative Period Jelly Jar Fixture
Decorative Angled Shade Light
Decorative Surface Jelly Jar Fixture
Decorative Bell Shade Fixture
Decorative Shade Fixture
LED Column Light Pole
Architectural Edge Lit Exit Sign
2-Sided Architectural Edge Lit Exit Sign
Model
Cooper Industries, Inc.
. Cooper Lighting
Barbican Lighting
Hi-Lite Manufacturing
Barbican Lighting
Juno Lighting
Group by Schneider Electric
Cooper
Lighting
Tech Lighting
Hi-Lite Manufacturing
Hi-Lite Manufacturing
Hi-Lite Manufacturing
Hi-Lite Manufacturing
Hi-Lite Manufacturing
Selux Corporation
Lithonia Lighting
Lithonia Lighting
LD4A1300D010TE ERWA13930 4LWO WH
LD6A20D010TE
ERW6A20830 6LWO WH
LD620
AND LD6R20
16-5048-LF-__-24-ACB-HTO-NT-RAL-277V
H-23638
16-0448-LF-__-24-ACB-HTO-NT-RAL-277V
. LSR6A-15-D010TE-MB-ERCW6A-15830-6LWO-WH
700LSKNOX LED277
H-MCGUS-6S
H-18110
H-LCGU-FB
H-1214
H-EMC-06
CCCL-10-4-4L35-30-__-277
EDG 1 R EL
EDG 2 RMR EL
Lamp
LED
2
LED
LED
DO NOT
42W
CFLUSE
LED
LED
LED
18W CFL
18W CFL
18W CFL
18W CFL
LED
LED
LED
LED
Voltage
277
120/277
120/277
Mounting
Comments
Recessed
Recessed
Finish Selection by Architect.
Finish Selection by Architect, Provide Rigid Stem Mount
Finish Selection by Architect.
Provide Rigid Stem, Finish Selection by Architect
Finish Selection by Architect
Provide Rigid Stem, Finish and Lens Selection by Architect
Provide with B-6 Wall Bracket Mount, Finish Selection by Architect
Finish and Lens Selection by Architect
Provide Rigid Stem, Finish and Lens Selection by Architect
Provide Rigid Stem & 60W Equiv. LED A19 bulb, 800 Lumens Min., Finish Selection by Architect
Finish Selection by Architect
. 277
120/277
277
120/277
120/277
120/277
120/277
120
277
120/277
120/277
Pendant
Suspended
Pendant
Wall - Arm
Wall
Pendant
Pendant
Pole
Surface
Surface
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
ENGINEER:
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
3' MIN. FROM EDGE OF CURB
PROVIDE TOP SURFACE TO
MATCH ADJACENT AREAS
(TOPSOIL AND SEED,
CONCRETE, PAVEMENT, ETC..)
1" PVC CONDUIT W/POWER &
GROUND CONDUCTORS
DETECTABLE MARKING TAPE
EXOTHERMIC WELD
12" MIN.
3" MIN.
3" MIN.
3/4" X 10'-0" COPPER
CLAD GROUNDING
ROD
CONDUIT COUPLING (TYP.)
RIGID SCHED. 80 PVC CONDUIT
(SIZED AS PER DRAWINGS)
RIGID STEEL CONDUIT SWEEP
CLEAN SAND
24" MIN.
BACKFILL IN 8" LIFT AND
COMPACT TO 95%
MODIFIED PROCTOR
1
LIGHT POLE FOUNDATION DETAIL
12" = 1'-0"
(4)-#7 VERTICAL BARS
SPACED EQUALLY
4" MIN.
COORDINATE BOLT
REQUIREMENTS AND PATTERN
W/POLE AND SHOP DRAWINGS
#3 TIES AT 12" O/C W/3" MIN. COVER
FOUNDATION TO BE PLACED IN
UNDISTURBED SOIL
NOTE: ALL WORK SHOW SHALL BE PERFORMED BY
THE E.C.
2
TRENCH DETAIL
N.T.S.
1'-6" MIN.
BACKFILL MATERIAL. SUITABLE
NATIVE BACKFILL COMPACTED TO
90% MODIFIED PROCTOR
1'-0" MIN.
6" CU. GND.
24" MIN.
PVC CONDUIT
WITH GROUND
CONDUCTOR
3/4" DIA. GALV. HEADED
AND PARTIALLY
THREADED ANCHOR
RODS, MIN. 36" LONG
(TYP.)
12" MIN.
FINISHED GRADE
ISSUED:
3.24.2016
DESCRIPTION:
BID DOCUMENTS
SHEET:
E-310
18031.00
OBTAIN BASE PLATE BOLT
PATTERN FROM
MANUFACTURER
WEF
505 RAMAPO VALLEY RD.
MAHWAH, NY 07430
TO POLE GROUND STUD
CHECKED BY:
RCNJ No. 201437-01C
PHASE 2: ALTERATIONS
BOLT CAP
BFD
RAMAPO COLLEGE
OF NEW JERSEY
TO POLE CIRCUIT
DRAWN BY:
ELECTRICAL DETAILS &
SCHEDULES
CONDUIT WITH BONDING BUSHING
4" MIN.
COORDINATE REVEAL
HEIGHT IN FIELD
REVISIONS
4 FEET
F1
F2
F3
F4
F5
F6
F7
F8
F9
F10
F11
F17
S1
X1
X2
Description
Download