HVAC LEGEND

advertisement
3/23/2016 3:20:15 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
SEALED:
HVAC LEGEND
PIPING SYMBOL
DESCRIPTION
PIPING SYMBOL
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DESCRIPTION
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
PIPING RISE
AD
ACCESS DOOR
PIPING DROP
AFF
ABOVE FINISH FLOOR
BTUH
BRITISH THERMAL UNITS PER HOUR
BOTTOM PIPE CONNECTION
DIA,
ø
DIAMETER
DN
DOWN
(E)
EXISTING
EWT
ENTERING WATER TEMPERATURE (°F)
°F
DEGREES FAHRENHEIT
GPM
GALLONS PER MINUTE
HWR
HOT WATER RETURN
HWS
HOT WATER SUPPLY
LWT
LEAVING WATER TEMPERATURE (°F)
NTS
NOT TO SCALE
TOP PIPE CONNECTION
STRAINER
BALANCE VALVE
PIPING REDUCER - CONCENTRIC
PIPE CAP
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
ENGINEER:
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
REVISIONS
RUNTAL RADIATION SCHEDULE
RUNTAL RADIATION WITH ENCLOSURE
T
UNIT NO.
THERMOSTAT
2-WAY CONTROL VALVE
MV
MANUAL AIR VENT
DIMENSIONS
CAPACITY
LOCATION
DESIGN BASIS
E.W.T.
L.W.T.
(degrees F)
(degrees F)
BTUH PER
LINEAR FT
LENGTH
HEIGHT
FTR-1
SEE PLANS
180
150
950
SEE PLANS
11.5"
RUNTAL - RF-5
FTR-2
SEE PLANS
180
150
800
SEE PLANS
11.5"
RUNTAL - UFLT-4
FTR-3
SEE PLANS
180
150
500
SEE PLANS
6"
RUNTAL - UFLT-2
NOTES
DRAWN BY:
CJZ
CHECKED BY:
PP
BALL VALVE
ALL VALVING & CONTROLS
TO BE IN CEILING SPACE
BALL VALVE
STRAINER
HWR
2-WAY CONTROL VALVE
HWS
M
1
RUNTAL RADIATION DETAIL
SCALE - NONE
RUNTAL RADIATION CONTROL
A. RUN CONDITIONS - CONTINUOUS: THE UNIT SHALL RUN CONTINUOUSLY AND SHALL MAINTAIN A
HEATINGB SETPOINT OF 70 DEGREE F (ADJ.).
HEATING VALVE (24v CONTROL WIRE )
RUNTAL RADIATOR.
CONTRACTOR RESPONSIBLE
FOR PROPER HOT WATER SUPPLY &
RETURN CONNECTION TYPES
ZONE SENSOR
T
HOT WATER SUPPLY
B. HEATING VALVE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND MODULATE THE
HEATING COIL VALVE TO MAINTAIN ITS HEATING SETPOINT.
ALL RUNTAL RADIATORS
HOT WATER RETURN
2
RUNTAL RADIATION CONTROL
SCALE - NONE
ISSUED:
3.24.2016
DESCRIPTION:
BID DOCUMENTS
SHEET:
M-000
18031.00
505 RAMAPO VALLEY RD.
MAHWAH, NJ 07430
RAMAPO COLLEGE
OF NEW JERSEY
BALANCE VALVE
SCHEDULES, DETAILS &
CONTROLS
AIR VENT
RCNJ No.201437.01C
ALTERATIONS
BALL VALVE - OPEN
3/23/2016 3:23:21 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
HVAC LEGEND
DIFFUSER & REGISTER SCHEDULE
UNIT
DUCT SYMBOL
DESCRIPTION
LINE TYPE SYMBOL
DESCRIPTION
DUCT UP - POSITIVE PRESSURE
ABBREVIATION
DEMOLITION EQUIPMENT
DUCT UP - NEGATIVE PRESSURE
EXISTING EQUIPMENT TO REMAIN
DUCT DN - POSITIVE PRESSURE
NEW EQUIPMENT
DUCT DN - NEGATIVE PRESSURE
SERVICE
DESCRIPTION
MAX CFM
FACE
NECK
SIZE
SIZE
MAX. NC
ARRANGEMENT
MAX. S.P.
BASIS
(in. wc.)
D-A
SUPPLY
250
12x12
10"
12
0.3
CEILING
TITUS SPECTRUM
BTU
BRITISH THERMAL UNIT
BTUH
BRITISH THERMAL UNIT PER HOUR
D-B
SUPPLY
300
18x8
-
15
0.07
DUCT MOUNTED
TITUS SPIRAL S301FL
DOUBLE DEFLECTION
CFM
CUBIC FEET PER MINUTE
D-C
SUPPLY
200
14x6
CUSTOM
12
0.03
WALL
TITUS 300RS
CUH
CABINET UNIT HEATER
D
DIFFUSER
D-D
SUPPLY
250
12x12
-
12
0.3
CEILING
TITUS SPECTRUM
1
DIA
DIAMETER
D-E
SUPPLY
1000
36x12
-
15
0.3
WALL
TITUS 300RS
1, 2
3
1
DUCT BALANCE OR VOLUME DAMPER
RECTANGULAR DUCT WITH TURNING VANES
RADIUS ELBOW (MIN. R/W = 1.5)
EXHAUST REGISTER
SUPPLY DIFFUSER
NOTES
DESIGN
D-E
SUPPLY
350
48x6
8" PLENUM
20
0.5
CEILING
TITUS FLOW BAR FL15
1.5" SLOT JET
R-A
EXHAUST
450
24x24
-
10
0.03
CEILING
TITUS 300RS
DN
DOWN
DWG
DRAWING
(E)
EXISTING
EA
EXHAUST AIR
1. NECK TO BE EXISTING BRANCH DUCT SIZE.
EF
EXHAUST FAN
2. D-E TO BE FACTORY PAINTED BLACK.
HP
HORSE POWER
KW
KILOWATTS
MBH
THOUSAND BTUH
MCA
MINIMUM CIRCUIT AMPACITY
MOP
MAXIMUM OVER-CURRENT PROTECTION
NTS
NOT TO SCALE
R
REGISTER
SEALED:
3. DIFFUSER TO COME WITH CORRESPONDING FACTORY PLENUM & FACE ADJUSTABLE VOLUME DAMPER. CONNECTION FOR GYPSUM BOARD.
ELECTRIC CABINET UNIT HEATER SCHEDULE
AIR FLOW
UNIT NO.
LOCATION
CFM
DIMENSIONS
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DESIGN BASIS
ELECTRICAL
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
NOTES
ARCHITECT:
CUH-1
MAIN VESTIBULE
LENGTH
WIDTH
HEIGHT
CAPACITY (BTUH)
36
30
10
10,236
300
CAPACITY (KW)
3KW
VOLTS/PHASE
HP
208/1
1/4
TRANE - FCEB030
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
ENGINEER:
FAN SCHEDULE
UNIT NO.
LOCATION
PERFORMANCE
AREA SERVED
C.F.M.
EF-1
ROOF
EXISTING WOK HOOD
2400
ELECTRICAL
TOTAL
S.P.
FAN SPEED
RPM
SONES
3.0
2655
27
VOLTS/PHASE
TYPE
DRIVE
CONN. POINTS
HP
ROOF OPG.
ROOF OPG.
LENGTH
WIDTH
PHYSICAL PROPERTIES
LENGTH"
460/3
5
1
UTILITY - KITCHEN EXHAUST
BELT
-
-
40
DESIGN BASIS
WIDTH"
HEIGHT"
WEIGHT LBS.
28
32
280
NOTES
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
GREENHECK-13-CSW-BI-21-10-I-50
1
REVISIONS
DUCT MAIN
DUCT MAIN
V.D.
INSULATED,
FLEXIBLE
DUCT
V.D.
MINIMUM 80"
DISCHARGE HEIGHT
EXHAUST FAN
DISCHARGE EXTENSION
BRANCH
V.D.
48" MAX
(TYP.)
1X DUCT DIA. OFFSET (MAX.)
BIRD SCREEN AND RAIN COVER
CAP DUCT END
EXHAUST FAN
MOTOR COVER
ACCESS DOOR
PANDUIT STRAP (TYP.)
SHEET METAL
"PLENUM" BOX
(TYP.)
SUPPLY AIR
DIFFUSER
(TYP.)
PAINT INSIDE FLAT BLACK
MIN. 6" HIGHER THAN
BRANCH DUCT DEPTH
MODIFY EXISTING
EXHAUST FAN SUPPORTS
AS REQUIRED FOR
NEW EXHAUST FAN
DUCT MAIN
DAMPER/REGISTER
30 DEGREE ANGLE
TOWARDS FLOOR,
AVOID NEW ARCHITECTURAL
CEILING CLOUD.
CEILING
EXISTING EXHAUST DUCT
FROM KITCHEN HOOD
FLEX CONNECTION
ROOF LINE
SUPPLY CEILING DIFFUSER
1
EXHAUST & SUPPLY REGISTER - WALL/CEILING
SUPPLY - ROUND DUCT MOUNTED DIFFUSER
2
DIFFUSERS & REGISTERS DETAIL
SCALE - NONE
EXHAUST FAN DETAIL
3" = 1'-0"
ELEC.
COIL
TEMPERATURE SENSOR IN
RETURN AIR
M
FAN STATUS
CT
13
FAN START/STOP
LEGEND:
1
4
5
6
11
10
12
2
7
3
1
ACCESS DOOR OPENING
2
ALL THREAD RODS
3
INSULATION PINS - WELDED TO COVER
4
FIRST LAYER FIRE RATED DUCT WRAP 2"
5
SECOND LAYER FIRE RATED DUCT WRAP 2", 1" OVERLAP
6
THIRD LAYER FIRE RATED DUCT WRAP 2", 1" OVERLAP
7
SPEED CLIPS/WASHERS
8
CUT EDGES SEALED WITH ALUMINUM FOIL TAPE
9
WING NUTS
CABINET UNIT HEATER CONTROL
A. RUN CONDITIONS - CONTINUOUS: THE UNIT SHALL RUN CONTINUOUSLY AND SHALL MAINTAIN A HEATING SETPOINT OF 70 DEG. F (ADJ.).
B. FAN: THE FAN SHALL RUN ANYTIME THE ZONE TEMPERATURE IS BELOW THE HEATING SETPOINT, UNLESS SHUTDOWN ON SAFETIES.
10 WASHERS
C. THE HEATING SHALL BE ENABLED WHENEVER:
1. OUTSIDE AIR TEMPERATURE IS LESS THAN 60 DEG. F (ADJ.)
2. ZONE TEMPERATURE IS BELOW HEATING SETPOINT.
11
INSULATION PLATE
D. THE CONTROLLER SHALL MONITOR THE FAN STATUS.
12
PRE-FABRICATED ACCESS DOOR
13
2 LAYERS FIRE RATED DUCT WRAP
E. ALARMS SHALL BE PROVIDED AS FOLLOWS:
1. FAN FAILURE: COMMAND ON, BUT THE STATUS IS OFF.
2. FAN IN HAND: COMMAND OFF, BUT THE STATUS IS ON.
3. LOW ZONE TEMP.: ID THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A USER DEFINABLE AMOUNT OF TIME (ADJ.).
8
ISSUED:
3.24.2016
DESCRIPTION:
9
3
FIRE RATED DUCT ACCESS DOOR DETAIL
SCALE - NONE
BID DOCUMENTS
4
CABINET UNIT HEATER CONTROL
SCALE - NONE
5
EXISTING EXHAUST FAN
SHEET:
SCALE - NONE
M-001
18031.00
DUCT MAIN
PP
RCNJ No.201437.01C
ALTERATIONS
HARD DUCT ELBOW.
CHECKED BY:
RAMAPO COLLEGE
OF NEW JERSEY
MANUAL VOLUME DAMPER
(TYP.)
CJZ
MECHANICAL LEGEND
SCHEDULES DETAILS & CONTROLS
SQUARE TO
ROUND
45° BOOT
TAKE-OFF
(TYP.)
DRAWN BY:
505 RAMAPO VALLEY RD.
MAHWAH, NJ 07430
NOTES: FAN TO BE CONTROLLED THROUGH EXISTING EXHAUST HOOD CONTROLS. COORDINATE WITH OWNER PRIOR TO EXHAUST FAN REMOVEL.
3/23/2016 3:28:11 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
DEMOLITION
GENERAL NOTES
1.
2.
3.
4.
DEMOLITION WORK LEGEND
5.
6.
EXISTING DUCTWORK, PIPING & EQUIPMENT TO REMAIN
7.
DUCTWORK, PIPING & EQUIPMENT TO BE REMOVED
POINT OF DISCONNECTION
8.
IDENTIFICATION AND/OR ABATEMENT OF
HAZARDOUS MATERIALS IS NOT PART OF THIS SCOPE
OF WORK. IF ASBESTOS OR OTHER HAZARDOUS
MATERIALS ARE ENCOUNTERED, THE CONTRACTOR
SHALL NOTIFY THE OWNER IMMEDIATELY.
REFER TO SPECIFICATIONS FOR RECYCLING,
CONSTRUCTION WASTE MANAGEMENT AND
DISPOSAL REQUIREMENTS.
OPENING IN THE EXISTING STRUCTURE SMALLER THAN
12" IN ANY DIRECTION ARE NOT IDENTIFIED ON THESE
DRAWINGS. SUBCONTRACTORS SHALL BE
RESPONSIBLE FOR PROVIDING OPENINGS SMALLER
THAN 12" AS REQUIRED FOR INSTALLATION OF THEIR
WORK.
OPENINGS IN THE EXISTING STRUCTURE SHALL NOT BE
MADE WITHOUT PRIOR APPROVAL OF THE
STRUCTURAL ENGINEER.
DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE
STRUCTURAL INTEGRITY OF THE BUILDING. IF HIDDEN
ELEMENTS OR DETERIORATED ELEMENTS ARE
ENCOUNTERED, NOTIFY THE ARCHITECT IMMEDIATELY.
PROTECT ADJACENT AREAS AND ITEMS "TO REMAIN"
DURING DEMOLITION/CONSTRUCTION.
REPAIR/REPLACE ITEMS DAMAGED DURING
CONSTRUCTION.
IF UNANTICIPATED HIDDEN ELEMENTS OR
DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY
THE OWNERS REPRESENTATIVE IMMEDIATELY.
REFER TO CONSULTANT DRAWINGS FOR ADDITIONAL
DEMOLITION WORK.
REVIEW w/ OWNER TO DETERMINE WHAT, IF
ANYTHING, WILL BE REMOVED BY OWNER AND WHAT,
IF ANYTHING, IS TO BE SALVAGED & TURNED OVER
TO OWNER.
SEALED:
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
KEYED NOTES
D1. REMOVE ALL EXISTING FIN TUBE RADIATION, VALVES AND
CONTROLS.
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
ENGINEER:
D2. REMOVE SUPPLY DUCTWORK.
D3. REMOVE EXISTING SUPPLY GRILLE.
D4. EXISTING HWS/R PIPING IN CHASE TO BE REUSED.
D5. EXISTING CABINET UNIT HEATER TO BE REMOVED AND
REUSED. EXISTING HWS/R PIPING, VALVES AND CONTROLS TO
BE REUSED.
5
D6. REMOVE EXISTING SUPPLY DIFFUSER AND PORTION OF
BRANCH DUCT.
6
D8. REMOVE SUPPLY DIFFUSER AND BRANCH DUCT BACK TO
MAIN.
3/4"
HWS/R
8
12"ø
1
1
1 1/4"
HWS/R
68"x14"
3
2
12"ø
EXISTING
HIGH WINDOW
FIN TUBE, VALVES & CONTROLS
TO REMAIN AND REUSED.
MODIFY AS REQUIRED.
1 1/4"
HWS/R
1" HWS/R
1
16"x12"
1"
HWS/R
3/4"
HWS/R
7
2
1
4
40"x14"
1
26"x14"
2
1"
HWS/R
12"ø
20"x14"
16"x12"
3/4"
HWS/R
1
3/4"
HWS/R
3/4"
HWS/R
12"ø
1
1
7
4
4
1
FIRST FLOOR DEMOLITION
0
8
16
24
1/8" = 1'-0"
NORTH
ISSUED:
3.24.2016
DESCRIPTION:
BID DOCUMENTS
SHEET:
MD-100
18031.00
7
3/4"
HWS/R
PP
RCNJ No.201437.01C
ALTERATIONS
EXISTING
HIGH WINDOW
FIN TUBE, VALVES & CONTROLS
TO REMAIN AND REUSED.
MODIFY AS REQUIRED.
4
CHECKED BY:
RAMAPO COLLEGE
OF NEW JERSEY
8
8
CJZ
DEMOLITION FIRST FLOOR
3/4"
HWS/R
3/4"
HWS/R
DRAWN BY:
505 RAMAPO VALLEY RD.
MAHWAH, NJ 07430
3/4"
HWS/R
1"
HWS/R
REMOVE INSULATION
OFF EXISTING SUPPLY
DUCT THAT IS TO BE EXPOSED
REVISIONS
D7. EXISTING HWS/R PIPING, VALVES AND CONTROLS
SERVING HIGH WINDOW FIN TUBE RADIATION TO REMAIN,
MODIFY AS REQUIRED.
1 1/2"
HWS/R
1
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
3/23/2016 4:03:34 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
DEMOLITION
GENERAL NOTES
1.
18"x10"
24"x10"
2.
24"x10"
3.
6
12x10
4
4.
2
EXISTING HOOD
TO REMAIN
ROOF PLAN DEMOLITION - ADD ALTERNATE-1
5.
1/8" = 1'-0"
5
6.
5
7.
VAV-9 (E)
8.
IDENTIFICATION AND/OR ABATEMENT OF
HAZARDOUS MATERIALS IS NOT PART OF THIS SCOPE
OF WORK. IF ASBESTOS OR OTHER HAZARDOUS
MATERIALS ARE ENCOUNTERED, THE CONTRACTOR
SHALL NOTIFY THE OWNER IMMEDIATELY.
REFER TO SPECIFICATIONS FOR RECYCLING,
CONSTRUCTION WASTE MANAGEMENT AND
DISPOSAL REQUIREMENTS.
OPENING IN THE EXISTING STRUCTURE SMALLER THAN
12" IN ANY DIRECTION ARE NOT IDENTIFIED ON THESE
DRAWINGS. SUBCONTRACTORS SHALL BE
RESPONSIBLE FOR PROVIDING OPENINGS SMALLER
THAN 12" AS REQUIRED FOR INSTALLATION OF THEIR
WORK.
OPENINGS IN THE EXISTING STRUCTURE SHALL NOT BE
MADE WITHOUT PRIOR APPROVAL OF THE
STRUCTURAL ENGINEER.
DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE
STRUCTURAL INTEGRITY OF THE BUILDING. IF HIDDEN
ELEMENTS OR DETERIORATED ELEMENTS ARE
ENCOUNTERED, NOTIFY THE ARCHITECT IMMEDIATELY.
PROTECT ADJACENT AREAS AND ITEMS "TO REMAIN"
DURING DEMOLITION/CONSTRUCTION.
REPAIR/REPLACE ITEMS DAMAGED DURING
CONSTRUCTION.
IF UNANTICIPATED HIDDEN ELEMENTS OR
DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY
THE OWNERS REPRESENTATIVE IMMEDIATELY.
REFER TO CONSULTANT DRAWINGS FOR ADDITIONAL
DEMOLITION WORK.
REVIEW w/ OWNER TO DETERMINE WHAT, IF
ANYTHING, WILL BE REMOVED BY OWNER AND WHAT,
IF ANYTHING, IS TO BE SALVAGED & TURNED OVER
TO OWNER.
SEALED:
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
1
FIRST FLOOR DEMOLITION - ADD ALTERNATE-1
ARCHITECT:
1/8" = 1'-0"
KEYED NOTES
T 9(E)
D1. REMOVE EXISTING EXHAUST GRILLE AND 2'-0" PORTION
OF EXISTING EXHAUST BRANCH DUCT. PER BASE BID.
VAV-10 (E)
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
1
D2. REMOVE EXISTING SUPPLY DIFFUSER AND ASSOCIATED
FLEX DUCT. PER BASE BID.
D3. EXISTING CABINET UNIT HEATER TO BE TEMPORARILY
DISCONNECTED FROM EXISTING HWS/R PIPING, CONTROLS
AND POWER. EXISTING CABINET UNIT HEATER TO BE
RELOCATED. MODIFY EXISTING HWS/R PIPING, VALVES &
CONTROLS AS REQUIRED AND REUSE.
18"x10"
24"x10"
VAV-8 (E)
24"x10"
12x10
D4. REMOVE EXISTING 12x10 GREASE EXHAUST DUCT FROM
EXISTING HOOD BACK TO EXTERIOR WALL PENETRATION.
PER ADD ALTERNATE-1.
1
ENGINEER:
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
REVISIONS
D5. REMOVE EXISTING SUPPLY GRILLE, INSULATE AND
PATCH EXISTING SUPPLY DUCT. PAINT TO MATCH
EXISTING DUCT COLOR. PER ADD ALTERNATE -1.
2
3
D6. REMOVE EXISTING GREASE EXHAUST HOOD FAN.
EXISTING CONTROLS AND ROOF SUPPORTS TO REMAIN
AND BE REUSED. PER ADD ALTERNATE -1.
2
VAV-7 (E)
VAV-6 (E)
6(E)
10(E)
T
E
T
E
1 1/2"
HWS/R
(E)
T
3(E)
VAV-4 (E)
VAV-3 (E)
VAV-5 (E)
T
T
4(E)
1 1/2"
HWS/R
5(E)
T E
7
T
E
VAV-1 (E)
T
T
1(E)
2(E)
DEMOLITION WORK LEGEND
VAV-2 (E)
CHECKED BY:
PP
EQUIPMENT TO BE REMOVED
EQUIPMENT TO REMAIN
T
E
POINT OF DISCONNECTION
T
E
T
E
T E
ISSUED:
3.24.2016
DESCRIPTION:
BID DOCUMENTS
3
FIRST FLOOR DEMOLITION - BASE BID
0
8
16
24
1/8" = 1'-0"
SHEET:
NORTH
MD-110
18031.00
7(E)
T
T
CJZ
RCNJ No.201437.01C
ALTERATIONS
T
DRAWN BY:
MECHANICAL DEMOLITION FIRST FLOOR
T
505 RAMAPO VALLEY RD.
MAHWAH, NJ 07430
D7. REMOVE EXISTING SUPPLY GRILLE. PER BASE BID.
1 1/2"
HWS/R
(E)
RAMAPO COLLEGE
OF NEW JERSEY
8(E)
3/23/2016 3:38:15 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
ADDITION/ALTERATION
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
VAV-9 (E)
8.
IDENTIFICATION AND/OR ABATEMENT OF
HAZARDOUS MATERIALS IS NOT PART OF THIS SCOPE
OF WORK. IF ASBESTOS OR OTHER HAZARDOUS
MATERIALS ARE ENCOUNTERED, THE CONTRACTOR
SHALL NOTIFY THE OWNER IMMEDIATELY.
REFER TO SPECIFICATIONS FOR RECYCLING,
CONSTRUCTION WASTE MANAGEMENT AND
DISPOSAL REQUIREMENTS.
OPENING IN THE EXISTING STRUCTURE SMALLER THAN
12" IN ANY DIRECTION ARE NOT IDENTIFIED ON THESE
DRAWINGS. SUBCONTRACTORS SHALL BE
RESPONSIBLE FOR PROVIDING OPENINGS SMALLER
THAN 12" AS REQUIRED FOR INSTALLATION OF THEIR
WORK.
OPENINGS IN THE EXISTING STRUCTURE SHALL NOT BE
MADE WITHOUT PRIOR APPROVAL OF THE
STRUCTURAL ENGINEER.
DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE
STRUCTURAL INTEGRITY OF THE BUILDING. IF HIDDEN
ELEMENTS OR DETERIORATED ELEMENTS ARE
ENCOUNTERED, NOTIFY THE ARCHITECT IMMEDIATELY.
PROTECT ADJACENT AREAS AND ITEMS "TO REMAIN"
DURING DEMOLITION/CONSTRUCTION.
REPAIR/REPLACE ITEMS DAMAGED DURING
CONSTRUCTION.
IF UNANTICIPATED HIDDEN ELEMENTS OR
DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY
THE OWNERS REPRESENTATIVE IMMEDIATELY.
REFER TO CONSULTANT DRAWINGS FOR ADDITIONAL
DEMOLITION WORK.
REVIEW w/ OWNER TO DETERMINE WHAT, IF
ANYTHING, WILL BE REMOVED BY OWNER AND WHAT,
IF ANYTHING, IS TO BE SALVAGED & TURNED OVER
TO OWNER.
SEALED:
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
ARCHITECT:
KEYED NOTES
T 9(E)
VAV-10 (E)
1656 Massachusetts Ave. | Lexington, MA 02420
Tel: 781-652-0114 | connorarchitecture.com
EXISTING HOOD EXHAUST
UP TO EXISTING FANS (TYP. 4)
ENGINEER:
300 CFM
18"x10"
24"x10"
VAV-8 (E)
24"x10"
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
300 CFM
12"x10"
REVISIONS
VAV-7 (E)
30"x12"
30"x12"
1"HWS/R
3/4"
HWS/R
T
INSTALL 3/4" HWS/R
HIGH AND TIGHT TO
CEILING ALONG WALL
6(E)
10(E)
T
S
INSTALL 3/4" HWS/R
DN ALONG COLUMN
IN ENCLOSURE
30"x14"
T
S
PAINT ALL EXISTING
AND NEW EXPOSED DUCT.
COLOR SELECTION
BY ARCHITECT.
FTR-2
1 1/2"
HWS/R
(E)
T
68"x20"
EXISTING
HIGH WINDOW
FIN TUBE, VALVES & CONTROLS
TO REMAIN AND REUSED.
MODIFY AS REQUIRED.
3(E)
26"x14"
40"x14"
3/4"
HWS/R (E)
1.5 GPM
2.5 GPM
VAV-4 (E)
VAV-3 (E)
VAV-5 (E)
3/4"
HWR DN
PROVIDE
PIPE CHASE
TO MATCH
ADJACENT WALL
26"x14"
1 1/4"
HWS/R
T
T
1 1/2"
HWS/R
4(E)
T
S
1" HWS/R
DN IN WALL
3.5
EXISTING
HIGH WINDOW
FIN TUBE, VALVES & CONTROLS
TO REMAIN AND REUSED.
MODIFY AS REQUIRED.
FTR-1 (RF-5)
CURVED RUNTAL
WALL HUNG
1 1/4"
HWS/R
5(E)
T S
3/4"
HWS/R
1 1/2"
HWS/R
1 1/4"
HWS/R
FTR-3
UFLT-4
VAV-1 (E)
T
T
1(E)
3/4"
HWS (E)
UP
PP
7(E)
T
T
CHECKED BY:
FTR-3
UFLT-4
300 CFM
EXISTING DUCT UP TO
EXISTING MAKE-UP AIR UNIT
CJZ
FIRST FLOOR ALTERATION/ADDITION
30"x22"
DRAWN BY:
RCNJ No.201437.01C
ALTERATIONS
T
2(E)
VAV-2 (E)
1 1/4"
HWS/R
T
FTR-3
UFLT-2
S
1" HWS/R
DN IN WALL
SERVING FTR-1 & 2
1" HWS/R
3/4"
HWS/R (E)
FTR-3
FTR-1 (RF-5)
CURVED RUNTAL
WALL HUNG (TYP. 3 SECTIONS)
RUN PIPING
BEHIND COLUMN
IN WALL
RUN PIPING
BEHIND COLUMN
IN WALL
FTR-3
T
3/4"
HWR (E)
UP
T
S
UFLT-4
S
T SFTR-3
2.5 GPM
FTR-3
UFLT-4
CONNECT NEW FTR-3
TO EXISTING HWS/R DN
IN EXISTING CHASE
FTR-3
UFLT-4
CONNECT NEW FTR-3
TO EXISTING HWS/R DN
IN EXISTING CHASE
ISSUED:
3.24.2016
DESCRIPTION:
BID DOCUMENTS
1
FIRST FLOOR - RENOVATION
0
8
16
24
1/8" = 1'-0"
SHEET:
NORTH
M-100
18031.00
1 1/2"
HWS/R
(E)
505 RAMAPO VALLEY RD.
MAHWAH, NJ 07430
VAV-6 (E)
8(E)
RAMAPO COLLEGE
OF NEW JERSEY
300 CFM
14"x8"
3/23/2016 4:09:10 PM
NJDCA ELECTRONIC SUBMITTAL STAMP:
ADDITION/ALTERATION
GENERAL NOTES
1.
EXISTING HOOD EXHAUST
UP TO EXISTING FANS (TYP. 4)
2.
18"x10"
3.
6
24"x10"
24"x10"
20"x12"
5
4.
2
5.
ROOF PLAN ALTERATION - ADD ALTERNATE-1
1/8" = 1'-0"
6.
D-F
330 CFM
(TYP. 2)
8"ø
8"ø
7.
14"x8"
30"x12"
8.
VAV-9 (E)
1.5 gpm
IDENTIFICATION AND/OR ABATEMENT OF
HAZARDOUS MATERIALS IS NOT PART OF THIS SCOPE
OF WORK. IF ASBESTOS OR OTHER HAZARDOUS
MATERIALS ARE ENCOUNTERED, THE CONTRACTOR
SHALL NOTIFY THE OWNER IMMEDIATELY.
REFER TO SPECIFICATIONS FOR RECYCLING,
CONSTRUCTION WASTE MANAGEMENT AND
DISPOSAL REQUIREMENTS.
OPENING IN THE EXISTING STRUCTURE SMALLER THAN
12" IN ANY DIRECTION ARE NOT IDENTIFIED ON THESE
DRAWINGS. SUBCONTRACTORS SHALL BE
RESPONSIBLE FOR PROVIDING OPENINGS SMALLER
THAN 12" AS REQUIRED FOR INSTALLATION OF THEIR
WORK.
OPENINGS IN THE EXISTING STRUCTURE SHALL NOT BE
MADE WITHOUT PRIOR APPROVAL OF THE
STRUCTURAL ENGINEER.
DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE
STRUCTURAL INTEGRITY OF THE BUILDING. IF HIDDEN
ELEMENTS OR DETERIORATED ELEMENTS ARE
ENCOUNTERED, NOTIFY THE ARCHITECT IMMEDIATELY.
PROTECT ADJACENT AREAS AND ITEMS "TO REMAIN"
DURING DEMOLITION/CONSTRUCTION.
REPAIR/REPLACE ITEMS DAMAGED DURING
CONSTRUCTION.
IF UNANTICIPATED HIDDEN ELEMENTS OR
DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY
THE OWNERS REPRESENTATIVE IMMEDIATELY.
REFER TO CONSULTANT DRAWINGS FOR ADDITIONAL
DEMOLITION WORK.
REVIEW w/ OWNER TO DETERMINE WHAT, IF
ANYTHING, WILL BE REMOVED BY OWNER AND WHAT,
IF ANYTHING, IS TO BE SALVAGED & TURNED OVER
TO OWNER.
SEALED:
CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR
UNAUTHORIZED USE OF THIS DOCUMENT.
DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.
ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.
1
FIRST FLOOR ALTERATION - ADD ALTERNATE-1
ARCHITECT:
1/8" = 1'-0"
KEYED NOTES
VAV-10 (E)
1 gpm
EXISTING HOOD EXHAUST
UP TO EXISTING FANS (TYP. 4)
T 9(E)
M1. CABINET UNIT HEATER (CUH-1) TO BE HUNG FROM ROOF
STRUCTURE, FLUSH WITH CEILING. PROVIDE TEMPERATURE
SENSOR IN RETURN AIR GRILLE PORTION OF CEILING MOUNTED
CABINET UNIT HEATER, COORDINATE WITH LIGHTING AND
SPRINKLER PIPING. INTEGRATE INTO EXISTING BUILDING
MANAGEMENT SYSTEM. PER BASE BID.
R-A
450 CFM
3
M2. EXISTING CABINET UNIT HEATER TO BE TEMPORARILY
DISCONNECTED FROM EXISTING HWS/R, CONTROLS & POWER.
EXISTING CABINET UNIT HEATER TO RELOCATED. MODIFY EXISTING
HWS/R PIPING AND CONTROLS AS REQUIRED AND REUSE. PER
BASE BID.
300 CFM
18"x10"
24"x10"
VAV-8 (E)
1 gpm
24"x10"
400 CFM
3
300 CFM
R-A
300 CFM
2
T
350 CFM
4
1 1/2"
HWS/R
28 GPM
30"x12"
1"
HWS/R
4.5 GPM
D-C
200 CFM
WALL MOUNTED
300 CFM
EXISTING DUCT UP TO
EXISTING MAKE-UP AIR UNIT
T
7(E)
T
T
6(E)
10(E)
400 CFM
30"x14"
T
T
VOLUME
DAMPER
E
PAINT ALL EXISTING
AND NEW EXPOSED DUCT.
COLOR SELECTION
BY ARCHITECT.
E
3/4" HWS/R
DN ALONG COLUMN
1.5 gpm
1
VOLUME
DAMPER
T
68"x20"
CUH-1
3(E)
26"x14"
VAV-4 (E)
1.5 gpm
40"x14"
EXISTING GRILLE
400 CFM
(TYP. 5)
VAV-3 (E)
1.5 gpm
VAV-5 (E)
1.5 gpm
26"x14"
T
5(E)
T E
T
4(E)
68"x20"
D-E
CENTER NEW DUCT MAIN
1000 CFM
OVER NEW CEILING
T
PAINT ALL NEW EXPOSED DUCT.
COLOR SELECTION
BY ARCHITECT.
D-E
1000 CFM
E
PAINT ALL NEW EXPOSED DUCT.
COLOR SELECTION
BY ARCHITECT.
36"x8"
VOLUME
DAMPER
INSTALL DUCT
TIGHT TO BEAM
1 1/4" HWS/R
8 GPM
18"ø
VAV-1 (E)
.5 gpm
T
T
1(E)
18"ø
T
E
D-A
250 CFM
(TYP. 6)
NEW DUCTWORK & EQUIPMENT
10" DIA.
(TYP. 6)
T
E
PP
VAV-2 (E)
.5 gpm
BALANCE DAMPER
D-B
300 CFM
DUCT MOUNTED
(TYP. 16)
2(E)
RENOVATION WORK LEGEND
36"x18"
CHECKED BY:
M6. PROVIDE EXHAUST FAN (EF-1). MODIFY EXISTING FAN
SUPPORT BASE AS REQUIRED TO MOUNT EXHAUST FAN (EF-1)
MAINTAIN ROOF INTEGRITY TO BE WEATHER TIGHT. CONNECT
EXISTING WOK EXHAUST HOOD CONTROLS TO NEW EXHAUST FAN
(EF-1). PER ADD ALTERNATE-1.
30"x12"
VOLUME
DAMPER
CJZ
EXISTING DUCTWORK & EQUIPMENT
D-B
200 CFM
DUCT MOUNTED
(TYP. 4)
POINT OF CONNECTION
1 1/4" HWS/R
16"ø
T
E
T E
ISSUED:
3.24.2016
DESCRIPTION:
BID DOCUMENTS
SHEET:
3
FIRST FLOOR ALTERATION - BASE BID
0
8
16
M-110
24
1/8" = 1'-0"
NORTH
18031.00
VAV-6 (E)
1.5 gpm
8(E)
DRAWN BY:
505 RAMAPO VALLEY RD.
MAHWAH, NJ 07430
VAV-7 (E)
1 gpm
300 CFM
M5. PROVIDE 20x12 GREASE EXHAUST DUCT AND ASSOCIATED FIRE
RATED DUCT ACCESS DOORS. CONNECT NEW 20x12 DUCT TO
EXISTING GREASE EXHAUST HOOD AND EXISTING EXTERIOR 20x12
GREASE EXHAUST DUCT.
PER ADD ALTERNATE - 1.
D-D
200 CFM
(TYP. 2)
RCNJ No.201437.01C
ALTERATIONS
400 CFM
350 CFM
30"x22"
REVISIONS
RAMAPO COLLEGE
OF NEW JERSEY
400 CFM
49 Court Street | P.O. Box 1980 | Binghamton, NY 13902
Tel: 607-723-9421 | mjinc.com
M4. PROVIDE NEW SUPPLY DIFFUSER (D-D). PROVIDE NEW
BRANCH DUCTWORK AS REQUIRED FOR DIFFUSER TO FIT IN NEW
CEILING GRID. NEW SUPPLY DUCT TO BE SAME SIZE AS EXISTING
BRANCH DUCT. PER BASE BID.
1.5 gpm
4
ENGINEER:
MECHANICAL ALTERATIONS FIRST FLOOR
400 CFM
M3. PROVIDE NEW EXHAUST GRILLE (R-A). PROVIDE NEW BRANCH
DUCTWORK AS REQUIRED FOR GRILLE TO FIT IN NEW CEILING
GRID. NEW EXHAUST DUCT TO BE SAME SIZE AS EXISTING BRANCH
DUCT. PER BASE BID.
1656 Massachusetts Ave. | Lexington, MA 02420