SWITCHES AND CONTROLS DISTRIBUTION EQUIPMENT (EQUIPMENT PREFIX) LIGHTING FIXTURES

advertisement
2
4
LIGHTING FIXTURES
SWITCHES AND CONTROLS
DISTRIBUTION EQUIPMENT (EQUIPMENT PREFIX)
SUBSCRIPTS: A1b = TYPE A, CIRCUIT 1, CONTROL ZONE b
SUBSCRIPTS: 3b = TYPE 3, CONTROL ZONE b
LIGHTING OR RECEPTACLE PANELBOARD
TOGGLE SWITCH: 3 = 3-WAY, 2 = DOUBLE POLE, 4 = 4 WAY, DM =
DIMMER, K = KEY OPERATED, EX = EXPLOSION
PROOF, T = TIMER OPERATED, LM = LOW
VOLTAGE MASTER, OC = OCCUPANCY SENSOR
SWITCH, F = FUSED, M = MANUAL MOTOR
STARTER, CB = CIRCUIT BREAKER
RELAY CABINET
3
CEILING OR PENDANT INCANDESCENT, HID OR COMPACT FLUORESCENT
CEILING OR PENDANT INCANDESCENT, HID OR COMPACT
FLUORESCENT EMERGENCY LIGHT
CEILING OR PENDANT HID WITH QUARTZ RESTRIKE
10
FLUORESCENT STRIP LIGHT
DISTRIBUTION OR POWER PANELBOARD
MOTOR CONTROL CENTER
SWITCHBOARD
DIMMER, 6 = 600W, 10 = 1000W
WALL MOUNTED INCANDESCENT, HID OR COMPACT FLUORESCENT
D
3
M
OCCUPANCY SENSOR, WALL MOUNTED OR CEILING MOUNTED,
DIRECTIONAL
M
OCCUPANCY SENSOR, CEILING MOUNTED, MULTI DIRECTIONAL
TIME CLOCK
PUSHBUTTON OR CONTROL STATION
CONTACTOR
RACEWAYS AND WIRES
4. FOR EXACT LOCATIONS OF RECESSED LIGHTING FIXTURES, REFERENCE
ARCHITECTURAL REFLECTED CEILING PLANS. COORDINATE
INSTALLATION OF LIGHTING FIXTURES WITH LOCATION OF EQUIPMENT,
PIPING AND DUCTWORK.
CONDUIT OR CABLE BELOW SLAB, IN SLAB OR UNDERGROUND
CONDUIT OR CABLE TURNING UP
0
MOTOR STARTER, 0 = STARTER SIZE
FLOODLIGHT
30
(12)
0
COMBINATION MOTOR STARTER AND DISCONNECT SWITCH
30 = SWITCH AMPERE RATING
(12) = FUSE AMPERE RATING
0 = STARTER SIZE
100
(70)
1
COMBINATION MOTOR STARTER AND CIRCUIT PROTECTOR
100 = FRAME SIZE
(70) = TRIP RATING
1 = STARTER SIZE
30
(15)
FUSED DISCONNECT SWITCH
30 = SWITCH AMPERE RATING
(15) = FUSE AMPERE RATING
OUTLET BOX WITH BLANK COVER
NON-FUSED DISCONNECT SWITCH
30 = SWITCH AMPERE RATING
JUNCTION BOX, FLOOR DUCT SYSTEM
ROADWAY OR PARKING LOT STANDARD
POST TOP WALKWAY OR PARKING LOT STANDARD
BUILDING MOUNTED WALLPACK
IN POOL WET NICHE LIGHT
LIGHTING TRACK WITH FIXTURES
30
DOCK LIGHT
CONDUIT CAPPED
WALL MOUNTED EXIT SIGN
TELEPHONE TERMINAL BOARD (TB)
SHADING INDICATES ILLUMINATED FACE OF EXIT SIGN
TELEPHONE TERMINAL CABINET (TC)
ARROW INDICATES EXIT SIGN DIRECTIONAL ARROW
TELEPHONE WALL OUTLET, W = WALL, P = PUBLIC,
F = FIRE FIGHTER, WP = WEATHERPROOF
#10,3/4"
JUNCTION BOX
PULL BOX
FCP
FIRE ALARM CONTROL PANEL
LOC
LOCAL OPERATING CONSOLE
FSA
FIRE ALARM SYSTEM ANNUNCIATOR
NAC
NAC EXTENDER PANEL (REMOTE POWER SUPPLY)
FTP
FIRE ALARM TRANSPONDER PANEL
TELEPHONE FLOOR OUTLET OR SERVICE FITTING
SPECIAL RECEPTACLE, X = NEMA DESIGNATION
B
PUBLIC ADDRESS PUSHBUTTON
DUPLEX FLOOR RECEPTACLE
VOLUME CONTROL AND CHANNEL SELECTOR
SINGLE FLOOR RECEPTACLE
CEILING MOUNTED SPEAKER, S=SOUND MASKING
DUPLEX RECEPTACLE AND DATA OUTLET IN
FLOOR BOX OR SERVICE FITTING
I
E
U
SPECIAL FLOOR RECEPTACLE
DUPLEX RECEPTACLE AND TELEPHONE OUTLET IN
FLOOR BOX OR SERVICE FITTING
P
WALL MOUNTED SPEAKER
S
MASTER CLOCK (CM)
C
C C
P
C
EOL
75
DOUBLE FACE CLOCK, A = ANALOG, D = DIGITAL
F
75
PROGRAM BELL
M
75
PROGRAM BUZZER
POKE-THROUGH WITH DUPLEX RECEPTACLE AND
FOUR CATEGORY 5 COMMUNICATION JACKS
BUZZER SWITCH
OFF AIR ANTENNA
TV
75
M
PARTITION SENSOR, 10= 1000, 6=600
75
F
A
LEGEND ABBREVIATIONS
FA
FLOUR
FIRE ALARM
FLOURESCENT
G
GFCI
GROUND
GROUND FAULT CIRCUIT INTERUPTER
INCND
INCANDESCENT
ELEVATOR RECALL PHOTOELECTRIC SMOKE DETECTOR
LTG
LIGHTING
DUCT SMOKE DETECTOR
MECH
MIN
MTD
MECHANICAL
MINIMUM
MOUNTED
N
NIC
NP
NEUTRAL
NIT IN CONTRACT
NOT PERMITTED
WALL-MOUNTED MASS NOTIFICATION STROBE (AMBER)
(NUMBER INDICATES CANDELA RATING)
EXP = EXPLOSION PROOF
PC
PWR
PERSONAL COMPUTER
POWER
WALL-MOUNTED SPEAKER/STROBE (CLEAR)
(NUMBER INDICATES CANDELA RATING)
EXP = EXPLOSION PROOF
QTY
QUANTITY
RECP
REQD
RM
RECEPTACLE
REQUIRED
ROOM
SC
SS
SW
SPLIT CIRCUIT
SINGLE STATION SMOKE ALARM
SWITCH
TEL
TELCOM
TYP
TELEPHONE
TELECOMMUNICATIONS
TYPICAL
UPS
UNINTERUPTABLE POWER SUPPLY
WP
WEATHER PROOF
XFRMR
TRANSFORMER
PHOTOELECTRIC SMOKE DETECTOR
IONIZATION SMOKE DETECTOR
SUB FLOOR SMOKE DETECTOR
END OF LINE DEVICE
WALL-MOUNTED FIRE ALARMSTROBE (CLEAR)
(NUMBER INDICATES CANDELA RATING)
EXP = EXPLOSION PROOF
WALL-MOUNTED FIRE ALARM SPEAKER
F
TELEVISION OUTLET
10
11. ALL EMERGENCY LIGHT FIXTURES SHALL BE UNSWITCHED SO AS
TO BE UTILIZED AS NIGHT LIGHTS.
ELECTRICAL
ELEVATION
EMERGENCY
SINGLE FACE CLOCK, A = ANALOG, D = DIGITAL
PROGRAM CLOCK WITH INTERCOM
DUPLEX RECEPTACLE, TELEPHONE AND DATA
OUTLET IN FLOOR BOX OR SERVICE FITTING
10. SIZE OUTLET AND JUNCTION BOXES PER 2005 NEC ARTICLE 314,
UNLESS OTHERWISE NOTED.
ELEC
ELEV
EMER
MANUAL PULL STATION
MICROPHONE OUTLET
DUPLEX CEILING RECEPTACLE
DOUBLE DUPLEX FLOOR RECEPTACLE
F
EQUIPMENT RACK
M
9. CONDUITS ARE 3/4", UNLESS OTHERWISE NOTED.
DIGITAL ALARM COMMUNICATOR TRANSMITTER
195 RATE OF RISE HEAT DETECTOR
R
195
FIXED TEMPERATURE HEAT DETECTOR
F
MISCELLANEOUS SYSTEMS
CLOCK RECEPTACLE WITH HANGER
8. WIRES ARE #12, UNLESS OTHERWISE NOTED.
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
ARCHITECTURAL
AVERAGE
LCD ANNUNCIATOR
LCD
COMBINATION TELEPHONE IN COMMON FLOOR BOX WITH
ELECTRICAL OUTLET
DATA CEILING OUTLET
DOUBLE DUPLEX RECEPTACLE
DUPLEX RECEPTACLE ON EMERGENCY CIRCUIT
DACT
COMBINATION TELEPHONE AND DATA WALL OUTLET, 2 = 2-PORT,
4 = 4-PORT, EXP = EXPLOSION PROOF, M = MODULAR
SINGLE RECEPTACLE
X
DATA OUTLET IN COMMON FLOOR BOX WITH ELECTRICAL
OUTLET
4'-0"
LIGHTING SWITCHES
1'-6"
GENERAL PURPOSE RECEPTACLES
COUNTER TOP RECEPTACLES
8 INCHES ABOVE COUNTER
1'-6"
TELEPHONE OUTLETS
1'-6"
DATA OUTLETS
1'-6"
TELEVISION OUTLET (COAX)
AFF
AFG
ARCH
AVG
DATA WALL OUTLET, D = DATA, F = FAX, S=SIPRNET
4
By: Description:
7. MOUNTING HEIGHTS ABOVE FINISHED FLOOR ARE AS FOLLOWS, UNLESS
OTHERWISE NOTED:
FIRE ALARM & MASS NOTIFICATION SYSTEM LEGEND
RECEPTACLES
SUBSCRIPTS: 1b = CIRCUIT 1, CONTROL ZONE b
GFCI = GROUND FAULT CIRCUIT INTERRUPTER
WP = WEATHERPROOF WHILE IN USE COVER
S = SWITCHED, F = FLUSH FLOOR,
SM = SURFACE MOUNT FLOOR
DUPLEX RECEPTACLE
Revision:
Date:
6. MOUNTING HEIGHTS FOR WALL MOUNTED FIXTURES OR DEVICES ARE TO
CENTER LINE OF OUTLET BOXES, UNLESS OTHERWISE NOTED.
WIRING: LONG SLASH = NEUTRAL (N)
SHORT SLASH = HOT
SHORT SLASH WITH HOOK = SWITCHED
LONG SLASH WITH DOT = GROUND (G)
#10 = WIRE SIZE
3/4" = CONDUIT SIZE
C
TELEPHONE AND DATA COMMUNICATIONS
501 North Broadway, St. Louis, Missouri 63102-2121
5. MOUNTING HEIGHTS FOR CEILING MOUNTED FIXTURES OR DEVICES ARE
TO BOTTOM OF FIXTURES OR DEVICES, UNLESS OTHERWISE NOTED.
LP1-2,4,6 HOMERUN, LP1 = PANEL DESTINATION, 2,4,6 = CIRCUITS
STEP OR AISLE LIGHT
CEILING OR PENDANT MOUNTED EXIT SIGN
NOT FOR
CONSTRUCTION
CONDUIT OR CABLE TURNING DOWN
REMOTE EMERGENCY HEAD
SPOTLIGHT, ARROW INDICATES DIRECTION OF AIM
2. LIGHTING CONTROL ZONE DESIGNATIONS INDICATE WHICH DEVICES
CONTROL WHICH GROUPS OF FIXTURES. WHERE LOCAL SWITCHES AND
DIMMERS ARE SHOWN, OR WHERE NO CONTROL ZONE DESIGNATION IS
INDICATED, LOCAL CONTROL DEVICES SHALL ONLY CONTROL FIXTURES IN
THEIR RESPECTIVE ROOMS.
3. SIZE OUTLET AND JUNCTION BOXES PER 2005 NEC ARTICLE 314,
UNLESS OTHERWISE NOTED.
CONDUIT OR CABLE BELOW RAISED FLOOR
FLUORESCENT EMERGENCY LIGHT
BATTERY PACK WITH HEADS
1. ALL SYMBOLS, ABBREVIATIONS AND GENERAL NOTES SHOWN ARE NOT
NECESSARILY USED ON THIS PROJECT.
TRANSFORMER
CONDUIT OR CABLE (RUN AS INDICATED)
FLUORESCENT
PHOTOCELL
ELECTRICAL GENERAL NOTES
911 Central Parkway N., Suite 425 San Antonio, TX 78323
FLUORESCENT STRIP EMERGENCY LIGHT
FLUORESCENT WITH ASYMMETRICAL DISTRIBUTION
LINE REPRESENTS LAMP AXIS
5
AIR FORCE CENTER FOR ENGINEERING AND THE
ENVIRONMENT (AFCEE)
FACILITIES DYNAMIC PROTOTYPES DESIGN FOR
DORMITORIES
1
CEILING-MOUNTED MASS NOTIFICATION STROBE (AMBER)
(NUMBER INDICATES CANDELA RATING)
CEILING-MOUNTED SPEAKER/STROBE (CLEAR)
(NUMBER INDICATES CANDELA RATING)
M
MINI-SPEAKER
FS
SPRINKLER FLOW SWITCH
TS
SPRINKLER TAMPER SWITCH
AIM
ADDRESSABLE INTERFACE MODULE
ACM
ADDRESSABLE CONTROL MODULE
DOOR HOLD AND RELEASE DEVICE
Scales:
NOT TO SCALE
Jacobs Project No.:
FDWD1301
Drawing Title:
NOTES AND
SYMBOLS
N
Date:
May 11, 2009
Designed By: Designer
Drawn By: SBW
Checked By: Checker
Drawing No.:
E-001
1
3
2
4
5
42 W
25 W
18 W
18 W
18 W
25 W
42TRT
T8
18DTT
18DTT
-T8
120 V
120 V
120 V
120 V
120 V
120 V
NOT FOR
CONSTRUCTION
911 Central Parkway N., Suite 425 San Antonio, TX 78323
MANUFACTURER
LITHONIA
LITHONIA
LITHONIA
LITHONIA
-LITHONIA
FIXTURE CATALOG NUMBER
WST 42TRT MDU 120 ELDWC PE LPI
WP 2 25 MVOLT S2 BF GEB10PS 2/1
LF6 2/18DTT F602A 120 GEB10
LF6 2/18DTT F602A 120 GEB10 EL
-SM 1 25 MVOLT ES GEB10RS
REMARKS
501 North Broadway, St. Louis, Missouri 63102-2121
Revision:
Date:
By: Description:
AIR FORCE CENTER FOR ENGINEERING AND THE
ENVIRONMENT (AFCEE)
FACILITIES DYNAMIC PROTOTYPES DESIGN FOR
DORMITORIES
1
2
2
2
3
1
LAMP TYPE
FIXTURE
VA
40 VA
40 VA
30 VA
30 VA
50 VA
20 VA
FIXTURE INPUT VOLTAGE
LAMP WATTAGE
FIXTURE DESCRIPTION
Exterior Wall
OUTDOOR WALL LIGHT WITH EMERGENCY BALLAST SURFACE
Bathroom Wall
WALL LIGHT
SURFACE
Ceiling
CAN LIGHT
RECESSED
Emergency Ceiling CAN LIGHT WITH EMERGENCY BALLAST
RECESSED
Ceiling Fan
CEILING FAN
SURFACE
Mech/Laundry Wall WALL LIGHT
SURFACE
LAMP QUANTITY
MOUNTING
D
Type
Mark
A
C
D
D
F
G
TYPE
LIGHTING FIXTURE SCHEDULE
C
B
Scales:
Jacobs Project No.:
A
FDWD1301
Drawing Title:
LIGHTING
SCHEDULE
Date:
May 11, 2009
Designed By: Designer
Drawn By: Author
Checked By: Checker
Drawing No.:
E-501
1
3
2
4
5
KEYED NOTES
Panel
PP-A
Voltage
120 V / 208 V
Phase
Three Phase
Mount
TBD
D
2
C
2
LIGHTING - WEST
LIGHTING - EAST
SPARE
SPARE
KITCHEN 113 REFRIGERATOR
KITCHEN 113 COUNTER TOP REC
KITCHEN 113 - 1/2HP
DISPOSER
KITCHEN 113 DISHWASHER
KITCHEN 113 MICROWAVE
KITCHEN 113 COUNTER TOP REC
Trip
15 A
Enclosure
Type 1
Poles
1
Ckt. No.
1
1
1
3
15 A
1
15 A
1
15 A
1
15 A
1
15 A
1
15 A
1
15 A
1
15 A
1
15 A
1
15 A
15 A
15 A
15 A
15 A
1
1
1
1
1
15 A
1
33
20 A
1
35
15 A
1
37
20 A
1
39
15 A
1
41
1
B
C
Ckt. No.
2
Poles
2
2
Trip
60 A
THE NOTATION "(AFCI)" INDICATES THAT THIS CIRCUIT BREAKER IS A
COMBINATION-TYPE ACR-FAULT CIRCUIT INTERUPTER.
LOAD FOR THIS SMALL-APPLIANCE OR LAUNDRY CIRCUIT IS SET TO
1500VA PER NEC 220.52.
NOT FOR
CONSTRUCTION
Load Name
KITCHEN 113 - RANGE
7
1
720 VA / 2880 VA
9
1
540 VA / 2880 VA
11
1
13
1
540 VA / 960 VA
19
1
540 VA / 696 VA
1
23
25
27
29
31
20 A
8
2
30 A
12
LAUNDRY 104 WASHER
LAUNDRY 104 - DRYER
2
20 A
HVAC CENTRAL (1HP)
1
15 A
1
15 A
1
15 A
1
15 A
24
26
28
30
32
1
1
1
1
1
15 A
15 A
15 A
15 A
15 A
HVAC - BEDROOM 101
(1/4HP)
HVAC - BEDROOM 108
(1/4HP)
HVAC - BEDROOM 111
(1/4HP)
HVAC - BEDROOM 116
(1/4HP)
SPARE
SPARE
SPARE
SPARE
SPARE
34
1
15 A
SPARE
36
1
15 A
SPARE
38
1
15 A
SPARE
40
1
15 A
SPARE
42
1
15 A
SPARE
16
360 VA / 696 VA
360 VA / 696 VA
21
1
1
2
Revision:
Date:
By: Description:
14
17
1
6
10
540 VA / 960 VA
15
1
501 North Broadway, St. Louis, Missouri 63102-2121
4
720 VA / 1500 VA
18
20
1260 VA / 696 VA
22
450 VA / 0 VA
460 VA / 0 VA
1500 VA / 0 VA
180 VA / 0 VA
1176 VA / 0 VA
744 VA / 0 VA
1500 VA / 0 VA
180 VA / 0 VA
Phase B
14772 VA
Mfg. / Type
--
Location
TBD
720 VA / 5760 VA
5
1
1
A
720 VA / 5760 VA
1
MCB
911 Central Parkway N., Suite 425 San Antonio, TX 78323
15 A
Phase A
15340 VA
Mains
200 A
Phase C
6582 VA
Modifications
--
1
1
1
1
AIR FORCE CENTER FOR ENGINEERING AND THE
ENVIRONMENT (AFCEE)
FACILITIES DYNAMIC PROTOTYPES DESIGN FOR
DORMITORIES
Load Name
BEDROOM 101 - DESK
AND CONV REC
BEDROOM 101 - CONV
REC
BEDROOM 108 - DESK
AND CONV REC
BEDROOM 108 - CONV
REC
BEDROOM 111 - DESK
AND CONV REC
BEDROOM 111 - CONV
REC
BEDROOM 116 - DESK
AND CONV REC
BEDROOM 116 - CONV
REC
BATHROOMS 102, 109 CONV REC
BATHROOMS 106, 115 CONV REC
LIVING 112 - REC
Wires
4 Wires
Total VA
36694 VA
Amps RMS. Sym.
--
B
Scales:
Jacobs Project No.:
A
FDWD1301
Drawing Title:
PANEL SCHEDULE A
Date:
May 11, 2009
Designed By: Designer
Drawn By: Author
Checked By: Checker
Drawing No.:
E-502
1
3
2
4
5
KEYED NOTES
Panel
PP-B
Voltage
120 V / 208 V
Phase
Three Phase
Mount
TBD
D
2
C
2
LIGHTING - NORTH
LIGHTING - SOUTH
SPARE
SPARE
KITCHEN 126 REFRIGERATOR
KITCHEN 126 COUNTER TOP REC
KITCHEN 126 DISHWASHER
KITCHEN 126 DISPOSAL (1/2HP)
KITCHEN 126 MICROWAVE
KITCHEN 126 COUNTER TOP REC
Trip
15 A
Enclosure
Type 1
Poles
1
Ckt. No.
1
1
1
3
15 A
1
15 A
1
15 A
1
15 A
1
15 A
1
15 A
1
15 A
1
15 A
1
15 A
1
15 A
15 A
15 A
15 A
15 A
1
1
1
1
1
15 A
1
33
15 A
1
35
20 A
1
37
20 A
1
39
15 A
1
41
1
B
C
Ckt. No.
2
Poles
2
2
Trip
60 A
THE NOTATION "(AFCI)" INDICATES THAT THIS CIRCUIT BREAKER IS A
COMBINATION-TYPE ACR-FAULT CIRCUIT INTERUPTER.
LOAD FOR THIS SMALL-APPLIANCE OR LAUNDRY CIRCUIT IS SET TO
1500VA PER NEC 220.52.
NOT FOR
CONSTRUCTION
Load Name
KITCHEN 126 - RANGE
7
1
720 VA / 2880 VA
9
1
540 VA / 2880 VA
11
1
13
1
540 VA / 960 VA
19
1
720 VA / 696 VA
1
23
25
27
29
31
1
20 A
8
2
30 A
12
LAUNDRY 124 WASHER
LAUNDRY 124 - DRYER
2
20 A
HVAC - CENTRAL (1HP)
1
15 A
1
15 A
1
15 A
1
15 A
24
26
28
30
32
1
1
1
1
1
15 A
15 A
15 A
15 A
15 A
HVAC - BEDROOM 117
(1/4HP)
HVAC - BEDROOM 127
(1/4HP)
HVAC - BEDROOM 122
(1/4HP)
HVAC - BEDROOM 132
(1/4HP)
SPARE
SPARE
SPARE
SPARE
SPARE
34
1
15 A
SPARE
36
1
15 A
SPARE
38
1
15 A
SPARE
40
1
15 A
SPARE
42
1
15 A
SPARE
16
360 VA / 696 VA
360 VA / 696 VA
21
1
6
2
Revision:
Date:
By: Description:
14
17
1
501 North Broadway, St. Louis, Missouri 63102-2121
10
720 VA / 960 VA
15
1
4
540 VA / 1500 VA
18
20
1440 VA / 696 VA
22
410 VA / 0 VA
440 VA / 0 VA
1500 VA / 0 VA
180 VA / 0 VA
744 VA / 0 VA
1176 VA / 0 VA
1500 VA / 0 VA
180 VA / 0 VA
Phase B
15132 VA
Mfg. / Type
--
1
Location
TBD
720 VA / 5760 VA
5
1
1
A
540 VA / 5760 VA
MCB
911 Central Parkway N., Suite 425 San Antonio, TX 78323
15 A
Phase A
15572 VA
Mains
200 A
Phase C
6110 VA
Modifications
--
1
1
1
1
AIR FORCE CENTER FOR ENGINEERING AND THE
ENVIRONMENT (AFCEE)
FACILITIES DYNAMIC PROTOTYPES DESIGN FOR
DORMITORIES
Load Name
BEDROOM 117 - DESK
AND CONV REC
BEDROOM 117 - CONV
REC
BEDROOM 127 - DESK
AND CONV REC
BEDROOM 127 - CONV
REC
BEDROOM 122 - DESK
AND CONV REC
BEDROOM 122 - CONV
REC
BEDROOM 132 - DESK
AND CONV REC
BEDROOM 132 - CONV
REC
BATHROOMS 118, 120 CONV REC
BATHROOMS 129, 131 CONV REC
LIVING 125 - REC
Wires
4 Wires
Total VA
36814 VA
Amps RMS. Sym.
--
B
Scales:
Jacobs Project No.:
A
FDWD1301
Drawing Title:
PANEL SCHEDULE B
Date:
May 11, 2009
Designed By: Designer
Drawn By: Author
Checked By: Checker
Drawing No.:
E-503
1
3
2
4
5
KEYED NOTES
Voltage
120 V / 208 V
Phase
Three Phase
Mount
TBD
Load Name
BEDROOM 133 - DESK
AND CONV REC
BEDROOM 133 - CONV
REC
BEDROOM 144 - DESK
AND CONV REC
BEDROOM 144 - CONV
REC
BEDROOM 136 - DESK
AND CONV REC
BEDROOM 136 - CONV
REC
BEDROOM 140 - DESK
AND CONV REC
BEDROOM 140 - CONV
REC
BATHROOMS 134, 138 CONV REC
BATHROOMS 143, 139 CONV REC
LIVING 145 - REC
D
2
C
2
LIVING 145 - REC
LIGHTING - EAST
LIGHTING - WEST
SPARE
KITCHEN 146 REFRIGERATOR
KITCHEN 146 COUNTER TOP REC
KITCHEN 146 DISPOSAL (1/2HP)
KITCHEN 146 DISHWASHER
KITCHEN 146 COUNTER TOP REC
KITCHEN 146 MICROWAVE
Trip
15 A
Wires
4 Wires
Mains
200 A MCB
Enclosure
Type 1
Poles
1
Ckt. No.
1
A
540 VA / 5760 VA
B
1
Location
2
TBD
C
Ckt. No.
2
Poles
2
Trip
60 A
Load Name
KITCHEN 146 - RANGE
1
15 A
1
15 A
1
15 A
1
15 A
1
15 A
1
15 A
1
15 A
1
15 A
1
15 A
1
15 A
15 A
15 A
15 A
15 A
1
1
1
1
1
15 A
1
33
20 A
1
35
15 A
1
37
15 A
1
39
20 A
1
41
Phase A
15350 VA
3
1
720 VA / 5760 VA
5
1
7
1
720 VA / 2880 VA
9
1
720 VA / 2880 VA
11
1
13
1
19
1
1
1
1
23
25
27
29
31
8
2
30 A
LAUNDRY 147 WASHER
LAUNDRY 147 - DRYER
2
Revision:
Date:
HVAC - CENTRAL (1HP)
12
1
15 A
1
15 A
1
15 A
1
15 A
440 VA / 0 VA
24
26
28
30
32
1
1
1
1
1
15 A
15 A
15 A
15 A
15 A
HVAC - BEDROOM 133
(1/4HP)
HVAC - BEDROOM 144
(1/4HP)
HVAC - BEDROOM 136
(1/4HP)
HVAC - BEDROOM 140
(1/4HP)
SPARE
SPARE
SPARE
SPARE
SPARE
180 VA / 0 VA
34
1
15 A
SPARE
36
1
15 A
SPARE
38
1
15 A
SPARE
40
1
15 A
SPARE
42
1
15 A
SPARE
By: Description:
14
720 VA / 696 VA
16
360 VA / 696 VA
360 VA / 696 VA
18
20
900 VA / 696 VA
22
1080 VA / 0 VA
470 VA / 0 VA
1500 VA / 0 VA
1176 VA / 0 VA
744 VA / 0 VA
180 VA / 0 VA
1500 VA / 0 VA
Phase B
13892 VA
Mfg. / Type
--
20 A
20 A
720 VA / 960 VA
21
1
1
2
17
1
6
10
720 VA / 960 VA
15
1
501 North Broadway, St. Louis, Missouri 63102-2121
4
540 VA / 1500 VA
LOAD FOR THIS SMALL-APPLIANCE OR LAUNDRY CIRCUIT IS SET TO
1500VA PER NEC 220.52.
NOT FOR
CONSTRUCTION
911 Central Parkway N., Suite 425 San Antonio, TX 78323
1
15 A
THE NOTATION "(AFCI)" INDICATES THAT THIS CIRCUIT BREAKER IS A
COMBINATION-TYPE ACR-FAULT CIRCUIT INTERUPTER.
Phase C
8532 VA
Modifications
--
1
1
1
1
AIR FORCE CENTER FOR ENGINEERING AND THE
ENVIRONMENT (AFCEE)
FACILITIES DYNAMIC PROTOTYPES DESIGN FOR
DORMITORIES
Panel
PP-C
Total VA
37774 VA
Amps RMS. Sym.
--
B
Scales:
Jacobs Project No.:
A
FDWD1301
Drawing Title:
PANEL SCHEDULE C
Date:
May 11, 2009
Designed By: Designer
Drawn By: Author
Checked By: Checker
Drawing No.:
E-504
1
3
2
4
5
GENERAL NOTES
1. CEILING MOUNTED LIGHT FIXTURES ARE MOUNTED AT 102" AFF.
2. WALL MOUNTED LIGHT FIXTURES IN BATHROOMS ARE COORDINATED
TO BE MOUNTED ABOVE THE WALL MIRROR.
NOT FOR
CONSTRUCTION
A
BEDROOM
BEDROOM
MECH.
117
127
123
G
911 Central Parkway N., Suite 425 San Antonio, TX 78323
501 North Broadway, St. Louis, Missouri 63102-2121
D
LAUNDRY
F
F
124
G
CLOSET
CLOSET
119
128
Revision:
Date:
D
BATHROOM
By: Description:
BATHROOM
KITCHEN
118
126
D
D
129
D
D
C
C
23
D
F
25
C
BATHROOM
C
120
D
D
131
CLOSET
CLOSET
121
130
C
BATHROOM
D
D
AIR FORCE CENTER FOR ENGINEERING AND THE
ENVIRONMENT (AFCEE)
FACILITIES DYNAMIC PROTOTYPES DESIGN FOR
DORMITORIES
D
D
F
F
LIVING
125
BEDROOM
BEDROOM
122
C1
132
PLAN B LIGHTING PLAN
1/4" = 1'-0"
C3
BATHROOM
102
BATHROOM
A
106
C
BEDROOM
C
G
MECH.
101
CLOSET
B
PLAN B LIGHTING AXON
D
105
103
BEDROOM
108
CLOSET
D
107
LAUNDRY
D
104
F
F
G
D
D
CLOSET
CLOSET
D
110
D
114
F
BATHROOM
BATHROOM
LIVING
109
112
D
D
115
D
D
C
C
D
KITCHEN
113
D
Scales:
D
1/4" = 1'-0"
Jacobs Project No.:
A
F
Drawing Title:
F
BEDROOM
BEDROOM
111
116
LIGHTING
PLANS/AXON
N
23
PLAN A LIGHTING PLAN
A1
1/4" = 1'-0"
FDWD1301
25
A3
PLAN A LIGHTING AXON
Date:
May 11, 2009
Designed By: Designer
Drawn By: SBW
Checked By: Checker
Drawing No.:
EL101
1
3
2
4
5
GENERAL NOTES
1. CEILING MOUNTED LIGHT FIXTURES ARE MOUNTED AT 102" AFF.
2. WALL MOUNTED LIGHT FIXTURES IN BATHROOMS ARE COORDINATED
TO BE MOUNTED ABOVE THE WALL MIRROR.
NOT FOR
CONSTRUCTION
911 Central Parkway N., Suite 425 San Antonio, TX 78323
501 North Broadway, St. Louis, Missouri 63102-2121
D
Revision:
Date:
AIR FORCE CENTER FOR ENGINEERING AND THE
ENVIRONMENT (AFCEE)
FACILITIES DYNAMIC PROTOTYPES DESIGN FOR
DORMITORIES
C
LAUNDRY
147
KITCHEN
G
146
MECH.
G
148
A
D
BEDROOM
LIVING
BEDROOM
133
145
144
B
F
F
F
BATHROOM
BATHROOM
134
143
D
C
CLOSET
CLOSET
137
141
D
CLOSET
D
D
135
D
D
CLOSET
C
142
D
D
D
C
Scales:
C
F
Jacobs Project No.:
BEDROOM
136
D
BATHROOM
138
140
D
27
25
FDWD1301
Drawing Title:
LIGHTING
PLANS/AXON
BATHROOM
139
N
PLAN C LIGHTING PLAN
A1
1/4" = 1'-0"
1/4" = 1'-0"
F
BEDROOM
A
By: Description:
A3
PLAN C LIGHTING AXON
Date:
May 11, 2009
Designed By: Designer
Drawn By: SBW
Checked By: Checker
Drawing No.:
EL102
1
3
2
4
5
GENERAL NOTES
1. RECEPTACLES ARE MOUNTED AT 18" AFF UNLESS OTHERWISE NOTED.
GFCI RECEPTACLES ARE MOUNTED AT 48" AFF UNLESS OTHERWISE
NOTED.
MECH.
123
2. ALL RECEPTACLES SHALL BE ARC-FAULT CIRCUIT INTERUPTER TYPE
EXCEPT WHEN LOCATED IN KITCHENS, BATHROOMS, AND OUTDOORS.
6
NOT FOR
CONSTRUCTION
8,10
D
911 Central Parkway N., Suite 425 San Antonio, TX 78323
7
3
BEDROOM
BEDROOM
117
127
501 North Broadway, St. Louis, Missouri 63102-2121
21
5
1
LAUNDRY
124
31
17 (SC) BATHROOM
118
CLOSET
33
121
9
By: Description:
19 (SC)
129
35
39
MICROWAVE
2,4
84" AFF
CLOSET
BATHROOM
128
37
DISPOSER
DISHWASHER
120
41
CLOSET
REFRIGERATOR
119
BATHROOM
Revision:
Date:
CLOSET
BATHROOM
130
131
RANGE
13
11
15
AIR FORCE CENTER FOR ENGINEERING AND THE
ENVIRONMENT (AFCEE)
FACILITIES DYNAMIC PROTOTYPES DESIGN FOR
DORMITORIES
LIVING
125
C
C1
BEDROOM
BEDROOM
122
132
PLAN B POWER PLAN
1/4" = 1'-0"
C3
17 (SC)
MECH.
8,10
6
PLAN B POWER AXON
19 (SC)
105
21
BATHROOM
BATHROOM
102
106
B
BEDROOM
BEDROOM
CLOSET
101
LAUNDRY
103
3
17 (SC)
109
108
107
104
1
BATHROOM
CLOSET
5
7
CLOSET
CLOSET
110
114
BATHROOM
115
LIVING
19 (SC)
112
11
DISHWASHER
KITCHEN
33
2,4
15
41
113
Scales:
39
BEDROOM
111
BEDROOM
9
DISPOSER
35
31 RANGE
MICROWAVE
84" AFF
REFRIGERATOR
Jacobs Project No.:
116
37
A
FDWD1301
Drawing Title:
13
POWER
PLANS/AXON
N
PLAN A POWER PLAN
A1
1/4" = 1'-0"
1/4" = 1'-0"
A3
PLAN A POWER AXON
Date:
May 11, 2009
Designed By: Designer
Drawn By: SBW
Checked By: Checker
Drawing No.:
EP101
1
3
2
4
5
GENERAL NOTES
1. RECEPTACLES ARE MOUNTED AT 18" AFF UNLESS OTHERWISE NOTED.
GFCI RECEPTACLES ARE MOUNTED AT 48" AFF UNLESS OTHERWISE
NOTED.
2. ALL RECEPTACLES SHALL BE ARC-FAULT CIRCUIT INTERUPTER TYPE
EXCEPT WHEN LOCATED IN KITCHENS, BATHROOMS, AND OUTDOORS.
NOT FOR
CONSTRUCTION
911 Central Parkway N., Suite 425 San Antonio, TX 78323
501 North Broadway, St. Louis, Missouri 63102-2121
D
Revision:
Date:
AIR FORCE CENTER FOR ENGINEERING AND THE
ENVIRONMENT (AFCEE)
FACILITIES DYNAMIC PROTOTYPES DESIGN FOR
DORMITORIES
C
41 2,4
RANGE
MICROWAVE
84" AFF
35
31
6
8,10
MECH.
KITCHEN LAUNDRY
147
146
DISPOSER
148
REFRIGERATOR
39
DISHWASHER
1
23
5
37
33
LIVING
145
B
BEDROOM
133
7
3
By: Description:
BEDROOM
144
21
BATHROOM
134
17(SC) CLOSET
CLOSET
CLOSET
137
141
CLOSET
135
19(SC)
BATHROOM
143
142
15
11
Scales:
9
BEDROOM
136
13
17 (SC)
19 (SC)
1/4" = 1'-0"
BEDROOM
140
Jacobs Project No.:
A
FDWD1301
Drawing Title:
BATHROOM
BATHROOM
138
139
POWER
PLANS/AXON
N
A1
PLAN C POWER PLAN
1/4" = 1'-0"
1
PLAN C POWER AXON
Date:
May 11, 2009
Designed By: Designer
Drawn By: SBW
Checked By: Checker
Drawing No.:
EP102
Download