The Eects of Harmonics in Power Systems and Methods to Reduce or Eliminate Them Wilbur N. Dale, Ph.D., P.E. wilburd@rstVA.com March 15, 2012 Overview • Introduction • Analysis of Harmonics • Sources of Harmonics • Tolerating Harmonics • Eliminating Harmonics 2 Introduction • Fourier series properties • Harmonic relationships • Fundamental Theorem of Engineering 3 Fourier Series Properties v(t) = i(t) = ∞ √ X k=1 ∞ √ X 2Vk cos (kωt + θk) 2Ik cos (kωt + φk) k=1 Typically, we do not see a DC term. We see only odd harmonics (half-wave symmetry). 4 Fourier Series Properties v u∞ uX u VRMS = t Vk2 k=1 v u∞ uX u I2k IRMS = t k=1 ∞ X VkIk cos (θk − φk) P= k=1 5 Harmonic relationships The Fourier coecients for a 1piecewise continuous signal decrease at the rate of O k . Theorem 2 The Fourier coecients for a continuous signal decrease at the rate of at least O k1 . Theorem 3 Narrow current pulses are rich in harmonics. Theorem 1 6 Fundamental Theorem of Engineering Follow the money. Corollary 1 Revenue is good. Corollary 2 Costs are bad. Theorem 4 7 Analysis of Harmonics + √ − 2VRMS cos ωt Non-linear load 8 Analysis of Harmonics + √ − 2VRMS cos ωt Non-linear load 9 Analysis of Harmonics √ p(t) = v(t)i(t) = = ∞ X 2V1 cos(ωt) ∞ √ X 2Ik cos(kωt + φk) k=1 V1Ik · [cos((k + 1)ωt + φk) k=1 + cos((k − 1)ωt + φk)] = V1I1 cos(φ1) + V1I2 cos(ωt + φ2) ∞ X + V1Ik−1 cos(kωt + φk−1) + k=2 ∞ X V1Ik+1 cos(kωt + φk+1) = T (t) ω k=2 10 Analysis of Harmonics • • • • Average P = V1I1 cos(φ1). Harmonic currents do not transfer power from the generator to the load. Harmonic currents do generate losses in the distribution system. Harmonic currents cause torsional vibrations in the generator shaft. There is a danger of fatigue fracture. 11 Analysis of Harmonics • • In three phase systems, a balanced non-linear load will have generator vibrations only at the triplen frequencies. If the balanced load also has odd half-wave symmetry, the generator vibration will be only at the sextuplen frequencies. 12 Analysis of Harmonics + √ − 2VRMS cos ωt Linear load Non-linear load 13 Analysis of Harmonics Transmission line + √ − 2VRMS cos ωt Linear load Fundamental current Harmonic currents 14 Analysis of Harmonics Transmission line Linear load Harmonic currents 15 Analysis of Harmonics • • Harmonic currents cause losses throughout the network. Harmonic currents cause larger RMS voltage drops in the lines. 16 Analysis of Harmonics For inductors: v v u∞ u∞ uX uX u u 2 VRMS = t Vk = t I2kX2L k=1 k=1 v v u∞ u∞ uX uX u u 2 2 Ik (kωL) = t I2kk2ω2L2 =t k=1 k=1 v u∞ uX u I2kk2 = ωLt k=1 v u ∞ uX 1 2 2 u → ωLt O k →∞ k=1 k 17 Analysis of Harmonics For 3-phase neutral currents: √ 2IRMS cos (kωt + φk) √ T + 2IRMS cos kω t − + φk 3 √ T + 2IRMS cos kω t + + φk 3 √ 2πk = 2IRMS cos (kωt + φk) 1 + 2 cos 3 √ = 3 2IRMS cos (kωt + φk) if k mod 3 = 0 IA + IB + I C = =0 otherwise 18 Sources of Harmonics √ + 2VRMS cos ωt − 19 Sources of Harmonics √ + 2VRMS cos ωt − 20 Tolerating Harmonics Previously: v u∞ uX u VRMS = ωLt I2kk2 k=1 Can we reduce L? Simple case of two parallel wires. d µ0 0 2 ln + 2 ln 2 + 1 L = 4π δ where d is the center to center distance between the wires and δ is the diameter of the wires. 21 Tolerating Harmonics • Smallest realizable inductance occurs with d = δ. µ0 (2 ln 2 + 1) • L0min = 4π • L0min • is not aected by wire size. Use several smaller cables and connect in parallel. 22 Tolerating Harmonics 1015™ IEEE Recommended Practice for Applying Low Voltage Circuit Breakers Used in Industrial and Commercial Power Systems Published by the Institute of Electrical and Electronics Engineers, Inc. IEEE Std 1015™-2006 (Revision of IEEE Std 1015-1997) Authorized licensed use limited to: Wilbur Dale. Downloaded on June 30,2010 at 04:20:08 UTC from IEEE Xplore. Restrictions apply. 23 Tolerating Harmonics • Circuit breakers vs. fuses: • Capacitor banks are a low impedance path. • Resistance welding machines. • Modern microprocessor controlled breakers. I2t. 24 Tolerating Harmonics 1100™ IEEE Recommended Practice for Powering and Grounding Electronic Equipment Published by the Institute of Electrical and Electronics Engineers, Inc. IEEE Std 1100™-2005 (Revision of IEEE Std 1100-1999) Authorized licensed use limited to: Wilbur Dale. Downloaded on June 30,2010 at 04:09:21 UTC from IEEE Xplore. Restrictions apply. 25 Tolerating Harmonics K= kX max (Ikk)2 15 < kmax < 34 k=1 Ik is in per-unit of transformer ratings. Non-linear load transformers with larger neutral conductors and temperature tolerance. 26 Eliminating Harmonics • • Delta-Wye eliminates triplen harmonics by absorption. Wye-Wye zigzag eliminates triplen harmonics and the 5th and 7th. 27 Eliminating Harmonics Change the load. Power factor correction power supplies are switching power supplies with near unit power factor and low harmonic content. In addition, the harmonics fall o at O 12 . k 28