SECTION 6.4 THE POWER-FLOW PROBLEM 327 shown in Figure 3.9 for a two-winding transformer, Figure 3.20 for a threewinding transformer, or Figure 3.25 for a tap-changing transformer. Input data for each transmission line include the per-unit equivalent p circuit series impedance Z 0 and shunt admittance Y 0 , the two buses to which the line is connected, and maximum MVA rating. Similarly, input data for each transformer include per-unit winding impedances Z, the per-unit exciting branch admittance Y, the buses to which the windings are connected, and maximum MVA ratings. Input data for tap-changing transformers also include maximum tap settings. The bus admittance matrix Ybus can be constructed from the line and transformer input data. From (2.4.3) and (2.4.4), the elements of Ybus are: Diagonal elements: O¤-diagonal elements: EXAMPLE 6.9 Ykk ¼ sum of admittances connected to bus k Ykn ¼ "ðsum of admittances connected between buses k and nÞ k0n ð6:4:2Þ Power-flow input data and Ybus Figure 6.2 shows a single-line diagram of a five-bus power system. Input data are given in Tables 6.1, 6.2, and 6.3. As shown in Table 6.1, bus 1, to which a generator is connected, is the swing bus. Bus 3, to which a generator and a load are connected, is a voltage-controlled bus. Buses 2, 4, and 5 are load buses. Note that the loads at buses 2 and 3 are inductive since Q 2 ¼ "QL2 ¼ "2:8 and "QL3 ¼ "0:4 are negative. For each bus k, determine which of the variables Vk , dk , Pk , and Q k are input data and which are unknowns. Also, compute the elements of the second row of Ybus . SOLUTION The input data and unknowns are listed in Table 6.4. For bus 1, the swing bus, P1 and Q1 are unknowns. For bus 3, a voltage-controlled bus, FIGURE 6.2 Single-line diagram for Example 6.9 Copyright 2010 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part. Due to electronic rights, some third party content may be suppressed from the eBook and/or eChapter(s). Editorial review has deemed that any suppressed content does not materially affect the overall learning experience. Cengage Learning reserves the right to remove additional content at any time if subsequent rights restrictions require it. (AutoPDF V7 8/12 14:39) Thomson-U (7.375x9.25") Tmath&GillSans J-1711 Glover Rev1:(CKN)27/4/2007 pp. 294–378 25795_06_ch06_p294-378 (p. 327) 328 CHAPTER 6 POWER FLOWS TABLE 6.1 Bus input data for Example 6.9* Bus 1 2 3 4 5 Type Swing Load Constant voltage Load Load V per unit d degrees PG per unit QG per unit PL per unit QL per unit QGmax per unit QGmin per unit 1.0 — 1.05 0 — — — 0 5.2 — 0 — 0 8.0 0.8 0 2.8 0.4 — — 4.0 — — "2.8 — — — — 0 0 0 0 0 0 0 0 — — — — * Sbase ¼ 100 MVA, Vbase ¼ 15 kV at buses 1, 3, and 345 kV at buses 2, 4, 5 Bus-to-Bus R0 per unit X0 per unit G0 per unit B0 per unit Maximum MVA per unit 2–4 2–5 4–5 0.0090 0.0045 0.00225 0.100 0.050 0.025 0 0 0 1.72 0.88 0.44 12.0 12.0 12.0 TABLE 6.2 Line input data for Example 6.9 R per unit X per unit Gc per unit Bm per unit Maximum MVA per unit Maximum TAP Setting per unit 0.00150 0.00075 0.02 0.01 0 0 0 0 6.0 10.0 — — TABLE 6.3 Transformer input data for Example 6.9 Bus-to-Bus 1–5 3–4 TABLE 6.4 Input data and unknowns for Example 6.9 Bus 1 2 3 4 5 Input Data Unknowns V1 ¼ 1:0, d1 ¼ 0 P2 ¼ PG2 " PL2 ¼ "8 Q 2 ¼ QG2 " QL2 ¼ "2:8 V3 ¼ 1:05 P3 ¼ PG3 " PL3 ¼ 4:4 P4 ¼ 0, Q4 ¼ 0 P5 ¼ 0, Q5 ¼ 0 P1 , Q1 V2 , d2 Q3 , d3 V4 , d4 V5 , d5 Q3 and d3 are unknowns. For buses 2, 4, and 5, load buses, V2 , V4 , V5 and d 2 , d4 , d5 are unknowns. The elements of Ybus are computed from (6.4.2). Since buses 1 and 3 are not directly connected to bus 2, Y21 ¼ Y23 ¼ 0 Using (6.4.2), Copyright 2010 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part. Due to electronic rights, some third party content may be suppressed from the eBook and/or eChapter(s). Editorial review has deemed that any suppressed content does not materially affect the overall learning experience. Cengage Learning reserves the right to remove additional content at any time if subsequent rights restrictions require it. (AutoPDF V7 8/12 14:39) Thomson-U (7.375x9.25") Tmath&GillSans J-1711 Glover Rev1:(CKN)27/4/2007 pp. 294–378 25795_06_ch06_p294-378 (p. 328)