PLUMBING GENERAL NOTES NO SERVICES DESCRIPTION WATER CLOSET (PRIVATE) WC1 WATER CLOSET-ADA (PRIVATE) WC2 CW HW 4" 2" 1/2" - 2" 4" WATER CLOSET-ADA (PUBLIC) WC4 V 4" WATER CLOSET (PUBLIC) WC3 REMARKS S/W 1/2" 2" 4" 2" FIXTURE: WHITE, FLOOR MOUNTED, 1.28 GPF SEAT: CLOSED FRONT WITH COVER - 1" FIXTURE: KOHLER WELLWORTH TANK 4498-0 & 4198-0 BOWL SEAT: BEMIS 1250TTA, WITH COVER FIXTURE: WHITE, FLOOR MOUNTED, 1.28 GPF, ADA HEIGHT SEAT: CLOSED FRONT WITH COVER - 1" BASIS OF DESIGN (OR EQUAL) - FIXTURE: KOHLER WELLWORTH TANK 4468-0 & 4189-0 BOWL SEAT: BEMIS 1250TTA, WITH COVER FIXTURE: WALL MOUNTED, 1.6 GPF FLUSH VALVE: CHROME FINISH, ECO-POWERED SENSOR SEAT: OPEN FRONT, NO COVER FIXTURE: SLOAN ST-2059 SEAT: BEMIS 1955-CT FLUSH VALVE: TOTO TET1GNC FIXTURE: WALL MOUNTED - ADA HEIGHT, 1.6 GPF FLUSH VALVE: CHROME FINISH, ECO-POWERED SENSOR SEAT: OPEN FRONT, NO COVER FIXTURE: SLOAN ST-2059 SEAT: BEMIS 1955-CT FLUSH VALVE: TOTO TET1GNC 1. ALL WORK SHALL CONFORM TO ALL APPLICABLE BUILDING CODES AND ALL STATE AND LOCAL AMENDMENTS AS WELL AS THE REQUIREMENTS AND STANDARDS OF BLOOMSBURG UNIVERSITY.. 2. 2" URINAL U2 URINAL-ADA L1 LAVATORY (PRIVATE) 2" 3/4" 2" 1-1/2" LAVATORY-ADA (PRIVATE) L2 2" 3. REFER TO ARCHITECTURAL PLANS FOR GENERAL CONSTRUCTION NOTES. 4. DRAWINGS ARE DIAGRAMMATIC: THE CONTRACTOR SHALL DETERMINE LOCATIONS OF SYSTEMS AND COMPONENTS IN FIELD, OFF OF ARCHTIECTURAL AND STRUCTURAL PLANS. 5. THE PLUMBING CONTRACTOR SHALL DETERMINE EXACT LOCATIONS OF EXISTING UTILITIES IN FIELD, WHETHER OR NOT SHOWN ON THE DRAWINGS. EXERCISE CAUTION AND IDENTIFY LOCATIONS OF UNMARKED UTILITY LINES AS NECESSARY TO PERFORM THIS WORK. 3/4" 2" 1-1/2" - 1/2" 2" 1/2" 1/2" 1/2" 7. FIXTURE: WALL MOUNTED, ADA HEIGHT, 1.0 GPF FLUSH VALVE: CHROME FINISH, ECO-POWERED SENSOR FIXTURE: TOTO UT4455U FLUSH VALVE: TOTO TEU1GNC-12 FIXTURE: COUNTER MOUNTED (UNDERMOUNT) FAUCET: CHROME FINISH, TWO-LEVER, ADA HANDLES MISC: SUPPLIES & STOPS FIXTURE: TOTO LT597 FAUCET: TOTO TL230DD FIXTURE: COUNTER MOUNTED (UNDERMOUNT) FAUCET: CHROME FINISH, TWO-LEVER, ADA HANDLES MISC: SUPPLIES & STOPS WITH INSULATION KIT 9. FIXTURE: TOTO LT597 FAUCET: TOTO TL230DD COLD WATER CW COLD WATER BELOW FLOOR HW HOT WATER S or W SOIL OR WASTE S or W SOIL OR WASTE BELOW FLOOR V VENT COND STORM/CONDUCTOR L3 LAVATORY (PUBLIC) L4 LAVATORY-ADA (PUBLIC) 1-1/2" 1-1/2" LAVATORY-ADA (PUBLIC) L5 2" 1/2" 2" 1-1/2" 1/2" 2" 1/2" 1/2" FIXTURE: INTEGRAL WITH COUNTER TOP FAUCET: CHROME FINISH, ECO-POWERED SENSOR MISC: SUPPLIES & STOPS 1/2" FIXTURE: INTEGRAL WITH COUNTER TOP FAUCET: CHROME FINISH, ECO-POWERED SENSOR MISC: SUPPLIES & STOPS WITH INSULATION KIT FAUCET: TOTO TEL101-D10EM#CP FAUCET: TOTO TEL101-D10EM#CP 1/2" FIXTURE: WALL MOUNTED, ADA HEIGHT, 0.125 GPF FAUCET: CHROME FINISH, ECO-POWERED SENSOR MISC: SUPPLIES & STOPS WITH INSULATION KIT G 1/2" FIXTURE: COUNTER TOP, SINGLE COMPARTMENT, STAINLESS STEEL FAUCET: CHROME FINISH, SINGLE LEVER SUPPLIES & STOPS WITH INSULATION KIT FIXTURE: ELKAY LRAD2521 FAUCET: ELKAY LKE4100 FIXTURE: ELKAY LRAD3322 FAUCET: ELKAY LKD231 S1 SINK (LAUNDRY) KS1 KITCHEN SINK (PRIVATE) 1-1/2" 2" 1/2" 1/2" FIXTURE: COUNTER TOP, DOUBLE COMPARTMENT, STAINLESS STEEL FAUCET: CHROME FINISH, TWO HANDLES WITH SPRAY SUPPLIES & STOPS WITH INSULATION KIT WB1 WASHING MACHINE BOX (RESIDENTIAL) 2" 2" 1/2" 1/2" SUPPLY AND DRAIN BOX: PC SHALL COORDINATE PROPER BOX CONNECTION MATERIAL TYPE 1-1/2" ICE MAKER CONNECTION BOX IM1 - JS1 JANITOR'S SINK EMSH EMERGENCY SHOWER AND EYEWASH SH2 SHOWER-ADA (PRIVATE) 2"FD TUB/SHOWER (PRIVATE) BT1 EWC 1-1/4" - 1/2" - G PRV PRESSURE REDUCING VALVE/ PRESSURE REGULATOR VIV VALVE IN VERTICAL ANY INTERFERENCE BETWEEN TRADES SHALL BE BROUGHT TO THE ATTENTION OF THE GENERAL CONTRACTOR/OWNER’S REPRESENTATIVE, AND SHALL BE RESOLVED PRIOR TO THE INSTALLATION OF THE WORK. CV CHECK VALVE DV HOSE END DRAIN VALVE ALL PIPE SLEEVES IN FLOORS SHALL EXTEND A MINIMUM OF TWO INCHES (2”) ABOVE THE FINISHED FLOOR UNLESS NOTED OTHERWISE. FILL ANNULAR SPACE WITH WATERPROOF, FIRE RETARDANT CAULKING PENETRATIONS. W&T WASTE & TRAP 1-1/4" 2" SINK: FIAT MSB 2424 FAUCET: T&S BRASS B-0665-CR-BSTR 1-1/4" FIXTURE: COMBINATION SHOWER AND EYEWASH UNIT, FLOOR MOUNTED UNIT WITH THERMOSTATIC MIXING VALVE. FIXTURE: BRADLEY S19-310 MIXING VALVE: BRADLEY S-19-2200 1/2" 1/2" - FIXTURE: FIBERGLASS WITH NO TOP VALVE/TRIM: PRESSURE BALANCING FIXTURE: KOHLER / STERLING 72260100 VALVE/TRIM: SYMMONS S-9601-X-P FIXTURE: FIBERGLASS WITH NO TOP VALVE/TRIM: PRESSURE BALANCING FIXTURE: KOHLER / STERLING 62070115 VALVE/TRIM: SYMMONS S-9603-X-P FIXTURE: BI-LEVEL, STAINLESS STEEL WITH BOTTLE FILLER DELIVERING FILTERED WATER 13. ALL PLUMBING EQUIPMENT, PIPING, INSULATION, ETC., INSTALLED IN HVAC PLENUM SPACES SHALL MEET ALL CODE REQUIREMENTS FOR SMOKE AND COMBUSTIBILITY, PER ASTM E-84. 1. PROVIDE WATTS SERIES MMV THERMOSTATIC MIXING VALVES AT ALL PUBLIC SINKS/LAVS THAT RECIEVE HOT WATER. SET TEMP AT MIXING VALVE TO 105° 2. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION AND MOUNTING HEIGHTS OF ALL PLUMBING FIXTURES AND FITTINGS. 3. PC TO COORDINATE COLORS AND FINISHES OF ALL PLUMBING FIXTURES AND FITTINGS WITH ARCHITECT PRIOR TO CONSTRUCTION. PUMP SCHEDULE BOOST (PSI) FIRE PUMP (FP-1) FIRE PUMP ROOM DOMESTIC WATER BOOSTER (DWB-1) 65 CENTRAL PLANT SUMP PIT @ ELEVATOR SUMP (SP-1) SINGLE ELEVATOR ELEVATOR SUMP (SP-2) SUMP PIT @ DOUBLE ELEVATOR FLOW (GPM) 1000 TDH (FEET) 75 HP 50 125 81 5 EA. - 50 20 1/2 - 100 20 1 REMARKS CONTROLS 60 (SEE REMARKS) HORIZONTAL SPLIT CASE, REDUCED VOLTAGE WYE-DELTA STARTER, 480 VOLT / 3 PHASE COORDINATE VOLTAGE W/ ELECTRICAL. CONTROLLER SHALL BE RATED FOR 65k AIC PATTERSON MODEL: 6x5x17 SCC JOCKEY PUMP (JP-1) : 1 HP HB HOSE BIBB 19. ALL PIPE HANGERS ON INSULATED PIPING SHALL BE PROVIDED WITH HANGER SHIELDS. WH'A' WALL HYDRANT & TYPE 20. ALL VALVES, CLEANOUTS AND COMPONENTS REQUIRING ACCESS BEHIND WALLS OR INACCESSIBLE CEILING SHALL BE PROVIDED WITH ACCESS PANELS. COORDINATE WITH ARCHITECT FOR REQUIRED TYPE, LOCATION, AND FINISH. 21. ALL P-TRAPS AND DOMESTIC WALTER PIPING INSTALLED IN SPACES SUBJECT TO FREEZING SHALL BE INSULATED AND HEAT TRACED. 22. TRAP GUARDS ARE TO BE INSTALLED ON ALL FLOOR DRAINS AND HUB DRAINS WHICH DO NOT RECEIVE A CONTINUOUS DISCHARGE. FLOOR DRAIN & TYPE RD-A ROOF DRAIN & TYPE TD'A' TRENCH DRAIN & TYPE PROVIDE VENTS AT HIGH POINTS IN PIPING SYSTEMS AND DRAIN VALVES AT LOW POINTS. DCVA DOUBLE CHECK VALVE ASSEMBLY 24. PROVIDE GAUGE FITTINGS AND THERMOMETER WELLS AT HOT WATER SUPPLY AND RETURN BRANCHES AND AT PUMP INLETS AND OUTLETS. RPBFP REDUCED PRESSURE BACKFLOW PREVENTER 25. SANITARY VENTS THROUGH THE ROOF MUST TERMINATE A MINIMUM OF 10 FEET AWAY FROM OUTSIDE AIR INTAKES, WHICH PROVIDE VENTILATION OR MAKE-UP AIR TO THE BUILDING. PG PRESSURE GAUGE WITH ISOLATION VALVE T&P TEMPERATURE & PRESSURE RELIEF VALVE 26. COORDINATE PROVISION FOR PROTECTING PIPING BENEATH HANDICAP LAVATORIES REQUIRED AND IDENTIFIED WITH TOILET ACCESSORIES. 27. PLUMBING FIXTURES FOR “ADA” COMPLIANCE SHALL BE INSTALLED WITH THE HORIZONTAL AND VERTICAL CLEARANCES OUTLINED IN THE “AMERICANS WITH DISABILITIES ACT”. REFER TO ARCHITECTURAL PLANS FOR ELEVATIONS OF TOILET ROOMS. 30. MANUFACTURER’S MODEL NUMBERS ARE SPECIFIED SOLELY TO ESTABLISH STANDARD OF QUALITY FOR PERFORMANCE AND MATERIALS. 31. INSTALLATIONS SHALL ADHERE TO MANUFACTURER’S RECOMMENDATIONS. 32. THE HOT AND COLD WATER RISERS SERVING THE RESIDENTIAL UNITS SHALL BE RUN VERTICALLY, EXPOSED WITHIN THE MECHANICAL CLOSETS. HOT AND COLD WATER SHUT-OFF VALVES SHALL BE PROVIDED FOR EACH RESIDENTIAL UNIT AND SHALL BE INSTALLED AS CLOSE TO THE FRONT OF THE CLOSET AS POSSIBLE AND AT AN ELEVATION DEEMED TO BE FULLY ACCESSIBLE. FULLY COORDINATE THE EXACT LOCATION OF SHUT-OFF VALVES WITH THE MECHANICAL CONTRACTOR PRIOR TO INSTALLATION. RISERS MAY OFFSET FROM FLOOR TO FLOOR. 33. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF ALL ROOF DRAINS, DECK DRAINS AND PLANTER DRAINS. 34. PLUMBING CONTRACTOR SHALL INSTALL A 3" HUB DRAIN IN EACH OF THE LOWEST RESIDENTIAL CLOSETS FOR CONDENSATE REMOVAL. REFER TO DETAIL 3/P-502. 37. PLUMBING CONTRACTOR SHALL COORDINATE THE EXACT LOCATION OF THE WATER METER REMOTE READERS WITH THE ARCHITECT, OWNER AND ELECTRICAL CONTRACTOR PRIOR TO CONSTRUCTION. 38. CLEANOUTS SHALL BE INSTALLED AT THE BASE OF ALL WASTE OR SOIL STACKS AS PER IPC 708.3.4 CENTRAL PLANT - 20 16 1/2 AQUASTAT TO BE FURNISHED AND INSTALLED WITH THERMOSTATIC MIXING VALVE STATION TMV-2 HOT WATER WATER CIRCULATING (CP-3) CENTRAL PLANT HOT WATER WATER CIRCULATING (CP-4) CENTRAL PLANT - 20 10 1/12 WATER HEATER CONTROLLER FURNISHED WITH WATER HEATER WH-1 B&G MODEL PL30-B HOT WATER WATER CIRCULATING (CP-5) CENTRAL PLANT - 20 10 1/12 WATER HEATER CONTROLLER FURNISHED WITH WATER HEATER WH-1 B&G MODEL PL30-B HOT WATER WATER CIRCULATING (CP-6) CENTRAL PLANT HOT WATER WATER CIRCULATING (CP-7) NEATLY INSTALL WHITE MILDEW-RESISTENT SILICONE SEALANT BEAD AROUND THE PERIPHERY OF ALL PLUMBING FIXTURES IN CONTACT WITH WALLS AND/OR FLOORS. PVC PIPING SHALL NOT BE INSTALLED IN RETURN AIR PLENUMS. HOT WATER WATER CIRCULATING (CP-2) TO BE FURNISHED AND INSTALLED WITH THERMOSTATIC MIXING VALVE STATION TMV-3 REFER TO TMV-3 ON DRAIN AND DEVICE SCHEDULE CENTRAL PLANT - 20 10 WATER HEATER CONTROLLER 1/12 FURNISHED WITH WATER HEATER WH-1 B&G MODEL PL30-B B&G MODEL PL30-B TEMPLATE VERSION: 2.6.8.20141012 12/14/2015 4:06:40 PM PLOT DATE: DESIGNATION LOCATION STORAGE (GAL) WH-1 CENTRAL PLANT N/A WH-2 CENTRAL PLANT N/A RECOVERY RATE (90 DEG. RISE) INSTANT INSTANT TEMP SETTING (°F) 160 160 ELECTRICAL REQUIREMENTS KW - - VOLTS PHASE REMARKS SPECIFICATION 120 1 STEAM TO WATER HEAT EXCHANGER PATTERSON -KELLEY PK10S, OMEGA TYPE-J THERMOCOUPLE, LOVE COMPACT CONTROLLER AND 2-1/2" WARREN MODEL AMURACT ELECTRIC VALVE 120 1 STEAM TO WATER HEAT EXCHANGER PATTERSON -KELLEY PK10S, OMEGA TYPE-J THERMOCOUPLE, LOVE COMPACT CONTROLLER AND 2-1/2" WARREN MODEL AMURACT ELECTRIC VALVE WH-3 CENTRAL PLANT N/A INSTANT 160 - 120 1 STEAM TO WATER HEAT EXCHANGER PATTERSON -KELLEY PK10S, OMEGA TYPE-J THERMOCOUPLE, LOVE COMPACT CONTROLLER AND 2-1/2" WARREN MODEL AMURACT ELECTRIC VALVE WH-4 CENTRAL PLANT N/A INSTANT 160 - 120 1 STEAM TO WATER HEAT EXCHANGER PATTERSON -KELLEY PK10S, OMEGA TYPE-J THERMOCOUPLE, LOVE COMPACT CONTROLLER AND 2-1/2" WARREN MODEL AMURACT ELECTRIC VALVE GAS COCK BALANCE VALVE THERMOMETER SF VTR INV TYP NTS AFF AFG NFRH NFWH WC LAV BT SK NPW FFE GC PC FPC FDV EC MC FS SS BFF BFG AAV B/G SQUARE FEET VENT THRU ROOF INVERT TYPICAL NOT TO SCALE ABOVE FINISHED FLOOR ABOVE FINISHED GRADE NON-FREEZE ROOF HYDRANT NON-FREEZE WALL HYDRANT WATER CLOSET LAVATORY BATHTUB SINK NON-POTABLE WATER FINISHED FLOOR ELEVATION GENERAL CONTRACTOR PLUMBING CONTRACTOR FIRE PROTECTION CONTRACTOR FIRE DEPARTMENT VALVE ELECTRICAL CONTRACTOR MECHANICAL / HVAC CONTRACTOR FLOW SWITCH SUPERVISORY SWITCH ABOVE FINISHED FLOOR ABOVE FINISHED GRADE AIR ADMITTANCE VALVE BELOW GRADE KEY PLAN A DRAIN, DEVICES & MISC. FITTING SCHEDULE DESCRIPTION REVISION NO. DESCRIPTION SPECIFICATION FD-A TOILET ROOMS & ALL PUBLIC ACCESS AREAS JAY R. SMITH: 2005-B-U FD-B CENTRAL PLANT AND MECHANICAL ROOMS JAY R. SMITH: 2110-B FD-C CENTRAL PLANT (FOR COOLING TOWER) JAY R. SMITH: 3980 RD-A ROOF DRAIN (PRIMARY) JAY R. SMITH: 1010-C-U-CID RD-B ROOF DRAIN (EMERGENCY) JAY R. SMITH: 1070-C-U-CID DSN DOWNSPOUT NOZZLE JAY R. SMITH: 1770-BS (INSTALL AS HIGH AS POSSIBLE UNLESS NOTED OTHERWISE) DD-A DECK/PLANTER DRAIN (PRIMARY) JAY R. SMITH: 1010-C-U-CID (W/ STAINLESS STEEL MESH OVER DOME) DD-B DECK/PLANTER DRAIN (SECONDARY) JAY R. SMITH: 1010-C-U-CID (W/ STAINLESS STEEL MESH OVER DOME) NFWH-1 RECESSED WALL HYDRANT WITH VACUUM BREAKER, ON EXTERIOR WALL (18" A.F.F.) JAY R. SMITH: 5519 NFWH-2 RECESSED, DUAL TEMP, WALL HYDRANT WITH VACUUM BREAKER, ON EXTERIOR WALL @ LOADING DOCK (18" A.F.F.) JAY R. SMITH: 5560QT SHOCK ABSORBER JAY R. SMITH: 5000 HB-1 INTERIOR HOSE BIBB (IN MECHANICAL AREAS) WITH VACUUM BREAKER. PROVIDE INTERNAL WALL PIPE BRACING TO PREVENT MOVEMENT (12" A.F.F.) WOODFORD: 26 WITH CP INLET HB-2 INTERIOR HOSE BIBB (IN PUBLIC ACCESS AREAS) WITH VACUUM BREAKER IN RECESSED LOCKING BOX. PROVIDE INTERNAL WALL PIPE BRACING TO PREVENT MOVEMENT (12" A.F.F.) WOODFORD: MB224 NFRH ROOF HYDRANT WITH BACKFLOW PREVENTOR. PROVIDE INTERNAL PIPE BRACING TO PREVENT MOVEMENT. WOODFORD: SRH-MS TMV-1 THERMOSTATIC MIXING VALVE STATION (HIGH ZONE) BRADLEY: NRS-20 (53 GPM FLOW) OR EQUAL BY POWERS TMV-2 THERMOSTATIC MIXING VALVE STATION (LOW ZONE) BRADLEY: NRS-20 (50 GPM FLOW) OR EQUAL BY POWERS TMV-3 THERMOSTATIC MIXING VALVE STATION (LOW ZONE) BRADLEY: NRS-13 (38 GPM FLOW) OR EQUAL BY POWERS BWV-1 BACKWATER VALVE ROYAL BUILDING PRODUCTS 1075P FLOOR SINK JAY R. SMITH: 3101-NB (COORDINATE EACH OF THE GRATE OPENINGS WITH INDIRECT WASTE PIPING PRIOR TO CONSTRUCTION) SA WATER HEATER SCHEDULE SOLENOID VALVE B NO. FURNISHED WITH WATER HEATER WH-1 VACUUM RELIEF VALVE ALL WATER CLOSETS OR URINALS SHALL BE CENTERED BETWEEN RESPECTIVE TOILET PARTITIONS EXCEPT AS SPECIFICALLY NOTED OTHERWISE: THE CONTRACTOR SHALL COORDINATE ROUGHING IN WITH APPROVED TOILET PARTITION SHOP DRAWINGS. 36. AQUASTAT WATER HEATER CONTROLLER RISER DESIGNATION X FD'A' REFER TO TMV-2 ON DRAIN AND DEVICE SCHEDULE 1/2 1/12 WALL CLEANOUT MECHANICSBURG, PA 17050 PROVIDE MANUFACTURED EXPANSION DEVICE OR FABRICATED EXPANSION LOOP ON ALL PIPING SYSTEMS CROSSING BUILDING EXPANSION JOINTS. ALL ABOVE AND BELOW GROUND SANITARY / WASTE PIPING, WITHIN THE FOOD SERVICE AREAS AND SUBJECT TO WASTE WATER TEMPERATURES GREATER THAN 130 DEGREES, SHALL BE CAST IRON. 18 10 WCO 100 STERLING PARKWAY, SUITE 108 DRESSER COUPLING DC 35. 20 20 GRADE CLEANOUT DC PROVIDE CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES AS NECESSARY TO PREVENT STRESS ON PIPING. REFER TO TMV-1 ON DRAIN AND DEVICE SCHEDULE - - GCO AUTOMATIC TRAP PRIMER 17. MEYERS ME100S (WITH OIL MINDER) (2" DISCHARGE PIPING AS SHOWN ON PLANS) AQUASTAT STRUCTURAL ENGINEER TP TP SUBMERSIBLE EFFLUENT PUMP WITH OIL SMART PANEL 3450 RPM 208 VOLT 1PH REFER TO DETAIL 1/6 FLUSH FLOOR CLEANOUT WATER HAMMER ARRESTOR(SHOCK ABSORBER) & TYPE CONTROL PANEL W/ FLOAT SWITCH CENTRAL PLANT 10 FCO STAE COLLEGE, PA 16801 SA'A' COORDINATE ANY & ALL POST TENSIONED SLAB PENETRATIONS WITH STRUCTURAL ENGINEER. 29. CMT LABORATORIES, INC. UNION 16. MEYERS SE50 (WITH OIL MINDER) (1-1/2" DISCHARGE PIPING AS SHOWN ON PLANS) TO BE FURNISHED AND INSTALLED WITH THERMOSTATIC MIXING VALVE STATION TMV-1 2 CLEANOUT PLUG WATERTIGHT SLEEVE SPECIFICATION HOT WATER WATER CIRCULATING (CP-1) - CO WTS SUBMERSIBLE EFFLUENT PUMP WITH OIL SMART PANEL 3450 RPM 208 VOLT 1PH REFER TO DETAIL CONTROL PANEL W/ FLOAT SWITCH OPEN END OR HUE DRAIN W/TRAP ARROW INDICATES DIRECTION OF SLOPE DOWN THE PLUMBING CONTRACTOR SHALL OBTAIN APPROVAL FROM THE STRUCTURAL ENGINEER PRIOR TO INSTALLING POWDER DRIVEN FASTENERS. HYFAB MODEL: MVP-850-460 (OR EQUAL BY TIGERFLOW) SHUT-OFF @ 5 PSI LITITZ, PA 17543 ARROW INDICATES DIRECTION OF FLOW THE PLUMBING CONTRACTOR SHALL PROVIDE SHUTOFF VALVES ON ALL BRANCH PIPING AND ON ALL SUPPLIES TO INDIVIDUAL FIXTURES AND EQUIPMENT. PROVIDE FULL PORT BALL VALVES ON ALL WATER MAIN BRANCHES IN CORRIDORS AND WHERE INDICATED ON DRAWINGS. DUPLEX, VARIABLE SPEED, 480 VOLT / 3 PHASE COORDINATE VOLTAGE W/ ELECTRICAL LOW WATER PRESSURE 33 SOUTH BROAD STREET WBCM 15. 28. LOCATION DERCK & EDSON ASSOCIATES FIXTURE: ELKAY LZWS-LRPBM28K NOTES: DESIGNATION SITE/CIVIL ENGINEER SLEEVE 23. 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 SL 18. FIXTURE: KOHLER / STERLING 71370110 VALVE/TRIM: SYMMONS S-9602-X-P FIXTURE: FIBERGLASS WITH NO TOP VALVE/TRIM: PRESSURE BALANCING ALL PIPING ABOVE GRADE SHALL BE PROPERLY SUPPORTED BY THE BUILDING STRUCTURE AND SHALL NOT REST ON CEILING STRUCTURE OR COMPONENTS. AHA CONSULTING ENGINEERS 2701 CAROLEAN INDUSTRIAL DRIVE All PIPING PENETRATING CEILINGS AND WALLS SHALL BE INSTALLED WITH ESCUTCHEONS AT THE PENETRATION. ALL PIPING PENETRATING EXTERIOR WALLS AND ROOFS SHALL BE FLASHED IN AN APPROVED MANNER AND SHALL BE SEALED WEATHERTIGHT. PIPING PENETRATING FIRE RATED ASSEMBLIES SHALL BE PROVIDED WITH FIRE RATED SEALS AS REQUIRED BY CODE AUTHORITY HAVING JURISDICTION. 12. MEP ENGINEER GEOTECHNICAL ENGINEER FIXTURE: GUY GRAY FRIB12ABSHA FIXTURE: FLOOR MOUNTED/ STAINLESS STEEL WALL GUARDS FAUCET: WALL MOUNTED 1/2" 1/2" FIXTURE: GUY GRAY FR12S 1600 NORTH SECOND STREET NATURAL GAS SHUT-OFF (GATE ) VALVE TOPS OF ALL FLOOR DRAINS SHALL BE SET LEVEL AND FLUSH WITH FINISHED FLOOR. 14. 1/2" 1/2" 1/2" - SUPPLY BOX: PC SHALL COORDINATE PROPER BOX CONNECTION MATERIAL TYPE - 1/2" 2" 2" ELECTRIC WATER COOLER (BI-LEVEL) 1/2" 2" 1-1/4" 2"FD 1/2" - 3" SHOWER (PRIVATE) SH1 2" ASSOCIATE ARCHITECT HARRISBURG, PA 17102-2499 GCO FIXTURE: AMERICAN STANDARD 0436.008 FAUCET: TOTO TEL101-D10EM#CP ATLANTA, GA 30326 SOV 11. 3445 PEACHTREE ROAD, NE, SUITE 675 MURRAY AND ASSOCIATES ARCHITECTS OED 10. HKS, INC. TWO LIVE OAK CENTER S THE PLUMBING CONTRACTOR SHALL PREPARE “COORDINATION” DRAWINGS THAT COORDINATE THE PLUMBING WORK WITH ALL OTHER TRADES INCLUDING, BUT NOT LIMITED TO, ELECTRICAL, HVAC, PROCESS PIPING, SPRINKLER, STRUCTURAL AND GENERAL ARCHTIECTURE. 8. CW ARCHITECT THE PLUMBING CONTRACTOR SHALL PREPARE “SLEEVE AND INSERT” COORDINATION PLANS (LOCATING ALL ROOF, FLOOR AND WALL PENETRATIONS) AND SUBMIT TO ARCHITECT FOR REVIEW. EACH PENETRATION SHALL BE LCOATED WITH A MINIMUM OF (2) DIMENSIONS IN (2) DIRECTIONS. FIXTURE: TOTO UT445U FLUSH VALVE: TOTO TEU1GNC-12 FIXTURE: WALL MOUNTED, 1.0 GPF FLUSH VALVE: CHROME FINISH, ECO-POWERED SENSOR - CW GENERAL NOTES, SYMBOLS LIST AND DETAILS ARE APPLICABLE TO ALL PLUMBING DRAWINGS. 6. U1 PLUMBING LEGEND BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE PLUMBING FIXTURE SCHEDULE FS-1 AD AREA DRAIN (LOADING DOCK) DATE AHA PROJECT NUMBER JAY R. SMITH: 2230-G G1215-004.00 DATE 03 DECEMBER 2015 ISSUE CONSTRUCTION DOCUMENTS SHEET TITLE REVISED 15 DECEMBER 2015 PLUMBING LEGEND, NOTES AND SCHEDULES SHEET NO. P-001 9 11 19 18 17.4 17 1514.8 16 13 14.1 14 10 12 ARCHITECT HKS, INC. x.2 x.4.1 TWO LIVE OAK CENTER x.6 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 8"B/G ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 UTILITY TUNNEL 6"RL DN (3147 sf) MEP ENGINEER AHA CONSULTING ENGINEERS 015 1801 OLD ALABAMA RD, SUITE 125 10" RL ROSWELL, GA 30076 10" RL 8"B/G (MINIMUM OF 3' OF COVER OVER PIPE) 1 P-408 DERCK & EDSON ASSOCIATES T.R LOCKER RM ICE/SODA 028.1 028 027 NFWH-1 6"CW DN 3"W UP CUST GCO 025 4"RL DN (1720 sf) 010 FAMILY TOILET 6"SAN B/G I.E. = 6.36' +/SEE CIVIL DWGS. FOR CONTINUATION 1 P-407 CENTRAL PLANT STO. 018 10" RL ELEC. SERVERY #2 011 MECHANICSBURG, PA 17050 FIRE PUMP CUST 10" RL (3147 sf) RL 015.3 015.4 023 6" RL (3956 sf) 100 STERLING PARKWAY, SUITE 108 GENERATOR RM 026 4" RL FIRE DEPARTMENT CONNECTION (FDC) WBCM FOOD SERVICE PREP CIRC 014 STRUCTURAL ENGINEER SERVERY #2 4" RL 6"WS DN STAE COLLEGE, PA 16801 015.1 012 3"W DN Z 024 2701 CAROLEAN INDUSTRIAL DRIVE y.6.5 y.6 OFFICE 029 PUBLIC TLT RM M 4"RL UP (2236 sf) CMT LABORATORIES, INC. 015.2 RL 013 TRANSFORMER RM BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE 4"RL UP (2236 sf) 3/4" CW LITITZ, PA 17543 6"RL UP (3147 sf) IDF PUBLIC TLT RM F FCO 33 SOUTH BROAD STREET GEOTECHNICAL ENGINEER 4"RL UP (1720 sf) 3/4"CW DN W/ VALVE IN RISE SITE/CIVIL ENGINEER 015.5 022 SP 6"RL DN6" RL (5391 sf) 1 DINING HALL VESTIBULE 008 Y.5 4"AD 10" RL (14,277 sf) (18,233 sf) 10" RL 6"ERL DN 4" RL 009 1 P-409 8" RL (11,130 sf) 20.8 FCO 3" GW RL STAIR 04 21.5 S-004 4" RL 22 L ER V.7 8" RL (11,130 sf) V M.2 W4 (9300 sf) 8" RL M RL 4" RL RL 019 2"V UP 4"S UP 8"RL DN (8300 sf) L RL 6"RL UP TO DD-A (4150 sf) 4" S FCO 6"ERL UP TO DD-B RL 4" S DCO 4"UP 2" CW 2" HW 1 1/2" HWR 1 1/2" HWR 2" HW 2" CW 4"RL UP (500 sf) CATCH BASIN (BY GC) ER L RL 4" RL 6" ERL 4" RL T.5 4" ERL 4"ERL UP TO DD-B 4"RL UP TO DD-A 4" ERL 4" S 4" ERL ER L T 4" S S 6" S 2"W UP 4" S 6" S R GCO RL 4"RL UP TO DD-A ER L U.3 8"B/G (MINIMUM OF 3' OF COVER OVER PIPE) U 4" RL CONNECT 6"RL TO CATCH BASIN @ I.E.= 4' BELOW TOP OF BASIN 4" ERL 4"ERL UP TO DD-B THIS HATCHED AREA TO BE COVERED BY DRY SPRINKLERS GCO 3" S DROP CLEANOUT 4"S UP RL 3" S 4"S UP 3"W UP 4"LAUNDRY WASTE JK (1830 sf) 4" RL CONNECT 8"RL TO CATCH BASIN @ I.E.= -4' BELOW TOP OF BASIN 4" RL (500 sf) RL 4"RL UP TO DD-A I.6 2" V 6" S 4"S DN 6" RL (1000 sf) (1830 sf) 4" RL 4" RL MATCHLINE: 1/ P-102 SP 6" RL (4150 sf) 4"RL UP TO DD-A 4"ERL UP TO DD-B 2 1/2" G (BELOW SLAB) 8" RL (8585 sf) 4"UP 4"AD 2 SERVERY #1 4"ERL UP TO DD-B 4"RL UP TO DD-A 3" GW GREASE TRAP: JAY R. SMITH 8235, COVER FLUSH WITH LOADING DOCK 017 RL L ER 24 RL 6"RL UP TO DD-A (4150 sf) 6" S 1 1/2" HWR 1 1/2" HWR T.R. 6" RL (4150 sf) 6"ERL UP TO DD-B (4150 sf) DROP CLEANOUT W/ HEAVY DUTY COVER 4" WS UP 4"S DN RL 23.6 4" ERL 2" PD 6"RL UP (5391 sf) 7 P-406 6" ERL 23 V.8 020 RL 6" ERL 3" CW 2 1/2" HW 1 1/2" HWR 1 1/2" HWR 2 1/2" HW 3" CW 016 ER L W 4"RL UP TO DD-A 4"ERL UP TO DD-B 6" S 4"RL DN BELOW BEAM 4" S 2 1/2" CW 2" HW 1 1/2" HWR 1 1/2" HWR 2" HW 2 1/2" CW RECEIVING/ INVENTORY STORAGE 007 RL GCO L ER ER L 6" ERL 4" ERL L ER 10"RW B/G (18,233 sf) I.E. =633' +/SEE CIVIL DWGS. FOR CONTINUATION RL RL 6"DSN CIRC 4" S POT WASH RL Y X.5 X.3 X 21 6" S 4" RL (500 sf) 4"S UP 6" S Q CONNECT 8"RL TO CATCH BASIN @ I.E.= 4' BELOW TOP OF BASIN CATCH BASIN (BY GC) P ELEC 007.1 O N CONNECT 6"RL TO CATCH BASIN @ I.E.= -4' BELOW TOP OF BASIN 2 1/2" G (BELOW SLAB) KEY PLAN RL A 1 P-101 PLUMBING PLAN - GROUND FLOOR - AREA A SCALE: 1/8" = 1'-0" B REVISION NO. DESCRIPTION DATE AHA PROJECT NUMBER 12/14/2015 4:06:59 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 G1215-004.00 DATE 03 DECEMBER 2015 ISSUE CONSTRUCTION DOCUMENTS SHEET TITLE REVISED 15 DECEMBER 2015 PLUMBING PLAN GROUND FLOOR AREA A SHEET NO. P-101 ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543 18 17 L 16 M 15 14 M.2 13 11 10 9 GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801 STRUCTURAL ENGINEER JK 4" RL RL 3/4" NON-POTABLE CW DN 4" RL (500 sf) 4"S UP 4" S 3/4" CW 3/4"NPW 4"LAUNDRY WASTE 3/4"CW DN ELEC 5'0 (TY " P) 4" RL RL 3" S S1 4"S UP S6 F.3 6" DSN 6" RL 6" ERL 4"RL UP (500 sf) SALES FLOOR 002 VESTIBULE 001 4"RL UP (2480 sf) 3/4" CW 6"RL UP (2900 sf) UP E D DSN RL S7 NEW GAS METER AND ALL PIPING UP TO GAS METER BY LOCAL GAS COMPANY. NEW METER SHALL DELIVER 5500 CFH @ 2 PSI. GCO 031 4"RL DN (1830 sf) GCO 6" S RL WATER METERS: CARLON 6251JLRSG ATM 3/4" NON-POTABLE CW B/G FOR WATER FEATURE MAKE-UP FCO 4" S 030 RL 8" RL (11,170 sf) NFWH-1 8" RL 4"RL UP 6" ERL MATCHLINE: 1/ P-101 6" RL (2900 sf) 1-1/2" CW & 3/4"HW CAPPED FOR FUTURE 2 1/2" G (BELOW SLAB) CONNECT 6"RL TO CATCH BASIN @ I.E.= -4' BELOW TOP OF BASIN P O N 4"UP TO ERD (3490 sf) 2 1/2" CW 2" HW 1 1/2" HWR 1 1/2" HWR 2" HW 2 1/2" CW RL NFWH-1 F ELEC EXPANSION LOOP MINIMUM TOTAL LENGTH = 13.8' ER L 4"RL UP (1830 sf) CATCH BASIN (BY GC) 4"UP TO RD (3490 sf) 007.1 ER L MECHANICSBURG, PA 17050 CONNECT 8"RL TO CATCH BASIN @ I.E.= 4' BELOW TOP OF BASIN 007 4" ERL I G RECEIVING/ INVENTORY STORAGE RL 4"ERL UP TO DD-B 4"RL UP TO DD-A 4" ERL 4" S 4" ERL (1830 sf) 4" RL 2 1/2" CW 2" HW 1 1/2" HWR 1 1/2" HWR 2" HW 2 1/2" CW 4"RL DN BELOW BEAM 4" S ER L 4"RL UP TO DD-A ER L I.6 RL RL ER L RL 4" RL 6" ERL 100 STERLING PARKWAY, SUITE 108 Q 4"S UP 4"ERL UP TO DD-B H.2 H WBCM 4"LAUNDRY WASTE OFFICE 6" RL (3490 sf) 005 OFFICE RL 6"RL DN (2900 sf) 6" RL 006 4"S UP 4" S 4"S UP 4"S UP 4" S 8"B/G (MINIMUM OF 3' OF COVER OVER PIPE) 3/4"NPW 4" S RL RL 4"S UP 4" RL 4" S S1 C.2 4" S 8" RL 4" S OFFICE 4" RL (1800 sf) L R 4"RL UP (1800 sf) 6" RL (7770 sf) 6" RL (4280 sf) W5 RL 4"S UP RL 8" RL 6" RL 3/4"NPW 004 DRY SPRINKLER VALVE 6" S 3/4"NPW 6" S 4"S UP 2"W UP 4"S DN 4" S 033 4" S 4" S 4" S 4"S UP B 4"S UP/DN 6" S 4" S 4"S UP B.5 4" S 4"S UP MECH RM 4"S UP 032 6"S DN 6"RL UP (3400 sf) 8"RL DN (11,170 sf) C STORAGE 4"S UP 4"SAN DROP INTO TOP OF 6"SAN B/G 4"S UP 3'W & 2"V UP TO AAV A.5 4"S UP A.3 3"FD-B W/ TRAP GUARD 3/4"CW DN A NFWH-1 3/4"CW DN TO RPZ & PRV (SET TO 45 PSI) AT 48"AFF,OFFSET NON-POTABLE WATER UP TO ABOVE CEILING 8 7 BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE MATCHLINE: 1/ P-101 6 THIS HATCHED AREA TO BE COVERED BY DRY SPRINKLERS 5.3 5 6"SAN B/G I.E. = 631.5' +/SEE CIVIL DWGS. FOR CONTINUATION 4 8"DUCTILE IRON COMBINED FIRE & DOMESTIC WATER SERVICE B/G, SEE CIVIL DWGS. FOR CONTINUATION 2 1 KEY PLAN 1 P-102 PLUMBING PLAN - GROUND FLOOR - AREA B A SCALE: 1/8" = 1'-0" B REVISION NO. DESCRIPTION DATE AHA PROJECT NUMBER 12/14/2015 4:07:14 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 G1215-004.00 DATE 03 DECEMBER 2015 ISSUE CONSTRUCTION DOCUMENTS SHEET TITLE REVISED 15 DECEMBER 2015 PLUMBING PLAN GROUND FLOOR AREA B SHEET NO. P-102 9 11 19 18 17.4 17 1514.8 16 1312.8 14.1 14 10 12 ARCHITECT HKS, INC. x.1 x.2 x.4 x.4.1 x.5 x.6 x.7 x.8 TWO LIVE OAK CENTER x.9x.10 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 MEP ENGINEER 3"FD-B W/ TRAP GUARD AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 SITE/CIVIL ENGINEER 6"RL DN (3147 sf) DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543 4"S UP 4"S DN MECH GEOTECHNICAL ENGINEER 101 CMT LABORATORIES, INC. 4" S OFFICE 6" RL 4"RL UP & DN (1720 sf) 4"UP TO ERD (1673 sf) STAIR 01 S-101 1 1/2" HW 103 1 MAIL VEST. 6"RL UP (3147 sf) 1 1/2" CW PUBLIC TLT RM -F 4"S UP 102 4" RL 4" S Z 2" CW - 1 1/4" HW 4" S 4"S UP STAIR 3/4" HW Y.5 4"S UP 1 1/4" CW 1" HW Y X.5 X.3 X LOUNGE S-104 3/4" CW 21 4"DD-B 4" S EXPANSION LOOP MINIMUM TOTAL LENGTH = 13.8' 2" HW 4"S UP 2" CW 107 TLT 112 4"S DN 3/4"CW DN M.2 104 4" WS ELEV. IDF 6"DD-B (4,150 sf) STO. - 107.1 ? 24 U 2" HW - W4 NFWH-1 2" CW MECH U.3 OFFICE 4 113 P-406 ? M 23.6 1 1/4" CW 1" HW 2"V DN T.5 2" V S1 4"DD-B V 6"RL DN (3194 sf) STAIR 02 S-102 RECP. 23 V.7 STANDPIPE "B" W/ 2-1/2"FDV SEE DETAIL 1/P-501 3/4" CW 6"DD-A (4,150 sf) V.8 4"RL UP (3718 sf) 4" WS 22 W 6" RL 4"S UP 4"S UP 21.5 4"S UP 6" RL 4"UP TO RD (3194 sf) 4" S 4"S UP 20.8 6"RL DN (5391 sf) 3"V DN 106 4"DD-A 100 4" S 4"V DN & VTR 4" S 04 COMMONS 4"S DN 2" HW 1 1/2" CW 3/4" CW STANDPIPE "A" W/ 2-1/2"FDV SEE DETAIL 1/P-501 4" S 4"UP TO ERD (3194 sf) 110.1 1 1/2" HW 4"S UP ELEV. 6" ERL MAIL LOBBY 3" V 3"V UP 4" S W1 4"RL UP (2236 sf) 4"S UP 108 1 1/2" CW 4"DD-B 4"RL UP & DN (500 sf) 4"DD-A 6"DD-A (4,150 sf) 4"DD-A 2" CW 2" HW OFFICE T 114 JS1 115 1/2"H & CW DN 1 1/4" CW 1" HW 3"W & 2"V 117 KS1 F 6"DD-B (4,150 sf) W2 IM1 MATCHLINE: 1/ P-104 4"S DN JC TRPL SUITE L JK 3/4"CW UP TO NFRH 110.2 RL 1 1/2" HW 100 STERLING PARKWAY, SUITE 108 NFWH-1 MAIL RECEIVING CONFERENCE RM 105 WBCM 3/4" CW ERL 4"S UP 4" S 2"V DN 4"S UP W8 STRUCTURAL ENGINEER 6"DSN 4" S 4" RL 3"FD-B W/ TP 4" S 1 1/2" CW INTEGRATIVE LEARNING STAE COLLEGE, PA 16801 MECHANICSBURG, PA 17050 4"DSN 4" S 1 1/2" HW 4" WS 111 L ER 4"S DN S5 110.3 3/4" CW 4"S DN 3" S MECH 4"UP TO RD (1673 sf) 110 4"S UP WKSTATIONS RL 4"RL DN (2236 sf) 110.4 PUBLIC TLT RM -M 2701 CAROLEAN INDUSTRIAL DRIVE y.6.5 y.6 2"VTR BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE 2 P-408 3/4" CW 3/4" HW 2" V 4" S 4"S UP 2"V UP S R STAFF BK RM 4"DD-A S1 CORRIDOR C-101 4"DD-B 4"DD-A 116 Q 2"W & V, 3/4"CW & 1/2"HW , DN, EXTEND 1/2"CW TO IM1, 1/2"H & CW TO KS1 S1 I.6 4"DD-B 4"DD-A QUAD SUITE B 122 4"DD-B P TRPL SUITE (MIR) O N 118 KEY PLAN F MATCHLINE: 1/ P-104 I A 1 P-103 PLUMBING PLAN - 1ST FLOOR - AREA A SCALE: 1/8" = 1'-0" B REVISION NO. DESCRIPTION KEYED NOTES 1 BASE OF STANDPIPE VALVE ASSEMBLY ABOVE CEILING. REFER TO DETAIL 10/P-501. DATE PLUMBING UNIT PLAN LEGEND A STAFF APARTMENT - REFER TO....... 3/P-401 B DOUBLE SUITE - REFER TO .... 3/P-403 C GRAD SUITE - REFER TO ..... 6/P-401 D RA SUITE (ZONE B) - REFER TO ..... 3/P-402 E RA SUITE (ZONE A) - REFER TO ...... 6/P-402 12/14/2015 4:07:32 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 AHA PROJECT NUMBER F TRIPLE SUITE - REFER TO........ 6/P-403 G1215-004.00 DATE G QUAD SUITE - REFER TO........ 3/P-404 03 DECEMBER 2015 ISSUE H QUAD SUITE A - REFER TO........ 6/P-404 I QUAD SUITE B - REFER TO........ 3/P-405 J QUAD SUITE C - REFER TO........ 6/P-405 K QUAD SUITE D - REFER TO........ 3/P-406 REVISED 15 DECEMBER 2015 CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING PLAN 1ST FLOOR - AREA A SHEET NO. P-103 ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543 18 17 L 16 M 15 14 M.2 12.8 11 10 9 GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE 13 MATCHLINE: 1/ P-103 STAE COLLEGE, PA 16801 4"DD-A JK STRUCTURAL ENGINEER STAFF BK RM S1 CORRIDOR WBCM 116 100 STERLING PARKWAY, SUITE 108 Q MECHANICSBURG, PA 17050 C-101 4"DD-B 4"DD-A S1 I.6 I P O N TRPL SUITE (MIR) 4"DD-A QUAD SUITE B 118 122 F 4"RD-A (3490 sf) I H.2 H S6 G 4"RD-B (3490 sf) 4"RL UP & DN (500 sf) S1 4"RL UP & DN (1830 sf) MATCHLINE: 1/ P-103 W6 W2 S7 W2 6"RL DN (2900 sf) W7 4" WS F.3 F 3/4" HW 3/4" CW S1 MECH 1 1/4" CW - IDF LAUNDRY ELEC 121 119 W5 1" HW B E DBL SUITE - CW ? 129 ? S1 1 1/4" CW 1 1/4" CW 1 1/4" HW 123 127 4"RL UP & DN (2480 sf) 1" HW E D RA SUITE G QUAD SUITE A F S1 133 S1 S1 4"SAN OFFSET A/C S1 4"WS UP 2" HW INSULATE AND HEAT TRACE ALL DOMESTIC WATER PIPING AND P-TRAPS WITHIN UNHEATED SPACES S1 S3 W2 W2 2" CW MECH 1 1/2" HW 2 1/2" CW 2 1/2" CW 120 W2 EXPANSION LOOP MINIMUM TOTAL LENGTH = 13.8' W2 2" HW W2 W2 LOUNGE 124 S1 1 1/2" HW 2" CW 4"RL UP & DN (1800 sf) 2" CW 2" CW 2" HW CORRIDOR 6"RL UP & DN (3400 sf) 2" HW 2" CW 1 1/2" CW C-102 1 1/4" CW S-105 W2 C 1" HW 1 1/4" HW 1 1/2" CW STAIR 05 W2 W2 3" RELIEF VENT A/C S2 S2 4"S UP 125 J S1 S1 S1 S1 S1 TRPL SUITE (MIR) DBL SUITE DBL SUITE 126 128 130 F B 4"SAN OFFSET A/C B 4" S 4" S W2 1 1/2" HW W2 B.5 4"S DN 1 1/2" HW QUAD SUITE C C.2 6"RL UP (2900 sf) A.5 AREA COORD. SUITE (AC) S2 STANDPIPE "C" W/ 2-1/2"FDV SEE DETAIL 1/P-501 STAIR 03 132 A A.3 S-103 4"SAN OFFSET A/C BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE 4"DD-B 4"DD-B B A 8 7 6 5.3 5 4 2 1 4.4 1 P-104 KEY PLAN PLUMBING PLAN - 1ST FLOOR - AREA B A SCALE: 1/8" = 1'-0" B REVISION NO. DESCRIPTION DATE PLUMBING UNIT PLAN LEGEND A STAFF APARTMENT - REFER TO....... 3/P-401 B DOUBLE SUITE - REFER TO .... 3/P-403 C GRAD SUITE - REFER TO ..... 6/P-401 D RA SUITE (ZONE B) - REFER TO ..... 3/P-402 E RA SUITE (ZONE A) - REFER TO ...... 6/P-402 12/14/2015 4:07:48 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 AHA PROJECT NUMBER F TRIPLE SUITE - REFER TO........ 6/P-403 G1215-004.00 DATE G QUAD SUITE - REFER TO........ 3/P-404 03 DECEMBER 2015 ISSUE H QUAD SUITE A - REFER TO........ 6/P-404 I QUAD SUITE B - REFER TO........ 3/P-405 J QUAD SUITE C - REFER TO........ 6/P-405 K QUAD SUITE D - REFER TO........ 3/P-406 REVISED 15 DECEMBER 2015 CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING PLAN 1ST FLOOR - AREA B SHEET NO. P-104 9 11 19 18 17.4 17 1514.8 16 1312.8 14.1 14 10 12 ARCHITECT HKS, INC. x.1 x.2 x.4 x.4.1 x.5 x.6 x.7 x.8 TWO LIVE OAK CENTER x.9x.10 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES S2 33 SOUTH BROAD STREET QUAD SUITE (MIR) LITITZ, PA 17543 234 GEOTECHNICAL ENGINEER G QUAD SUITE D 238 IDF K 236 CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE y.6.5 y.6 STAE COLLEGE, PA 16801 STRUCTURAL ENGINEER WBCM 6"RL UP & DN (3147 sf) STAIR 01 S2 S-201 2"VTR S2 W1 4"RL UP & DN (1720 sf) GRAD SUITE W1 MECHANICSBURG, PA 17050 4"RD-B (1673 sf) 232 MECH C - 4"RD-A (1673 sf) NFRH CORRIDOR ELEC. S5 W1 S2 146 235 S2 JS1 JC RA SUITE 242 243 Z W1 S2 W1 4"RD-B (3194 sf) 230 237 G D 4"RL UP & DN (2236 sf) DBL SUITE S2 239 STANDPIPE "A" W/ 2-1/2"FDV SEE DETAIL 1/P-501 Y.5 4"RD-A (3194 sf) QUAD SUITE BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE W8 LOUNGE 100 STERLING PARKWAY, SUITE 108 S2 TRPL SUITE (MIR) B W1 233 W1 20.8 S2 21 Y X.5 X.3 X STANDPIPE "B" W/ 2-1/2"FDV SEE DETAIL 1/P-501 W1 F 4"VTR 4"RL UP & DN (3718 sf) S2 W1 S2 S2 STAIR 02 TRPL SUITE 21.5 241 S2 S-202 TRPL SUITE 22 F TRSH/ REC 231 W S2 F ELEV. 23 V.8 U.3 - ELEV. V.7 - M 23.6 U MECH - W4 24 T.5 QUAD SUITE (MIR) W1 201 S1 T G V TRPL SUITE L 4"RL UP & DN (500 sf) 202 S F W2 S2 JK MATCHLINE: 1/ P-106 R Q S1 CORRIDOR 147 S1 I.6 P ? ? TRPL SUITE (MIR) 203 O N KEY PLAN MATCHLINE: 1/ P-106 A 1 P-105 PLUMBING PLAN - 2ND FLOOR - AREA A SCALE: 1/8" = 1'-0" B REVISION NO. DESCRIPTION DATE PLUMBING UNIT PLAN LEGEND A STAFF APARTMENT - REFER TO....... 3/P-401 B DOUBLE SUITE - REFER TO .... 3/P-403 C GRAD SUITE - REFER TO ..... 6/P-401 D RA SUITE (ZONE B) - REFER TO ..... 3/P-402 E RA SUITE (ZONE A) - REFER TO ...... 6/P-402 12/14/2015 4:08:01 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 AHA PROJECT NUMBER F TRIPLE SUITE - REFER TO........ 6/P-403 G1215-004.00 DATE G QUAD SUITE - REFER TO........ 3/P-404 03 DECEMBER 2015 ISSUE H QUAD SUITE A - REFER TO........ 6/P-404 I QUAD SUITE B - REFER TO........ 3/P-405 J QUAD SUITE C - REFER TO........ 6/P-405 K QUAD SUITE D - REFER TO........ 3/P-406 REVISED 15 DECEMBER 2015 CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING PLAN 2ND FLOOR - AREA A SHEET NO. P-105 ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543 18 17 L 16 M 15 14 13 12.8 11 10 9 GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801 STRUCTURAL ENGINEER MATCHLINE: 1/ P-105 WBCM JK 100 STERLING PARKWAY, SUITE 108 Q S1 MECHANICSBURG, PA 17050 CORRIDOR 147 I P O N TRPL SUITE (MIR) ? 203 ? F MATCHLINE: 1/ P-105 I H.2 H S1 4"RL UP & DN (1830 sf) G S7 W2 W6 S6 W7 W2 4"RL UP & DN (500 sf) RA SUITE F.3 F MECH QUAD SUITE B B DBL SUITE - CW F TRPL SUITE (MIR) - CW QUAD SUITE - CW DBL SUITE - CW 213 215 217 219 211 S1 ELEC - LAUNDRY W5 204 IDF E 4"RL UP & DN (2480 sf) 206 S1 G S1 B 221 I S1 S1 S1 S1 208 S2 6"RL UP & DN (2900 sf) W2 MECH W2 TRSH/ REC 205 E D W2 W2 - W2 C.2 W2 W2 LOUNGE C 209 CORRIDOR B.5 148 4"RL UP & DN (1800 sf) S1 B QUAD SUITE C W2 W2 W2 S2 1 6"RL UP & DN (3400 sf) W2 W2 210 A.5 J S1 S1 S1 TRPL SUITE (MIR) DBL SUITE S1 S1 212 F S2 S2 DBL SUITE 214 216 B B BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE S1 I.6 S2 QUAD SUITE DBL SUITE (MIR) 218 220 G B STAIR 03 S-203 A STANDPIPE "C" W/ 2-1/2"FDV SEE DETAIL 1/P-501 8 7 6 5.3 5 4 3 2 1 4.4 1 P-106 KEY PLAN PLUMBING PLAN - 2ND FLOOR - AREA B A SCALE: 1/8" = 1'-0" B REVISION NO. DESCRIPTION KEYED NOTES 1 BASE OF STANDPIPE VALVE ASSEMBLY ABOVE CEILING. REFER TO DETAIL 10/P-501. DATE PLUMBING UNIT PLAN LEGEND A STAFF APARTMENT - REFER TO....... 3/P-401 B DOUBLE SUITE - REFER TO .... 3/P-403 C GRAD SUITE - REFER TO ..... 6/P-401 D RA SUITE (ZONE B) - REFER TO ..... 3/P-402 E RA SUITE (ZONE A) - REFER TO ...... 6/P-402 12/14/2015 4:08:14 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 AHA PROJECT NUMBER F TRIPLE SUITE - REFER TO........ 6/P-403 G1215-004.00 DATE G QUAD SUITE - REFER TO........ 3/P-404 03 DECEMBER 2015 ISSUE H QUAD SUITE A - REFER TO........ 6/P-404 I QUAD SUITE B - REFER TO........ 3/P-405 J QUAD SUITE C - REFER TO........ 6/P-405 K QUAD SUITE D - REFER TO........ 3/P-406 REVISED 15 DECEMBER 2015 CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING PLAN 2ND FLOOR - AREA B SHEET NO. P-106 9 11 19 18 17.4 17 16 1514.8 1312.8 14.1 14 10 12 ARCHITECT HKS, INC. x.4 x.5 x.6 x.7 x.8 TWO LIVE OAK CENTER x.9x.10 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET S2 LITITZ, PA 17543 QUAD SUITE (MIR) QUAD SUITE D 334 338 GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. G K IDF 336 4"RL UP & DN (1720 sf) 3/4" HWR W1 100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050 S2 332 - B CORRIDOR S5 ELEC. 3/4" HWR W1 S2 C-300 335 W8 BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE 1" HWR S2 JS1 JC 342 S2 RA SUITE 3/4" HWR W1 Z W1 337 4"RL UP & DN (2236 sf) QUAD SUITE D 330 S2 W1 DBL SUITE S2 B STANDPIPE "B" W/ 2-1/2"FDV SEE DETAIL 1/P-501 W1 TRPL SUITE (MIR) 4"RL UP & DN (3718 sf) 333 20.8 S2 21 Y X.5 X.3 X G 1" HWR 339 STANDPIPE "A" W/ 2-1/2"FDV SEE DETAIL 1/P-501 Y.5 DOUBLE SUITE MECH 343 STRUCTURAL ENGINEER 4"RL UP & DN (3147 sf) W1 LOUNGE STAE COLLEGE, PA 16801 WBCM STAIR 01 S-301 2701 CAROLEAN INDUSTRIAL DRIVE y.6.5 y.6 S2 F STAIR 02 W1 1 1/4" HWR S-302 S2 S2 TRPL SUITE 341 21.5 F S2 22 TRPL SUITE - 331 W S2 F 23 V.8 TRASH/ RECYCLING U.3 V.7 23.6 U MECH M - W4 24 1 1/4" HWR W1 301 1 1/2" HWR S1 T.5 QUAD SUITE (MIR) V T G 4"RL UP & DN (500 sf) L TRPL SUITE S 302 F W2 S2 JK MATCHLINE: 1/ P-108 R S1 Q CORRIDOR C-301 S1 I.6 BALANCING VALVE ASSEMBLY (TYP) SEE DETAIL 8/P-501 P ? ? TRPL SUITE (MIR) 303 O N KEY PLAN MATCHLINE: 1/ P-108 A 1 P-107 PLUMBING PLAN - 3RD FLOOR - AREA A SCALE: 1/8" = 1'-0" B REVISION NO. DESCRIPTION DATE PLUMBING UNIT PLAN LEGEND A STAFF APARTMENT - REFER TO....... 3/P-401 B DOUBLE SUITE - REFER TO .... 3/P-403 C GRAD SUITE - REFER TO ..... 6/P-401 D RA SUITE (ZONE B) - REFER TO ..... 3/P-402 E RA SUITE (ZONE A) - REFER TO ...... 6/P-402 12/14/2015 4:08:27 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 AHA PROJECT NUMBER F TRIPLE SUITE - REFER TO........ 6/P-403 G1215-004.00 DATE G QUAD SUITE - REFER TO........ 3/P-404 03 DECEMBER 2015 ISSUE H QUAD SUITE A - REFER TO........ 6/P-404 I QUAD SUITE B - REFER TO........ 3/P-405 J QUAD SUITE C - REFER TO........ 6/P-405 K QUAD SUITE D - REFER TO........ 3/P-406 REVISED 15 DECEMBER 2015 CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING PLAN 3RD FLOOR - AREA A SHEET NO. P-107 ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543 18 17 L 16 M 15 14 13 12.8 11 10 9 GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801 STRUCTURAL ENGINEER WBCM MATCHLINE: 1/ P-107 S1 JK 100 STERLING PARKWAY, SUITE 108 Q CORRIDOR MECHANICSBURG, PA 17050 C-301 I 303 ? F I H.2 H P O N TRPL SUITE (MIR) ? MATCHLINE: 1/ P-107 4"RL UP & DN (500 sf) S1 4"RL UP & DN (1830 sf) W2 S6 BALANCING VALVE ASSEMBLY (TYP) SEE DETAIL 8/P-501 W6 G W7 W2 S7 E D RA SUITE 3/4" HWR F.3 F LAUNDRY S1 - IDF B G B DBL SUITE - CW F TRPL SUITE (MIR) - CW QUAD SUITE - CW DBL SUITE - CW 313 315 317 319 311 ELEC 306 MECH 3/4" HWR W5 304 3/4" HWR 4"RL UP & DN (2480 sf) 308 E S1 S1 S1 S1 QUAD SUITE B 321 I S1 S1 S2 6"RL UP & DN (2900 sf) MECH TRASH/ RECYCLING 305 1 1/2" HWR W2 W2 W2 - LOUNGE W2 C.2 W2 W2 C 309 CORRIDOR 1" HWR W2 1 1/2" HWR S1 C-302 1 1/4" HWR 1" HWR 1" HWR 3/4" HWR 3/4" HWR 4"RL UP & DN (1800 sf) B W2 6"RL UP & DN (3400 sf) W2 QUAD SUITE C W2 W2 S2 W2 310 A.5 J S1 S1 S1 TRPL SUITE (MIR) 312 F S1 S1 S2 S2 BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE S1 I.6 S2 DBL SUITE DBL SUITE QUAD SUITE DBL SUITE (MIR) 314 316 318 320 B B STAIR 03 S-303 G B A STANDPIPE "C" W/ 2-1/2"FDV SEE DETAIL 1/P-501 8 7 6 5.3 5 4 3 2 1 4.4 1 P-108 KEY PLAN PLUMBING PLAN - 3RD FLOOR - AREA B A SCALE: 1/8" = 1'-0" B REVISION NO. DESCRIPTION DATE PLUMBING UNIT PLAN LEGEND A STAFF APARTMENT - REFER TO....... 3/P-401 B DOUBLE SUITE - REFER TO .... 3/P-403 C GRAD SUITE - REFER TO ..... 6/P-401 D RA SUITE (ZONE B) - REFER TO ..... 3/P-402 E RA SUITE (ZONE A) - REFER TO ...... 6/P-402 12/14/2015 4:08:41 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 AHA PROJECT NUMBER F TRIPLE SUITE - REFER TO........ 6/P-403 G1215-004.00 DATE G QUAD SUITE - REFER TO........ 3/P-404 03 DECEMBER 2015 ISSUE H QUAD SUITE A - REFER TO........ 6/P-404 I QUAD SUITE B - REFER TO........ 3/P-405 J QUAD SUITE C - REFER TO........ 6/P-405 K QUAD SUITE D - REFER TO........ 3/P-406 REVISED 15 DECEMBER 2015 CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING PLAN 3RD FLOOR - AREA B SHEET NO. P-108 9 11 19 18 17.4 17 16 1514.8 1312.8 14.1 14 10 12 ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET S2 LITITZ, PA 17543 QUAD SUITE D GEOTECHNICAL ENGINEER 438 QUAD SUITE (MIR) CMT LABORATORIES, INC. 434 STAE COLLEGE, PA 16801 K IDF STAIR 01 G 436 4"RL UP & DN (1720 sf) STRUCTURAL ENGINEER WBCM 4"RL UP & DN (3147 sf) W3 S-401 2701 CAROLEAN INDUSTRIAL DRIVE 100 STERLING PARKWAY, SUITE 108 S2 1 1/2" HW W3 432 1 1/2" CW B MECH 1 1/2" HW - 1 1/2" CW 1 1/4" HW W8 LOUNGE W3 S2 JC RA SUITE 442 1" HW 1 1/4" CW 4"RL UP & DN (2236 sf) 1" HW 1" CW S2 W3 437 QUAD SUITE 2" HW 430 2" CW D W3 S2 G W3 DBL SUITE S2 W3 TRPL SUITE (MIR) B 20.8 S2 21 Y X.5 X.3 X 4"RL UP & DN (3718 sf) C-400 433 S2 2" HW F STAIR 02 W3 S-402 S2 S2 TRPL SUITE 2" CW 21.5 441 S2 STANDPIPE "B" W/ 2-1/2"FDV SEE DETAIL 1/P-501 W3 CORRIDOR 439 STANDPIPE "A" W/ 2-1/2"FDV SEE DETAIL 1/P-501 Y.5 S2 435 JS1 443 Z 1 1/2" HW 1 1/2" CW ELEC. BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE S5 MECHANICSBURG, PA 17050 DOUBLE SUITE S2 F TRPL SUITE 22 TRSH/ REC 431 W - S2 F 23 V.8 U.3 V.7 23.6 U MECH M - W4 2" HW 24 T.5 2" CW W3 2" CW S1 V QUAD SUITE (MIR) T 401 2" HW G L 4"RL UP & DN (500 sf) TRPL SUITE W3 S2 R 402 JK MATCHLINE: 1/ P-110 S 1 1/4" CW 1" HW F S1 Q CORRIDOR C-401 I.6 S1 P ? TRPL SUITE (MIR) ? 403 O N KEY PLAN MATCHLINE: 1/ P-110 A 1 P-109 PLUMBING PLAN - 4TH FLOOR - AREA A SCALE: 1/8" = 1'-0" B REVISION NO. DESCRIPTION DATE PLUMBING UNIT PLAN LEGEND A STAFF APARTMENT - REFER TO....... 3/P-401 B DOUBLE SUITE - REFER TO .... 3/P-403 C GRAD SUITE - REFER TO ..... 6/P-401 D RA SUITE (ZONE B) - REFER TO ..... 3/P-402 E RA SUITE (ZONE A) - REFER TO ...... 6/P-402 12/14/2015 4:08:57 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 AHA PROJECT NUMBER F TRIPLE SUITE - REFER TO........ 6/P-403 G1215-004.00 DATE G QUAD SUITE - REFER TO........ 3/P-404 03 DECEMBER 2015 ISSUE H QUAD SUITE A - REFER TO........ 6/P-404 I QUAD SUITE B - REFER TO........ 3/P-405 J QUAD SUITE C - REFER TO........ 6/P-405 K QUAD SUITE D - REFER TO........ 3/P-406 REVISED 15 DECEMBER 2015 CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING PLAN 4TH FLOOR - AREA A SHEET NO. P-109 ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543 18 17 L 16 M 15 14 13 12.8 11 10 9 GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801 TRPL SUITE MATCHLINE: 1/ P-109 STRUCTURAL ENGINEER 402 JK WBCM F CORRIDOR S1 100 STERLING PARKWAY, SUITE 108 Q MECHANICSBURG, PA 17050 C-401 I.6 I H.2 H ? TRPL SUITE (MIR) ? 403 I F S6 W3 MATCHLINE: 1/ P-109 4"RL UP & DN (500 sf) W6 4"RL UP & DN (1830 sf) G P O N W3 S1 S7 E D W7 F 1 1/4" CW 1 1/4" CW 1" HW F.3 RA SUITE S1 LAUNDRY ELEC 406 404 MECH 1" HW B E W5 - DBL SUITE - CW F TRPL SUITE (MIR) - CW QUAD SUITE - CW DBL SUITE - CW 413 415 417 419 S1 4"RL UP & DN (2480 sf) 2" HW IDF QUAD SUITE B 411 S1 G S1 S1 B S1 421 I S2 S1 W3 MECH 408 2" CW 1 1/2" HW LOUNGE 405 2 1/2" CW TRSH/ REC 2" HW - 2 1/2" CW 409 6"RL UP & DN (2900 sf) W3 W3 W3 C.2 W3 1" HW W3 C 1 1/4" CW W3 S1 2" CW 2" HW 2" CW 2" HW CORRIDOR 2" CW 2" HW C-402 1 1/2" HW 2" CW 1 1/2" CW 1 1/2" HW 1 1/2" HW 1 1/2" CW 1 1/4" HW 4"RL UP & DN (1800 sf) B 6"RL UP & DN (3400 sf) W3 QUAD SUITE C W3 W3 W3 W3 S2 410 J S1 S1 S1 S1 S2 S2 A.5 S2 BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE S1 S1 TRPL SUITE (MIR) DBL SUITE DBL SUITE QUAD SUITE DBL SUITE (MIR) 412 414 416 418 420 F B B G STAIR 03 S-403 B A STANDPIPE "C" W/ 2-1/2"FDV SEE DETAIL 1/P-501 8 7 6 5.3 5 4 3 2 1 4.4 1 P-110 KEY PLAN PLUMBING PLAN - 4TH FLOOR - AREA B A SCALE: 1/8" = 1'-0" B REVISION NO. DESCRIPTION DATE PLUMBING UNIT PLAN LEGEND A STAFF APARTMENT - REFER TO....... 3/P-401 B DOUBLE SUITE - REFER TO .... 3/P-403 C GRAD SUITE - REFER TO ..... 6/P-401 D RA SUITE (ZONE B) - REFER TO ..... 3/P-402 E RA SUITE (ZONE A) - REFER TO ...... 6/P-402 12/14/2015 4:09:13 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 AHA PROJECT NUMBER F TRIPLE SUITE - REFER TO........ 6/P-403 G1215-004.00 DATE G QUAD SUITE - REFER TO........ 3/P-404 03 DECEMBER 2015 ISSUE H QUAD SUITE A - REFER TO........ 6/P-404 I QUAD SUITE B - REFER TO........ 3/P-405 J QUAD SUITE C - REFER TO........ 6/P-405 K QUAD SUITE D - REFER TO........ 3/P-406 REVISED 15 DECEMBER 2015 CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING PLAN 4TH FLOOR - AREA B SHEET NO. P-110 9 11 19 18 17.4 17 16 1514.8 1312.8 14.1 14 10 12 ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET S2 LITITZ, PA 17543 GEOTECHNICAL ENGINEER QUAD SUITE (MIR) QUAD SUITE D CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE 534 538 STAE COLLEGE, PA 16801 IDF K G 536 STRUCTURAL ENGINEER WBCM 4"RL UP & DN (3147 sf) STAIR 01 W3 S2 S-501 100 STERLING PARKWAY, SUITE 108 4"RL UP & DN (1720 sf) MECH MECHANICSBURG, PA 17050 S2 W3 DOUBLE SUITE 532 - CORRIDOR ELEC. W8 543 JS1 S2 S2 JC RA SUITE 542 Z C-500 535 W3 LOUNGE B S2 W3 QUAD SUITE 537 4"RL UP & DN (2236 sf) 530 D S2 W3 W3 G STANDPIPE "A" W/ 2-1/2"FDV SEE DETAIL 1/P-501 TRPL SUITE (MIR) 539 S2 B W3 533 20.8 S2 21 Y X.5 X.3 X STANDPIPE "B" W/ 2-1/2"FDV SEE DETAIL 1/P-501 W3 DBL SUITE Y.5 BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE S5 4"RL UP & DN (3718 sf) S2 STAIR 02 F W3 S-502 S2 TRPL SUITE S2 541 S2 21.5 F TRASH/ RECYCLING TRPL SUITE 22 531 W - S2 F 23 V.8 U.3 V.7 23.6 U MECH M - W4 24 T.5 QUAD SUITE (MIR) W3 501 V T G S1 L 4"RL UP & DN (500 sf) S W3 TRPL SUITE 444 JK MATCHLINE: 1/ P-112 CORRIDOR S2 R C-501 Q F S1 I.6 P S1 TRPL SUITE (MIR) ? ? 503 O N KEY PLAN MATCHLINE: 1/ P-112 A 1 P-111 PLUMBING PLAN - 5TH FLOOR - AREA A SCALE: 1/8" = 1'-0" B REVISION NO. DESCRIPTION DATE PLUMBING UNIT PLAN LEGEND A STAFF APARTMENT - REFER TO....... 3/P-401 B DOUBLE SUITE - REFER TO .... 3/P-403 C GRAD SUITE - REFER TO ..... 6/P-401 D RA SUITE (ZONE B) - REFER TO ..... 3/P-402 E RA SUITE (ZONE A) - REFER TO ...... 6/P-402 12/14/2015 4:09:26 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 AHA PROJECT NUMBER F TRIPLE SUITE - REFER TO........ 6/P-403 G1215-004.00 DATE G QUAD SUITE - REFER TO........ 3/P-404 03 DECEMBER 2015 ISSUE H QUAD SUITE A - REFER TO........ 6/P-404 I QUAD SUITE B - REFER TO........ 3/P-405 J QUAD SUITE C - REFER TO........ 6/P-405 K QUAD SUITE D - REFER TO........ 3/P-406 REVISED 15 DECEMBER 2015 CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING PLAN 5TH FLOOR - AREA A SHEET NO. P-111 ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543 18 17 L 16 M 15 14 13 12.8 11 10 9 GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801 CORRIDOR TRPL SUITE MATCHLINE: 1/ P-111 444 JK STRUCTURAL ENGINEER C-501 WBCM 100 STERLING PARKWAY, SUITE 108 Q F MECHANICSBURG, PA 17050 S1 I.6 P O N TRPL SUITE (MIR) ? I H.2 H 503 ? F I S6 4"RL UP & DN (1830 sf) 4"RL UP & DN (500 sf) W6 S1 S7 G MATCHLINE: 1/ P-111 W3 W7 W3 RA SUITE S1 F.3 F S7 ELEC LAUNDRY MECH - 504 506 W5 IDF E D QUAD SUITE B 511 B E DBL SUITE - CW 4"RL UP & DN (2480 sf) S1 F TRPL SUITE (MIR) - CW G B 521 QUAD SUITE - CW DBL SUITE - CW I 515 517 519 513 S1 508 S1 S1 S1 S1 W3 S2 MECH TRASH/ RECYCLING 505 W3 W3 W3 W3 C.2 W3 6"RL UP & DN (2900 sf) - LOUNGE C 4"RL UP & DN (1800 sf) 509 CORRIDOR W3 6"RL UP & DN (3400 sf) C-502 S1 B W3 W3 W3 W3 W3 S2 A.5 QUAD SUITE C S1 510 S1 J S1 S1 S1 S2 S2 S2 TRPL SUITE (MIR) DBL SUITE DBL SUITE QUAD SUITE DBL SUITE (MIR) 512 514 516 518 520 B G B F B BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE S1 STAIR 03 S-503 A STANDPIPE "C" W/ 2-1/2"FDV SEE DETAIL 1/P-501 8 7 6 5.3 5 4 3 2 1 4.4 1 P-112 KEY PLAN PLUMBING PLAN - 5TH FLOOR - AREA B A SCALE: 1/8" = 1'-0" B REVISION NO. DESCRIPTION DATE PLUMBING UNIT PLAN LEGEND A STAFF APARTMENT - REFER TO....... 3/P-401 B DOUBLE SUITE - REFER TO .... 3/P-403 C GRAD SUITE - REFER TO ..... 6/P-401 D RA SUITE (ZONE B) - REFER TO ..... 3/P-402 E RA SUITE (ZONE A) - REFER TO ...... 6/P-402 12/14/2015 4:09:40 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 AHA PROJECT NUMBER F TRIPLE SUITE - REFER TO........ 6/P-403 G1215-004.00 DATE G QUAD SUITE - REFER TO........ 3/P-404 03 DECEMBER 2015 ISSUE H QUAD SUITE A - REFER TO........ 6/P-404 I QUAD SUITE B - REFER TO........ 3/P-405 J QUAD SUITE C - REFER TO........ 6/P-405 K QUAD SUITE D - REFER TO........ 3/P-406 REVISED 15 DECEMBER 2015 CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING PLAN 5TH FLOOR - AREA B SHEET NO. P-112 9 11 19 18 17.4 17 16 1514.8 1312.8 14.1 14 10 12 ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 4"DSN ROSWELL, GA 30076 SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 4" ERL 33 SOUTH BROAD STREET S2 QUAD SUITE (MIR) LITITZ, PA 17543 634 QUAD SUITE D STAIR 01 GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. G 2701 CAROLEAN INDUSTRIAL DRIVE 4"UP TO ERD 638 K 4"DSN STAE COLLEGE, PA 16801 IDF 4"UP TO RD 4" V 4"RL DN (1720 sf) 4"RL UP TO RD AND DN (3147 sf) 636 STRUCTURAL ENGINEER WBCM 4" @ 2% 100 STERLING PARKWAY, SUITE 108 S2 1" HWR W3 S-601 MECHANICSBURG, PA 17050 4"UP TO ERD W3 S2 DOUBLE SUITE S5 3/4" HWR - ELEC. W3 LOUNGE 643 635 1" HWR JC 3/4" HWR 642 1 1/4" HWR W3 CORRIDOR S2 4"UP TO RD 4" RL 4" V D 4"RL DN (2236 sf) QUAD SUITE 637 4" VTR W3 S2 F 20.8 4" V 21 4" ERL TRPL SUITE (MIR) 4"@ 2% S2 21.5 641 4"DSN 4"RL DN (3718 sf) W3 633 3/4"CW UP TO NFRH S2 S2 TRPL SUITE F STANDPIPE "B" W/ 2-1/2"FDV SEE DETAIL 1/P-501 W3 4" V B S2 S2 G W3 1 1/4" HWR 639 4"DSN 630 4" V DBL SUITE 4"UP TO ERD Y X.5 X.3 X C-600 S2 4" V STANDPIPE "A" W/ 2-1/2"FDV SEE DETAIL 1/P-501 S2 RA SUITE W3 Y.5 B 4" V W8 JS1 Z 632 4" V 4"VTR F 22 4" V 4"UP TO ERD 4"UP TO RD 4" V 631 STAIR 02 S-602 1 1/4" HWR TRPL SUITE W TRSH/ REC - S2 23 V.8 U.3 S2 4" V V.7 23.6 U MECH M - W4 24 4"VTR W3 V 601 1 1/2" HWR T G 1 1/2" HWR 4" V 4"RL DN (500 sf) L T.5 QUAD SUITE (MIR) 1 1/4" HWR S1 S TRPL SUITE 602 JK W3 CORRIDOR F MATCHLINE: 1/ P-114 BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE 4" V MECH 4" V 4" V S1 R BALANCING VALVE ASSEMBLY (TYP) SEE DETAIL 8/P-501 S1 I.6 S2 C-601 4" ERL Q 4"UP TO RD 4"DSN P TRPL SUITE (MIR) 603 4" V O N KEY PLAN A 1 P-113 PLUMBING PLAN - 6TH FLOOR - AREA A SCALE: 1/8" = 1'-0" B REVISION NO. DESCRIPTION DATE PLUMBING UNIT PLAN LEGEND A STAFF APARTMENT - REFER TO....... 3/P-401 B DOUBLE SUITE - REFER TO .... 3/P-403 C GRAD SUITE - REFER TO ..... 6/P-401 D RA SUITE (ZONE B) - REFER TO ..... 3/P-402 E RA SUITE (ZONE A) - REFER TO ...... 6/P-402 12/14/2015 4:09:55 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 AHA PROJECT NUMBER F TRIPLE SUITE - REFER TO........ 6/P-403 G1215-004.00 DATE G QUAD SUITE - REFER TO........ 3/P-404 03 DECEMBER 2015 ISSUE H QUAD SUITE A - REFER TO........ 6/P-404 I QUAD SUITE B - REFER TO........ 3/P-405 J QUAD SUITE C - REFER TO........ 6/P-405 K QUAD SUITE D - REFER TO........ 3/P-406 REVISED 15 DECEMBER 2015 CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING PLAN 6TH FLOOR - AREA A SHEET NO. P-113 ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543 17 L 16 M 15 14 13 12.8 11 10 9 GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. TRPL SUITE 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801 602 CORRIDOR F 4" V JK STRUCTURAL ENGINEER C-601 MATCHLINE: 1/ P-113 WBCM S1 4"DSN 4"UP TO ERD P O N TRPL SUITE (MIR) ? I 4"DSN W6 S6 W3 S1 4" ERL 4" ERL G 4" ERL 4" V 4"RL DN (1830 sf) W7 4"DSN 4"UP TO RD 4" V W3 4" V S7 F.3 4"UP TO ERD F BALANCING VALVE ASSEMBLY (TYP) SEE DETAIL 8/P-501 4"RL DN (500 sf) 4"DSN 4"UP TO RD - 3/4" HWR LAUNDRY 606 IDF 608 611 3/4" HWR ELEC 3/4" HWR W5 604 4" V DBL SUITE - CW TRPL SUITE (MIR) - CW QUAD SUITE - CW DBL SUITE - CW 613 615 617 619 B F G B 621 I S1 S1 S1 S1 S1 S1 S2 W3 4" ERL MECH 1" HWR 4" RL 4"UP TO ERD 4"UP TO RD 4" V TRSH/ REC 605 LOUNGE E 4"RL DN (2480 sf) 1 1/2" HWR - W3 4"UP TO RD 1 1/2" HWR 4" V 1 1/4" HWR 1 1/4" HWR 6" RL 4"UP TO ERD 1" HWR 3/4" HWR 3/4" HWR 3/4" HWR C-602 4"UP TO ERD 1 1/4" HWR B 4" VTR 4" VTR 4" V W3 W3 6"RL DN (3400 sf) W3 4" ERL 6"DSN 6" ERL 4" V 4"UP TO ERD 610 C 4"UP TO RD CORRIDOR 6" RL C.2 W3 4" V 4"UP TO RD 3/4" HWR 4" V QUAD SUITE C 6"RL DN (2900 sf) 4" VTR 3/4" HWR 3/4" HWR 4"RL DN (1800 sf) W3 4" V 4" V W3 S1 W3 4" V W3 1 1/2" HWR 609 E D QUAD SUITE B RA SUITE 3/4"CW UP TO NFRH S1 MECH MATCHLINE: 1/ P-113 4" VTR F I H.2 H 4" V 603 ? MECHANICSBURG, PA 17050 4"UP TO RD 4" ERL 4" V I.6 100 STERLING PARKWAY, SUITE 108 Q S1 4" V W3 4" V W3 S2 A.5 J S1 S1 S1 S1 S1 TRPL SUITE (MIR) DBL SUITE DBL SUITE 612 614 F B 4"DSN 8 S2 S2 S2 QUAD SUITE DBL SUITE (MIR) 616 618 620 B G B 6" ERL STAIR 03 S-603 A 6"DSN 7 6 5.3 STANDPIPE "C" W/ 2-1/2"FDV SEE DETAIL 1/P-501 5 4 3 2 1 4.4 1 P-114 BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE 18 KEY PLAN PLUMBING PLAN - 6TH FLOOR - AREA B A SCALE: 1/8" = 1'-0" B REVISION NO. DESCRIPTION DATE PLUMBING UNIT PLAN LEGEND A STAFF APARTMENT - REFER TO....... 3/P-401 B DOUBLE SUITE - REFER TO .... 3/P-403 C GRAD SUITE - REFER TO ..... 6/P-401 D RA SUITE (ZONE B) - REFER TO ..... 3/P-402 E RA SUITE (ZONE A) - REFER TO ...... 6/P-402 12/14/2015 4:10:11 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 AHA PROJECT NUMBER F TRIPLE SUITE - REFER TO........ 6/P-403 G1215-004.00 DATE G QUAD SUITE - REFER TO........ 3/P-404 03 DECEMBER 2015 ISSUE H QUAD SUITE A - REFER TO........ 6/P-404 I QUAD SUITE B - REFER TO........ 3/P-405 J QUAD SUITE C - REFER TO........ 6/P-405 K QUAD SUITE D - REFER TO........ 3/P-406 REVISED 15 DECEMBER 2015 CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING PLAN 6TH FLOOR - AREA B SHEET NO. P-114 9 11 19 18 17.4 17 16 1514.8 1312.8 14.1 14 10 12 ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543 GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801 4"RD-B (1720 sf) STRUCTURAL ENGINEER WBCM 100 STERLING PARKWAY, SUITE 108 4"RD-A (1720 sf) MECHANICSBURG, PA 17050 4"RD-B (3147 sf) 4"RD-A (3147 sf) BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE 4"VTR 4"VTR 4"RD-A (2236 sf) Z 4"VTR 4"RD-B (2236 sf) NFRH Y.5 4"RD-B (3718 sf) 20.8 21 Y X.5 X.3 X 4"RD-A (3718 sf) 21.5 4"VTR 22 W 23 V.8 U.3 4"VTR V.7 U M 23.6 T.5 24 T V L S 4"RD-B (500 sf) JK MATCHLINE: 1/ P-116 R 4"RD-A (500 sf) Q I.6 P O N KEY PLAN MATCHLINE: 1/ P-116 A 1 P-115 PLUMBING PLAN - ROOF - AREA A SCALE: 1/8" = 1'-0" B REVISION NO. DESCRIPTION DATE AHA PROJECT NUMBER 12/14/2015 4:10:24 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 G1215-004.00 DATE 03 DECEMBER 2015 ISSUE CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING PLAN ROOF - AREA A REVISED 15 DECEMBER 2015 SHEET NO. P-115 ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543 18 17 L 16 M 15 14 13 12.8 11 10 9 GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801 4"RD-B (500 sf) MATCHLINE: 1/ P-115 STRUCTURAL ENGINEER WBCM JK 4"RD-A (500 sf) 100 STERLING PARKWAY, SUITE 108 Q MECHANICSBURG, PA 17050 P O N I 4"VTR H.2 H MATCHLINE: 1/ P-115 4"RD-B (500 sf) 4"RD-A (500 sf) G NFRH 4"RD-A (1830 sf) 4"RD-B (1830 sf) F.3 F 4"RD-A (1800 sf) 4"VTR C.2 4"RD-B (1800 sf) 4"RD-A (2480 sf) 4"RD-A (3400 sf) 4"RD-A (2900 sf) 4"RD-B (2480 sf) 4"RD-B (3400 sf) 4"RD-B (2900 sf) B 4"VTR 4"VTR BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE I.6 A 8 7 6 5.3 5 4 3 2 1 4.4 1 P-116 KEY PLAN PLUMBING PLAN - ROOF - AREA B A SCALE: 1/8" = 1'-0" B REVISION NO. DESCRIPTION DATE AHA PROJECT NUMBER 12/14/2015 4:10:36 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 G1215-004.00 DATE 03 DECEMBER 2015 ISSUE CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING PLAN ROOF - AREA B REVISED 15 DECEMBER 2015 SHEET NO. P-116 4 4.4 5 5.3 ARCHITECT HKS, INC. TWO LIVE OAK CENTER 1/2" CW 1/2" HW 3445 PEACHTREE ROAD, NE, SUITE 675 A 1/2" CW CW RISER ATLANTA, GA 30326 2" V ASSOCIATE ARCHITECT HW RISER MURRAY AND ASSOCIATES ARCHITECTS 2" V 1/2" HW 1/2" CW 1600 NORTH SECOND STREET 3/4" HW 3/4" CW 1/2" HW HARRISBURG, PA 17102-2499 MEP ENGINEER T cto ie g n ri h y p o C 7 0 t2 A.3 1/2" CW AHA CONSULTING ENGINEERS 1/2" CW KS1 2" S 3/4" CW 3/4" HW 1/2" HW 1/2" CW IM1 KS1 1801 OLD ALABAMA RD, SUITE 125 2" V CONNECT TO 3"VENT RISER 1/2" HW 1/2" CW 3"VENT RISER 1/2" HW 1/2" CW 3" HD 1/2" HW LITITZ, PA 17543 L2 1/2" CW WB1 2" S CW RISER 33 SOUTH BROAD STREET 1/2" CW 1/2" HW 1/2"CW DN 2"W & V 1/2" CW HW RISER 1/2"H & CW DN 2" V 2" SANITARY IN WALL 1/2" CW SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 2" V WB1 ROSWELL, GA 30076 4"SAN RISER 1/2" CW 1/2" HW KS1 2"W & V 2701 CAROLEAN INDUSTRIAL DRIVE 2" V 2" V BT1 BT1 3/4" HW 1/2" CW 3" HD 2" S 1/2"H & CW DN 2" V STRUCTURAL ENGINEER WBCM WC2 1/2" HW CMT LABORATORIES, INC. STAE COLLEGE, PA 16801 2" V WC2 GEOTECHNICAL ENGINEER 1/2" HW 100 STERLING PARKWAY, SUITE 108 BT1 1/2" CW 2"BATHTUB DRAIN MECHANICSBURG, PA 17050 WB1 L2 B L2 IM1 WC2 HW RISER CONNECT TO 4" SANITARY RISER 2" S 3/4" CW 1/2"CW DN CW RISER 1 P-401 WATER RISER - STAFF APARTMENT SANITARY RISER - STAFF APARTMENT 2 SCALE: N.T.S. P-401 3 SCALE: N.T.S. P-401 PLUMBING PLAN - STAFF APARTMENT SCALE: 1/4" = 1'-0" 17 16 15 CW RISER 1/2" CW 3"VENT RISER HW RISER 2" V 3/4" CW 3/4" CW 1/2" CW U 3/4" HW 1/2" CW 1/2" HW 1/2" HW 2" V 1/2" CW 1/2" CW 2" V 2" V 1/2" CW T.5 1/2" CW 4"SAN RISER 1/2" HW 1/2" CW 2"W & V 1/2" CW WC1 L1 1/2" HW 1/2"H & CW DN 2" S WC1 2" V SH1 3" S SH1 2"W & V L1 1/2" CW 3" S 1/2" CW KS1 2" V 1/2" HW 2" S KS1 WC1 2"SHOWER DRAIN 1/2"H & CW DN KS1 1/2"CW DN L1 BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE NOTE: 1/2"H & CW DN 3" HUB DRAIN WITH TRAP GUARD IN MECHANICAL CLOSET OCCURS IN BOTTOM LEVEL ONLY. COORDINATE EXACT LOCATION WITH 2"W EQUIPMENT. REFER TO DETAIL 3/P-502. &V 3/4" HW CW RISER 4"SAN RISER 3/4" CW HW RISER 3" HD EXTEND 2"WASTE DN TO BELOW FLOOR IM1 1/2"CW DN IM1 1/2"H & CW DN 1/2" CW 3" HD SH1 S CW RISER HW RISER 3"VENT RISER NOTE: 3" HUB DRAIN WITH TRAP GUARD IN MECHANICAL CLOSET OCCURS IN BOTTOM LEVEL ONLY. COORDINATE EXACT LOCATION WITH EQUIPMENT. REFER TO DETAIL 3/P-502. 4 P-401 WATER RISER - GRAD SUITE SCALE: N.T.S. 5 P-401 SANITARY RISER - GRAD SUITE SCALE: N.T.S. 6 P-401 PLUMBING PLAN - GRAD SUITE KEY PLAN SCALE: 1/4" = 1'-0" A B REVISION NO. DESCRIPTION DATE AHA PROJECT NUMBER 12/14/2015 4:20:55 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 G1215-004.00 DATE 03 DECEMBER 2015 ISSUE CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING ENLARGED PLANS REVISED 15 DECEMBER 2015 SHEET NO. P-401 L 12.8 11 CW RISER ARCHITECT 4"SAN RISER 1/2" HW HKS, INC. TWO LIVE OAK CENTER HW RISER 3"VENT RISER 1/2" CW 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT 1/2" CW 2" V MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET 3/4" HW 1/2" HW 2" V 1/2" CW 3/4" CW D K J HARRISBURG, PA 17102-2499 MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 1/2" CW L1 1/2" HW SITE/CIVIL ENGINEER 1/2" CW DERCK & EDSON ASSOCIATES 2" S L1 3" S 33 SOUTH BROAD STREET 2"W & V 1/2" CW 1/2"H & CW DN 3"VENT RISER GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2"SHOWER DRAIN WC1 3" S 2701 CAROLEAN INDUSTRIAL DRIVE WC1 STAE COLLEGE, PA 16801 3" S 3" HD LITITZ, PA 17543 2" S SH2 SH2 1/2"CW DN L1 WBCM WC1 1/2" HW 3"VENT RISER STRUCTURAL ENGINEER 100 STERLING PARKWAY, SUITE 108 HW RISER 2" S 3" S MECHANICSBURG, PA 17050 CW RISER C.2 2" S 4"SAN RISER 4"SAN RISER SH2 1/2"H & CW DN CW RISER C 3/4" CW 3/4" HW HW RISER NOTE: 3" HUB DRAIN WITH TRAP GUARD IN MECHANICAL CLOSET OCCURS IN BOTTOM LEVEL ONLY. COORDINATE EXACT LOCATION WITH EQUIPMENT. REFER TO DETAIL 3/P-502. 7 1 P-402 WATER RISER - RA SUITE (ZONE B) SCALE: N.T.S. 2 P-402 SANITARY RISER - RA SUITE (ZONE B) 3 SCALE: N.T.S. P-402 PLUMBING PLAN - RA SUITE (ZONE B) SCALE: 1/4" = 1'-0" O 20.8 HW RISER CW RISER 3/4" HW 1/2" HW 1/2" CW V 1/2" HW 3" VENT RISER 3/4" CW 4"SAN RISER 1/2" HW 1/2" CW 18 1/2" CW 3"VENT RISER 1/2" HW 2"W & V 4"SAN RISER SH1 2" V 1/2"H & CW DN 1/2"CW DN SH1 1/2" CW 1/2" CW 2"SHOWER DRAIN L1 L1 3" S L1 WC1 3" HD 2" S 3/4" CW 3" S 2" S WC1 1/2" HW V.7 3" S HW RISER 3" S CW RISER 3" HD 2" S WC1 2" S V.8 CW RISER 1/2"H & CW DN 3" S BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE 3" HD HW RISER SH1 W KEY PLAN 2" S 3" S NOTE: 3" HUB DRAIN WITH TRAP GUARD IN MECHANICAL CLOSET OCCURS IN BOTTOM LEVEL ONLY. COORDINATE EXACT LOCATION WITH EQUIPMENT. REFER TO DETAIL 3/P-502. 4"SAN RISER A 4 P-402 WATER RISER - RA SUITE (ZONE A) SCALE: N.T.S. 5 P-402 SANITARY RISER - RA SUITE (ZONE A) SCALE: N.T.S. 6 P-402 PLUMBING PLAN - RA SUITE (ZONE A) B SCALE: 1/4" = 1'-0" REVISION NO. DESCRIPTION DATE AHA PROJECT NUMBER 12/14/2015 4:11:26 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 G1215-004.00 DATE 03 DECEMBER 2015 ISSUE CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING ENLARGED PLANS REVISED 15 DECEMBER 2015 SHEET NO. P-402 5.3 6 ARCHITECT HKS, INC. TWO LIVE OAK CENTER 1/2" HW 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 3/4" CW 2" V 3"VENT RISER 2" V A ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1/2" CW 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 1/2" HW 4"SAN RISER MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 2" V 1/2" CW SITE/CIVIL ENGINEER 1/2" CW 1/2" HW SH1 SH1 DERCK & EDSON ASSOCIATES 4"SAN RISER 33 SOUTH BROAD STREET 3"VENT RISER LITITZ, PA 17543 1/2"CW DN 2"SHOWER DRAIN GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. L1 3" HD STAE COLLEGE, PA 16801 2" S WC1 CW RISER 2701 CAROLEAN INDUSTRIAL DRIVE L1 3" S 3" S WC1 3" S 2" S WC1 3" S 1/2" CW STRUCTURAL ENGINEER WBCM 2" S 2" S 100 STERLING PARKWAY, SUITE 108 HW RISER MECHANICSBURG, PA 17050 CW RISER L1 2" S 3" S 1/2"H & CW DN SH1 3" S B 1/2"H & CW DN 2" V 2"W & V 3/4" CW 1/2" HW BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE HW RISER NOTE: 3" HUB DRAIN WITH TRAP GUARD IN MECHANICAL CLOSET OCCURS IN BOTTOM LEVEL ONLY. COORDINATE EXACT LOCATION WITH EQUIPMENT. REFER TO DETAIL 3/P-502. WATER RISER - DOUBLE SUITE 1 P-403 2 SCALE: N.T.S. P-403 SANITARY RISER - DOUBLE SUITE PLUMBING PLAN - DOUBLE SUITE 3 SCALE: N.T.S. P-403 SCALE: 1/4" = 1'-0" CW RISER 1/2" HW 4"SAN RISER HW RISER 3"VENT RISER 3/4" HW 1/2" CW 3/4" CW O P 3/4" HW 1/2" CW 2" V 1/2" HW 1/2" HW 3/4" CW 2" V 3/4" CW 2" V 1/2" CW 1/2"CW DN 1/2" HW 3"VENT RISER 4"SAN RISER 1/2" HW 1/2" CW L1 1/2" CW 4"SAN RISER 3"VENT RISER 1/2" CW 3"VENT RISER 1/2"CW DN L1 4"SAN RISER 2" S 3" S 3" HD HW RISER WC1 CW RISER 1/2" CW SH1 L1 2" S 2" V 2" V L1 WC1 WC1 1/2" CW WC1 Q SH1 1/2" CW 3/4" CW 2" S 2" S 2"SHOWER DRAIN 3" S 3" S 1/2"H & CW DN R 3" S L1 3"VENT RISER 1/2"H & CW DN 2" V 2" S 3/4" HW L1 SH1 3/4" CW 1/2" HW WC1 CW RISER 2"W & V HW RISER 1/2" HW 3/4" CW 2" V 1/2"H & CW DN 2"W & V NOTE: 3" HUB DRAIN WITH TRAP GUARD IN MECHANICAL CLOSET OCCURS IN BOTTOM LEVEL ONLY. COORDINATE EXACT LOCATION WITH EQUIPMENT. REFER TO DETAIL 3/P-502. 3"VENT RISER 4"SAN RISER WC1 KEY PLAN 2" S 14 14.1 15 16 A 4 P-403 WATER RISER - TRIPLE SUITE SCALE: N.T.S. 5 P-403 SANITARY RISER - TRIPLE SUITE SCALE: N.T.S. 4"SAN RISER 6 P-403 PLUMBING PLAN - TRIPLE SUITE SCALE: 1/4" = 1'-0" B REVISION NO. DESCRIPTION DATE AHA PROJECT NUMBER 12/14/2015 4:11:43 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 G1215-004.00 DATE 03 DECEMBER 2015 ISSUE CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING ENLARGED PLANS REVISED 15 DECEMBER 2015 SHEET NO. P-403 4"SAN RISER 3"VENT RISER 1/2" CW 1/2" CW ARCHITECT 2" V 3/4" CW HKS, INC. D 3/4" CW 1/2" CW 3/4" HW 1/2" HW 1/2" HW TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1/2" CW 1600 NORTH SECOND STREET 2" V HARRISBURG, PA 17102-2499 3/4" CW SH1 4"SAN RISER SH1 1/2" CW WC1 1/2" HW 3/4" CW 3/4" HW WC1 2"SHOWER DRAIN 3"VENT RISER 2" V 1/2" HW L1 1/2" CW CW RISER HW RISER 3" S DERCK & EDSON ASSOCIATES 2" V 33 SOUTH BROAD STREET LITITZ, PA 17543 3" S 3" HD 2" V 3" S 2" S 1/2" CW 2"SHOWER DRAIN SH1 SH1 WC1 2701 CAROLEAN INDUSTRIAL DRIVE WC1 C.2 CW RISER 3" S WC1 2" S CMT LABORATORIES, INC. 2" S 3/4" CW L1 3/4" CW 2" S 1/2"H & CW DN 1/2"H & CW DN HW RISER L1 WBCM 100 STERLING PARKWAY, SUITE 108 SH1 L1 MECHANICSBURG, PA 17050 3" S 2" S STAE COLLEGE, PA 16801 STRUCTURAL ENGINEER 3/4" HW SH1 GEOTECHNICAL ENGINEER 2" V 3/4" HW 3" S WC1 1/2" CW 3" S 3/4" CW 3" S L1 SITE/CIVIL ENGINEER 1/2"CW DN 3" HD 2" S 1/2" HW 1/2" CW ROSWELL, GA 30076 1/2"CW DN 2" S 1/2" CW 1801 OLD ALABAMA RD, SUITE 125 4"SAN RISER L1 1/2" HW AHA CONSULTING ENGINEERS 3"VENT RISER 3"VENT RISER 4"SAN RISER MEP ENGINEER C 2" S 1/2" HW 1/2"H & CW DN 2"W & V 2" V 1/2" HW 3/4" CW 1/2"H & CW DN 2"W & V 5 1 P-404 WATER RISER - QUAD SUITE 2 SCALE: N.T.S. P-404 SANITARY RISER - QUAD SUITE 3 SCALE: N.T.S. P-404 4.4 4 PLUMBING PLAN - QUAD SUITE SCALE: 1/4" = 1'-0" HW RISER CW RISER 3/4" CW 3/4" CW D 3"VENT RISER 2" V 3/4" CW 2" V 3/4" CW 3/4" HW 1/2" HW 1/2" HW 2" V 1/2" HW 1/2" CW 1/2" CW CONNECT TO 3"VENT RISER 1/2" CW 1/2" HW 1/2" CW 4"SAN RISER L1 1/2" HW 3" S L1 SH1 L1 1/2"CW DN WC1 1/2" CW L1 1/2" CW SH1 3" S 1/2"H & CW DN 2" S CW RISER WC1 HW RISER 3" HD SH1 3" S SH1 WC1 WC1 2" S ROUTED IN WALL CW RISER 3/4" CW 3" HD 3/4" HW L1 C.2 4"SAN RISER L1 3" S WC1 WC1 3/4" HW HW RISER 3" S SH1 C SH1 2" S 3" S 1/2"H & CW DN (TYP @ EACH L1) 3" S BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE NOTE: 3" HUB DRAIN WITH TRAP GUARD IN MECHANICAL CLOSET OCCURS IN BOTTOM LEVEL ONLY. COORDINATE EXACT LOCATION WITH EQUIPMENT. REFER TO DETAIL 3/P-502. 2"W & V 1/2"CW DN 2" V 3/4" CW 1/2" HW 2"SHOWER DRAIN NOTE: 3" HUB DRAIN WITH TRAP GUARD IN MECHANICAL CLOSET OCCURS IN BOTTOM LEVEL ONLY. COORDINATE EXACT LOCATION WITH EQUIPMENT. REFER TO DETAIL 3/P-502. 2" S 5 4.4 4 KEY PLAN 4 P-404 WATER RISER - QUAD SUITE A SCALE: N.T.S. 5 P-404 SANITARY RISER - QUAD SUITE A SCALE: N.T.S. 6 P-404 PLUMBING PLAN - QUAD SUITE A SCALE: 1/4" = 1'-0" A B REVISION NO. DESCRIPTION DATE AHA PROJECT NUMBER 12/14/2015 4:21:09 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 G1215-004.00 DATE 03 DECEMBER 2015 ISSUE CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING ENLARGED PLANS REVISED 15 DECEMBER 2015 SHEET NO. P-404 C.2 E 3/4" HW 3/4" CW C A.5 D B A CONNECT TO 4"SAN RISER 3/4" CW 1 3"VENT RISER 1/2" CW ARCHITECT HKS, INC. 2" V 3/4" CW TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 2" V 3/4" HW ASSOCIATE ARCHITECT 2" V 1/2" CW 3/4" CW 1/2" CW ATLANTA, GA 30326 MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET 1/2" HW 1/2" HW 1/2" HW 4"SAN RISER 3"VENT RISER 1/2" CW HARRISBURG, PA 17102-2499 MEP ENGINEER 1/2" HW L1 AHA CONSULTING ENGINEERS 1/2" CW 1801 OLD ALABAMA RD, SUITE 125 1/2" CW L1 L1 1/2" CW ROSWELL, GA 30076 3" HD SH1 3" S L1 HW RISER SH1 CW RISER SITE/CIVIL ENGINEER WC1 1/2"H & CW DN 1/2" HW DERCK & EDSON ASSOCIATES 2" V 33 SOUTH BROAD STREET WC1 2" S 3" S SH1 3" S 3" S LITITZ, PA 17543 1/2"CW DN 3" S GEOTECHNICAL ENGINEER SH1 2" S ROUTED IN WALL WC1 2" S L1 3" S CMT LABORATORIES, INC. 3/4" CW 3/4" HW WC1 WC1 3" S 3" S 2701 CAROLEAN INDUSTRIAL DRIVE 3/4" CW L1 WC1 SH1 3/4" HW STAE COLLEGE, PA 16801 SH1 2 2" S 3" HD 3" S 2"SHOWER DRAIN 3" S CW RISER 2" S HW RISER 2"W & V 2" V 1/2" HW 1/2"CW DN 3/4" CW 1/2"H & CW DN (TYP @ EACH L1) STRUCTURAL ENGINEER WBCM 100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050 1/2"H & CW DN 2" V NOTE: 3" HUB DRAIN WITH TRAP GUARD IN MECHANICAL CLOSET OCCURS IN BOTTOM LEVEL ONLY. COORDINATE EXACT LOCATION WITH EQUIPMENT. REFER TO DETAIL 3/P-502. 8 P-405 WATER RISER - QUAD SUITE B 2 SCALE: N.T.S. P-405 SANITARY RISER - QUAD SUITE B 3 SCALE: N.T.S. P-405 PLUMBING PLAN - QUAD SUITE B SCALE: 1/4" = 1'-0" 8 A CW RISER 3/4" CW 1/2" CW HW RISER 3"VENT RISER 1/2" HW 4"SAN RISER 2" V 3"VENT RISER 2"W & V 4"SAN RISER 1/2"H & CW DN 1/2" HW 3/4" CW 1/2" HW 3" S 2" S 2" V 1/2" CW 1/2"CW DN 2" V SH1 1/2" HW 1/2" CW WC1 L1 SH1 1/2" CW 3/4" HW 3/4" CW 2"SHOWER DRAIN 1/2" HW WC1 2" S L1 1/2" HW 1/2" CW 3/4" CW WC1 3" S L1 2" S 2" S 1/2"H & CW DN 3" S 3"VENT RISER 2" S 1/2" HW 3" S HW RISER CW RISER 1/2" CW 3" S F SH1 B 3" HD 1/2" CW 3/4" CW 1/2" HW 3/4" HW 4"SAN RISER 3/4" CW 4"SAN RISER 3"VENT RISER SH1 1/2" HW 1/2" HW SH1 2" V 3"HD 1/2" CW 3" S CW RISER C L1 2" S HW RISER L1 WC1 3" S 2" S 1/2" CW 2" V 2" S WC1 2"W & V C.2 WC1 KEY PLAN 3" S 1/2" HW 11 13 G I NOTE: 3" HUB DRAIN WITH TRAP GUARD IN MECHANICAL CLOSET OCCURS IN BOTTOM LEVEL ONLY. COORDINATE EXACT LOCATION WITH EQUIPMENT. REFER TO DETAIL 3/P-502. P-405 SCALE: N.T.S. 5 P-405 SANITARY RISER - QUAD SUITE C SCALE: N.T.S. 1/2"H & CW DN 2" V 4"SAN RISER WATER RISER - QUAD SUITE C 1/2" CW 2" V 2" S SH1 1/2"H & CW DN 2" S 2" S F.3 1/2"CW DN 3" S 2"SHOWER DRAIN L1 4 BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE 3 6 P-405 14 A H PLUMBING PLAN - QUAD 12.8 SUITE C B SCALE: 1/4" = 1'-0" REVISION NO. DESCRIPTION DATE AHA PROJECT NUMBER 12/14/2015 4:12:30 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 G1215-004.00 DATE 03 DECEMBER 2015 ISSUE CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING ENLARGED PLANS REVISED 15 DECEMBER 2015 SHEET NO. P-405 3"VENT RISER 4"SAN RISER 1/2" CW ARCHITECT 2" V 1/2" HW HKS, INC. 3/4" CW 1/2" CW Z 3/4" HW TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 1/2" HW ATLANTA, GA 30326 ASSOCIATE ARCHITECT 3/4" CW MURRAY AND ASSOCIATES ARCHITECTS 3/4" HW 1600 NORTH SECOND STREET 19 3/4" CW 1/2" HW 3/4" HW 1/2" CW 3/4" CW SH1 1/2" CW 2" V HARRISBURG, PA 17102-2499 MEP ENGINEER 3/4" HW AHA CONSULTING ENGINEERS 3/4" CW 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 WC1 WC1 Y.5 SH1 SH1 3" S 4"SAN RISER SH1 SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 3"VENT RISER 33 SOUTH BROAD STREET 1/2" CW 3" S 1/2"CW DN 3" S 3" S 1/2" HW 2" V 1/2" CW 3" S 1/2"H & CW DN 2" S GEOTECHNICAL ENGINEER 3/4" CW CMT LABORATORIES, INC. 3" S 2701 CAROLEAN INDUSTRIAL DRIVE 2" V 2" S 3" S Y WC1 L1 1/2" CW STAE COLLEGE, PA 16801 2" S 3" S L1 WC1 X.51/2"H & CW DN 2"SHOWER DRAIN L1 3" S 1/2"CW DN 3" S STRUCTURAL ENGINEER CW RISER L1 WBCM HW RISER 100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050 L1 L1 1/2" HW 3" S 3" S SH1 X WC1 SH1 3/4" CW 1/2" HW 2" S U 2"W & V 2" V 3/4" HW HW RISER CW RISER 1/2"H & CW DN (TYP @ EACH L1) NOTE: 3" HUB DRAIN WITH TRAP GUARD IN MECHANICAL CLOSET OCCURS IN BOTTOM LEVEL ONLY. COORDINATE EXACT LOCATION WITH EQUIPMENT. REFER TO DETAIL 3/P-502. 2" S 3" HD 22 1 P-406 WATER RISER - QUAD SUITE D 2 SCALE: N.T.S. P-406 SANITARY RISER - QUAD SUITE D 21 R20 19.9 20.8 S T.5 PLUMBING PLAN - QUAD SUITE D 3 SCALE: N.T.S. 21.5 P-406 SCALE: 1/4" = 1'-0" 4"SAN, SEE FLOOR PLAN FOR CONTINUATION 2"V, SEE FLOOR PLAN FOR CONTINUATION 12 11 2" V SEE FLOOR PLAN FOR CONTINUATION 4" S 2" V 3/4" HW 2" V 1 1/4" CW 2" V T.5 2" V 2" V 1/2" HW 1 1/4" CW WC4 4" S 1 1/4" CW 1/2" CW 10 2"V DN L5 SA"A" WC4 L5 2"VENT UP TO VENT RISER ON FLOOR ABOVE L5 2" S 3" S 3" FD-A WITH TRAP GUARD 3" S 2"W & V STACK 1-1/4"CW & 1/2"HW, SEE FLOOR PLAN FOR CONTINUATION WC4 T 1-1/4"CW DN 4"SAN UP TO SAN RISER ON FLOOR ABOVE 1" CW BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE 1/2" CW LITITZ, PA 17543 WC1 4"SAN DN TO FLOOR BELOW S 4"SAN, SEE FLOOR PLAN FOR CONTINUATION KEY PLAN 6 P-406 WATER RISER - FIRST FLOOR TOILET #112 5 SCALE: N.T.S. P-406 SANITARY RISER - FIRST FLOOR TOILET #112 SCALE: N.T.S. 4 P-406 PLUMBING PLAN - 1ST FLOOR TOILET ROOM #112 A SCALE: 1/4" = 1'-0" 13 SEE FLOOR PLAN FOR CONTINUATION B REVISION NO. DESCRIPTION 1" CW DATE 1/2" HW 1/2"H & CW DN 2" V 1 1/4" CW 3" FD-A WITH TRAP GUARD 1" CW 1/2" HW WC4 SEE FLOOR PLAN FOR CONTINUATION 1/2" HW 1/2" CW 2"W & V STACK 3"S, SEE FLOOR PLAN FOR CONTINUATION 2" S 2" V 4"S, SEE FLOOR PLAN FOR CONTINUATION 2" V 2" V WC4 1"CW DN SA"A" 2" S R L5 TEMPLATE VERSION: 2.6.8.20141012 12/14/2015 4:12:58 PM S 4"SAN DN EXTEND AND CONNECT TO HOT & COLD WATER PIPING A/C, SEE FLOOR PLAN SA"A" L5 2" V 1" CW 2" V PLOT DATE: 1 1/4" CW AHA PROJECT NUMBER G1215-004.00 2"V, SEE FLOOR PLAN FOR CONTINUATION L5 DATE 03 DECEMBER 2015 2"V DN 2" S WC4 Q 3" S 4" S ISSUE CONSTRUCTION DOCUMENTS 4" S SHEET TITLE 3" S 9 P-406 WATER RISER - 00 FLOOR TOILET #017 SCALE: N.T.S. 8 P-406 SANITARY RISER - 00 FLOOR TOILET #017 SCALE: N.T.S. PLUMBING ENLARGED PLANS 3" FD-A WITH TRAP GUARD 7 P-406 PLUMBING PLAN - 00 GROUND FLOOR - TOILET ROOM #017 SCALE: 1/4" = 1'-0" REVISED 15 DECEMBER 2015 SHEET NO. P-406 6" DOMESTIC WATER (RPZ) BACKFLOW PREVENTER, 8"FIRE SERVICE (DDCVA)BACKFLOW PREVENTER, 2 1/2" NPW (RPZ) BACKFLOW PREVENTER, SUPPORTED FROM FLOOR WITH THE CENTER LINE OF PIPE A MINIMUM OF 18" OFF OF WALL. REFER TO P-702 & 11/P-501 ARCHITECT 16 SEE P-101 FOR CONTINUATION 15 SEE DETAIL 9/P-501 SEE DETAIL 13/P-501 DWB WH 1 1 4" CW x.2 14.8 SEE DETAIL 13/P-501 x.4.1 14.114 SEE DETAIL 14/P-501 SEE DETAIL 14/P-501 WH WH WH 2 3 4 HKS, INC. x.6 13 12 11 10 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 3/4"GAS B/G FOR FIRE PIT 4" CW TWO LIVE OAK CENTER 1600 NORTH SECOND STREET 9 HARRISBURG, PA 17102-2499 8"DN 6"DN MEP ENGINEER 4" CW AHA CONSULTING ENGINEERS PRV ASSEMBLY SEE P-702 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 4"FD-B 6" CW 4"FD-B 8"DN 10"HD DERCK & EDSON ASSOCIATES REFER TO RISER DIAGRAMS FOR CONTINUATION OF ALL OF THIS PIPING. 140° 2 1/2" HW 1 1/4" HW 8" WS 33 SOUTH BROAD STREET LITITZ, PA 17543 4" S GEOTECHNICAL ENGINEER 4"FD-B 140° FCO BACKWATER VALVE, SEE DEVICE SCHEDULE SITE/CIVIL ENGINEER 4" CW CMT LABORATORIES, INC. 4"FD-B 2701 CAROLEAN INDUSTRIAL DRIVE 3/4" HWR FCO 4"FD-B 4"FD-B STAE COLLEGE, PA 16801 6"W & 3"V STRUCTURAL ENGINEER 2 1/2" HW WBCM 6" S 6" S 100 STERLING PARKWAY, SUITE 108 6" S MECHANICSBURG, PA 17050 6" S SEE P-409 FOR CONTINUATION 4"FD-B 1 1/2" HWR 1 1/2" HWR 3" V 3" CW 4"FD-B 6"FD-C 2 1/2" HW 1 1/2" HWR 2 1/2" HW 3" CW BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE 1 1/2" HWR y.6.5 3/4" HWR 1 1/4" HW 2 1/2" HW 140° 140° y.6 3"W DN 3" S 2"V UP 3" V 3/4" G 1" G 4"SAN DN 4"FD-B 4"FD-B 1" G 1" G 1 1/4" HW 3/4" HWR SEE P-409 FOR CONTINUATION 3"W UP 3" S FCO 140° 1" G 4" S 4" S 140° FIRE PUMP CONTROL PANEL 3" CW 2 1/2" CW 2 1/2" HW 4" S 4" S 1" G 4"FD-B 3" V 1 1/2" HWR 8" WS 2 1/2" G JOCKEY PUMP CONTROL PANEL 2" GAS DN TO 24" A/F 1 1/2" HWR 2 1/2" HW 3" CW 6" S 2 1/2" G 6" WS 1/2"H & CW DN 1 1/2" HWR FP 4"FD-B 1 1/2" HWR 3" S 1 4" WS 2"V DN 4" S FCO 3/4" CW 1 1/4" CW 8" WS 3/4" HW 1 1/4" HW EMSH SEE DETAIL 6/P-701 4"W & 3"V 4"FD-B DRY SPRINKLER VALVE 8" WS FCO 6"RL DN (3194 sf) W/ CO @ 18" AFF 4"FD-B 2" V 4" S 6"HUB DRAIN, SEE DETAIL 4/P-501 1-1/4"H & CW DN TO MIXING VALVE FOR EMERGENCY SHOWER & EYEWASH 6"W & 3"V 4"FD-B CO 6" RL 3" V 2-1/2" GAS DN TO B/G 3" V 3"V UP 6" S 2" PD NFWH-2 @ 18" A.F.F. 4" WS 6" S S 1 P-407 6"RL DN (5391 sf) W/ CO @ 18" AFF SEE P-101 FOR CONTINUATION SEE P-101 FOR CONTINUATION 6" RL (5391 sf) 6"RL UP (3194 sf) (8585 sf) 8" RL SEE P-101 FOR CONTINUATION T.5 U U.3 KEY PLAN PLUMBING PLAN - CENTRAL PLANT A SCALE: 1/4" = 1'-0" B REVISION NO. DESCRIPTION DATE AHA PROJECT NUMBER 12/14/2015 4:21:21 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 G1215-004.00 DATE 03 DECEMBER 2015 ISSUE CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING ENLARGED PLANS REVISED 15 DECEMBER 2015 SHEET NO. P-407 REVISED 15 DECEMBER 2015 REVISED 15 DECEMBER 2015 2-1/2" HVAC MAKE-UP BACKFLOW PRENVENTER DISCHARGE FLOOR 3 COMBINATION STANDPIPE WET PIPE SPRINKLER RISER IN STAIR 2 5 4 TO SPRINKLER SYSTEM 5 OIL MINDER POWER CABLE, PROBE CABLE AND HIGH LIQUID ALARM CABLE. 9 7 7 ELEVATOR MACHINE ROOM ELEVATOR PIT 8 9 23 1/2"X23 1/2" OPEN GRATING WITH CUT OUT FOR DISCHARGE BY THE G.C. 2 1/2" FIRE DEPARTMENT VALVE (FDV) W/ 1 1/2" REDUCER, CAP AND CHAIN 3" CAPPED HOSE CONNECTION AND ADAPTER FLOOR 1600 NORTH SECOND STREET STANDPIPE (SIZE INDICATED ON DRAWINGS) FINISHED FLOOR AHA CONSULTING ENGINEERS 2" FLOOR ROSWELL, GA 30076 SITE/CIVIL ENGINEER 8 PUMPED DISCHARGE, SEE DWGS. FOR SIZE & CONTINUATION 33 SOUTH BROAD STREET LITITZ, PA 17543 6 9 DERCK & EDSON ASSOCIATES FLOW FLOW 4" SCHED 40PVC CONDUIT WITH LONG RADIUS BENDS 1 1/4" 1 GEOTECHNICAL ENGINEER 10" RAIN LEADER B/F OIL MINDER POWER CABLE, PROBE CABLE, AND HIGH LIQUID ALARM CABLE, LENGTHS AS REQUIRED, IN CONDUIT. 10 CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE 3 STAE COLLEGE, PA 16801 PUMP ON-OFF FLOAT STRUCTURAL ENGINEER 2 WBCM 100 STERLING PARKWAY, SUITE 108 2 P-501 ELEVATOR SUMP PUMP PIPING DIAGRAM SCALE: N.T.S. RISER 5 CHECK VALVE 2 OS&Y VALVE W/SUPERVISORY SWITCH 6 INSPECTORS TEST VALVE 3 PRESSURE GAUGE W/SHUT-OFF VALVE 7 1" SIGHT GLASS 4 WATERFLOW SWITCH 8 UNION ORIFICE 9 AUXILARY DRAIN VALVE SCALE: N.T.S. HUB DRAIN FOR ELEVATOR SUMP PUMP DISCHARGE FDC WALL PLATE ALL BRONZE REDUCED PRESSURE BACKFLOW PREVENTER ASSEMBLY REFER TO DETAIL 12/P-501 2-1/2" NON-POTABLE WATER, SEE MECH. DWGS FOR CONTINUATION FIRE DEPARTMENT CONNECTION WITH INLETS PARALLEL TO THE SIDE WALK. EMERGENCY GENERATOR GAS COCK (TYP) UNION 6" CW TO SYSTEM BALL DRIP FINISHED FLOOR FINISHED GRADE OR SIDEWALK FULL SIZE DIRT LEG ALL BRONZE REDUCED PRESSURE BACKFLOW PREVENTER ASSEMBLY 6" DOMESTIC WATER MAIN BALL DRIP DISCHARGE THROUGH WALL 2-1/2" EPOXY COATED OS&Y VALVE SLEEVE SUPPORT PROVIDED AND INSTALLED BY THIS CONTRACTOR, CONSULT A STRUCTURAL ENGINEER FOR EXACT CONSTRUCTION 36" ABOVE FINISHED FLOOR FLOOR NOTE: NOTE: THE GAS PRESSURE REGULATOR SHALL BE INSTALLED A MINIMUM OF 5' UPSTREAM OF THE EQUIPMENT GAS CONNECTION POINT. SHOWN HERE FOR CLARITY ONLY. FIRE DEPARTMENT AND FLOOR CONTROL VALVES P-501 CONNECTION TO GAS FIRED EQUIP. 5 SCALE: N.T.S. P-501 FINISHED FLOOR INSTALL FIRE DEPARTMENT CONNECTION 36" ABOVE FINISHED GRADE SCALE: N.T.S. DRAIN TO CLEARWATER HUB DRAIN, SEE DETAIL 3/P-501. SUPPORT ON WALL NOTES: 1. FURNISH TO OWNER ONE TEST KIT AND SPARE PARTS KIT. THE PLUMBING CONTRACTOR SHALL ACT AS THE OWNERS AGENT IN SEEKING APPROVAL FROM ALL LOCAL 2. AND STATE AUTHORITIES. THIS CONTRACTOR SHALL SUBMIT ALL PLANS, SPECS. AND APPLICATIONS REQUIRED FOR APPROVAL AND PAY ALL FEES. 3. SEE FLOOR PLANS FOR SIZES 4. MAINTAIN 1'-6" CLEARANCE FROM WALL. 5. TEST AND CERTIFY EACH INSTALLATION. FIRE DEPARTMENT CONNECTION (FDC) WALL MOUNTED 6 P-501 SCALE: N.T.S. 7 P-501 DOMESTIC WATER BACKFLOW PREVENTER SCALE: N.T.S. DOUBLE DECTECTOR CHECK VALVE ASSEMBLY (METERED BY-PASS NOT SHOWN) NOTES: DOMESTIC WATER MAIN FROM STREET PC SHALL PROVIDE (6) PRESSURE GUAGES, IN MAINTENENCE OFFICE, WITH CONNECTIONS TO SUIT INSTALLED BALANCING VALVE ASSEMBLY. FULL SIZE VALVED BY-PASS (NORMALLY CLOSED) DUPLEX DOMESTIC WATER BOOSTER PUMP PACKAGE BALANCING VALVES SHALL BE SET TO FLOW 0.5 GPM UNLESS NOTED OTHERWISE. CHECK VALVE (TYP) DOMESTIC WATER TO BLDG. EPOXY COATED OS&Y VALVE WITH SUPERVISORY SWITCH THIS ASSEMBLY SHALL OCCUR ABOVE THE CEILING IN THE COORIDOR AT THE TOP OF EACH HOT WATER RISER AT THE CIRULATION LOOP AS SHOWN ON 1/8" SCALE FLOOR PLANS. EPOXY COATED OS&Y VALVE WITH SUPERVISORY SWITCH 8" FIRE SERVICE MAIN 8" TO SPRINKLER SYSTEM FLOOR CONCRETE INERTIA PAD (BY GC) THERMOMETER (TYP) 3/4" FROM HOT WATER RISER SUPPORT PROVIDED AND INSTALLED BY PLUMBING CONTRACTOR, CONSULT A STRUCTURAL ENGINEER FOR EXACT CONSTRUCTION 36" ABOVE FINISHED FLOOR 3/4"HOSE END DRAIN (TYP) TO STANDPIPE FLOOR CHECK VALVE 3/4" TO CIRCULATION SYSTEM 8 P-501 SHUT-OFF VALVE (TYP) BALANCING VALVE: B&G CB-3/4LF W/ TEST PORTS FOR PRESSURE GUAGES BALANCING VALVE ASSEMBLY 9 SCALE: N.T.S. DOMESTIC BOOSTER PUMP (DUPLEX) P-501 FINISHED FLOOR SUPERVISED STANDPIPE CONTROL VALVE FULL SIZE FLEXIBLE CONNECTORS (TYP) BY PC SEE PUMP SCHEDULE FOR PUMP CHARACTERISTICS MECHANICSBURG, PA 17050 SCALE: N.T.S. 2-1/2" CW PRESSURE REGULATOR (VENTLESS): PIETRO FIORENTINI MODEL 30153-DC INLET= 2psi / OUTLET = 15"W.C. (MAX. 20" W.C.) 4" 4 P-501 EXTERIOR WALL TEE FITTING WITH TEST PLUG (TYP) 1 CLEARWATER HUB DRAIN FOR BFP DISCHARGE 3 P-501 ROUTE DRAINS TO INDIRECT WASTE RECEPTOR OR TO GRADE 1 HARRISBURG, PA 17102-2499 MEP ENGINEER FINISHED FLOOR UNION 24"X24"X24" SUMP BY GC OIL CONTROL SYSTEM PROBE CONFIRM EXACT HEIGHT W/ FIRE MARSHALL 5' AFF (MAX) NOTE: RISER CLAMPS INSTALLED AT ALL FLOORS MURRAY AND ASSOCIATES ARCHITECTS 5 ANGLE IRON GRATING SUPPORT ALL SIDES BY GC C L ATLANTA, GA 30326 1801 OLD ALABAMA RD, SUITE 125 5 5 3445 PEACHTREE ROAD, NE, SUITE 675 ASSOCIATE ARCHITECT WALL SUPPORT POWER SUPPLY PD 3" DRAIN RISER TERMINATE PUMP DISCHARGE INSIDE STANDPIPE WITH AIR BREAK 10" STANDPIPE ELECTRICAL OUTLET NIPC 4 6 TWO LIVE OAK CENTER WALL SUPPORT GATE VALVE SS HKS, INC. TERMINATE BFP DISCHARGES INSIDE STANDPIPE WITH AIR BREAK PROVIDE A MINIMUM OF 5 FEET EXTRA OF EACH CABLE (SLACK) ROLLED AND CLAMPED TO THE DISCHARGE PIPE TO ALLOW FOR THE REMOVAL OF THE PUMP FROM THE PIT. 10 WATERTIGHT SLEEVE ARCHITECT HIGH LIQUID ALARM FLOAT WITH CLAMP DEVICE TO MOUNT TO PUMP DISCHARGE PIPING. 8 OIL CONTROL SYSTEM WITH OPTIONAL BUILT IN AUDIBLE AND VISUAL ALARM WHEN PUMP DOES NOT RUN DUE TO OIL IN PIT OR HIGH LIQUID ALARM. PROVIDE SILENCING BUTTON FOR AUDIBLE ALARM BUILT INTO PANEL. PANEL SHALL HAVE ADDITIONAL CONTACT FOR A REMOTE ALARM LOCATION. 10" x 12" INCREASER BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE 1 7 PUMP DISCHARGE (SIZE INDICATED ON DRAWINGS) 6" DOMESTIC BACKFLOW PREVENTER DISCHARGE FDC FIRE RATED PROTECTION PACKING ALL BURIED PUMP PRESSURE DISCHARGE PIPING SHALL BE PROTECTED WITH TAPECOAT CT CORROSION PROTECTION TAPE. BLEED HOLE 3/16 3 REFLUX CHECK VALVE 4 6 12" 2 SUBMERSIBLE EFFLUENT PUMP, REFER TO PUMP SCHEDULE FOR DISCHARGE CONNECTION SIZE. INSTALL REDUCER AT PUMP IF REQUIRED. 12" 1 10 SCALE: N.T.S. P-501 NOTES: 1. FURNISH TO OWNER ONE TEST KIT AND SPARE PARTS KIT. THE PLUMBING CONTRACTOR SHALL ACT AS THE OWNERS AGENT IN SEEKING APPROVAL FROM ALL LOCAL 2. AND STATE AUTHORITIES. THIS CONTRACTOR SHALL SUBMIT ALL PLANS, SPECS. AND APPLICATIONS REQUIRED FOR APPROVAL AND PAY ALL FEES. 3. SEE FLOOR PLANS FOR SIZES 4. MAINTAIN 1'-6" CLEARANCE FROM WALL. 5. TEST AND CERTIFY EACH INSTALLATION. BASE OF STANDPIPE VALVE ASSEMBLY 11 SCALE: N.T.S. P-501 KEY PLAN A FIRE SERVICE BACKFLOW PREVENTER SCALE: N.T.S. B WATER METER WITH REMOTE READER: CARLON 150 JLRFG T. & P. RELIEF VALVE - (WHEN NOT PROVIDED ON HEAT TRANSFER DEVICE) PIPED TO FLOOR DRAIN PRESSURE REDUCING VALVE (SET AT 4 PSIG HIGHER THAN THE PRESSURE AT THE HIGH POINT IN THE SYSTEM). COORDINATE WITH HVAC CONTRACTOR FOR FINAL SETTING NOTES: 1. ALL STEAM PIPING, VALVES, FITTINGS, ETC. TO BE FURNISHED AND INSTALLED BY HVAC CONTRACTOR. CHECK VALVE (TYP) GATE VALVE (TYP) GLOBE VALVE (NORMALLY CLOSED) HOT WATER RETURN SEE P-702 PRESSURE GAUGE W/ NEEDLE VALVE FULL SIZE BY-PASS 2. FINAL CONNECTION OF STEAM PIPING TO BE BY HVAC CONTRACTOR. VACUUM RELIEF VALVE (TYP) 3. CONTROLLERS SHALL BE WIRED TO THE BAS SYSTEM SO THAT EACH HEATER OPERATES IN A LEADLAG SEQUENCE. WIRING SHALL BE FURNISHED AND INSTALLED BY HVAC CONTRACTOR. PRESSURE RELIEF VALVE (TYP) PIPE TO DRAIN CHECK VALVE (TYP) GATE VALVE (TYP) HOT WATER RETURN SEE P-702 THERMOMETER (TYP) 2-1/2" HW (160°) TO MIXING VALVE STATION SEE DETAIL 2/P-502 2-1/2" 2-1/2"CW SUPPLY SEE P-702 REDUCED PRESSURE TYPE BACK FLOW PREVENTER NOTES: 1. ALL STEAM PIPING, VALVES, FITTINGS, ETC. TO BE FURNISHED AND INSTALLED BY HVAC CONTRACTOR. OMEGA TYPE-J THERMOCOUPLE WITH LOVE CONTROLLER COMPACT CONTROL BOX (TYP FOR EACH HEATER) FILL LINE (2-1/2") BALL VALVE (TYP) 12/14/2015 4:13:46 PM TEMPLATE VERSION: 2.6.8.20141012 UNION (TYP) PLOT DATE: VACUUM RELIEF VALVE (TYP) 3. CONTROLLERS SHALL BE WIRED TO THE BAS SYSTEM SO THAT EACH HEATER OPERATES IN A LEADLAG SEQUENCE. WIRING SHALL BE FURNISHED AND INSTALLED BY HVAC CONTRACTOR. PRESSURE RELIEF VALVE (TYP) PIPE TO DRAIN 2-1/2" HW (160°) TO MIXING VALVE STATIONS SEE DETAIL 1/P-502 2-1/2" WATER SOLENOID DISCHARGE (TYP) PIPE TO DRAIN STEAM CONNECTION (BY HVAC CONTRACTOR, TYPICAL) CIRCULATION PUMP (CP-4 & 5) SEE PUMP SCHEDULE 2-1/2" WH-2 OMEGA TYPE-J THERMOCOUPLE WITH LOVE CONTROLLER COMPACT CONTROL BOX (TYP FOR EACH HEATER) 2-1/2" 2-1/2" 2-1/2" WH-3 STEAM WATER HEATERS: SEE WATER HEATER SCHEDULE WH-4 FINISHED FLOOR DATE 2-1/2" 4"HOUSEKEEPING PAD (BY GC) CONNECT STEAM TO EXCHANGER (BY HVAC CONTRACTOR) G1215-004.00 03 DECEMBER 2015 2-1/2" 4"HOUSEKEEPING PAD (BY GC) CONNECT STEAM TO EXCHANGER (BY HVAC CONTRACTOR) AHA PROJECT NUMBER 2-1/2" EXPANSION TANK: 22 GALLON (ACCEPTANCE VOLUMN) EXPANSION TANK: 22 GALLON (ACCEPTANCE VOLUMN) 2-1/2" DRAIN TO CLEARWATER HUB DRAIN, SEE DETAIL 3/P-501. SUPPORT ON WALL. CIRCULATION PUMPS (CP-6 & 7) SEE PUMP SCHEDULE 1" STEAM WATER HEATERS: SEE WATER HEATER SCHEDULE 2-1/2" WH-1 PROVIDED BY PLUMBING CONTRACTOR FINISHED FLOOR REDUCER (WHERE REQUIRED) ISSUE CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING DETAILS 12 P-501 HVAC MAKE-UP WATER SCALE: N.T.S. 13 P-501 WATER HEATERS (WH-1 & WH-2) SCALE: N.T.S. DATE THERMOMETER (TYP) WATER SOLENOID DISCHARGE (TYP) PIPE TO DRAIN 1" PROVIDED BY HVAC CONTRACTOR 2. FINAL CONNECTION OF STEAM PIPING TO BE BY HVAC CONTRACTOR. 2-1/2"CW SUPPLY SEE P-702 STEAM CONNECTION (BY HVAC CONTRACTOR, TYPICAL) FILL LINE (2-1/2") REVISION NO. DESCRIPTION 14 P-501 WATER HEATERS (WH-3 & WH-4) SCALE: N.T.S. REVISED 15 DECEMBER 2015 SHEET NO. P-501 THERMOMETER (TYP) THERMOMETER (TYP) UNION (TYP) HW TO FIXTURES SEE P-702 110° UNION (TYP) HW TO FIXTURES SEE P-702 110° 2-1/2" 2-1/2" 1 NOTE: MOUNT MIXING VALVE ASSEMBLIES SIDE-BY-SIDE ON WALL AT AN ELEVATION OF 5'-0" AFF. SHOWN HERE FOR CLARITY ONLY. COORDINATE EXACT LOCATION WITH ALL OTHER TRADES INVOLVED PRIOR TO CONSTRUCTION. CHECK VALVE (TYP) TMV-2 STRAINER (TYP) CONDENSATE RISER (BY MC) 3445 PEACHTREE ROAD, NE, SUITE 675 1 TMV-1 STRAINER (TYP) ATLANTA, GA 30326 ASSOCIATE ARCHITECT GATE VALVE (TYP) 160° MURRAY AND ASSOCIATES ARCHITECTS 2-1/2" 2 HW FROM WATER HEATER 2-1/2" 2 HW FROM WATER HEATER CW, SEE P-702 HKS, INC. TWO LIVE OAK CENTER CHECK VALVE (TYP) GATE VALVE (TYP) ARCHITECT 1600 NORTH SECOND STREET 160° HARRISBURG, PA 17102-2499 CW, SEE P-702 2-1/2" 2-1/2" AQUASTAT HEAT TRAP (MIN. 27" DEEP) 1-1/2" HWR FROM FIXTURES SEE P-702 1-1/2" 3 4 3 1-1/2" 3 1-1/2" 4 CIRCULATING PUMP (CP-2) (140°) HWR TO WATER HEATERS SEE DETAIL MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 HWR FROM FIXTURES SEE P-702 HWR TO WATER HEATERS SEE DETAIL 1-1/2" 4 HVAC UNIT (BY MC) AQUASTAT ROSWELL, GA 30076 1-1/2" 4 SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES CIRCULATING PUMP (CP-1) 33 SOUTH BROAD STREET LITITZ, PA 17543 HW TO FIXTURES SEE P-702 3/4" GEOTECHNICAL ENGINEER 1-1/4" 1-1/4" 1 TMV-3 1 INSTALL MIXING VALVE AND PIPING CONNECTIONS AS PER MANUFACTURER'S PUBLISHED INSTALLATION DETAILS. 2 160° 3 AQUASTAT 3/4" FINISHED FLOOR 100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050 3" (TYP) BALANCING VALVE ASSEMBLIES ARE TO BE SET PER MIXING VALVE MANUFACTURER'S BALANCING INSTRUCTIONS. 3"HUB DRAIN 4 4 3/4" 4 P-TRAP W/ TRAP GUARD OMIT UNIONS WHEN PUMP IS FURNISHED WITH FLANGES. REFER TO P-400 SERIES DRAWINGS FOR CONTINUATION KEY NOTES: INSTALL MIXING VALVE AND PIPING CONNECTIONS AS PER MANUFACTURER'S PUBLISHED INSTALLATION DETAILS. NOTES: 1. 2. HWC CONNECTION VARIES DEPENDING ON MIXING VALVE MANUFACTURER AND PUMPED FLOW RATE. 3. 1 P-502 STAE COLLEGE, PA 16801 WBCM 1" HWR CONNECTION VARIES DEPENDING ON MIXING VALVE MANUFACTURER AND PUMPED FLOW RATE. CIRCULATING PUMP (CP-3) 2 2701 CAROLEAN INDUSTRIAL DRIVE HWR FROM FIXTURES SEE P-702 3 1 CMT LABORATORIES, INC. STRUCTURAL ENGINEER 1-1/4" 2 HEAT TRAP (MIN. 27" DEEP) TOP OF P-TRAP OPEN TO ATMOSPHERE (BY MC) KEY NOTES: BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE 1-1/2" 2-1/2" CD HEAT TRAP (MIN. 27" DEEP) 3 BALANCING VALVES ARE TO BE SET PER MIXING VALVE MANUFACTURER'S BALANCING INSTRUCTIONS. 4 OMIT UNIONS WHEN PUMP IS FURNISHED WITH FLANGES. MIXING VALVE STATION (LOW ZONE) MIXING VALVE STATION (HIGH ZONE) 2 SCALE: N.T.S. P-502 P-502 3 A 5 2 SCALE: N.T.S. 3 3 A CONDENSATE DRAIN TO SANITARY 3 SCALE: N.T.S. 1 4 1 SYSTEM NO. W-L-1001 (FORMERLY SYSTEM NO. 147) 1A F RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 2 AND 3) T RATINGS - 0,1,2,3 AND 4 HR (SEE ITEM 3) L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT L RATING AT 400 F - LESS THAN 1 CFM/SQ FT 2 5 1A SYSTEM NO. F-A-5011 3 A F RATING - 3 HR T RATING - 1 HR L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT (SEE ITEM 3) L RATING AT 400 F - LESS THAN 1 CFM/SQ FT (SEE ITEM 3) 3 4 A A 2 2 A SECTION A-A 2 SYSTEM NO. C-AJ-1008 (FORMERLY SYSTEM NO. 111) 1. FLOOR-CEILING ASSEMBLY - THE FIRE-RATED UNPROTECTED STEEL DECK FLOOR-CEILING ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL D900 SERIES DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND AS SUMMARIZED BELOW: A. NORMAL WEIGHT OR LIGHTWEIGHT CONCRETE - CONCRETE THICKNESS ABOVE THE CREST OF THE DECK SHALL BE MIN. 3-1/4 IN. NORMAL WEIGHT CONCRETE WITH CARBONATE OR SILICEOUS AGGREGATE, 145 TO 155 PCF UNIT WEIGHT, MIN. 3000 PSI COMPRESSIVE STRENGTH. LIGHTWEIGHT CONCRETE WITH EXPANDED SHALE, CLAY OR SLATE AGGREGATE, 105 TO 115 PCF UNIT WEIGHT, MIN. 3000 PSI COMPRESSIVE STRENGTH. B. WELDED WIRE FABRIC - 6x6, W1.4xW1.4 C. STEEL FLOOR AND FORM UNITS*-COMPOSITE OR NONCOMPOSITE 1-5/16 TO 3 IN. DEEP GALV. UNITS OR AS SPECIFIED IN THE INDIVIDUAL FLOOR-CEILING DESIGNS. MAX AREA OF OPENING IS 300 SQ IN. WITH MAX DIMENSION OF 30 IN. A 1B SECTION A-A 1. FLOOR OR WALL ASSEMBLY - REINFORCED LIGHT WEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE HAVING A MIN THICKNESS AS SPECIFIED IN THE TABLE BELOW (ITEM 3). WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAMETER OF OPENNING IS 8 IN. SEE CONCRETE BLOCK (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS. 2. METALIC SLEEVE - (OPTIONAL) - NOM 8 IN. DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL SLEEVE CAST GROUNTED INTO WALL OR FLOOR ASSEMBLY, FLUSH WITH FLOOR OR WALL SURFACES. 1. WALL ASSEMBLY - THE 1 OR 2 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM. 2 BY 4 IN. LUMBER SPACED 16 IN. OC. STEEL STUDS TO BE MIN. 3-5/8 IN. WIDE AND SPACED MAX. 24 IN. OC. B. GYPSUM BOARD* - 5/8 IN. THICK, 4 FT. WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX. DIAMETER OF OPENING IS 9 IN. THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WLL ASSEMBLY IN WHICH IT IS INSTALLED. 3. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE ANNULAR SPACE SHALL BE AS SPECIFIED IN THE TABLE BELOW. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED. A. STEEL PIPE - NOM 6 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE. B. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METTALIC TUBING. C. CONDUIT - NOM 6 IN. DIAM (OR SMALLER) RIGID GALV STEEL CONDUIT. THE F AND T RATING OF THE SYSTEM IS DEPENDENT UPON THE DIAM OF THE PIPE OR CONDUIT AND ANNULAR SPACE BETWEEN THE PIPE OR CONDUIT AND THE PERIPHERY OF THE OPENING AS SHOWN IN THE TABLE BELLOW. 2. THROUGH PENETRANTS - ONE METALIC PIPE OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. PIPE OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALIC TUBING MAY BE USED. A. STEEL PIPE - NOM. 4 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE. B. IRON PIPE - NOM. 4 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE. C. COPPER TUBING - NOM. 4 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBE. D. COPPER PIPE - NOM. 4 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE. MIN. FLOOR MAX DIAM. MIN. OR WALL OR WALL THCKNS IN. OF STEEL PIPE OR CONDIUT IN. ANNULAR SPACE IN. F F F F F F W W W W 3. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING. A. PIPE AND EQUIPMENT COVERING MATERIALS* - MAX 2 IN. THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN 3.5 PCF) GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED WITH MEATL FASTENERS OR FACTORY APPLIED SELFSEALLING LAP TAPE. PIPE COVERING TO BE WRAPPED AROUND THE THROUGH PENETRANT AND EXTEND A MIN 2-1/2 IN. BEYOND BOTH SURFACES OF THE WALL. THE ANNULAR SPACE BETWEEN PIPE COVERING AND THE EDGE OF THE THROUGH OPENING SHALL BE MIN. 0 IN. (CONTINUOUS POINT CONTACT) TO MAX 1/2 IN. SEE PIPE AND EQUIPMENT COVERING MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVEING MATERIAL MEETING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE USED. B. FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 5/8 IN. THICKNESS MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. A MIN 1/4 IN. CROWN OF FILL MATERIAL SHALL BE APPLIED TO THE PIPE COVERING/GYPSUM WALLBOARD INTERFACE AT THE POINT CONTACT LOCATION ABD LAPPING 1/4 IN. BEYIND THE PERIPHERY OF THE OPPENING ON BOTH SIDES OF THE WALL. SPECIFIED TECHNOLOGIES INC - SPECSEAL 100, 101, 102 AND 105 SEALANT. 3-3/4 3-3/4 3-3/4 4-1/2 4-1/2 4-1/2 5-1/2 5-1/2 6-1/2 6-1/2 1-1/2 6 6 1-1/2 6 6 1-1/2 6 1-1/2 6 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 2-1/8 1 3/4 1 1 2 2-1/8 1 3/4 1 1 2 2-1/8 1 3/4 1 2-1/8 2 1 2 2-3/4 2-3/4 1-3/4 3-1/2 3-1/2 2-1/2 3-1/2 3-1/2 2-1/2 2-1/2 MAX. ANNULAR SPACE IN. 2 2 2 MIN. FORMING F RATING T RATING METAL THCKNS IN. METAL THCKNS IN. HR HR 0 0 0 3 3 3 3/4 3 3/4 1 0 5. FILL, VOID OR CAVITY MATERIAL* - CAULK - MIN THICKNESS OF FILL MATERIAL AS SPECIFIED IN THE ABOVE TABLE (ITEM 3) APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF THE WALL. USG INTERIORS INC - TYPE SS CONDUIT/STEEL PIPE PENETRATION OF CONCRETE WALL/FLOOR 3. PIPE COVERINGS - ONE OF THE FOLLOWING TYPES OF PIPE COVERINGS MAY BE USED: A. PIPE AND EQUIPMENT COVERING MATERIALS* - NOM. 1 IN. THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN 3.5 PCF) GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS OR FACTORY-APPLIED SELF SEALING LAP TAPE. TRANSVERSE JOINTS SECURED WITH METAL FASTENERS OR WITH BUTT TAPE SUPPLIED WITH THE PRODUCT. THE ANNULAR SPACE WITHIN THE FIRESTOP SYSTEM SHALL BE MIN. 7/8 IN. TO MAX 15-1/2 IN. SEE PIPE AND EQUIPMENT COVERING MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE USED. B. PIPE COVERING MATERIALS* - NOM. 1 IN. THICK UNFACED MINERAL FIBER PIPE INSULATION HAVING A NOM. DENSITY OF 3.5 PCF (OR HEAVIER) AND SIZED TO THE OUTSIDE DIAM. OF THE PIPE OR TUBE. PIPE INSUALTION SECURED WITH A MIN. 8 AWG STEEL WIRE SPACED MAX 12 IN. OC. THE ANNULAR SPACEWITHIN THE FIRESTOP SYSTEM SHALL BE MIN. 7/8 IN. TO MAX 15-1/2 IN. OWENS CORNING HT INC, DIVISION OF OWENS CORNING - HIGH TEMPERATURE PIPE INSULATION 1200, HIGH TEMPERATURE PIPE INSULATION BWT OR HIGH TEMPERATURE PIPE INSULATION THERMALOC L RATINGS NOT APPLICABLE WHEN MINERAL WOOL PIPE COVERING MATERIAL IS USED. 2 A 2 A 1B SECTION A-A SECTION A-A 1. WALL ASSEMBLY - THE 1, 2, 3, OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: A. STUDS - WALL FRAMING CONSISTS OF STEEL CHANNEL STUDS. STEEL STUDS TO BE MIN. 3-5/8 IN. WIDE BY 1-3.8 IN. DEEP CHANNELS SPACED MAX. 24 IN. OC. B. GYPSUM BOARD* - NOM. 5/8 IN. THICK, 4 FT. WIDE WITH SQUARE OT TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX. DIAMETER OF OPENING IS 13-1/2 IN. 2. PIPE OR CONDUIT - NOM. 12 IN. DIAMETER (OR SMALLER) SCHEDULE 10 OR (OR HEAVIER) STEEL PIPE, NOM. 12 IN. DIAMETER (OR SMALLER) SERVICE WEIGHT (OR HEAVIER) CAST IRON SOIL PIPE, NOM 12 IN. DIAMETER (OR SMALLER) CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE, NOM. 6 IN. DIAMETER (OR SMALLER) STEEL CONDUIT, NOM. 4 IN. DIAMETER (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING, NOM. 6 IN. DIAMETER (OR SAMLLER) TYPE L (OR HEAVIER) COPPER TUBING OR NOM. 1 IN. DIAMETER (OR SMALLER) FLEXIBLE STEEL CONDUIT. WHEN COPPER PIPE IS USED, MAX F RATING OF FIRESTOP SYSTEM (ITEM 3) IS 3 HR. STEEL PIPES OR CONDUITS LARGER THAN NOM. 4 IN. DIAMETER MAY ONLY BE USED IN WALLS CONSTRUCTED USING STEEL CHANNEL STUDS. A MAX OF ONE PIPE OR CONDUIT IS PERMITTED IN THE FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE INSTALLED NEAR CENTER OF STUD CAVITY WIDTH AND TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. 3. FILL, VOID, OR CAVITY MATERIAL*-CAULK- CAULK FILL MATERIAL INSTALLED TO COMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND GYPSUM WALLBOARD AND WITH A MIN. 1/4 IN. DIAMETER BEAD OF CAULK APPLIED TO PERIMETER OF PIPE OR CONDUIT AT ITS EGRESS FROM THE WALL. CAULK INSTALLED SYMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY. THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE. THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW: 1. FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE. WALL ALSO MAY BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIM OF OPENING IS 8 IN. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES AND MANUFACTURERS. KEY PLAN 2. METALLIC PIPE - MAX 6 IN. DIAM (OR SMALLER) RIGID GALV STEEL CONDUIT, SCHEDULE 10 (OR HEAVIER) STEEL PIPE OR MAX 4 IN. DIAM (OR SMALLER) STEEL EMT CONDUIT CENTERED IN THE OPENING. PIPE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE T RATING OF THE SYSTEM IS DEPENDENT ON THE SIZE OF THE CONDUIT AND THROUGH OPENING AS SHOWN IN THE TABLE BELOW. (SEE ITEM 5) A 3. FORMS - (NOT SHOWN, OPTIONAL) - USED AS A FORM TO PREVENT LEAKAGE OF FILL MATERIAL DURING INSTALLATION. FORMS TO BE A RIGID SHEET MATERIAL, CUT TO FIT THE CONTOUR OF THE PENETRATING ITEM. FORMS FRICTION FITTED INTO THE OPENING OR LOCATED ON THE UNDERSIDE OF FLOOR ON BOTH SIDES OF WALL TO PREVENT THE LEAKAGE OF FILL MATERIAL. THE FORMS TO BE REMOVED AFTER THE FILL MATERIAL HAS CURED. 4. PACKING MATERIAL - (NOT SHOWN, OPTIONAL) - MINERAL WOOL BATT INSULATION FIRMLY PACKED BETWEEN THE FORMS AND PENETRATING ITEMS TO PREVENT THE LEAKAGE OF FILL MATERIAL. THE PACKING MATERIAL MAY BE REMOVED AFTER THE FILL MATERIAL HAS CURED. B 5. FILL, VOID, OR CAVITY MATERIAL* - SEALANT - FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL. THE T RATING OF THE SYSTEM IS DEPENDENT UPON THE SIZE OF THE OPENING, SIZE OF THE PENETRATING ITEM, NOM ANNULAR SPACE WITHIN OPENING AND THICKNESS OF THE FILL MATERIAL AS SHOWN IN THE TABLE BELOW: 4. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING: A. FORMS-(NOT SHOWN) USED AS A FORM TO PREVENT LEAKAGE OF FILL MATERIAL DURING INSTALLATION. FORMS TO BE RIGID SHEET MATERIAL, CUT TO FIT THE CONTOUR OF THE PENETRATING ITEM AND FASTENED TO THE UNDERSIDE OF FLOOR. FORMS TO BE REMOVED AFTER FILL MATERIAL HAS CURED. B. FILL, VOID, OR CAVITY MATERIAL*-MORTAR-MIN. 3-1/4 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP OF SURFACE FLOOR. MORTAR IS TO BE MIXED WITH WATER AT A RATE OF 1.9 TO 2.4 GAL. PER 25 LB. BAG IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS. MAX OPENING SIZE IN. MAX PIPE OR CONDUIT DIAM., IN. ANNULAR SPACE IN. F RATING HR. T RATING HR. 1 0 TO 3/16 1 OR 2 1 1/4 TO 1/2 3 OR 4 4 0 TO 1-1/2 1 OR 2 0 6 1/4 TO 1/2 3 OR 4 0 12 3/16 TO 3/8 1 OR 2 0 0+, 1 OR 2 3 OR 4 REVISION NO. DESCRIPTION DATE PIPE PENETRATION OF FIRE RATED FLOOR NTS PIPE PENETRATION OF FIRE RATED WALL NOM ANNULAR SPACE IN. MIN FILL MTL. THK. IN. T RATING HR 3 1-1/2 9/16 4-1/2 1-1/2 5 3 3/4 4-1/2 1/2 5 1/2 2 3-1/2 3 8 6 11/16 3-1/2 0 8 6 11/16 4-1/2 1/2 THIS DETAIL SHALL BE USED FOR ALL PENETRATIONS OF MECHANICAL ROOM 110A AND PENETRATIONS OF OTHER 2 HOUR SEPARATIONS. *BEARING THE UL CLASSIFICATION MARK NTS MAX DIAM. PENETRATION ITEM IN. *BEARING THE UL CLASSIFICATION MARK *BEARING THE UL CLASSIFICATION MARK *BEARING THE UL CLASSIFICATION MARK NTS 2. THROUGH PENETRANTS - A MAX OF TWO METALLIC PIPES OR TUBINGS TO BE INSTALLED WITHIN THE FIRESTOP SYSTEM. PIPE OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUIT OR TUBING MAY BE USED: A. STEEL PIPE - NOM. 6 IN. DIAMETER (0R SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE WITH 1 IN. MINERAL FIBER PIPE INSULATION. B. STEEL PIPE - NOM. 4 IN. DIAMETER (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE WITH 1 IN. GLASS FIBER OR MINERAL FIBER PIPE INSULATION. C. COPPER PIPE - NOM. 4 IN. DIAMETER (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE WITH 1 IN. MINERAL FIBER PIPE INSULATION. D. COPPER TUBING - NOM. 4 IN. DIAMETER (OR SMALLER) TYPE L (OR HEAVIER) COPPER PIPE WITH 1 IN. MINERAL FIBER PIPE INSULATION. E. COPPER PIPE - NOM. 2 IN. DIAMETER (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE WITH 1 IN. GLASS FIBER PIPE INSULATION. F. COPPER TUBING - NOM. 2 IN. DIAMETER (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING WITH 1 IN. GLASS FIBER PIPE INSULATION. C. SHEATHING MATERIAL*-(OPTIONAL)-USED IN CONJUNCTION WITH ITEM 3B. FOIL-SCRIM-KRAFT OR ALL SERVICE JACKET MATERIAL SHALL BE WRAPPED AROUND THE OUTER CIRCUMFERENCE OF THE PIPE INSULATION (ITEM 3B) WITH THE KRAFT SIDE EXPOSED. LONGITUDINAL JOINTS AND TRANSVERSE JOINTS SEALED WITH MATCHING FOIL-SCRIM-KRAFT TAPE. (SEE SHEATHING MATERIALS (BVDV) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY SHEATHING MATERIAL MEETING THE ABOVE SPECIFICATION AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE USED. 0 3 1 SEE ARCHITECTURAL DRAWINGS FOR FIRE RATING OF WALLS. 0 0 3 3 MIN. FILL 4. FORMING MATERIAL* - MIN 4.0 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM AT THE MIN THICKNESS SPECIFIED IN THE ABOVE TABLE (ITEM 3). FORMING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMODATE THE REQUIRED THICKNESS OF FILL MATERIAL. THERMAFIBER LLC - TYPE SAF *BEARING THE UL CLASSIFICATION MARK INSULATED PIPE PENETRATION OF FIRE RATED WALL FLOOR 5 A F RATING - 3 HR T RATINGS - 0,1/2,1 1/2 AND 3 HR (SEE ITEM 5) 3A System No. W-L-1101 F Rating - 1&2 Hr (See Item 1) T Rating - 0 Hr 5 UL DETAIL 3 SECTION A-A SYSTEM NO. C-AJ-1020 (FORMERLY SYSTEM NO. 165) F RATING - 2 AND 3 HR (SEE ITEM 3) T RATING - 0, 3/4, AND 1 HR (SEE ITEM 3) L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT L RATING AT 400 F - LESS THAN 1 CFM/SQ FT 3B THIS DETAIL OCCURS AT EACH LOWEST LEVEL RESIDENTIAL MECHANICAL CLOSET. PLUMBING CONTRACTOR SHALL FULLY COORDINATE THE EXACT LOCATION OF HUB DRAIN WITH THE EQUIPMENT AND STRUCTURE. HUB DRAINS SHOWN ON PLAN FOR CLARITY ONLY. HUB DRAINS SHALL BE ACCESSIBLE AS PER CODE. NTS CONDUIT/STEEL PIPE PENETRATION OF CONCRETE WALL/FLOOR NTS 12/14/2015 4:14:10 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 AHA PROJECT NUMBER G1215-004.00 DATE 03 DECEMBER 2015 ISSUE 4 P-502 CONSTRUCTION DOCUMENTS UL DETAILS SCALE: N.T.S. SHEET TITLE PLUMBING DETAILS REVISED 15 DECEMBER 2015 SHEET NO. P-502 SHEET NOTES 1. SEE P-407 FOR CONTINUATION WHERE SPACE DOES NOT ALLOW THE BOTTOM HORZONTAL WASTE BRANCH TO CONNECT TO VERTICAL STACK, THE PLUMBING CONTRACTOR SHALL OFFSET THE VERTICAL STACK HORIZONTALLY, THEN CONNECT THE BOTTOM WASTE BRANCE TO THE HORIZONTAL OFFSET AT A MINIMUM DISTANCE OF TEN PIPE DIAMETERS AWAY FROM THE VERTICAL STACK. ARCHITECT SEE P-407 FOR CONTINUATION HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 6" WS ATLANTA, GA 30326 6" WS 8" WS ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET GATE VALVE CHECK VALVE HARRISBURG, PA 17102-2499 GATE VALVE MEP ENGINEER OS& Y GATE VALVE (SUPERVISED) OS& Y GATE VALVE (SUPERVISED) AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 4" BYPASS 6" WS SITE/CIVIL ENGINEER MIN. OF 10 x PIPE DIAMETERS OF SMOOTH PIPE UPSTREAM OF FIRE PUMP (MINUS ONE ELBOW) DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET CHECK VALVE LITITZ, PA 17543 RELIEF VALVE GEOTECHNICAL ENGINEER HORIZONTAL FIRE PUMP CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE 8" WS STAE COLLEGE, PA 16801 FIRE PUMP 6 STRUCTURAL ENGINEER SCALE: N.T.S. P-701 WBCM 100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050 4" V BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE 4" V 4" V 3" V 3" V WB1 LS1 4" V 4" V JS1 3" S 3"FD-A W/ TRAP GUARD 2" V (TYP) 3" S (TYP) 3" S 4" V 2" V 4" S 4" V 3" WASTE STACK VENT 4" 3" S V WB1 3" WASTE STACK VENT 4" V 3" V LS1 JS1 3" S 3"FD-A W/ TRAP GUARD 3" S 2" V 4" V 4" S 3" V WB1 LS1 4" S JS1 3" S 3"FD-A W/ TRAP GUARD 3" S 2" V (TYP) 3" S (TYP) 2" V (TYP) 3" S (TYP) 4" S 3" V 2" V 4" S 3" V 4" V WB1 3" WASTE STACK VENT 3" WASTE STACK VENT LS1 4" S JS1 3" S 3"FD-A W/ TRAP GUARD 3" S 2" V WB1 4" V KEY PLAN LS1 JS1 3"FD-A W/ TRAP GUARD 3" S 3" S A 4" S 3" S (TYP) 2" V (TYP) 3" S (TYP) 2" V (TYP) 4" V 2" V 4" S 3" V 3" WASTE STACK VENT 3" WASTE STACK VENT 4" S 3" V B WB1 4" V WB1 REVISION NO. DESCRIPTION LS1 3"FD-A W/ TRAP GUARD JS1 WB1 3" S DATE 3" S 3" S 3" S 2" S 4" S 4" S S2 S1 S5 S7 S6 1 SCALE: 2 P-701 SANITARY STACK 2 SCALE: 3 P-701 SANITARY STACK 5 SCALE: 4 P-701 SANITARY STACK 6 SCALE: 5 P-701 SANITARY STACK 7 AHA PROJECT NUMBER SCALE: G1215-004.00 12/14/2015 4:21:31 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 P-701 SANITARY STACK 1 DATE 03 DECEMBER 2015 ISSUE CONSTRUCTION DOCUMENTS SHEET TITLE PLUMBING RISER DIAGRAMS REVISED 15 DECEMBER 2015 SHEET NO. P-701 ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076 SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543 GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801 STRUCTURAL ENGINEER NFRH NFRH WBCM 100 STERLING PARKWAY, SUITE 108 W6 1" 3/4" 3/4" WB1 WB1 WB1 3/4" JS1 TO LAUNDRY ROOM SINK 1-1/4" 3/4" 1-1/2" 3/4" 1-1/2" 3/4" 1-1/2" 1-1/2" 1-1/2" 1" 1" 1" 110° 3/4" 1-1/4" 3/4" 1" 1/2" MECHANICSBURG, PA 17050 BALANCING VALVE ASSEMBLY SET AT 0.5 GPM UNLESS NOTED OTHERWISE SEE DETAIL 8/P-501 (TYP) ROOF W5 W8 1" 110° SEE FLOOR PLAN FOR CONTINUATION (TYP) W4 W7 BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE BALANCING VALVE ASSEMBLY SET AT 0.5 GPM UNLESS NOTED OTHERWISE SEE DETAIL 8/P-501 (TYP) 3/4" SIXTH FLOOR 3/4" JS1 TO LAUNDRY ROOM SINK WB1 WB1 3/4" WB1 1/2" 3/4" 3/4" 1" 1/2" (TYP) 1-1/4" 1-1/4" 1-1/4" 3/4" 1-1/4" 1-1/4" SEE FLOOR PLAN FOR CONTINUATION (TYP) 1-1/4" 1-1/4" 1-1/4" WB1 2" JS1 1" 1" 1-1/4" 1-1/4" 2-1/2" 2" BALANCING VALVE ASSEMBLY SET AT 0.5 GPM UNLESS NOTED OTHERWISE SEE DETAIL 8/P-501 (TYP) TO LAUNDRY ROOM SINK 2" 1-1/2" SEE FLOOR PLAN FOR CONTINUATION (TYP) 1/2" 1" W3 W3 W3 2" 2" W3 2" 2" 2-1/2" 2" 2-1/2" 1-1/2" W6 3/4" 1-1/4" 1-1/2" 1" 1-1/4" 1/2" 1" FIFTH FLOOR SEE FLOOR PLAN FOR CONTINUATION (TYP) WB1 1" 1" 3/4" 1" WB1 1" 1" 1" HOT & COLD WATER TO RESIDENTIAL UNITS (TYP) W3 W3 1 1/2" 3/4" FOURTH FLOOR 3/4" 3/4" 3/4" 1" 1" 3/4" 1-1/2" 1" 1" 2" JS1 1/2" 1-1/4" 110° WB1 1-1/2" 3/4" 1" 110° WB1 3/4" 1-1/2" 110° WB1 1-1/4" TO LAUNDRY ROOM SINK 110° 3/4" 3/4" 110° W7 1" 110° SEE FLOOR PLAN FOR CONTINUATION (TYP) 1-1/2" 3/4" THIRD FLOOR 1" HOT & COLD WATER TO RESIDENTIAL UNITS (TYP) 3/4" 3/4" TO LAUNDRY ROOM SINK WB1 WB1 3/4" WB1 1" 1" 1" 2" 1-1/2" 2-1/2" 1-1/2" 1" 1" 1" JS1 1/2" 3/4" 3/4" 1" 1/2" (TYP) 1-1/4" 1-1/4" 2" 3/4" 1-1/4" 1-1/4" 2" 1-1/4" SECOND FLOOR SEE FLOOR PLAN FOR CONTINUATION (TYP) SEE FLOOR PLAN FOR CONTINUATION (TYP) 1-1/4" 2" SEE FLOOR PLAN FOR CONTINUATION (TYP) 1/2" 3/4" 8" TO SPRINKLER SYSTEM, SEE FLOOR PLAN FOR CONTINUATION 3/4" 3" 1-1/2" 1-1/2" 4" 2-1/2" 1-1/2" 2-1/2" 3" 1-1/4" W2 W2 2-1/2" 2-1/2" 1-1/2" 2" 2-1/2" 1-1/2" 2" 1-1/2" 2-1/2" 1-1/2" 110° 2-1/2" 4" 4" 2-1/2" 110° 1 1/2" 3" 6" 4" 160° RPBFP-2, SEE DETAIL 12/P-501 8" 8" 2-1/2" DWB 1 SEE DETAIL 9/P-501 WH1 1-1/4" 2-1/2" TMV-2 (SET @ 110°) TMV-1 (SET @ 120°) 4" 3/4" 1-1/2" 2-1/2" 2-1/2" 2-1/2" 4" 36" 160° WH2 WH3 WH4 TMV-3 (SET @ 140°) 4" FOOD SERVICE BACK-OF-HOUSE M M 2-1/2" B 110° 110° 3" 140° 4" KEY PLAN 110° 110° 140° W2 2" 110° 110° 4" W2 A SEE FLOOR PLAN FOR CONTINUATION (TYP) 110° 2" FIRST FLOOR 2-1/2" 2" 110° 2-1/2" 2" 110° 1-1/4" 110° 2" 1" 110° W8 TO LAUNDRY ROOM SINK 8" COMBINED DOMESTIC AND FIRE SERVICE, SEE FLOOR PLAN FOR CONTINUATION 1-1/2" 1" 110° WB1 W1 110° WB1 1" W1 110° WB1 3/4" 110° 1" 1-1/4" 110° 2-1/2" 1-1/4" 3" 2-1/2" 2-1/2" 1-1/2" 1-1/2" 1-1/2" W4 2" 2-1/2" REVISION NO. DESCRIPTION W5 1-1/4"H & CW VALVED AND CAPPED FOR FOOD SERVICE TENANTS WATER SUB METER WITH REMOTE READER (TYP) GROUND FLOOR RPZBFP-1, SEE DETAIL 7/P-501 PIPE STAND (TYP) SEE DETAILS 2/P-502 & 13/P-501 WATER METER: CARLON MODEL C300T W/ REMOTE "CAR-LOGGER" READER. PLUMBING CONTRACTOR SHALL COORDINATE THE EXACT LOCATION OF READER W/ OWNER / ARCHITECT PRIOR TO CONSTRUCTION. 2" PRV SET AT 65 PSI, WATTS LF223S OR SIMILAR 2" PRV SET AT 70 PSI, WATTS LF223S OR SIMILAR SEE DETAILS 1/P-502 & 14/P-501 AHA PROJECT NUMBER G1215-004.00 TEMPLATE VERSION: 2.6.8.20141012 8"DOUBLE DETECTOR CHECK VALVE ASSEMBLY SEE DETAIL 11/P-501 DATE 03 DECEMBER 2015 ISSUE CONSTRUCTION DOCUMENTS SHEET TITLE 12/14/2015 4:15:08 PM 1 PLOT DATE: DATE P-702 PLUMBING RISER DIAGRAMS DOMESTIC WATER RISER DIAGRAM SCALE: N.T.S. REVISED 15 DECEMBER 2015 SHEET NO. P-702 1/2" CW ARCHITECT L4 L3 2 1/2" CW 1/2" HW SA"B" TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 2 1/2" HW SA"B" HKS, INC. SEE FLOOR PLAN FOR CONTINUATION 1 1/4" CW 3/4" CW ASSOCIATE ARCHITECT 1 1/2" CW U2 3/4" HW 1 1/4" CW MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 U1 WC4 MEP ENGINEER EWC 1/2" HW AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 WC4 3/4" CW ROSWELL, GA 30076 3/4" HW SITE/CIVIL ENGINEER WC3 2 1/2" CW SEE FLOOR PLAN FOR CONTINUATION 2" CW WC3 2 1/2" HW 1 1/4" CW 33 SOUTH BROAD STREET 1/2" HW WC4 L4 3/4" HW 2 1/2" HW 2" CW CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE 1/2" CW SA"A" 1 1/4" HW 2" CW 2" CW GEOTECHNICAL ENGINEER 1/2" CW L3 3/4" CW LITITZ, PA 17543 2" CW 1 1/2" CW 1 1/2" CW DERCK & EDSON ASSOCIATES STAE COLLEGE, PA 16801 L5 1/2" HW 1" HW STRUCTURAL ENGINEER 3/4" CW WBCM 2 1/2" HW 100 STERLING PARKWAY, SUITE 108 3/4" HW 1 1/4" CW 3/4" CW RPZ/BFP 1" HW 3/4"NPW, COORDINATE THE EXACT LOCATION WITH LIVE WALL VENDOR 1 1/2" CW 2" CW 2" CW 2 1/2" HW U2 WC4 1" HW 1/2" CW U1 3/4"NPW 1/2" HW L4 1/2" HW L3 2 1/2" HW WC3 WC4 WC3 2" CW WC3 WC3 L4 EWC 1 1/4" CW L3 3/4" HW 1" HW JS1 WC4 SA"A" 4"SAN, SEE FLOOR PLAN FOR CONTINUATION 1/2" HW 1/2" CW BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE 3/4"NPW 1 1/4" CW 2" CW MECHANICSBURG, PA 17050 SA"C" 2" V L5 2" V 3"V, SEE FLOOR PLAN FOR CONTINUATION 2" V 2" V 4" S 2" V 1 P-703 4"SAN, SEE FLOOR PLAN FOR CONTINUATION 2" V WATER RISER - PUBLIC TOILETS 2" V 2" V SCALE: N.T.S. 3"FD-B W/ TRAP GUARD 2" V 2" V L4 L3 2" V 3" V 2" V 2" V 2" S U1 3" V 1 1/2" V WC4 2" S U2 4" S 3" S 2" V EWC WCO 4" S 3" S WC3 2" S WC3 3" V 3"FD-A W/ TRAP GUARD (TYP) 2" V 4" S 3" V 2" S 2" V 2" V 2" V L4 L3 4" S 2" V 3" S 2" V 2" S 1 1/2" PD 2" S 2" V 4" S 2" S KEY PLAN WC4 L5 4" S 3"FD-A W/ TRAP GUARD (TYP) 2" V 3" V 4" S 2" V WC4 3" V 2" V WC3 3" V 4"HUB DRAIN W/ TRAP GUARD, SEE DETAIL 4/P-501 3"FD-A W/ TRAP GUARD (TYP) 4" S 4" S WC3 L4 A 2" S 2" V 6"SAN, SEE FLOOR PLAN FOR CONTINUATION 2" V 3"FD-A W/ TRAP GUARD (TYP) B WC3 WC3 WCO L3 L4 2" V 1 1/2" PD 2" V EWC REVISION NO. DESCRIPTION 4" S L3 U2 JS1 2" S 2" V U1 DATE 4" S 2" S 4" S 6" S WC4 4" S 4" S 4" S 3" S 3"FD-A W/ TRAP GUARD (TYP) 3" S 2" V 4" S L5 FCO 4" S 4" S 3"FD-B W/ TRAP GUARD, COORDINATE EXACT LOCATION WITH LIVE-WALL VENDOR 4" S 3" S 4" S G1215-004.00 TEMPLATE VERSION: 2.6.8.20141012 12/14/2015 4:15:32 PM PLOT DATE: AHA PROJECT NUMBER 4" S 6" S DATE 03 DECEMBER 2015 ISSUE CONSTRUCTION DOCUMENTS SHEET TITLE 2 P-703 PLUMBING RISER DIAGRAMS SANITARY RISER - PUBLIC TOILETS SCALE: N.T.S. REVISED 15 DECEMBER 2015 SHEET NO. P-703 3/4"GAS B/G FOR OUTDOOR FIRE PIT ARCHITECT HKS, INC. 3/4" G (300 CFH) TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326 GAS COCK 1" G (470 CFH) ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 MEP ENGINEER ELECTRIC SOLENOID VALVE, COORDINATE WIRING WITH ELECTRICAL CONTRACTOR. (LOCATE 7'-0'' AFF, COORDINATE W/ OWNER) AHA CONSULTING ENGINEERS 1" G 1801 OLD ALABAMA RD, SUITE 125 (470 CFH) ROSWELL, GA 30076 PRESSURE REGULATOR (VENTLESS): PIETRO FIORENTINI MODEL 30051 INLET= 2 PSI / OUTLET: 11"W.C. (LOCATE 7'-0'' AFF, COORDINATE W/ OWNER) (470 CFH) 1" G SITE/CIVIL ENGINEER (300 CFH) 3/4" G DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543 GEOTECHNICAL ENGINEER 1" G CMT LABORATORIES, INC. (770 CFH) 1" G (470 CFH) 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801 STRUCTURAL ENGINEER CONNECT FULL LINE SIZE GAS TO EACH OF THREE PIECES OF EQUIPMENT. REFER TO FOOD SERVICE DRAWINGS FOR CONNECTION SIZE. INSTALL A GAS COCK AND DIRT LEG AT EACH CONNECTION POINT. WBCM 100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050 (470 CFH) 2" G (770 CFH) 1" G 2 1/2" G (5385 CFH) (4615 CFH) 2" G PRESSURE REGULATOR (VENTLESS): PIETRO FIORENTINI MODEL 30153-DC INLET= 2 PSI / OUTLET: 15"W.C. (MAX. 20" W.C.) 2 1/2" G (5385 CFH) 4" G CONNECT 4" GAS TO EMERGENCY GENERATOR REFER TO DETAIL 5/P-501 2 1/2" G (5385 CFH) BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE 2"HEADER 12" ABOVE FLOOR AS TIGHT TO WALL AS POSSIBLE (5385 CFH) 2 1/2" G KEY PLAN A B REVISION NO. DESCRIPTION DATE NEW GAS METER: DELIVER 5500 CFH @ 2 PSI, TOTAL DEVELOED DESIGN LENGTH IS 400' 2 1/2" G (5385 CFH) 12/14/2015 4:15:50 PM PLOT DATE: TEMPLATE VERSION: 2.6.8.20141012 AHA PROJECT NUMBER G1215-004.00 DATE 03 DECEMBER 2015 ISSUE CONSTRUCTION DOCUMENTS 1 P-704 NATURAL GAS RISER SHEET TITLE PLUMBING RISER DIAGRAMS SCALE: N.T.S. REVISED 15 DECEMBER 2015 SHEET NO. P-704