GENERAL HVAC NOTES GENERAL DUCTWORK NOTES GENERAL PIPING NOTES

advertisement
GENERAL PIPING NOTES
1.
MINIMUM SIZE OF STEAM CONDENSATE RETURN PIPING SHALL BE 1" UNLESS
OTHERWISE NOTED.
THE HEATING, VENTILATING AND AIR CONDITIONING (HVAC) CONTRACTOR
SHALL VISIT THE SITE TO DETERMINE ALL PRE-EXISTING CONDITIONS AND
WORK NECESSARY PRIOR TO SUBMISSION OF BID PRICE.
2.
PROVIDE ISOLATION VALVES IN SUPPLY AND RETURN PIPING ON EACH FLOOR, AND
IN BRANCH PIPING SERVING MORE THAN ONE PIECE OF EQUIPMENT.
THE HEATING, VENTILATING AND AIR CONDITIONING (HVAC) CONTRACTOR
SHALL BE FAMILIAR WITH ALL CONTRACT DOCUMENTS FOR ALL TRADES AND
COORDINATE WITH OTHER CONTRACTORS.
3.
DRAWINGS ARE DIAGRAMMATIC ONLY: FINAL ROUTING OF DUCTWORK,
PIPING AND EQUIPMENT LOCATIONS SHALL BE DETERMINED IN THE FIELD.
ADDITIONAL OFFSETS, ELBOWS, ETC., SHALL BE PROVIDED AND INSTALLED
WITHOUT ADDITIONAL COST TO THE OWNER.
1.
ALL DUCTWORK SHALL BE CONSTRUCTED AND INSTALLED IN ACCORDANCE
WITH THE LATEST EDITION OF SMACNA STANDARDS.
1.
MINIMUM SIZE OF HOT WATER SUPPLY, HOT WATER RETURN AND CONDENSATE
DRAIN PIPING SHALL BE 3/4" UNLESS OTHERWISE NOTED.
2.
PROVIDE VOLUME DAMPERS AT ALL LOW PRESSURE SUPPLY, RETURN AND
EXHAUST DUCTWORK BRANCH TAKE-OFFS.
2.
SUPPLY AND RETURN DUCT MAINS FROM AIR HANDLING EQUIPMENT SHALL BE
INTERNALLY LINED WITH 1" ACCOUSTICAL LINING A MINIMUM OF 10'-0" FROM THE
UNIT UNLESS OTHERWISE NOTED. ALL DUCTWORK DIMENSIONS INDICATED
ARE CLEAR INSIDE DIMENSIONS. ALL INTERNAL ACCOUSTICAL DUCT LINING
SHALL HAVE AIR SURFACE COATED WITH ACRYLIC COATING FORMULATED WITH
IMMOBILIZED EPA REGISTERED ANTI-MICROBIAL AGENT PROVEN TO RESIST
MICROBIAL GROWTH AS DETERMINED BY ASTM G21 AND G22.
3.
3.
4.
5.
REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR FINAL LOCATIONS OF
DIFFUSERS, REGISTERS AND GRILLES.
FIRE DAMPERS AND ACCESS PANELS SHALL BE INSTALLED AT ALL FIRE RATED
ASSEMBLIES AND FLOOR PENETRATIONS. REFER TO ARCHITECTURAL DRAWINGS
FOR ASSEMBLY LOCATIONS. WHERE DUCTS PENETRATE WALLS THAT CARRY
BOTH FIRE AND SMOKE RATINGS, THE DAMPER SHALL BE COMBINATION FIRE/
SMOKE DAMPERS. COMBINATION FIRE/ SMOKE DAMPERS SHALL BE PROVIDED
WITH POWER IN ACCORDANCE WITH MANUFACTURER REQUIREMENTS. THE
MECHANICAL SUBCONTRACTOR SHALL COORDINATE COMBINATION FIRE/ SMOKE
DAMPER POWER REQUIREMENTS WITH THE ELECTRICAL SUBCONTRACTOR.
6.
PROVIDE FIRE DAMPERS AT ALL TRANSFER DUCTS IN FIRE RATED PARTITIONS.
7.
EACH SUPPLY DIFFUSER/REGISTER RUNOUT SHALL BE PROVIDED WITH A
VOLUME DAMPER. REFER TO CEILING DIFFUSER BRANCH TAKE-OFF DETAIL FOR
ADDITIONAL INFORMATION.
8.
9.
4.
5.
6.
7.
8.
RUNOUT SIZES TO DIFFUSERS/REGISTERS SHALL MATCH INLET SIZE NOTED IN THE
DIFFUSER REGISTER/ GRILLE SCHEDULE OR TAG UNLESS SHOWN OTHERWISE ON
THE FLOOR PLANS.
11. ALL FANS SUPPLYING MORE THAN 2,000 CFM OF AIR TO ANY SPACE SHALL BE
INSTALLED WITH A SMOKE DETECTOR IN THE RETURN DUCTWORK. DUCT
SMOKE DETECTORS SHALL BE INSTALLED IN THE RETURN AIR PATH OF AIR
DISTRIBUTION SYSTEMS UTILIZING A COMMON SUPPLY AND/OR RETURN AIR
PLENUM WITH A COMBINED DESIGN CAPACITY GREATER THAN 2,000 CFM. THE
SMOKE DETECTOR SHALL BE WIRED TO STOP THE FAN UPON DETECTION OF
SMOKE, AND SIGNAL THE BUILDING FIRE ALARM CONTROL PANEL. THE SMOKE
DETECTOR SHALL BE FURNISHED BY ELECTRICAL CONTRACTOR, MOUNTED IN
THE DUCT BY MECHANICAL CONTRACTOR AND WIRED BY THE ELECTRICAL
CONTRACTOR
12. LOCATIONS OF LOUVERS SHOWN ON THE PLANS ARE APPROXIMATE. REFER TO
ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION.
13. FLEXIBLE DUCT LENGTH SHALL NOT EXCEED 6'-0" IN LENGTH. FLEXIBLE
DUCTWORK SHALL BE INSTALLED AS STRAIGHT AS POSSIBLE AND SHALL BE
ROUTED AND SUPPORTED WITHOUT FORMING CRIMPS OR OTHER AIR FLOW
RESTRICTIONS. PROVIDE SQUARE TO ROUND ADAPTERS OR BOOTS TO CONNECT
TO AIR DEVICES NECK WHEN REQUIRED.
4.
PIPING AT PUMPS AND EQUIPMENT SHALL BE SUPPORTED SO THAT NO
PIPING OR ACCESSORY LOAD IS CARRIED BY THE PUMP OR EQUIPMENT.
5.
ALL VOLUME DAMPERS LOCATED ABOVE HARD NON-ACCESSIBLE CEILINGS
SHALL BE PROVIDED WITH A YOUNG REGULATOR VOLUME DAMPER FOR
REMOTE BALANCING.
10. RUNOUT SIZES TO TERMINAL UNITS SHALL MATCH INLET SIZE UNLESS
OTHERWISE NOTED OR SHOWN ON THE FLOOR PLANS.
PROVIDE SHUTOFF VALVES IN THE SUPPLY AND RETURN PIPING TO ALL
EQUIPMENT TO ALLOW FOR SERVICING. UNIONS AND FLANGES SHALL BE
ARRANGED SUCH THAT EQUIPMENT CAN BE SERVICED WITHOUT CUTTING AND
MINIMAL DISRUPTION OF PIPING SERVING THE EQUIPMENT.
9.
ALL PIPING ABOVE GRADE SHALL BE SUPPORTED BY THE BUILDING
STRUCTURE AND SHALL NOT REST ON CEILING TILES OR CEILING STRUCTURE.
PIPING HUNG FROM JOISTS SHALL BE HUNG FROM THE TOP CHORDS OF THE
JOISTS.
INSULATE ALL CHILLED WATER PIPING. ALL EXPOSED INSULATED PIPING BELOW
10'-0" AFF SHALL BE JACKETED. ALL EXTERIOR COOLING WATER PIPING SHALL
BE INSULATED & JACKETED OVER ELECTRIC HEAT TRACING. REFER TO
SPECIFICATIONS FOR INSULATION & JACKETING REQUIREMENTS.
WHERE MAXIMUM OPERATING PRESSURE IS GREATER THAN 150 PSIG IN
ANY SYSTEM, THE HVAC CONTRACTOR SHALL FURNISH AND INSTALL
PRODUCTS, PIPING, VALVES, FITTINGS AND ACCESSORIES WITH PRESSURE
CLASSIFICATIONS THAT ARE SUITABLE FOR SERVICE. IN GENERAL, ALL
PRODUCTS, PIPING, VALVES, FITTINGS AND ACCESSORIES BELOW 350 FEET
OF THE HIGHEST PIPING POINT MUST HAVE PRESSURE RATINGS OF 300 PSI
W.O.G. OR GREATER. ALL PRODUCTS, PIPING, VALVES, FITTINGS, AND
ACCESSORIES BELOW 575 FEET OF THE HIGHEST PIPING POINT MUST HAVE
PRESSURE RATINGS OF 500 PSI W.O.G. OR GREATER.
EXPANSION IN PIPING SYSTEMS SHALL BE COMPENSATED FOR BY THE USE
OF U-BENDS, Z-BENDS OR EXPANSION JOINTS AS INDICATED. U-BENDS
(LOOPS) AND Z-BENDS SHALL BE COMPLETE WITH PIPE GUIDES AND
ANCHORS.
10. PROVIDE AUTOMATIC AIR VENT (WITH DRAIN) AT HIGH POINTS OF ALL
RECIRCULATING WATER PIPING SYSTEMS.
11. CONDENSATE FROM ALL EVAPORATOR COILS SHALL BE TRAPPED AND
ROUTED TO THE NEAREST HUB/FLOOR DRAIN, STORM OR EXTERIOR DRY
WELLS. CONDENSATE PIPING SHALL BE INSULATED COPPER IN HVAC
PLENUMS, SCHEDULE 40 PVC ACCEPTABLE ELSEWHERE. CONDENSATE
SHALL BE PUMPED AS REQUIRED.
12. REFRIGERANT PIPING SHALL BE TYPE L OR REFRIGERATION SERVICE COPPER
TUBING WITH BRAZED JOINTS. SUCTION PIPING SHALL BE INSULATED WITH 3/4"
MANVILLE AEROTUBE II PIPE INSULATION OVER TUBING WITHOUT CUTTING. ALL
JOINTS AND SEAMS SHALL BE SEALED WITH ADHESIVE.
13. REFRIGERANT PIPING CARRYING OTHER THAN GROUP A1 OR B1
REFRIGERANTS AND INTERCONNECTING SEPARATE PIECES OF EQUIPMENT
AND PASSING VERTICALLY THROUGH FLOORS FROM ONE STORY TO
ANOTHER SHALL BE ENCLOSED IN A CODE APPROVED RIGID AND TIGHT
CONTINUOUS FIRE RESISTING PIPE DUCT OR SHAFT HAVING NO OPENINGS
INTO FLOORS NOT SERVED BY THE REFRIGERATING SYSTEM, AS REQUIRED
BY LOCAL CODE AUTHORITIES. THE PIPE DUCT OR SHAFT SHALL BE
VENTED TO OUTDOORS.
HVAC LEGEND
GENERAL HVAC NOTES
6.
THE HVAC CONTRACTOR SHALL COORDINATE ALL ELECTRICAL AND
PLUMBING REQUIREMENTS WITH THE ELECTRICAL AND PLUMBING
CONTRACTORS.
THE AUTOMATIC TEMPERATURE CONTROL (ATC) CONTRACTOR SHALL
COORDINATE THERMOSTAT LOCATIONS WITH THE ARCHITECTURAL
FURNITURE PLANS. THERMOSTATS SHALL BE INSTALLED 54" ABOVE
FINISHED FLOOR UNLESS OTHERWISE NOTED.
THE HVAC CONTRACTOR SHALL FURNISH AND INSTALL ALL INCIDENTAL
ACCESSORIES NECESSARY TO MAKE THE HVAC WORK COMPLETE AND
READY FOR OPERATION.
7.
ALL HVAC WORK SHALL BE IN ACCORDANCE WITH APPLICABLE FEDERAL,
STATE AND LOCAL CODES.
8.
ALL HVAC EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS.
9.
FURNISH TO THE GENERAL CONTRACTOR ALL INFORMATION REQUIRED FOR
SETTING OF WALL, ROOF AND PARTITION OPENINGS FOR HVAC WORK. THIS
INFORMATION SHALL BE FURNISHED IN A TIMELY MANNER SUCH THAT
CONSTRUCTION SCHEDULE IS NOT JEOPARDIZED.
PIPING SYSTEMS
PIPING SPECIALTIES
BOILER FEED WATER
GATE VALVE
BS
BRINE SUPPLY
CHECK VALVE
BR
BRINE RETURN
BFW
CHWS
DUCTWORK SPECIALTIES
CWR
TRIPLE DUTY VALVE
CD
CONDENSATION DRAIN
CWS
CONDENSER WATER SUPPLY
CWR
CONDENSER WATER RETURN
BALANCING VALVE
PRESSURE REDUCING VALVE
DIRECTION OF FLOW
3 WAY CONTROL VALVE
VOLUME EXTRACTOR
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
RELIEF VALVE
FILL
SPLITTER DAMPER
FUEL OIL GAUGE
AIR VENT
UP
G
GLYCOL SUPPLY
GR
GLYCOL RETURN
CD
HIGH PRESSURE STEAM SUPPLY
14. HEATING DESIGN CONDITIONS ARE AND 70ºF INDOOR AT 3ºF OUTDOOR.
HSS
HIGH PRESSURE STEAM CONDENSATE
15. THE HVAC CONTRACTOR SHALL COORDINATE THE INSTALLATION OF ALL
MECHANICAL EQUIPMENT,DUCTWORK, PIPING, ETC. TO FIT WITHIN THE SPACE
ALLOWED BY THE ARCHITECTURAL AND STRUCTURAL CONDITIONS. CUTTING
OR OTHERWISE ALTERING ANY STRUCTURAL MEMBERS SHALL NOT BE
PERMITTED WITHOUT WRITTEN PERMISSION FROM THE ARCHITECT.
HWS
HOT WATER SUPPLY
24. UNLESS NOTED OTHERWISE, TRANSFORMERS, CONTROLS AND CONTROL
WIRING REQUIRED FOR ALL MECHANICAL SYSTEMS SHALL BE FURNISHED
WITH THE EQUIPMENT IT SERVES AND INSTALLED BY THE MECHANICAL
CONTRACTOR. MOTOR STARTERS FOR HVAC EQUIPMENT SHALL BE
FURNISHED WITH THE MOTOR OR APPARATUS WHICH IT OPERATES. MOTOR
STARTER INSTALLATION SHALL BE BY THE ELECTRICAL CONTRACTOR.
25. ALL EVAPORATORS AND COOLING COILS LOCATED ABOVE THE LOWEST
LEVEL FINISHED FLOOR SHALL BE INSTALLED WITH AN AUXILIARY
CONDENSATE DRAIN PAN UNDER THE UNIT. PROVIDE AN ELECTRONIC
WATER LEVEL DETECTOR WIRED TO SHUTDOWN THE UNIT UPON
DETECTION OF WATER IN THE AUXILIARY DRAIN PAN.
26. AS AN ALTERNATE TO THE AUXILIARY CONDENSATE DRAIN PAN, AN
ELECTRONIC WATER LEVEL DETECTOR WIRED TO SHUTDOWN THE UNIT
UPON DETECTION OF WATER MAY BE INSTALLED IN THE PRIMARY DRAIN
LINE, THE OVERFLOW DRAIN LINE OR THE EQUIPMENT-SUPPLIED DRAIN
PAN. THE WATER LEVEL DETECTOR SHALL BE LOCATED AT A POINT
HIGHER THAN THE PRIMARY DRAIN LINE CONNECTION AND BELOW THE
OVERFLOW RIM OF SUCH PAN.
DUCT DROP IN RESPECT TO AIR FLOW
HWR
HOT WATER RETURN
LSS
LOW PRESSURE STEAM SUPPLY
LSC
LOW PRESSURE STEAM CONDENSATE
MSS
MEDIUM PRESSURE STEAM SUPPLY
MSC
MEDIUM PRESSURE STEAM CONDENSATE
BT
DUCT RISE IN RESPECT TO AIR FLOW
STAE COLLEGE, PA 16801
STRAINER
FLEXIBLE DUCT CONNECTION
STRUCTURAL ENGINEER
FLOAT & THERMOSTATIC TRAP
DIFFUSER
WBCM
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
INVERTED BUCKET TRAP
RETURN/EXHAUST OUTLET
TEE-TURNED DOWN
A
G
ELBOW-TURNED DOWN
DIFFUSER WITH FLEX DUCT
ELBOW-TURNED UP
RETURN/EXHAUST OUTLET
PIPE ANCHOR
RETURN GRILLE RG-1
PIPE GUIDE
ACOUSTICAL DUCT LINING
FLEXIBLE PIPE CONNECTION
PC
PUMPED CONDENSATE
RL
REFRIGERANT LIQUID
RS
REFRIGERANT SUCTION
RHG
REFRIGERANT HOT GAS
UNION
VENT
COMPANION FLANGE
SOUND ATTENUATOR
REDUCER
V
NEW DUCTWORK
PIPE CAP
FUTURE DUCTWORK
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE REMOVED
BLIND FLANGE
FIRE DAMPER (VERTICAL)
FLOW MEASURING STATION
MISCELLANEOUS
FIRE DAMPER (HORIZONTAL)
FLOW VENTURI
T
THERMOSTAT (TEMPERATURE SENSOR)
T
E
T
R
T
N
THERMOSTAT-RELOCATED (TEMPERATURE SENSOR)
GAUGES (PRESSURE)
THERMOSTAT-NEW (TEMPERATURE SENSOR)
2 WAY CONTROL VALVE
HUMIDISTAT (HUMIDITY SENSOR)
CO2
CARBON DIOXIDE (CO2) SENSOR
CARBON MONOXIDE (CO) SENSOR
CO
THERMOMETER
THERMOSTAT-EXISTING (TEMPERATURE SENSOR)
H
FIRE SMOKE DAMPER (VERTICAL)
FIRE SMOKE DAMPER (HORIZONTAL)
H
MD
HUMIDIFIER
MOTORIZED DAMPER
TAGS
TRANSFER DUCT
CONNECT NEW TO EXISTING
LIMIT OF REMOVAL
SD
EQP
#
MOTORIZED EQUIPMENT (EF, B)
UPPER - EQUIPMENT DESIGNATION
LOWER - EQUIPMENT NUMBER
EQP
#
NON-MOTORIZED EQUIPMENT (ET, AS, CV)
UPPER - EQUIPMENT DESIGNATION
LOWER - EQUIPMENT NUMBER
SMOKE DETECTOR
U
UNDERCUT DOOR
L
LOUVERED DOOR
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
A
F&TT
LITITZ, PA 17543
GEOTECHNICAL ENGINEER
GAS
GS
AHA CONSULTING ENGINEERS
ROSWELL, GA 30076
FOG
23. ALL REQUIRED CONTROL WIRING (INCLUDING POWER WIRING REQUIRED
FOR CONTROL PANELS, DEVICES, ETC. ) NOT SHOWN ON THE ELECTRICAL
DRAWINGS SHALL BE INCLUDED AS PART OF THE MECHANICAL WORK.
MEP ENGINEER
DUCT TURNING DOWN
11. FIELD MEASURE THE EXACT SIZES AND VERIFY ALL OPENINGS FOR SHAFTS
AND LOUVERS PRIOR TO SUBMISSION OF SHOP DRAWINGS AND
INSTALLATION.
22. ALL MECHANICAL EQUIPMENT REQUIRING ELECTRICAL POWER SHALL BE
INSTALLED WITH DISCONNECT SWITCHES AT EACH PIECE OF EQUIPMENT.
COORDINATE SWITCH TYPE WITH EQUIPMENT CHARACTERISTICS,
MANUFACTURER'S RECOMMENDATIONS AND THE ELECTRICAL DRAWINGS.
FLAT OVAL DUCT WITH SIZE
ANGLE VALVE
DN
21. THE HVAC CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS
AND REQUIREMENTS OF ALL MECHANICAL EQUIPMENT WITH ELECTRICAL
DRAWINGS PRIOR TO SUBMITTING SHOP DRAWINGS OR ORDERING
EQUIPMENT. EQUIPMENT SHALL BE FURNISHED WIRED FOR THE VOLTAGES
SHOWN ON THE ELECTRICAL PLANS.
12
DIRECTION OF PITCH
F
1600 NORTH SECOND STREET
1801 OLD ALABAMA RD, SUITE 125
DRAIN/HOSE BIBB
20. WHERE ABOVE CEILING VOLUMES AND MECHANICAL CLOSETS ARE UTILIZED
AS A RETURN AIR PLENUM, ALL MATERIALS EXPOSED WITHIN THE PLENUMS
SHALL BE NON-COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF
NOT MORE THAN 25 AND A SMOKE DEVELOPED INDEX OF NOT MORE THAN 50
AS DETERMINED IN ACCORDANCE WITH ASTM E84.
12Ø
ROUND DUCT WITH SIZE
DUCT TURNING UP
FUEL OIL RETURN
19. ALL PIPE AND DUCT PENETRATIONS OF FIRE AND/OR SMOKE-RATED
ASSEMBLIES SHALL BE FIRE-STOPPED AS REQUIRED TO RESTORE THE
ASSEMBLY TO ITS ORIGINAL INTEGRITY. FIRE BARRIER PRODUCTS SHALL BE
AS MANUFACTURED BY TREMCO, HILTI, 3M OR APPROVED EQUAL.
ASSOCIATE ARCHITECT
BUTTERFLY VALVE
FOR
18. PORTIONS OF DUCTWORK AND PIPE INSULATION VISIBLE THROUGH AIR
DISTRIBUTION DEVICES IN FINISHED AREAS SHALL BE PAINTED FLAT BLACK.
DUCT SECTION - RETURN
48
10. COORDINATE PHASING REQUIREMENTS FOR THE PROJECT WITH THE
GENERAL CONTRACTOR.
17. PROVIDE ACCESS PANELS IN NON-ACCESSIBLE CEILINGS AND IN WALL
STRUCTURE OF ADEQUATE SIZE TO ALLOW FOR MAINTENANCE, BALANCING
AND COMPLETE REPLACEMENT OF EQUIPMENT WITHOUT DISTURBING
PERMANENT CONSTRUCTION. ACCESS PANELS IN CEILINGS AND WALLS SHALL
BE PROVIDED WHERE SHOWN ON THE PLANS OR NECESSARY TO ACCESS
DAMPERS, VALVES, ETC. COORDINATE EXACT LOCATION & SIZES OF ALL
ACCESS PANELS WITH THE ARCHITECT DURING THE SHOP DRAWING
PROCESS.
12
HARRISBURG, PA 17102-2499
WEIGHTED LEVER VALVE
16. ANY EXISTING WALL, FLOOR, OR CEILING SURFACE THAT IS DISTURBED
DURING THE COURSE OF THE HVAC WORK SHALL BE REPAIRED TO
MATCH NEW AND/OR EXISTING CONDITIONS.
ATLANTA, GA 30326
MURRAY AND ASSOCIATES ARCHITECTS
FUEL OIL SUPPLY
13. COOLING DESIGN CONDITIONS ARE 75 F, 50% RH, INDOOR AT 89ºF DB/72ºF WB
OUTDOOR.
DUCT SECTION - SUPPLY
24
FOS
12. MINIMAL CONTROL POWER HAS BEEN IDENTIFIED ON THE DRAWINGS. IF ANY
ADDITIONAL POWER IS REQUIRED BASED ON SYSTEMS DESIGN BY THE
CONTROLS CONTRACTOR THE ATC/BAS CONTRACTOR SHALL BE
RESPONSIBLE TO SUPPLY THAT POWER.
12
BALL VALVE
CITY WATER MAKEUP
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
24
CHILLED WATER RETURN
COMPRESSED AIR
ARCHITECT
HKS, INC.
ROUND DUCT
12Ø
CHILLED WATER SUPPLY
CA
FLAT OVAL DUCT
24 x 12
GLOBE VALVE
CHWR
RECTANGULAR DUCT
14 x 6
H-1
A
P
1
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
GENERAL DUCTWORK NOTES
UPPER - SECTION DESIGNATION
LOWER - DRAWING NUMBER
UPPER - RISER DESIGNATION
LOWER - RISER NUMBER
KEY PLAN
A
HVAC ABBREVIATIONS
FPM
FEET PER MINUTE
AD
ACCESS DOOR
FPT
FAN POWERED TERMINAL
PRV
PRESSURE REDUCING VALVE
AFF
ABOVE FINISHED FLOOR
GPH
GALLONS PER HOUR
PSIG
POUNDS PER SQUARE INCH GAUGE
AP
ACCESS PANEL
GPM
GALLONS PER MINUTE
AS
AIR SEPARATOR
HP
TEMPLATE VERSION: 2.6.8.20141012
REQ'D
RETURN AIR
HPR
HIGH PRESSURE STEAM CONDENSATE RETURN
CFM
CUBIC FEET PER MINUTE
HPS
HIGH PRESSURE STEAM SUPPLY
RPM
REVOLUTIONS PER MINUTE
CHWR
CHILLED WATER RETURN
HWR
HEATING WATER RETURN
SMD
SMOKE DAMPER
CHWS
CHILLED WATER SUPPLY
HWS
HEATING WATER SUPPLY
SD
SMOKE DETECTOR
CO
CLEAN OUT
LAT
LEAVING AIR TEMPERATURE
SP
STATIC PRESSURE (INCHES OF WATER)
CW
COLD WATER (PLUMBING)
LBS/HR
RH
SPD
SPLITTER DAMPER
CWR
CONDENSER WATER RETURN
LPR
LOW PRESSURE STEAM CONDENSATE RETURN
T&P
TEMPERATURE AND PRESSURE
CWS
CONDENSER WATER SUPPLY
LPS
LOW PRESSURE STEAM SUPPLY
TYP
TYPICAL
DRAIN
LRA
LOCK ROTOR AMPS
DB
DRY BULB
LWT
LEAVING WATER TEMPERATURE
DIM
DIMENSION
MAX
MAXIMUM
DRAWING
MBH
THOUSAND BTU PER HOUR
VAC
VD
VDC
DX
DIRECT EXPANSION
MD
MOTORIZED DAMPER
EAT
ENTERING AIR TEMPERATURE
MIN
MINIMUM
ETR
EXISTING TO REMAIN
MPR
MEDIUM PRESSURE STEAM RETURN
WB
ELECTRIC PNEUMATIC RELAY
MPS
MEDIUM PRESSURE STEAM SUPPLY
WMS
EP
W/
W/OUT
DATE
RELATIVE HUMIDITY
POUNDS PER HOUR
V
REVISION
NO.
DESCRIPTION
REQUIRED
AUTOMATIC TEMPERATURE CONTROL
DWG
12/14/2015 11:03:10 PM
RA
PLUMBING
ATC
D
PLOT DATE:
HORSEPOWER
PLBG
B
AUTOMATIC CONTROL DAMPER
ACD
VOLTS
VOLTS A/C
VOLUME DAMPER
AHA PROJECT NUMBER
VOLTS D/C
G1215-004.00
WITH
DATE
WITHOUT
WET BULB TEMPERATURE °F
03 DECEMBER 2015
1/2" x 1/2" GALVANIZED WIRE MESH SCREEN
ISSUE
WET SPRINKLER
ENTERING WATER TEMPERATURE
NC
NORMALLY CLOSED
EXH
EXHAUST
NIC
NOT IN CONTRACT
CONSTRUCTION
DOCUMENTS
F&T
FLOAT AND THERMOSTATIC
NO
NORMALLY OPEN
SHEET TITLE
FACP
FIRE ALARM CONTROL PANNEL
OA
OUTSIDE AIR
HVAC GENERAL
NOTES AND
LEGEND
EWT
FCU
FAN COIL UNIT
OBD
OPPOSED BLADE DAMPER
FLA
FULL LOAD AMPS
OED
OPEN END DRAIN
FD
FIRE DAMPER OR FLOOR DRAIN
PD
PRESSURE DROP
COMBINATION FIRE DAMPER/SMOKE DAMPER
PE
PNEUMATIC ELECTRIC SWITCH
FD/SMD
WS
REVISED
15 DECEMBER 2015
SHEET NO.
M-001
19
18
17.4
17
1514.8
16
13
14.1 14
12
11
10
9
ARCHITECT
HKS, INC.
19.9
x.2
20
x.4.1
TWO LIVE OAK CENTER
x.6
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
2
M-201
20.8
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
21
UTILITY TUNNEL
T.R
028.1
WL
G-2
22
SITE/CIVIL ENGINEER
23
DERCK & EDSON ASSOCIATES
ER-3
125
ER-2
75
027
GEOTECHNICAL ENGINEER
TRANSFORMER
RM
T
IDF
013
A-1
ER-1
50
CUST
FAMILY 014
TOILET
6"x8"
SD-2
125
SD-2
120
010
011
WBCM
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
015.1
SERVERY #2
STO.
025
SD-4
485
SD-1
40
STRUCTURAL ENGINEER
CENTRAL PLANT
012
8"x14"
CIRC
STAE COLLEGE, PA 16801
1
M-404
024
PUBLIC TLT RM ER-4
M
300
G-1
2701 CAROLEAN INDUSTRIAL DRIVE
y.6.5
y.6
OFFICE
018
UH
CMT LABORATORIES, INC.
015.2
FOOD SERVICE
PREP
DSS
029
SD-2
115
ER-2
75
LITITZ, PA 17543
18"x12"
PUBLIC TLT RM F
MOD
T
33 SOUTH BROAD STREET
ICE/SODA
6"x10"
G-1
WL
G-1
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
EF
24
AHA CONSULTING ENGINEERS
028
18"x12"
23.6
MEP ENGINEER
026
SD-4
485
FIRE PUMP
ELEC.
GENERATOR RM
015.5
015.4
015.3
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
21.5
015
LOCKER RM
1
M-406
CUST
SD-4
485
FTR
SD-5
630
A
(TYP. 4)
RG-1
--(TYP 12)
16"x14"
16"x16"
VESTIBULE
SD-5
545
Y.5
Y
X.5
X.3
023
POT WASH
SD-5
630
008
SERVERY #2
020
70"x20"
SD-5
545
SD-4
485
SD-4
485
60"x20"
CIRC
88"x30"
Z
022
016
STAIR 04
LD-4
340
24"x20"
24"x18"
S-004
SD-4
485
X
LD-4
340
SR
255
FD
SD-4
485
SD-5
630
50"x20"
W
SR
485
T.R.
017
V.8
U.3
SD-5
630
V.7
LD-4
340
23.6
32"x20"
SD-5
630
24
12"x18"
SD-4
485
SD-4
485
T.5
SERVERY #1
FTR
LD-4
340
U
FD
019
A
T
V
32"x16"
LD-4
340
14"ø
DINING HALL
SD-4
485
SD-5
630
KEF
009
MAU
G-1
SD-5
630
LD-4
340
MATCHLINE: 3/ M-102
SD-3
245
KEF
I.6
LD-4
340
SD-3
245
Q
18"ø
WL
G-3
T
DSS
LD-4
340
SD-5
630
R
007
SD-3
245
SD-3
245
22"x16"
RECEIVING/
INVENTORY
STORAGE
SR
255
G-2
SD-5
630
S
48"x16"
SR
255
K
LD-4
340
SR
255
G-1
40"x16"
B-2
SD-3
245
P
ELEC
007.1
SD-3
245
O
N
KEY PLAN
MATCHLINE: 3/ M-102
24"x18"
1
M-101
HVAC PLAN - GROUND FLOOR - AREA A
J
K
L
M
A
M.2
SCALE: 1/8" = 1'-0"
B
REVISION
NO.
DESCRIPTION
SHEET NOTES
DATE
KEYED NOTES
AHA PROJECT NUMBER
12/14/2015 11:03:15 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC DUCTWORK
PLAN - GROUND
FLOOR - AREA A
REVISED
15 DECEMBER 2015
SHEET NO.
M-101
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
18
17
L
16
15
14
M.2
13
11
10
9
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
M
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
STRUCTURAL ENGINEER
WBCM
JK
LD-4
340
KEF
SD-5
630
I.6
LD-4
340
SD-3
245
MECHANICSBURG, PA 17050
18"ø
WL
G-3
SD-3
245
SD-3
245
22"x16"
100 STERLING PARKWAY, SUITE 108
SR
255
G-2
T
ELEC
DSS
I
SD-5
630
LD-4
340
H.2
H
G
SD-3
245
DSS
SD-3
245
24"x18"
B-1
SD-3
245
SD-3
245
030
MATCHLINE: 1/ M-101
SD-3
245
SD-3
245
ELEC
007.1
B-2
SD-3
245
WL
G-10
UP
SD-4
465
ATM
SD-3
245
SD-3
245
031
SD-3
245
SALES FLOOR
OFFICE
002
006
30"x18"
F.3
SD-3
205
SD-3
210
EUH
E
D
MOD
T
G-1
VESTIBULE
SD-4
460
SD-3
245
001
14"x18"
FTR
A
SD-3
245
SD-4
460
SD-3
245
SD-3
245
SD-3
245
40"x18"
005
C.2
OFFICE
18"x18"
004
SD-3
245
LD-3
245
WL
G-8
OFFICE
64"x20"
F
SD-3
245
FTR
25
(TYP. 7)
SD-3
150
SD-3
245
A
B.5
EWH
B
G-4
SD-3
245
LD-3
245
C
84"x21"
MECH RM
STORAGE
033
SD-3
245
032
84"x21"
A.5
72"x18"
LD-3
245
WL
G-9
EF
A.3
G-6
FTR
LD-3
245
LD-3
245
LD-3
245
8
LD-3
245
LD-3
245
LD-3
245
A
AHU
(TYP. 14)
G-3
A
WL
G-11
LD-3
245
7
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
MATCHLINE: 1/ M-101
6
5.3
5
4
2
1
KEY PLAN
3
M-102
HVAC PLAN - GROUND FLOOR - AREA B
A
SCALE: 1/8" = 1'-0"
B
REVISION
NO.
DESCRIPTION
SHEET NOTES
DATE
KEYED NOTES
AHA PROJECT NUMBER
12/14/2015 11:03:17 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC DUCTWORK
PLAN - GROUND
FLOOR - AREA B
REVISED
15 DECEMBER 2015
SHEET NO.
M-102
9
11
19
18
17.4
17
1514.8
16
1312.8
14.1
14
10
12
ARCHITECT
HKS, INC.
x.1
x.2
x.4 x.4.1 x.5
x.6
x.7
x.8
TWO LIVE OAK CENTER
x.9x.10
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
MECH
AHA CONSULTING ENGINEERS
WL
1-3
101
1801 OLD ALABAMA RD, SUITE 125
LD-1
145
AHU
ROSWELL, GA 30076
LD-1
145
1-1
50"x20"
PUBLIC
TLT1-1RM -M
72"x15"
COMMONS
100
1-1
12"x10" FPT
INTEGRATIVE
LEARNING
LD-1
170
24"x14"
102
SD-1
70
LD-1
170
SD-2
150
1-4
12"x10"108
-
SD-2
160
FPT
SD-2
150
22"x10"
28"x10"
18"ø
T
TO FPT-1-2
Y.5
32"x10"
Y
X.5
X.3
X
FTR
40"x10"
SD-2
165
A
LD-1
145
LD-1
145
LD-1
170
LD-1
145
LD-1
170
W
V.8
LD-1
170
FTR
LD-1
170
LD-1
170
LD-1
145
LD-1
145
21
LD-1
170
LD-3
240
T
TO FPT-1-5
18"x10"
20.8
LD-3
240
22
LD-3
240
22"x12"
M.2
M
RD-5
---
SD-3
235
FTR
SD-3
275
110.2
RD-5
---
1-3
RF
1-1
SD-3
250
18"x14"
32"x14"
WL
1-5
32"x14"
EWH
1-5
10"x10"
1-4
MAIL LOBBY
STAIR 02
110.1
S-102
SD-2
150
14"ø
RECP.
SD-1
90
14"ø
107
SD-1
25
EF
1-2
6"x6"
LD-3
240
24
16"x12"
(TYPICAL)
LD-3
240
23.6
TO AHU-1-2
10"x12"
FPT
RG-1
---
LD-3
240
A
V.7
MAIL RECEIVING
SD-3
250
SD-2
150
A
21.5
23
32"x14"
RD-5
---
RD-5
---
20"x10"
106
S-104
1-2
SD-3
240
10"x10"
LOUNGE
MECHANICSBURG, PA 17050
EWH
T
(TYP. 2)
STRUCTURAL ENGINEER
111
TO FPT-1-3
STAIR 04
LD-1
170
SD-3
235
A
SD-2
185
1-3
FPT
FTR
STAE COLLEGE, PA 16801
MECH
30"x12"
16"x12"
CONFERENCE RM
2701 CAROLEAN INDUSTRIAL DRIVE
y.6.5
y.6
100 STERLING PARKWAY, SUITE 108
22"x12"
RD-4
---
LD-1
180
T
SD-2
145
SD-2
145
ELEV.
24"x10"
LD-1
170
SD-2
185
14"ø
105
Z
T
22"x10"
FPT
16"ø
LD-1
180
32"x14"
WBCM
20"x14"
TO FPT-1-4
16"x10"
32"x14"
110
(TYP. 6)
22"x10"
PUBLIC TLT RM 28"x14"
-F
50"x16"
LD-1
180
1-2
CMT LABORATORIES, INC.
SD-3
330
A
T
110.3
110.4
MAIL VEST.
FTR
SD-2
145
TO FPT-1-1
ER-3
225
1-1
FTR
SD-2
160
A
WL
1-4
AHU
OFFICE
LD-2
185
LD-1
180
FTR
RD-3
---
SD-3
250
LD-2
185
A
16"x10"
100"x30"
EWH
14"x10"
FTR
LD-1
150
103
S-101
WKSTATIONS
LD-1
150
SD-2
145
75"x15"
GEOTECHNICAL ENGINEER
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
50"x24"
ER-3
225
LD-1
150
12"x10"
1-2
LD-1
170
A
LITITZ, PA 17543
EF
STAIR 01
LD-1
170
33 SOUTH BROAD STREET
EWH
WL
1-1
SD-1
100
DERCK & EDSON ASSOCIATES
LD-1
145
WL
1-2
12"x10"
SITE/CIVIL ENGINEER
T
LD-3
220
DSS
A-2
SD-2
145
ELEV.
LD-5
500
TLT
1-6
112
-
20"x10"
6"ø
STO.
U.3
14"x10"
SD-1
90
IDF
104
FPT
102"x26"
SD-3
220
113
107.1
40"x16"
JC
V
U
OFFICE
EF
T.5
OFFICE
1-3
115
T
114
1
L
SD-3
220
2
F
S
4
CORRIDOR
TRPL SUITE
JK
MATCHLINE: 1/ M-104
C-101
117
WL
1-6
SD-3
235
WL
1-7
CD-1
160
I.6
Q
SD-3
240
STAFF BK RM
1
R
116
P
1
O
N
TRPL SUITE (MIR)
118
KEY PLAN
A
1
M-103
HVAC PLAN - 1ST FLOOR - AREA A
SCALE: 1/8" = 1'-0"
B
REVISION
NO.
DESCRIPTION
HVAC UNIT PLAN LEGEND
SHEET NOTES
A
STAFF APARTMENT - REFER TO.......
1/M-401
B
GRAD SUITE - REFER TO ....
2/M-401
C
RA SUITE (AREA A) - REFER TO .....
3/M-401
D
RA SUITE (AREA B) - REFER TO .....
4/M-401
E
DOUBLE SUITE - REFER TO ......
5/M-401
DATE
KEYED NOTES
12/14/2015 11:03:21 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
AHA PROJECT NUMBER
F
G1215-004.00
TRIPLE SUITE - REFER TO........
6/M-401
DATE
G
03 DECEMBER 2015
QUAD SUITE - REFER TO........
1/M-402
ISSUE
H
QUAD SUITE A - REFER TO........
2/M-402
I
QUAD SUITE B - REFER TO........
3/M-402
J
QUAD SUITE C - REFER TO........
1/M-403
K
QUAD SUITE D - REFER TO........
2/M-403
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC DUCTWORK
PLAN - 1ST FLOOR
- AREA A
REVISED
15 DECEMBER 2015
SHEET NO.
M-103
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
18
17
L
16
M 15
14
M.2
13
12.8
11
10
9
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
STRUCTURAL ENGINEER
WBCM
JK
WL
1-7
P
O
N
TRPL SUITE (MIR)
I
118
F
H.2
H
QUAD SUITE B
I
G
121
2
20"x10"
FCU
F.3
4
10"x10"
10"x8"
LAUNDRY
122
E
RG-A
--3
RD-3
--(TYP. 2)
8"x8"
B-4
24"x10"
1
119
RA SUITE
127
T
EF
A
IDF
T
123
CD-1
160
ELEC
FCU
DSS
E
1-4
T
30"x10"
T
12"x10"
E
D
10"x8"
10"x10" RG-A
---
1
F
2
ER-1
200
SD-3
350
SD-2
150
6"x4"
1
BDBL SUITE - CW
129
MECH
12"x12"
FTR
LOUNGE
A
(TYP. 10)
MATCHLINE: 1/ M-103
20"x10"
T
120
CD-1
160
124
1
DSS
D
2
B-3
22"x10"
20"x10"
10"x10"
SD-2
225
(TYP. 2)
2
QUAD SUITE A
131
1
2
G
133
2
1
2
C.2
5
C
2
14"x10"
QUAD SUITE C 14"x10"
LD-2
225
(TYP. 4)
1
1
TRPL SUITE (MIR)
- CW
F
125
J
10"x10"
14"x10"
25
1
10"x10"
1
TRPL SUITE (MIR)
F
126
CORRIDOR
2
CD-1
160
1
2
1
2
M-106
STAIR 05
C-102
B.5
S-105
1
2
DBL SUITE
DBL SUITE
128
130
B
B
1
2
CD-1
160
B
AREA COORD.
SUITE (AC)
A
A.5
132
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
1
D
3
MECHANICSBURG, PA 17050
CD-1
160
1
I.6
100 STERLING PARKWAY, SUITE 108
Q
EWH
STAIR 03
1-5
A.3
S-103
A
8
7
6
5.3
5
4
2
1
4.4
1
M-104
KEY PLAN
HVAC PLAN - 1ST FLOOR - AREA B
A
SCALE: 1/8" = 1'-0"
B
REVISION
NO.
DESCRIPTION
HVAC UNIT PLAN LEGEND
SHEET NOTES
A
STAFF APARTMENT - REFER TO.......
1/M-401
B
GRAD SUITE - REFER TO ....
C
DATE
KEYED NOTES
1
6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
2/M-401
2
6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR
WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
RA SUITE (AREA A) - REFER TO .....
3/M-401
3
6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU.
PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP.
BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.
D
RA SUITE (AREA B) - REFER TO .....
4/M-401
4
IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF
SR-A GRILLES.
E
DOUBLE SUITE - REFER TO ......
5/M-401
12/14/2015 11:03:24 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
AHA PROJECT NUMBER
F
G1215-004.00
TRIPLE SUITE - REFER TO........
6/M-401
DATE
G
03 DECEMBER 2015
QUAD SUITE - REFER TO........
1/M-402
ISSUE
H
QUAD SUITE A - REFER TO........
2/M-402
I
QUAD SUITE B - REFER TO........
3/M-402
J
QUAD SUITE C - REFER TO........
1/M-403
K
QUAD SUITE D - REFER TO........
2/M-403
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC DUCTWORK
PLAN - 1ST FLOOR
- AREA B
REVISED
15 DECEMBER 2015
SHEET NO.
M-104
19
18
17.4
17
1514.8
16
13 12.8
14.1 14
10
12 11
9
ARCHITECT
HKS, INC.
x.1
x.2
x.4 x.4.1 x.5
x.6
x.7
x.8
TWO LIVE OAK CENTER
x.9x.10
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
QUAD SUITE D
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
238
LITITZ, PA 17543
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
1
236
A-3
T
K
G
CD-1
170 QUAD
STAIR 01
D
4
S-201
FCU
2701 CAROLEAN INDUSTRIAL DRIVE
y.6.5
y.6
IDF
DSS
STAE COLLEGE, PA 16801
STRUCTURAL ENGINEER
WBCM
SUITE (MIR)
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
234
2
F
CD-1
170
3
FTR
A
JC
242
LD-2
230
SD-2
230
(TYP. 3)
ELEC.
2
D
239
LOUNGE
RA SUITE
237
1
2
243
1
C
1
10"x10"
B
6"x4"
T
CORRIDOR
DBL SUITE
1
T
235
10"x10"
ER-1
50
232
A-4
2
1
1
(TYP. 8)
2
DSS
SR-1
1170
20"x10"
Z
GRAD SUITE
1
2
146
16"x10"
1
2
F
TRPL SUITE (MIR)
1
1
CD-1
170
233
2
2
Y.5
Y
X.5
X.3
1
LD-1
170
G
1
16"x10"
LD-1
180
QUAD SUITE
230
20.8
F
21.5
CT
2
3
(FUTURE)
(FUTURE)
CRCU
CRCU
G-1
G-2
SR-1
1170
1
TRPL SUITE
CT
1
S-202
F
241
CT
STAIR 02
14"x10"
21
TRPL SUITE
X
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
RG-A
---
1
231
22"x10"
22
W
D
4
1
ELEV.
23
V.8
-
V.7
QUAD SUITE (MIR)
-
M
23.6
U.3
D
1ELEV.
18"x10"
U
201
T.5
24
G
10"x10"
10"x10"
V
T
2
1
L
2
S
1
F
R
TRPL SUITE
JK
MATCHLINE: 1/ M-106
CD-1
170
CORRIDOR
202
Q
147
1
I.6
P
1
TRPL SUITE (MIR)
O
N
203
KEY PLAN
MATCHLINE: 1/ M-106
F
A
1
M-105
HVAC PLAN - 2ND FLOOR - AREA A
SCALE: 1/8" = 1'-0"
B
REVISION
NO.
DESCRIPTION
HVAC UNIT PLAN LEGEND
SHEET NOTES
A
STAFF APARTMENT - REFER TO.......
1/M-401
B
GRAD SUITE - REFER TO ....
C
DATE
KEYED NOTES
1
6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
2/M-401
2
6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR
WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
RA SUITE (AREA A) - REFER TO .....
3/M-401
3
6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU.
PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP.
BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.
D
RA SUITE (AREA B) - REFER TO .....
4/M-401
4
IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF
SR-A GRILLES.
E
DOUBLE SUITE - REFER TO ......
5/M-401
12/14/2015 11:03:28 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
AHA PROJECT NUMBER
F
G1215-004.00
TRIPLE SUITE - REFER TO........
6/M-401
DATE
G
03 DECEMBER 2015
QUAD SUITE - REFER TO........
1/M-402
ISSUE
H
QUAD SUITE A - REFER TO........
2/M-402
I
QUAD SUITE B - REFER TO........
3/M-402
J
QUAD SUITE C - REFER TO........
1/M-403
K
QUAD SUITE D - REFER TO........
2/M-403
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC DUCTWORK
PLAN - 2ND FLOOR
- AREA A
REVISED
15 DECEMBER 2015
SHEET NO.
M-105
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
18
17
L
16
M 15
14
13
12.8
11
10
9
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
F
STRUCTURAL ENGINEER
MATCHLINE: 1/ M-105
WBCM
TRPL SUITE
JK
202
MECHANICSBURG, PA 17050
147
1
P
O
N
TRPL SUITE (MIR)
I
203
D
3
F
H.2
H
QUAD SUITE B
206
I
G
2
FCU
E
SD-3
350
ER-1
200
SD-2
150
RD-3
--(TYP 2)
1
3
RG-A
---
RG-A
---
1
10"x10"
DSS
IDF T
8"ø
208
14"x4"
12"x8"
FTR
(TYP. 10)
2
1
204
QUAD SUITE B
DSS
B-5
E
T
14"x4"
LOUNGE
209
4
F
TRPL SUITE (MIR)
- CW
4
DBL SUITE - CW
213
2
1
1
215
2
1
2
1
1
4
G
QUAD SUITE - CW
4
B
DBL SUITE - CW
217
219
1
2
2
1
2
I
C.2
2
C
10"x10"
34"x10"
12"x10"
LD-2
225
(TYP. 4)
B
6"x4"
6"x4"
6"x4"
8"ø
1
SD-2
225
(TYP. 2)
14"x4"
211
D
2
12"x12"
T
14"x4"
221
RA SUITE
A
T
CD-1
190
E
D
2
ELEC
FCU
B-6
A
CD-1
190
LAUNDRY
207
F.3
MATCHLINE: 1/ M-105
20"x10"
16"x10"
22"x10"
22"x10"
25
J
1
CORRIDOR
1
2
1
1
1
2
1
2
1
TRPL SUITE (MIR)
QUAD SUITE C
212
210
CD-1
190
2
M-106
F
B
B.5
14"x4"
10"x10"
148
14"x10"
DBL SUITE
214
2
QUAD SUITE
G
216
1
B
1
DBL SUITE (MIR)
CD-1
190
DBL SUITE
B
2
8"ø
220
218
B
1
4
A.5
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
1
I.6
F
100 STERLING PARKWAY, SUITE 108
Q
CORRIDOR
SR-1
1170
STAIR 03
D
5
S-203
A
LD-2
190
8
7
6
5.3
5
4
3
2
1
4.4
1
M-106
KEY PLAN
HVAC PLAN - 2ND FLOOR - AREA B
A
SCALE: 1/8" = 1'-0"
B
REVISION
NO.
DESCRIPTION
HVAC UNIT PLAN LEGEND
25
BBBB
CC
C
C
PLUMBING PIPING. SEE
PLUMBING PLANS FOR
TYPES AND SIZES.
STAFF APARTMENT - REFER TO.......
1/M-401
B
GRAD SUITE - REFER TO ....
C
1
6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
2/M-401
2
6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR
WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
RA SUITE (AREA A) - REFER TO .....
3/M-401
3
6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU.
PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP.
BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.
D
RA SUITE (AREA B) - REFER TO .....
4/M-401
4
IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF
SR-A GRILLES.
E
DOUBLE SUITE - REFER TO ......
5/M-401
AHA PROJECT NUMBER
F
TEMPLATE VERSION: 2.6.8.20141012
12/14/2015 11:03:32 PM
A
4X6 OA DUCT
FIRE PROTECTION PIPING.
PLOT DATE:
KEYED NOTES
C.2
C.2
14X10 EA DUCT
20X10 OA DUCT
4X6 EA DUCT
SHEET NOTES
DATE
G1215-004.00
TRIPLE SUITE - REFER TO........
6/M-401
DATE
B.5
G
03 DECEMBER 2015
QUAD SUITE - REFER TO........
1/M-402
ISSUE
H
QUAD SUITE A - REFER TO........
2/M-402
I
QUAD SUITE B - REFER TO........
3/M-402
J
QUAD SUITE C - REFER TO........
1/M-403
K
QUAD SUITE D - REFER TO........
2/M-403
CONSTRUCTION
DOCUMENTS
2ND FLOOR
129' - 3"
2
M-106
TYPICAL CORRIDOR SECTION
SCALE: 1/4" = 1'-0"
SHEET TITLE
HVAC DUCTWORK
PLAN - 2ND FLOOR
- AREA B
REVISED
15 DECEMBER 2015
SHEET NO.
M-106
9
11
19
18
17.4
17
1514.8
16
1312.8
14.1
14
10
12
ARCHITECT
HKS, INC.
x.4
x.5
x.6
x.7
x.8
TWO LIVE OAK CENTER
x.9x.10
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
IDF
DSS
A-5
QUAD SUITE D
D
4
FCU
K
STAIR 01
336
334
T
CD-1
170
338
S-301
STAE COLLEGE, PA 16801
STRUCTURAL ENGINEER
WBCM
G
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
2
F
RG-A
---
1
2
1
ER-1
50
A
(TYP. 8)
JC
EWH
342
LD-2
230
SD-2
230
(TYP. 3)
2
3-1
DBL SUITE
1
T
16"x10"
3-1
10"x10"
D
1
DOUBLE SUITE
1
332
B
10"x10"
339
RA SUITE
B
337
2
16"x10"
2
333
343
1
2
F
TRPL SUITE (MIR)
1
LOUNGE
2
C-300
EF
1
CORRIDOR
335
3
FTR
2
T
1
1
CD-1
170
1
LD-1
180
1
G
QUAD SUITE
20.8
F
14"x10"
EWH
3-2
STAIR
02
330
S-302
21
TRPL SUITE
Y
X.5
X.3
X
LD-1
170
2
2
Y.5
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
ELEC.
CD-1
170
20"x10"
Z
QUAD SUITE (MIR)
1
2701 CAROLEAN INDUSTRIAL DRIVE
y.6.5
y.6
F
341
1
TRPL SUITE
21.5
1
331
22"x10"
8"ø
22
W
D
4
1
14"x4"
23
V.8
U.3
D
1
V.7
M
23.6
U
18"x10"
24
T.5
QUAD SUITE (MIR)
301
10"x10"
10"x10"
V
T
G
2
1
L
2
S
1
CD-1
170
F
TRPL SUITE
JK
MATCHLINE: 1/ M-108
R
CORRIDOR
C-301
302
Q
1
I.6
P
1
TRPL SUITE (MIR)
O
N
303
KEY PLAN
MATCHLINE: 1/ M-108
F
A
1
M-107
HVAC PLAN - 3RD FLOOR - AREA A
SCALE: 1/8" = 1'-0"
B
REVISION
NO.
DESCRIPTION
HVAC UNIT PLAN LEGEND
SHEET NOTES
A
STAFF APARTMENT - REFER TO.......
1/M-401
B
GRAD SUITE - REFER TO ....
C
DATE
KEYED NOTES
1
6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
2/M-401
2
6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR
WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
RA SUITE (AREA A) - REFER TO .....
3/M-401
3
6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU.
PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP.
BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.
D
RA SUITE (AREA B) - REFER TO .....
4/M-401
4
IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF
SR-A GRILLES.
E
DOUBLE SUITE - REFER TO ......
5/M-401
12/14/2015 11:03:36 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
AHA PROJECT NUMBER
F
G1215-004.00
TRIPLE SUITE - REFER TO........
6/M-401
DATE
G
03 DECEMBER 2015
QUAD SUITE - REFER TO........
1/M-402
ISSUE
H
QUAD SUITE A - REFER TO........
2/M-402
I
QUAD SUITE B - REFER TO........
3/M-402
J
QUAD SUITE C - REFER TO........
1/M-403
K
QUAD SUITE D - REFER TO........
2/M-403
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC DUCTWORK
PLAN - 3RD FLOOR
- AREA A
REVISED
15 DECEMBER 2015
SHEET NO.
M-107
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
18
17
L
16
M 15
14
13
12.8
11
10
9
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
1
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
F
MATCHLINE: 1/ M-107
TRPL SUITE
JK
STRUCTURAL ENGINEER
CORRIDOR
WBCM
C-301
302
MECHANICSBURG, PA 17050
1
P
O
N
TRPL SUITE (MIR)
I
303
D
3
CD-1
190
F
H.2
H
MATCHLINE: 1/ M-107
QUAD SUITE B
LAUNDRY
307
306
G
I
2
FCU
E
RG-A
---
SD-3
350
ER-1
200
SD-2
150
RD-3
--(TYP 2)
8"x8"
1
3
T
1
ELEC
FCU
A
DSS
B-7
IDFT
T
FTR
14"x4"
T
14"x4"
321
B
6"x4"
6"x4"
6"x4"
8"ø
2
1
1
DBL SUITE - CW
TRPL SUITE
4(MIR)
F
- CW
4
G
QUAD SUITE - CW
313
315
317
4
2
2
1
1
1
34"x10"
20"x10"
22"x10"
22"x10"
25
J
1
2
1
1
16"x10"
CORRIDOR
14"x10"
C-302
TRPL SUITE (MIR)
QUAD SUITE C
310
312
CD-1
190
F
B
4
2
C.2
DBL SUITE - CW
1
1
I
319
2
C
10"x10"
14"x4"
10"x10"
1
1
2
1
B
2
2
12"x10"
LD-2
225
(TYP. 4)
311
E
D
2
12"x12"
1
SD-2
225
(TYP. 2)
QUAD SUITE B
EF
LOUNGE
309
RA SUITE
3-2
CD-1
190
16"x10"
14"x4"
A
(TYP. 10)
304
8"ø
308
14"x4"
12"x8"
E
D
1
RG-A
--10"x10"
F
2
2
2
1
DBL SUITE
DBL SUITE
314
316
CD-1
190
G
B
1
2
QUAD SUITE
DBL SUITE (MIR)
318
320
B
1
8"ø
1
B
4
A.5
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
1
I.6
F.3
100 STERLING PARKWAY, SUITE 108
Q
EWH
3-3
STAIR 03
D
5
S-303
A
LD-2
190
8
7
6
5.3
5
4
3
2
1
4.4
1
M-108
KEY PLAN
HVAC PLAN - 3RD FLOOR - AREA B
A
SCALE: 1/8" = 1'-0"
B
REVISION
NO.
DESCRIPTION
HVAC UNIT PLAN LEGEND
SHEET NOTES
A
STAFF APARTMENT - REFER TO.......
1/M-401
B
GRAD SUITE - REFER TO ....
C
DATE
KEYED NOTES
1
6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
2/M-401
2
6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR
WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
RA SUITE (AREA A) - REFER TO .....
3/M-401
3
6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU.
PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP.
BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.
D
RA SUITE (AREA B) - REFER TO .....
4/M-401
4
IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF
SR-A GRILLES.
E
DOUBLE SUITE - REFER TO ......
5/M-401
12/14/2015 11:03:39 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
AHA PROJECT NUMBER
F
G1215-004.00
TRIPLE SUITE - REFER TO........
6/M-401
DATE
G
03 DECEMBER 2015
QUAD SUITE - REFER TO........
1/M-402
ISSUE
H
QUAD SUITE A - REFER TO........
2/M-402
I
QUAD SUITE B - REFER TO........
3/M-402
J
QUAD SUITE C - REFER TO........
1/M-403
K
QUAD SUITE D - REFER TO........
2/M-403
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC DUCTWORK
PLAN - 3RD FLOOR
- AREA B
REVISED
15 DECEMBER 2015
SHEET NO.
M-108
9
11
19
18
17.4
17
1514.8
16
1312.8
14.1
14
10
12
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
IDF
DSS
A-6
QUAD SUITE D
S-401
1
CD-1
170
SR-1
1170
FTR
1
JC
SD-2
230
16"x10"
ELEC.
10"x10"
ER-1
50
442
(TYP. 3)
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
2
DBL SUITE
1
T
C-400
T
1
1
DOUBLE SUITE
432
D
B
10"x10"
439
RA SUITE
B
437
2
16"x10"
2
433
443
1
2
F
TRPL SUITE (MIR)
1
LOUNGE
2
CORRIDOR
A-7
435
(TYP. 8)
LD-2
230
G
DSS
2
1
3
A
WBCM
2
RG-A
--20"x10"
STRUCTURAL ENGINEER
CD-1
170
438
F
Z
434
T
1
CD-1
170
1
1
LD-1
170
2
G
2
LD-1
180
Y.5
1
14"x10"
STAIR 02
430
S-402
21
TRPL SUITE
Y
X.5
X.3
X
QUAD SUITE
20.8
F
F
441
21.5
SR-1
1170
1
TRPL SUITE
1
431
22"x10"
8"ø
22
W
D
4
1
23
V.8
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
D
4
FCU
K
STAIR 01
436
STAE COLLEGE, PA 16801
QUAD SUITE (MIR)
1
U.3
D
1
V.7
M
23.6
U
18"x10"
24
T.5
QUAD SUITE (MIR)
401
10"x10"
10"x10"
V
T
G
2
1
L
2
S
1
CD-1
170
F
TRPL SUITE
JK
MATCHLINE: 1/ M-110
R
CORRIDOR
C-401
402
Q
1
I.6
P
TRPL SUITE (MIR)
1
O
N
403
?
KEY PLAN
MATCHLINE: 1/ M-110
F
A
?
1
M-109
HVAC PLAN - 4TH FLOOR - AREA A
SCALE: 1/8" = 1'-0"
B
REVISION
NO.
DESCRIPTION
HVAC UNIT PLAN LEGEND
SHEET NOTES
A
STAFF APARTMENT - REFER TO.......
1/M-401
B
GRAD SUITE - REFER TO ....
C
DATE
KEYED NOTES
1
6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
2/M-401
2
6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR
WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
RA SUITE (AREA A) - REFER TO .....
3/M-401
3
6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU.
PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP.
BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.
D
RA SUITE (AREA B) - REFER TO .....
4/M-401
4
IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF
SR-A GRILLES.
E
DOUBLE SUITE - REFER TO ......
5/M-401
12/14/2015 11:03:43 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
AHA PROJECT NUMBER
F
G1215-004.00
TRIPLE SUITE - REFER TO........
6/M-401
DATE
G
03 DECEMBER 2015
QUAD SUITE - REFER TO........
1/M-402
ISSUE
H
QUAD SUITE A - REFER TO........
2/M-402
I
QUAD SUITE B - REFER TO........
3/M-402
J
QUAD SUITE C - REFER TO........
1/M-403
K
QUAD SUITE D - REFER TO........
2/M-403
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC DUCTWORK
PLAN - 4TH FLOOR
- AREA A
REVISED
15 DECEMBER 2015
SHEET NO.
M-109
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
18
17
L
16
M 15
14
13
12.8
11
10
9
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
1
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
F
MATCHLINE: 1/ M-109
TRPL SUITE
JK
STRUCTURAL ENGINEER
CORRIDOR
WBCM
C-401
402
100 STERLING PARKWAY, SUITE 108
Q
MECHANICSBURG, PA 17050
I
403
D
3
MATCHLINE: 1/ M-109
CD-1
190
F
?
H.2
H
P
O
N
1
TRPL SUITE (MIR)
?
LAUNDRY
G
406
I
2
FCU
E
F.3
RG-A
---
3
SD-3
350
ER-1
200
SD-2
150
RD-3
--(TYP 2)
8"x8"
1
1
T
RG-A
--10"x10"
F
IDFT
8"ø
408
14"x4"
12"x8"
FTR
ELEC
404
DSS
14"x4"
411
421
FCU
LD-2
225
(TYP. 4)
B
6"x4"
6"x4"
6"x4"
8"ø
1
SD-2
225
(TYP. 2)
14"x4"
E
D
2
12"x12"
LOUNGE
409
QUAD SUITE B
T
CD-1
190
14"x4"
(TYP. 10)
RA SUITE
B-8
T
A
E
D
1
A
DSS
B-9
2
DBL SUITE - CW
413
2
1
1
2
1
415
2
1
1
12"x10"
20"x10"
22"x10"
22"x10"
25
J
1
2
1
1
1
16"x10"
CORRIDOR
14"x10"
C-402
2
CD-1
190
412
410
F
2
C.2
I
419
2
1
1
2
C
10"x10"
14"x4"
10"x10"
1
1
TRPL SUITE (MIR)
QUAD SUITE C
4
DBL SUITE - CW
417
2
34"x10"
B
G
4
QUAD SUITE - CW
4
F
TRPL SUITE (MIR)
- CW
4
2
1
DBL SUITE
DBL SUITE
414
416
2
CD-1
190
G
B
B
1
2
QUAD SUITE
DBL SUITE (MIR)
418
420
B
B
1
8"ø
1
4
A.5
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
1
I.6
SR-1
1170
STAIR 03
D
5
S-403
A
LD-2
190
8
7
6
5.3
5
4
3
2
1
4.4
1
M-110
KEY PLAN
HVAC PLAN - 4TH FLOOR - AREA B
A
SCALE: 1/8" = 1'-0"
B
REVISION
NO.
DESCRIPTION
HVAC UNIT PLAN LEGEND
SHEET NOTES
A
STAFF APARTMENT - REFER TO.......
1/M-401
B
GRAD SUITE - REFER TO ....
C
DATE
KEYED NOTES
1
6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
2/M-401
2
6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR
WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
RA SUITE (AREA A) - REFER TO .....
3/M-401
3
6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU.
PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP.
BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.
D
RA SUITE (AREA B) - REFER TO .....
4/M-401
4
IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF
SR-A GRILLES.
E
DOUBLE SUITE - REFER TO ......
5/M-401
12/14/2015 11:03:46 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
AHA PROJECT NUMBER
F
G1215-004.00
TRIPLE SUITE - REFER TO........
6/M-401
DATE
G
03 DECEMBER 2015
QUAD SUITE - REFER TO........
1/M-402
ISSUE
H
QUAD SUITE A - REFER TO........
2/M-402
I
QUAD SUITE B - REFER TO........
3/M-402
J
QUAD SUITE C - REFER TO........
1/M-403
K
QUAD SUITE D - REFER TO........
2/M-403
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC DUCTWORK
PLAN - 4TH FLOOR
- AREA B
REVISED
15 DECEMBER 2015
SHEET NO.
M-110
9
11
19
18
17.4
17
1514.8
16
1312.8
14.1
14
10
12
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
IDF
DSS
A-8
QUAD SUITE D
K
STAIR 01
RG-A
---
G
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
1
CD-1
170
20"x10"
ELEC.
2
1
A
JC
(TYP. 8)
542
SD-2
230
LD-2
230
10"x10"
ER-1
50
2
DBL SUITE
1
T
(TYP. 3)
16"x10"
CORRIDOR
C-500
EF
1
FTR
2
T
535
3
1
1
DOUBLE SUITE
532
5-1
D
B
10"x10"
539
RA SUITE
B
537
2
16"x10"
2
F
TRPL SUITE (MIR)
1
2
533
1
1
1
LD-1
170
1
2
2
LOUNGE
Y.5
WBCM
2
F
Z
STRUCTURAL ENGINEER
CD-1
170
538
S-501
FCU
534
T
LD-1
180
543
1
QUAD SUITE
14"x10"
STAIR 02
530
S-502
21
TRPL SUITE
Y
X.5
X.3
X
G
20.8
F
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
D
4
536
STAE COLLEGE, PA 16801
QUAD SUITE (MIR)
1
F
541
1
TRPL SUITE
21.5
1
531
22"x10"
22
W
D
4
1
23
V.8
U.3
D
1
V.7
M
23.6
U
18"x10"
24
T.5
QUAD SUITE (MIR)
501
10"x10"
10"x10"
V
T
G
2
1
L
2
S
1
CD-1
170
F
TRPL SUITE
JK
MATCHLINE: 1/ M-112
R
CORRIDOR
C-501
444
Q
1
I.6
P
TRPL SUITE (MIR)
1
O
N
503
KEY PLAN
MATCHLINE: 1/ M-112
F
QUAD SUITE B
A
C-603
1
M-111
HVAC PLAN - 5TH FLOOR - AREA A
SCALE: 1/8" = 1'-0"
B
REVISION
NO.
DESCRIPTION
HVAC UNIT PLAN LEGEND
SHEET NOTES
A
STAFF APARTMENT - REFER TO.......
1/M-401
B
GRAD SUITE - REFER TO ....
C
DATE
KEYED NOTES
1
6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
2/M-401
2
6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR
WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
RA SUITE (AREA A) - REFER TO .....
3/M-401
3
6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU.
PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP.
BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.
D
RA SUITE (AREA B) - REFER TO .....
4/M-401
4
IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF
SR-A GRILLES.
E
DOUBLE SUITE - REFER TO ......
5/M-401
12/14/2015 11:03:50 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
AHA PROJECT NUMBER
F
G1215-004.00
TRIPLE SUITE - REFER TO........
6/M-401
DATE
G
03 DECEMBER 2015
QUAD SUITE - REFER TO........
1/M-402
ISSUE
H
QUAD SUITE A - REFER TO........
2/M-402
I
QUAD SUITE B - REFER TO........
3/M-402
J
QUAD SUITE C - REFER TO........
1/M-403
K
QUAD SUITE D - REFER TO........
2/M-403
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC DUCTWORK
PLAN - 5TH FLOOR
- AREA A
REVISED
15 DECEMBER 2015
SHEET NO.
M-111
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
18
17
L
16
M 15
14
13
12.8
11
10
9
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
F
MATCHLINE: 1/ M-111
TRPL SUITE
JK
STRUCTURAL ENGINEER
CORRIDOR
WBCM
C-501
444
100 STERLING PARKWAY, SUITE 108
Q
MECHANICSBURG, PA 17050
I
P
O
N
1
TRPL SUITE (MIR)
503
D
3
CD-1
190
F
QUAD SUITE B
H.2
H
C-603
MATCHLINE: 1/ M-111
LAUNDRY
506
G
I
2
FCU
E
F.3
RG-A
---
3
SD-3
350
ER-1
200
SD-2
150
RD-3
--(TYP 2)
8"x8"
1
T
1
F
2
ELEC
RG-A
--10"x10"
504
EF
IDFT
B-10
8"ø
508
14"x4"
12"x8"
FTR
FCU
511
521
T
CD-1
190
14"x4"
14"x4"
QUAD SUITE B
5-2
509
14"x4"
SD-2
225
(TYP. 2)
DBL SUITE - CW
513
2
1
1
2
1
515
2
B
4
G
QUAD SUITE - CW
F
4
TRPL SUITE (MIR)
- CW
4
1
2
C.2
DBL SUITE - CW
517
1
4
1
2
1
I
519
2
C
2
34"x10"
12"x10"
LG-2
225
(TYP. 4)
B
6"x4"
6"x4"
6"x4"
8"ø
1
LOUNGE
E
D
2
12"x12"
T
(TYP. 10)
RA SUITE
A
DSS
A
E
D
1
20"x10"
22"x10"
22"x10"
25
J
1
1
2
QUAD SUITE C
TRPL SUITE (MIR)
510
512
1
1
16"x10"
CORRIDOR
14"x10"
C-502
2
14"x4"
10"x10"
1
1
CD-1
190
F
10"x10"
2
2
1
DBL SUITE
DBL SUITE
514
516
CD-1
190
G
B
B
1
QUAD SUITE
DBL SUITE (MIR)
518
520
B
B
1
2
8"ø
1
4
A.5
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
1
I.6
STAIR 03
D
5
S-503
A
LD-2
190
8
7
6
5.3
5
4
3
2
1
4.4
1
M-112
KEY PLAN
HVAC PLAN - 5TH FLOOR - AREA B
A
SCALE: 1/8" = 1'-0"
B
REVISION
NO.
DESCRIPTION
HVAC UNIT PLAN LEGEND
SHEET NOTES
A
STAFF APARTMENT - REFER TO.......
1/M-401
B
GRAD SUITE - REFER TO ....
C
DATE
KEYED NOTES
1
6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
2/M-401
2
6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR
WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
RA SUITE (AREA A) - REFER TO .....
3/M-401
3
6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU.
PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP.
BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.
D
RA SUITE (AREA B) - REFER TO .....
4/M-401
4
IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF
SR-A GRILLES.
E
DOUBLE SUITE - REFER TO ......
5/M-401
12/14/2015 11:03:53 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
AHA PROJECT NUMBER
F
G1215-004.00
TRIPLE SUITE - REFER TO........
6/M-401
DATE
G
03 DECEMBER 2015
QUAD SUITE - REFER TO........
1/M-402
ISSUE
H
QUAD SUITE A - REFER TO........
2/M-402
I
QUAD SUITE B - REFER TO........
3/M-402
J
QUAD SUITE C - REFER TO........
1/M-403
K
QUAD SUITE D - REFER TO........
2/M-403
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC DUCTWORK
PLAN - 5TH FLOOR
- AREA B
REVISED
15 DECEMBER 2015
SHEET NO.
M-112
9
11
19
18
17.4
17
1514.8
16
1312.8
14.1
14
10
12
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
IDF
DSS
A-9
STAIR 01
RG-A
---
(TYP. 8)
LD-2
230
Z
SR-1
1170
14"x10"
16"x10"
ELEC.
ER-1
50
642
2
DBL SUITE
T
LD-1
180
CD-1
170
1
DOUBLE SUITE
1
632
639
RA SUITE
B
637
2
B
5
D
1
LOUNGE
2
C-600
T
10"x10"
12"x10"
JC
CORRIDOR
635
1
(TYP. 3)
A-10
2
1
1
SD-2
230
100 STERLING PARKWAY, SUITE 108
DSS
10"x10"
CD-1
170
3
A
G
10"x10"
1
FTR
WBCM
2
F
20"x10"
STRUCTURAL ENGINEER
CD-1
170
MECHANICSBURG, PA 17050
S-601
FCU
634
T
2
54"x18"
54"x16"
1
2
F
TRPL SUITE (MIR)
633
1
LD-1
170
1
6
643
1
2
G
2
Y.5
21
TRPL SUITE
Y
X.5
X.3
X
QUAD SUITE
20.8
F
1
STAIR 02
630
54"x16"
S-602
40"x16"
F
641
SR-1
1170
TRPL SUITE
21.5
631
22
1
1
30"x20"
W
23
D
1
V.7
D
4
1
40"x16"
V.8
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
D
4
636
QUAD SUITE D
K
638
STAE COLLEGE, PA 16801
QUAD SUITE (MIR)
1
U.3
10"x8"
U
M
23.6
24
T.5
QUAD SUITE (MIR)
601
V
T
G
2
1
L
2
S
1
F
R
TRPL SUITE
JK
MATCHLINE: 1/ M-114
CD-1
170
4
Q
CORRIDOR
602
C-601
1
I.6
P
1
TRPL SUITE (MIR)
O
N
603
KEY PLAN
MATCHLINE: 1/ M-114
F
4
A
1
M-113
HVAC PLAN - 6TH FLOOR - AREA A
SCALE: 1/8" = 1'-0"
B
REVISION
NO.
DESCRIPTION
12/14/2015 11:03:57 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
HVAC UNIT PLAN LEGEND
SHEET NOTES
A
STAFF APARTMENT - REFER TO.......
1/M-401
B
GRAD SUITE - REFER TO ....
C
KEYED NOTES
1
6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
2/M-401
2
6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR
WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
RA SUITE (AREA A) - REFER TO .....
3/M-401
3
6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU.
PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP.
BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.
D
RA SUITE (AREA B) - REFER TO .....
4/M-401
4
IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF
SR-A GRILLES.
E
DOUBLE SUITE - REFER TO ......
5/M-401
5
54"X18" OUTSIDE AIR DOWN FROM ERU-1 ON ROOF.
6
40"X16" EXHAUST AIR UP TO ERU-1 ON ROOF.
F
TRIPLE SUITE - REFER TO........
DATE
AHA PROJECT NUMBER
G1215-004.00
6/M-401
DATE
G
03 DECEMBER 2015
QUAD SUITE - REFER TO........
1/M-402
ISSUE
H
QUAD SUITE A - REFER TO........
2/M-402
I
QUAD SUITE B - REFER TO........
3/M-402
J
QUAD SUITE C - REFER TO........
1/M-403
K
QUAD SUITE D - REFER TO........
2/M-403
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC DUCTWORK
PLAN - 6TH FLOOR
- AREA A
REVISED
15 DECEMBER 2015
SHEET NO.
M-113
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
18
17
L
16
M 15
14
13
12.8
11
10
9
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
1
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
F
4
STRUCTURAL ENGINEER
MATCHLINE: 1/ M-113
WBCM
TRPL SUITE
JK
602
100 STERLING PARKWAY, SUITE 108
Q
CORRIDOR
MECHANICSBURG, PA 17050
C-601
I.6
1
P
O
N
TRPL SUITE (MIR)
I
603
D
3
F
H.2
H
QUAD SUITE B
LAUNDRY
C-605
606
G
I
2
SD-3
350
ER-1
200
SD-2
150
RD-3
--(TYP 2)
FCU
E
F.3
6
RG-A
---
8"x8"
60"x16"
F
RG-A
---
1
3
T
1
DSS
10"x10"
FCU
IDFT
24"x10"
CD-1
190
2
ELEC
604
DSS
RA SUITE
QUAD SUITE B
611
621
B-11
T
60"x14"
12"x12"
8"ø
T
LOUNGE
609
CD-1
190
SD-2
225
5
1
E
D
2
14"x4"
2
B
6"x4"
6"x4"
6"x4"
8"ø
34"x10"
FTR
20"x10"
E
D
1
608
(TYP. 10)
4
A
B-12
A
MATCHLINE: 1/ M-113
DBL SUITE - CW
613
2
1
1
1
2
20"x10"
(TYP. 4)
QUAD SUITE - CW
1
1
2
CD-1
190
4
2
C.2
DBL SUITE - CW
I
619
617
1
2
1
C
20"x10"
20"x10"
25
J
1
16"x10"
CORRIDOR
12"x10"
LD-2
225
615
2
B
4
10"x10"
(TYP. 2)
10"x10"
G
4
F
TRPL SUITE (MIR)
- CW
4
14"x4"
10"x10"
C-602
14"x10"
1
1
2
QUAD SUITE C
TRPL SUITE (MIR)
610
612
1
2
1
1
CD-1
190
F
2
2
1
DBL SUITE
DBL SUITE
614
616
G
B
B
2
1
QUAD SUITE
DBL SUITE (MIR)
618
620
B
B
1
8"ø
1
4
A.5
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
1
SR-1
1170
LD-2
190
STAIR 03
D
5
S-603
A
8
7
6
5.3
5
4
3
2
1
4.4
1
M-114
KEY PLAN
HVAC PLAN - 6TH FLOOR - AREA B
SCALE: 1/8" = 1'-0"
A
B
REVISION
NO.
DESCRIPTION
12/14/2015 11:04:00 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
HVAC UNIT PLAN LEGEND
SHEET NOTES
A
STAFF APARTMENT - REFER TO.......
1/M-401
B
GRAD SUITE - REFER TO ....
C
KEYED NOTES
1
6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
2/M-401
2
6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.
RA SUITE (AREA A) - REFER TO .....
3/M-401
3
6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU.
PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP.
BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.
D
RA SUITE (AREA B) - REFER TO .....
4/M-401
4
IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF
SR-A GRILLES.
E
DOUBLE SUITE - REFER TO ......
5/M-401
5
70"X20" OUTSIDE AIR DOWN FROM ERU-2 ON ROOF.
6
60"X16" EXHAUST AIR UP TO ERU-2 ON ROOF.
F
TRIPLE SUITE - REFER TO........
DATE
AHA PROJECT NUMBER
G1215-004.00
6/M-401
DATE
G
03 DECEMBER 2015
QUAD SUITE - REFER TO........
1/M-402
ISSUE
H
QUAD SUITE A - REFER TO........
2/M-402
I
QUAD SUITE B - REFER TO........
3/M-402
J
QUAD SUITE C - REFER TO........
1/M-403
K
QUAD SUITE D - REFER TO........
2/M-403
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC DUCTWORK
PLAN - 6TH FLOOR
- AREA B
REVISED
15 DECEMBER 2015
SHEET NO.
M-114
9
11
19
18
17.4
17
16
1514.8
1312.8
14.1
14
10
12
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
STRUCTURAL ENGINEER
WBCM
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
RH
R-1
SPF
Z
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
1
CU
A
ERU
1
Y.5
20.8
21
Y
X.5
X.3
X
SPF
2
RH
R-2
21.5
22
EPF
W
1
RH
R-4
23
V.8
U.3
RH
R-5
V.7
U
M
23.6
T.5
24
EPF
2
T
V
L
S
R
JK
MATCHLINE: 1/ M-116
Q
I.6
P
O
N
KEY PLAN
MATCHLINE: 1/ M-116
A
1
M-115
HVAC PLAN - ROOF - AREA A
SCALE: 1/8" = 1'-0"
B
REVISION
NO.
DESCRIPTION
SHEET NOTES
DATE
KEYED NOTES
AHA PROJECT NUMBER
12/14/2015 11:04:01 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC PLAN - ROOF
- AREA A
REVISED
15 DECEMBER 2015
SHEET NO.
M-115
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
18
L
17
16
M 15
14
13
12.8
11
10
9
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
STRUCTURAL ENGINEER
MATCHLINE: 1/ M-115
WBCM
JK
100 STERLING PARKWAY, SUITE 108
Q
MECHANICSBURG, PA 17050
P
O
N
I
MATCHLINE: 1/ M-115
H.2
H
DEF
G
F.3
1
ERU
2
F
CU
B
C.2
B
SPF
3
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
I.6
RH
R-3
A
8
7
6
5.3
5
4
3
2
1
4.4
1
M-116
KEY PLAN
HVAC PLAN - ROOF - AREA B
A
SCALE: 1/8" = 1'-0"
B
REVISION
NO.
DESCRIPTION
SHEET NOTES
DATE
KEYED NOTES
AHA PROJECT NUMBER
12/14/2015 11:04:03 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC PLAN - ROOF
- AREA B
REVISED
15 DECEMBER 2015
SHEET NO.
M-116
9
11
19
18
17.4
17
1514.8
16
13
14.1
14
10
12
ARCHITECT
HKS, INC.
19.9
20
x.2
x.4.1
TWO LIVE OAK CENTER
x.6
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
2
M-201
20.8
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
21
MEP ENGINEER
12" PCHWS (FUTURE)
12" PCHWR (FUTURE)
UTILITY TUNNEL
21.5
AHA CONSULTING ENGINEERS
6" LPC
6" HPS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
015
22
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
028.1
LITITZ, PA 17543
027
LOCKER RM
GEOTECHNICAL ENGINEER
028
23.6
24
TRANSFORMER
RM
PUBLIC TLT RM F
013
G-1
ADD ALTERNATE:
PROVIDE STEAM SNOW
MELT SYSTEM. ROUTE
STEAM LOOP
UNDERNEATH STAIRS.
DSS
029
OFFICE
A-1
024
UH
G-1
CUST
FAMILY 014
TOILET
TIE 6" HPS AND 6" LPC
INTO EXISTING 6" MAIN
IN MANHOLE MH-7.
REFER TO CIVIL
DRAWINGS FOR
CONTINUATION.
PUBLIC TLT RM M
FOOD SERVICE
PREP
012
018
CIRC
SERVERY #2
010
025
2701 CAROLEAN INDUSTRIAL DRIVE
y.6.5
y.6
015.2
IDF
EF
CMT LABORATORIES, INC.
STAE COLLEGE, PA 16801
STRUCTURAL ENGINEER
WBCM
1
M-405
CENTRAL PLANT
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
015.1
STO.
026
011
FIRE PUMP
ELEC.
GENERATOR RM
015.5
015.4
EWH
015.3
G-2
EF
CUST
Z
G-2
022
EWH
EF
G-3
G-5
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
23
33 SOUTH BROAD STREET
ICE/SODA
T.R
EWH
G-1
EF
EF
G-3
G-4
SERVERY #2
023
VESTIBULE
Y.5
CIRC
008
016
POT WASH
020
Y
X.5
X.3
X
STAIR 04
S-004
W
8" SCHWR
8" SCHWS
6" HWR
6" HWS
T.R.
V.8
017
M.2
V.7
U.3
U
M
T.5
SERVERY #1
FTR
019
A
RECEIVING/
INVENTORY
STORAGE
(TYP. 18)
V
2 1/2" SCHWR
2 1/2" SCHWS
2" HWR
2" HWS
PROVIDE FLOW METER IN
HWS PIPING. PROVIDE
TEMPERATURE SENSORS
IN HWS&R
KEFPIPING.
DINING HALL
L
009
MAU
T
007
G-1
S
G-1
1 1/4" HWS
1 1/4" HWR
KEF
R
G-2
MATCHLINE: 1/ M-101
JK
MATCHLINE: 3/ M-102
Q
T
FM
I.6
P
DSS
ELEC
B-2
007.1
I
O
N
MATCHLINE: 1/ M-101
KEY PLAN
MATCHLINE: 3/ M-102
A
1
M-201
HVAC PIPING PLAN - GROUND FLOOR - AREA A
B
SCALE: 1/8" = 1'-0"
REVISION
NO.
DESCRIPTION
SHEET NOTES
DATE
KEYED NOTES
1ST FLOOR
116' - 0"
12" PCHWS
12" PCHWR
6" HPS
6" LPC
AHA PROJECT NUMBER
12/14/2015 11:04:04 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
PIPE SUPPORTS
BY GENERAL
CONTRACTOR.
CONSTRUCTION
DOCUMENTS
Level
1
GROUND
FLOOR
100'
0"
0' - 0"
2
M-201
SHEET TITLE
HVAC PIPING PLAN
- GROUND FLOOR AREA A
SERVICE TUNNEL SECTION
SCALE: 1/4" = 1'-0"
REVISED
15 DECEMBER 2015
SHEET NO.
M-201
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
18
17
L
16
M 15
14
M.2
13
11
10
9
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
1 1/4" HWS
1 1/4" HWR
STAE COLLEGE, PA 16801
KEF
STRUCTURAL ENGINEER
G-2
MATCHLINE: 1/ M-101
WBCM
JK
MATCHLINE: 3/ M-102
100 STERLING PARKWAY, SUITE 108
Q
MECHANICSBURG, PA 17050
T
FM
I.6
P
ELEC
B-2
O
N
007.1
I
MATCHLINE: 3/ M-102
DSS
B-1
SALES FLOOR
FM
ELEC
T
030
FM
002
PROVIDE FLOW METERS IN
HWS AND SCHWS PIPING.
PROVIDE TEMPERATURE
SENSORS IN HWS&R AND
SCHWS&R PIPING.
UP
T
H.2
H
G
MATCHLINE: 1/ M-101
E
D
ATM
031
2 1/2" SCHWR
2 1/2" SCHWS
2" HWR
2" HWS
F.3
F
EUH
OFFICE
G-1
006
VESTIBULE
001
OFFICE
005
C.2
OFFICE
004
C
STORAGE
032
FTR
(TYP. 7)
B.5
EWH
A
25
B
G-4
MECH RM
033
AHU
A.5
G-3
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
DSS
EF
G-6
T C
o
n
p
tcie r2
g
0
iyh
t7
A.3
FTR
A
(TYP. 14)
8
7
A
6
5.3
5
4
2
1
KEY PLAN
1
M-202
HVAC PIPING PLAN - GROUND FLOOR - AREA B
SCALE: 1/8" = 1'-0"
A
B
REVISION
NO.
DESCRIPTION
SHEET NOTES
DATE
KEYED NOTES
AHA PROJECT NUMBER
12/14/2015 11:04:06 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC PIPING PLAN
- GROUND FLOOR AREA B
REVISED
15 DECEMBER 2015
SHEET NO.
M-202
19
18
17.4
17
16
1514.8
x.1
14.1
14
x.2
x.4.1
x.4
13
12.8
x.5
x.6
x.7
1211
10
x.8
9
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
x.9x.10
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
P
4
MECH
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
EWH
101
LITITZ, PA 17543
1-2
P
4
PUBLIC1-1
TLT RM -M
24
COMMONS
1-1
EF
CMT LABORATORIES, INC.
AHU
100
103
OFFICE
PUBLIC TLT RM -F
102
111
EWH
P
4
(TYP. 6)
3 1/2" HWS
3 1/2" HWR
4" SCHWS
4" SCHWR
3/4" HWS
3/4" HWR
1 1/4" SCHWS
1 1/4" SCHWR
MAIL RECEIVING
MAIL LOBBY
1-4
FPT
1-3
CONFERENCE RM
2 1/2" HWS
2 1/2" HWR
2 1/2" SCHWS
2 1/2" SCHWR
110.2
110.1
108
RF
1-1
19.9
20
.
STAIR 04
6"
3 '-
2" HWS
2" HWR
2 1/2" SCHWS
2 1/2" SCHWR
Y.5
S-104
106
P
2
FPT
20.8
1-5
21.5
105
P
2
1-4
STAIR 02
S-102
T
1-2
EWH
T
21
FPT
INTEGRATIVE
LEARNING
6" SCHWR
6" SCHWS
4" HWR
4" HWS
LOUNGE
FM
MIN
FM
"
18
Y
X.5
X.3
X
110.3
MECHANICSBURG, PA 17050
1-3
FPT
-
MECH
A
1-1
Z
WKSTATIONS
110
FTR
ELEV.
100 STERLING PARKWAY, SUITE 108
MAIL VEST.
P
11
(TYP. 6)
EWH
2" HWS
2" HWR
2" SCHWS
2" SCHWR
STRUCTURAL ENGINEER
WBCM
FTR
A
FPT
STAE COLLEGE, PA 16801
110.4
S-101
1-1
2701 CAROLEAN INDUSTRIAL DRIVE
y.6.5
y.6
1-2
1 1/2" HWS
1 1/2" HWR
2 1/2" SCHWS
2 1/2" SCHWR
STAIR 01
P
8
GEOTECHNICAL ENGINEER
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
AHU
6" SCHWS
6" SCHWR
4" HWS
4" HWR
RECP.
P
6
107
22
P
6
P
6
W
V.8
V.7
EF
1-2
23
M.2
M
23.6
TLT
T
ELEV.
DSS
A-2
IDF
112
-
STO.
U.3
FPT
1-6
U
107.1
104
OFFICE
113
T.5
EF
JC
V
1-3
T
OFFICE
115
114
L
S
F
STAFF BK RM
116
TRPL SUITE
MATCHLINE: 1/ M-103
117
JK
MATCHLINE: 1/ M-104
P
4
R
P
5
Q
CORRIDOR
C-101
I.6
PROVIDE ISOLATION
VALVES AT THE BOTTOM
OF EACH RISER (TYPICAL).
P
O
N
TRPL SUITE (MIR)
I
118
MATCHLINE: 1/ M-103
KEY PLAN
MATCHLINE: 1/ M-104
F
A
1
M-203
HVAC PIPING PLAN - IST FLOOR - AREA A
B
SCALE: 1/8" = 1'-0"
REVISION
NO.
DESCRIPTION
HVAC UNIT PLAN LEGEND
SHEET NOTES
A
STAFF APARTMENT - REFER TO.......
1/M-401
B
GRAD SUITE - REFER TO ....
2/M-401
C
RA SUITE (AREA A) - REFER TO .....
3/M-401
D
RA SUITE (AREA B) - REFER TO .....
4/M-401
E
DOUBLE SUITE - REFER TO ......
5/M-401
DATE
KEYED NOTES
12/14/2015 11:04:10 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
AHA PROJECT NUMBER
F
G1215-004.00
TRIPLE SUITE - REFER TO........
6/M-401
DATE
G
03 DECEMBER 2015
QUAD SUITE - REFER TO........
1/M-402
ISSUE
H
QUAD SUITE A - REFER TO........
2/M-402
I
QUAD SUITE B - REFER TO........
3/M-402
J
QUAD SUITE C - REFER TO........
1/M-403
K
QUAD SUITE D - REFER TO........
2/M-403
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC PIPING PLAN
- 1ST FLOOR AREA A
REVISED
15 DECEMBER 2015
SHEET NO.
M-203
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
18
17
L
16
M15
14
M.2
13
12.8
11
10
9
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
F
116
TRPL SUITE
MATCHLINE: 1/ M-103
STRUCTURAL ENGINEER
WBCM
117
JK
MATCHLINE: 1/ M-104
STAE COLLEGE, PA 16801
STAFF BK RM
P
5
100 STERLING PARKWAY, SUITE 108
Q
MECHANICSBURG, PA 17050
CORRIDOR
C-101
I.6
PROVIDE ISOLATION
VALVES AT THE BOTTOM
OF EACH RISER (TYPICAL).
P
O
N
TRPL SUITE (MIR)
I
118
MATCHLINE: 1/ M-103
MATCHLINE: 1/ M-104
F
H.2
H
P
5
QUAD SUITE B
LAUNDRY
122
I
G
P
10
121
P
1
P
1
P
5
P
9
P
2
FCU
E
P
4
ELEC
F.3
FCU
A
F
119
RA SUITE
EF
127
1-4
DSS
B-4
IDF
T
FTR
A
T
MECH
LOUNGE
124
(TYP. 10)
6" SCHWS
6" SCHWR
4" HWS
4" HWR
T
123
T
2 1/2" SCHWS
2 1/2" SCHWR
2" HWS
2" HWR
120
E
D
E
BDBL SUITE - CW
129
DSS
B-3
?
F
3" SCHWS
3" SCHWR
2" HWS
2" HWR
QUAD SUITE A
3" SCHWS
3" SCHWR
1 1/2" HWS
1 1/2" HWR
?
G
133
C.2
HEAT TRACE ALL
EXTERIOR PIPING.
C
QUAD SUITE C
CORRIDOR
125
P
7
STAIR 05
C-102
4" SCHWS
4" SCHWR
3" HWS
3" HWR
B.5
S-105
25
B
J
TRPL SUITE (MIR)
126
4" SCHWS
4" SCHWR
2 1/2" HWS
2 1/2" HWR
2
M-106
F
DBL SUITE
DBL SUITE
128
130
B
2" SCHWS
2" SCHWR
1" HWS
1" HWR
B
AREA COORD.
SUITE (AC)
A
A.5
132
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
P
3
EWH
P
3
STAIR 03
1-5
A.3
S-103
A
P
5
8
P
1
7
P
1
6
P
9
5.3
5
P
2
4
2
1
4.4
1
M-204
KEY PLAN
HVAC PIPING PLAN - IST FLOOR - AREA B
SCALE: 1/8" = 1'-0"
A
B
REVISION
NO.
DESCRIPTION
HVAC UNIT PLAN LEGEND
SHEET NOTES
A
STAFF APARTMENT - REFER TO.......
1/M-401
B
GRAD SUITE - REFER TO ....
2/M-401
C
RA SUITE (AREA A) - REFER TO .....
3/M-401
D
RA SUITE (AREA B) - REFER TO .....
4/M-401
E
DOUBLE SUITE - REFER TO ......
5/M-401
DATE
KEYED NOTES
12/14/2015 11:04:13 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
AHA PROJECT NUMBER
F
G1215-004.00
TRIPLE SUITE - REFER TO........
6/M-401
DATE
G
03 DECEMBER 2015
QUAD SUITE - REFER TO........
1/M-402
ISSUE
H
QUAD SUITE A - REFER TO........
2/M-402
I
QUAD SUITE B - REFER TO........
3/M-402
J
QUAD SUITE C - REFER TO........
1/M-403
K
QUAD SUITE D - REFER TO........
2/M-403
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC PIPING PLAN
- 1ST FLOOR AREA B
REVISED
15 DECEMBER 2015
SHEET NO.
M-204
9
11
19
18
17.4
17
16
1514.8
1312.8
14.1
14
10
12
ARCHITECT
HKS, INC.
x.1
x.2
x.4 x.4.1 x.5
x.6
x.7
x.8
TWO LIVE OAK CENTER
x.9x.10
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
QUAD SUITE D
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
238
LITITZ, PA 17543
GEOTECHNICAL ENGINEER
IDF
DSS
14" CWR (FUTURE)
14" CWR
14" CWS (FUTURE)
14" CWS
236
A-3
T
K
FCU
CMT LABORATORIES, INC.
HEAT TRACE ALL
EXTERIOR PIPING.
G
STAIR 01
QUAD SUITE (MIR)
S-201
234
2701 CAROLEAN INDUSTRIAL DRIVE
y.6.5
y.6
STAE COLLEGE, PA 16801
STRUCTURAL ENGINEER
WBCM
8" CWR
8" CWS
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
F
GRAD SUITE
DSS
232
A-4
T
C
235
JC
FTR
A
Z
CORRIDOR
DBL SUITE
242
(TYP. 8)
D
239
146
RA SUITE
B
T
237
LOUNGE
243
F
TRPL SUITE (MIR)
233
"
18
MIN
G
.
6"
3 '-
Y.5
CT
CT
1
2
3
(FUTURE)
(FUTURE)
QUAD SUITE
230
20.8
F
STAIR 02
CRCU
CRCU
G-1
G-2
CT
S-202
21
TRPL SUITE
Y
X.5
X.3
X
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
ELEC.
2
F
241
TRPL SUITE
21.5
231
22
W
ELEV.
23
V.8
U.3
-
ELEV.
V.7
-
M
23.6
QUAD SUITE (MIR)
U
201
T.5
24
G
T
V
L
S
F
MATCHLINE: 1/ M-105
TRPL SUITE
JK
MATCHLINE: 1/ M-106
202
R
CORRIDOR
Q
147
I.6
P
TRPL SUITE (MIR)
203
O
N
MATCHLINE: 1/ M-105
KEY PLAN
MATCHLINE: 1/ M-106
F
?
A
?
1
M-205
HVAC PIPING PLAN - 2ND FLOOR - AREA A
B
SCALE: 1/8" = 1'-0"
REVISION
NO.
DESCRIPTION
DATE
AHA PROJECT NUMBER
12/14/2015 11:04:16 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC PIPING PLAN
- 2ND FLOOR AREA A
REVISED
15 DECEMBER 2015
SHEET NO.
M-205
12.8
17
4
4.4
5
16
11
L
15
5.3
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
5
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
5
SR-A
175
U
SR-A
150
SR-A
150
SR-B
250
SR-A
150
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
K
SR-A
125
A
D
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
J
8"ø
8"ø
MEP ENGINEER
AHA CONSULTING ENGINEERS
T.5
8"ø
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
DERCK & EDSON ASSOCIATES
10"x10"
6"ø
10"x10"
SITE/CIVIL ENGINEER
8"ø
10"x10"
8"ø
8"ø
A.3
8"ø
SR-A
100
33 SOUTH BROAD STREET
LITITZ, PA 17543
GEOTECHNICAL ENGINEER
10"x10"
CMT LABORATORIES, INC.
4"ø
SR-A
25
14"x10"
$
8"ø
B
8"ø
T
6"ø
3
B
STRUCTURAL ENGINEER
ER-A
50
FCU
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
3
T
RG-A
---
1-5
WBCM
C.2
T
RG-A
---
6"x4"
6"x4"
6"x4"
2
C
6"x4"
S
6"x4"
6"x4"
ER-A
50
4"ø
3
2-1
EF
SR-A
100
STAE COLLEGE, PA 16801
B
EF
RG-A
---
11
ER-A
50
FCU
2701 CAROLEAN INDUSTRIAL DRIVE
SR-A
25
SR-A
25
2
1
1
$
FCU
1
1
M-401
2
HVAC PLAN - STAFF APARTMENT
7
2
SCALE: 1/4" = 1'-0"
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
D
M-401
HVAC PLAN - UNIT GRAD
3
SCALE: 1/4" = 1'-0"
20.8
M-401
HVAC PLAN - UNIT SINGLE
SCALE: 1/4" = 1'-0"
5.3
O
14
15
16
6
4
4
V
O
P
SR-A
125
8"ø
8"ø
8"ø
SR-A
175
SR-A
125
SR-A
175
8"ø
8"ø
SR-A
175
8"ø
10"ø
18
4
4
A
SR-B
275
4
SR-A
25
ER-A
50
FCU
B
V.7
3
V.8
T
RG-A
--6"x4"
1
10"x10"
4"ø
6"x4"
SR-A
25
SR-A
25
ER-A
50
Q
M-401
SCALE: 1/4" = 1'-0"
SR-A
100
RG-A
---
T
ER-A
50
3
W
RG-A
---
2
6"x4"
D
6"x4"
R
B
5
M-401
6"x4"
1
HVAC PLAN - UNIT DOUBLE
SCALE: 1/4" = 1'-0"
6"x4"
6"x4"
2
2
1
1
14.1
A
HVAC PLAN - UNIT SINGLE A
SR-A
25
FCU
FCU
4
ER-A
50
3
T
4"ø
6"ø
4"ø
6"ø
SR-A
75
14"x10"
10"x10"
4"ø
8"ø
10"x10"
6
M-401
HVAC PLAN - UNIT TRIPLE
KEY PLAN
SCALE: 1/4" = 1'-0"
A
B
REVISION
NO.
DESCRIPTION
SHEET NOTES
KEYED NOTES
1
6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-103 THROUGH M-114 FOR CONTINUATION.
2
6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-103 THROUGH M-114 FOR CONTINUATION.
3
6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU.
PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP.
BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.
4
IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF
SR-A GRILLES.
5
PROVIDE SOLER PALAU MODEL PER-150W PLASTIC LOUVER SHUTTER AT
EXHAUST OUTLET. REFER TO ARCHITECTURAL DRAWINGS FOR
MOUNTING HEIGHTS, COLOR SELECTION AND PAINT REQUIREMENTS.
TEMPLATE VERSION: 2.6.8.20141012
12/14/2015 11:04:21 PM
PLOT DATE:
DATE
AHA PROJECT NUMBER
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC - ENLARGED
PLANS
REVISED
15 DECEMBER 2015
SHEET NO.
M-401
5
5
4
4
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
4
4
4
ATLANTA, GA 30326
4
ASSOCIATE ARCHITECT
D
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
SR-A
150
8"ø
SR-A
150
8"ø
SR-A
150
D
SR-A
125
SR-A
125
8"ø
SR-A
150
SR-A
125
MEP ENGINEER
SR-A
125
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
8"ø
8"ø
8"ø
8"ø
SITE/CIVIL ENGINEER
4"ø
8"ø
12"x10"
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
8"x10"
LITITZ, PA 17543
8"x10"
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
C.2
MECHANICSBURG, PA 17050
10"ø
T
3
6"x4"
4"ø
SR-B
250
FCU
3
6"x4"
C
1
100 STERLING PARKWAY, SUITE 108
SR-A
125
C
2
FCU
D
6"x4"
1
T
SR-A
25
4"ø
ER-A
50
RG-A
--SR-A
25
C.2
ER-A
50
8"x4"
C
4.4
1
M-402
2
HVAC PLAN - UNIT QUAD
2
SCALE: 1/4" = 1'-0"
E
M-402
D
C.2
B
C
A.5
5
4.4
HVAC PLAN - UNIT QUAD A
SCALE: 1/4" = 1'-0"
A
1
10"x10"
16"x10"
4"ø
10"x10"
8"ø
SR-A
150
8"ø
SR-A
150
8"ø
SR-A
150
8"ø
SR-A
150
SR-A
25
ER-A
50
4"ø
10"ø
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
RG-A
---
ER-A
50
WBCM
14"x10"
4"ø
STRUCTURAL ENGINEER
SR-A
25
16"x10"
SR-A
25
6"x4"
STAE COLLEGE, PA 16801
4"ø
ER-A
50
T
RG-A
---
3
6"x4"
SR-B
250
ER-A
50
SR-A
25
6"x4"
6"x4"
2
FCU
C
2
1
1
KEY PLAN
3
A
3
M-402
HVAC PLAN - UNIT QUAD END
B
SCALE: 1/4" = 1'-0"
REVISION
NO.
DESCRIPTION
SHEET NOTES
DATE
KEYED NOTES
1
6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-103 THROUGH M-114 FOR CONTINUATION.
2
6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-103 THROUGH M-114 FOR CONTINUATION.
3
6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU.
PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP.
BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.
4
IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF
SR-A GRILLES.
5
8"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-103 THROUGH M-114 FOR CONTINUATION.
AHA PROJECT NUMBER
12/14/2015 11:04:25 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC - ENLARGED
PLANS
REVISED
15 DECEMBER 2015
SHEET NO.
M-402
8
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
A
SR-A
215
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
8"ø
SR-A
215
MEP ENGINEER
22
21
AHA CONSULTING ENGINEERS
20
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
8"ø
SITE/CIVIL ENGINEER
SR-A
150
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
8"ø
12"x10"
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
SR-A
25
2701 CAROLEAN INDUSTRIAL DRIVE
Z
SR-A
150
STAE COLLEGE, PA 16801
SR-A
125
6"ø
ER-A
50
SR-A
125
SR-A
125
LD-1
150
SR-A
125
STRUCTURAL ENGINEER
10"x10"
8"ø
8"ø
8"ø
8"ø
8"ø
8"ø
WBCM
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
LD-1
150
12"x10"
6"x4"
8"ø
4"ø
F
B
19
18"x10"
1
ER-A
50
T
3
4"ø
F.3
C
RG-A
---
2
SR-A
25
SR-A
25
FCU
ER-A
50
Y
C
6"x4"
SR-A
50
ER-A
50
3
X
11
12.8
13
HVAC PLAN - UNIT QUAD CURVE A
SCALE: 1/4" = 1'-0"
I
H
FCU
6"x4"
6"x4"
1
14
T
RG-A
---
6"x4"
1
M-403
4"ø
X.5
C.2
1
SR-A
25
6"ø
16"x10"
6"x4"
C
1
U
2
G
22
2
M-403
21.5
21
R
20.8
20 19.9
T.5
S
HVAC PLAN - UNIT QUAD CURVE B
SCALE: 1/4" = 1'-0"
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
Y.5
8"ø
SR-A
120
KEY PLAN
A
B
REVISION
NO.
DESCRIPTION
SHEET NOTES
DATE
KEYED NOTES
1
6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-103 THROUGH M-114 FOR CONTINUATION.
2
6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL
PENETRATION. SEE M-103 THROUGH M-114 FOR CONTINUATION.
3
6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU.
PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP.
BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.
AHA PROJECT NUMBER
12/14/2015 11:04:28 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC - ENLARGED
PLANS
REVISED
15 DECEMBER 2015
SHEET NO.
M-403
17
16
15
14.8
14.114 x.4.1
x.2
x.613
12
11
10
9
ARCHITECT
HKS, INC.
PCHWP
PCHWP
PCHWP
3
2
1
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
(FUTURE)
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
BT
MEP ENGINEER
1
ET
AS
UH
1
G-3
1
AHA CONSULTING ENGINEERS
CRAC
T
1801 OLD ALABAMA RD, SUITE 125
G-1
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
CWP
HXS
SCP
GEOTECHNICAL ENGINEER
TRANSFORMER
RM
1
1
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
015.2
1
STRUCTURAL ENGINEER
CWP
HEX
HXS
SCP
WBCM
2
2
100 STERLING PARKWAY, SUITE 108
2
MECHANICSBURG, PA 17050
2
66"x15"
HWP
AS
CWP
2
3
3
(FUTURE)
HEX
1
1
ET
WFS
3
1
y.6
COOLING TOWER
FILTRATION SYSTEM.
FD
AHU
G-1
CH
CH
CH
1
2
3
(FUTURE)
T
T
(FUTURE)
CRAC
66"x18"
G-2
CENTRAL PLANT
015.1
UH
G-2
FD
T
T
T
ELEC.
015.4
FIRE PUMP
GENERATOR RM
015.5
92"x24"
015.3
93"x21"
EWH
G-2
AHU
G-2
FD
ET
EF
EF
2
G-2
G-3
EF
G-1
WL
G-4
36"x26"
6"ø
WL
G-5
WL
G-6
WL
G-7
SCHWP
SCHWP
1
S
M-404
G-4
EWH
78"x24"
1
G-3
92"x24"
AS
FD
EF
G-5
T
18"x12"
2
EWH
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
y.6.5
HWP
2
FD
T.5
U
U.3
KEY PLAN
HVAC PLAN - CENTRAL PLANT
SCALE: 1/4" = 1'-0"
A
B
REVISION
NO.
DESCRIPTION
SHEET NOTES
DATE
KEYED NOTES
AHA PROJECT NUMBER
12/14/2015 11:04:30 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC - ENLARGED
PLANS
REVISED
15 DECEMBER 2015
SHEET NO.
M-404
17
16
15
14.8
14.114
x.2
x.4.1
x.6
13
12
11
10
9
ARCHITECT
HKS, INC.
PROVIDE 12"Ø PCHWS&R FLANGED CONNECTIONS FOR A
TEMPORARY EMERGENCY AIR COOLED CHILLER ON GRADE.
PCHWP
PCHWP
PCHWP
3
2
1
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
(FUTURE)
ASSOCIATE ARCHITECT
12" PCHWS
MURRAY AND ASSOCIATES ARCHITECTS
12" PCHWS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
BT
MEP ENGINEER
1
4" HPS
ET
AS
UH
AHA CONSULTING ENGINEERS
1
G-3
1801 OLD ALABAMA RD, SUITE 125
1
4" LPC
ROSWELL, GA 30076
12" PCHWR
SITE/CIVIL ENGINEER
12" PCHWR
12" PCHWR
DERCK & EDSON ASSOCIATES
4" HPS
33 SOUTH BROAD STREET
LITITZ, PA 17543
14" CWS
CWP
12" PCHWR
12" PCHWS
1
1
2
2
AS
2
3
6" HWS
14" CWR
HWP
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
STRUCTURAL ENGINEER
CWP
HEX
14" CWS
2
SCP
8" PCHWS
HXS
GEOTECHNICAL ENGINEER
TRANSFORMER
RM
015.2
WBCM
2
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
14" CWS
SCP
14" CWS
HXS
8" PCHWR
CWP
3
(FUTURE)
y.6.5
HEX
1
HWP
ET
WFS
1
3
1
y.6
14" CWR
GFS
CH
CH
1
2
3
(FUTURE)
ROUTE RUPTURE DISC
DISCHARGE PIPING FROM
CHILLER TO OUTSIDE, NOT
LESS THAN 20 FEET FROM ALL
OPENINGS INTO BUILDING.
AHU
G-1
1
CH
(FUTURE)
CENTRAL PLANT
015.1
UH
T
6" HWR
6" HWS
G-2
PROVIDE FLOW METERS IN
SCHWS AND HWS PIPING
SERVING AHU-G-1 AND AHUG-2. PROVIDE TEMPERATURE
SENSORS IN HWS&R AND
SCHWS&R PIPING.
FM
FIRE PUMP
ELEC.
GENERATOR RM
015.5
015.4
015.3
8" SCHWR
8" SCHWS
ET
2
AS
2
AHU
G-2
8" SCHWR
REFRIGERANT DETECTION SYSTEM BY MSE MODEL
CHILLGARD LE, OR APPROVED EQUAL. SYSTEM
SHALL HAVE AUDIBLE AND VISUAL ALARMS.
PROVIDE ADDITIONAL AUDIBLE AND VISUAL ALARM
DIRECTLY OUTSIDE OF CENTRAL PLANT.
INTERFACE CONTROLS WITH THE BUILDING
AUTOMATION SYSTEM AND EXHAUST FAN EF-G-2.
SCHWP
SCHWP
2
1
S
1
M-405
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
4" LPC
1
T.5
U
KEY PLAN
A
PIPING PLAN - CENTRAL PLANT
SCALE: 1/4" = 1'-0"
B
REVISION
NO.
DESCRIPTION
SHEET NOTES
DATE
KEYED NOTES
AHA PROJECT NUMBER
12/14/2015 11:04:32 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC - ENLARGED
PLANS
REVISED
15 DECEMBER 2015
SHEET NO.
M-405
SHEET NOTES
19
18
17.4
17
16
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ER-3
125
ER-2
75
ASSOCIATE ARCHITECT
SD-1
60
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
15
SD-3
235
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
KD-1
485
KD-1
485
SITE/CIVIL ENGINEER
RG-1
--(TYP 6)
DERCK & EDSON ASSOCIATES
48"x20"
33 SOUTH BROAD STREET
14.8
LITITZ, PA 17543
SD-2
125
Y
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
24"x16"
1
STRUCTURAL ENGINEER
X
32"x20"
KEYED NOTES
52"x20"
EXHAUST AIR CONNECTION DOWN TO KITCHEN HOOD. TRANSITION TO
HOOD CONNECTION SIZE IN DROP. SEE FOOD SERVICE DRAWINGS FOR
HOOD CONNECTION SIZE, LOCATION, AND AIRFLOW.
2
SUPPLY AIR CONNECTION DOWN TO KITCHEN HOOD. TRANSITION TO
HOOD CONNECTION SIZE IN DROP. SEE FOOD SERVICE DRAWINGS FOR
HOOD CONNECTION SIZE, LOCATION, AND AIRFLOW.
KD-1
485
KD-1
485
W
U.3
KD-1
485
16"x14"
KD-1
485
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
1
KD-1
485
2
SD-1
60
KD-1
485
SD-2
175
U
V.7
93"x21"
40"x14"
2
12"x10"
24"x16"
T.5
1
12"x12"
SD-2
175
KD-1
485
19.9
20
KD-1
485
AHU-G-1 T
80"x20"
V
14.1
14
20.8
SD-3
275
S
16"x14"
KD-1
485
40"x10"
21
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
16"x14"
SD-2
175
WBCM
R
20"x16"
KD-1
485
Q
KEY PLAN
8"x14"
KD-1
485
SD-2
215
M.2
1
A
1
2
KD-1
485
M
B
30"x16"
REVISION
NO.
DESCRIPTION
SD-2
215
14"ø
DATE
KD-1
485
P
O
KD-1
485
13
L
MAU
G-1
AHA PROJECT NUMBER
12/14/2015 8:00:08 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC - ENLARGED
PLANS
1
M-406
HVAC PLAN - KITCHEN
SCALE: 1/4" = 1'-0"
REVISED
15 DECEMBER 2015
SHEET NO.
M-406
PRESSURE GAUGE
W/NEEDLE VALVE
MANUAL AIR
VENT
BALANCING VALVE
HIGH CAPACITY,
AUTOMATIC AIR VENT
UNION,
TYPICAL
PRESSURE REDUCING VALVE - (SET AT 4
PSIG HIGHER THAN PRESSURE AT HIGH
POINT IN SYSTEM)
STEAM SUPPLY LINE
GLOBE VALVE
CENTRIFUGAL AIR SEPARATOR
(PROVIDE LINE SIZE)
RETURN
PIPING
SEE NOTE 1
HWS
ARCHITECT
HWR
UNION, TYPICAL
HKS, INC.
FILL LINE - REFER TO PLBG DWG
2-WAY CONTROL VAVLE
T&P RELIEF VALVE - (WHEN NOT
PROVIDED ON HEAT TRANSFER
DEVICE) PIPED TO FLOOR DRAIN
FROM SYSTEM
TO PUMP SUCTION
LOW CAPACITY, AUTOMATIC AIR VENT
BRACKET SUPPORTS
W/OVERHEAD SUPPORTS
(WHERE REQUIRED)
HVAC COIL/CONDENSER
MEP ENGINEER
DRAIN VALVE W/HOSE
CONNECTION
1/2" PRESSURE RELIEF
VALVE. SEE NOTE 4
CONCRETE HOUSEKEEPING PAD.
REFER TO STRUCTURAL DWGS.
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
F&T TRAP
NOTES:
1. MAX. AUTOMATIC CONTROL VALVE SIZE 2 1/2". FOR STEAM FLOW RATE GREATER THAN
2 1/2" VALVE CAPACITY, FURNISH TWO CONTROL VALVES IN PARALLEL AS INDICATED.
ONE SIZED FOR 1/3 AND ONE SIZED FOR 2/3 TOTAL CAPACITY.
2. BY-PASS PIPING AROUND F & T TRAP LEG SHALL BE SAME SIZE AS TRAP.
3. PROVIDE PIPE UNIONS, FLANGES & ARRANGE WATER PIPING TO FACILITATE TUBE BUNDLE
REMOVAL WITH MINIMUM DISTURBANCE TO PIPING.
4. PRESSURE RELIEF VALVE SET AT 20% OVER WORKING PRESSURE.
AIR CHARGING VALVE
(PRESSURIZED DRY TANK EQUAL
TO FILL VALVE PRESSURE)
UNDERSLUNG CONNECTION CREATES
THERMAL TRAP (12" MIN DROP)
HOSE END DRAIN VALVE
HARRISBURG, PA 17102-2499
3/4" GATE VALVE & CAPPED CONNECTION
SEE NOTE 3
EXPANSION TANK, FLOOR MOUNTED REPLACEABLE BLADDER TYPE
COMBINATION
TEMPERATURE/PRESSURE TEST PORT
, TYPICAL
1600 NORTH SECOND STREET
6" DIRT
POCKET
STRAINER WITH
BLOW-OFF VALVE
ATLANTA, GA 30326
MURRAY AND ASSOCIATES ARCHITECTS
PRESSURE GAUGE W/NEEDLE VALVE
SYSTEM CONNECTION (CONNECT TO
SIDE OR BOTTOM OF MAIN HEADER)
3445 PEACHTREE ROAD, NE, SUITE 675
ASSOCIATE ARCHITECT
3/4" VACUUM BREAKER
PROVIDE TEE WHEN PARALLEL
TANKS ARE TO BE USED
BLOWDOWN AND DRAIN VALVE
W/HOSE CONNECTION
SHUT-OFF VALVE , TYPICAL
(BUTTERFLY OR GATE)
MANUAL AIR VENT
BYPASS SAME SIZE AS CONTROL VALVES
12"MIN.
SUPPLY
PIPING
TWO LIVE OAK CENTER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
1
M-501
2-WAY VALVE COIL/CONDENSER CONNECTION
2
SCALE: N.T.S.
M-501
AIR SEPARATOR & EXPANION TANK
3
SCALE: N.T.S.
M-501
STEAM TO WATER HEAT EXCHANGER PIPING DETAIL
STRUCTURAL ENGINEER
WBCM
SCALE: N.T.S.
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
AIR FLOW
TRANSITION TO ROUND OR FLAT OVAL BOX
INLET CONNECTION AS REQUIRED
AQUASTAT
VD
VD
UNION
STANDAR 45º
RECTANGULAR TO ROUND
BOOT CONNECTION
MODEL 33000
45° RECTANGULAR
TAKE OFF
BRANCH
RECTANGULAR BRANCH DUCT TAKE OFFS
MANUAL AIR VENT
STRAP HANGER - TYP. FOUR (4) PER
BOX ATTACHED TO STRUCTURE
TRANSITION TO SUPPLY DUCT SIZE
SHOWN ON DWGS. BY SHEET METAL
CONTRACTOR
ROUND BRANCH DUCT TAKE OFFS
M
COIL
HWR
HWS
NOTES:
SHUT-OFF BALL VALVE
ALL ROUND AND RECTANGULAR BELL MOUTH FITTINGS SHALL
BE INCLUDED WITH THE FOLLOWING STANDARD FEATURES:
1. NEOPRENE GASKET TO MINIMIZE AIR LEAKAGE.
2. PRE-DRILLED HOLES FOR QUICK MOUNTING.
3. CONSTRUCTED OF HEAVY DUTY GALVANIZED STEEL.
4. 26 GAUGE GALVANIZED QUADRANT VOLUME DAMPER WITH
TIGHT FITTING GASKETING TO MINIMIZE LEAKAGE AT DAMPER
PIVOT POINTS.
4
M-501
STRAINER
SEE SPECIFICATION FOR FLEXIBLE
DUCTWORK UTILIZATION
AUTOMATIC CONTROL VALVE. SEE SPECIFICATION
FOR CONTROL SEQUENCE.
3/4" DRAIN VALVE W/ DIRT LEG & CAP
RUN OUTS FROM SUPPLY DUCT
MAIN TO BOXES SHALL BE 2"
LARGER THAN BOX INLET SIZE
UNLESS NOTED OTHERWISE ON
FLOOR PLANS.
BELL MOUTH CONNECTION DETAIL
5
SCALE: N.T.S.
M-501
NOTES:
1. FOR PIPE SIZES AND LOCATIONS SEE DRAWINGS.
2. VALVES SHALL BE INSTALLED WITHIN CABINET WHERE POSSIBLE. PROVIDE ACCESS TO ALL VALVES.
3. PROVIDE UNIT MOUNTED OR REMOTE THERMOSTAT AS SHOWN ON DRAWINGS.
VARIABLE + CONSTANT AIR VOLUME BOX DETAIL
6
SCALE: N.T.S.
M-501
CABINET UNIT HEATER DETAIL (HOT WATER)
SCALE: N.T.S.
3-1/2" OPENING
1" I.P.T
FLEX DUCT MAX LENGTH = 5'-0"
PETCOCK 1/4" I.P.S.
BELLMOUTH TAKE-OFF
SUPPLY DUCT
T. & P. RELIEF VALVE - (WHEN
NOT PROVIDED ON HEAT TRANSFER
DEVICE) PIPED TO FLOOR DRAIN
1" I.P.T.
FLEX DUCT SIZE SHALL MATCH DIFFUSER NECK SIZE.
CHECK VALVE
GLOBE VALVE
PRESSURE GAUGE
W/ NEEDLE VALVE
BALANCING VALVE ADJUST TO PREVENT
EXCESSIVE CIRCULATION THRU FEEDER
UNION (TYP)
BALL VALVE
VOLUME DAMPER
BALL VALVE
W/MEMORY STOP
DRAW BAND WITH SILICONE SEALER
REFER TO PLBG
DWGS FOR RPZ AND
ADDITIONAL TRIM
1" BALL TYPE DRAIN
VALVE W/CAP
WATER
SYSTEM
SUPPLY
CEILING
PRESSURE REDUCING VALVE (SET AT 4 PSIG HIGHER THAN
THE PRESSURE AT THE HIGH
POINT IN THE SYSTEM)
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
SHUT-OFF / BALANCING BALL
VALVE WITH MEMORY STOP
CEILING DIFFUSER
RETURN
REDUCER
(WHERE REQ'D.)
KEY PLAN
NOTES:
1.
PIPING TO/FROM SHOT FEEDER SHALL BE 1". ENTIRE INSTALLATION SHALL BE IN STRICT
ACCORDANCE WITH CHEMICAL TREATMENT SUBCONTRACTOR'S INSTRUCTIONS.
A
7
M-501
CEILING DIFFUSER BRANCH TAKE-OFF DETAIL (FLEX)
8
SCALE: N.T.S.
M-501
CHEMICAL SHOT FEEDER
9
SCALE: N.T.S.
M-501
CITY MAKE-UP WATER PIPE TRIM
SCALE: N.T.S.
B
4" DRYER
EXHAUST
DUCT
REVISION
NO.
DESCRIPTION
6" WALL
FULL SIZE VENT PIPE TO ATMOSPHERE
PUMPED CONDENSATE
PRESSURE GAUGE
OVERFLOW TO SAME SIZE AS DRAIN LINE
OPEN TO ATMOSPHERE
DATE
DRYER VENT BOX DRYERBOX MODEL 425
OR EQUAL
PITCH DOWN
TOWARD DRAIN
A
GRAVITY RETURN HEADER
A
B
DRAW THRU
2" PLUS X
X
BLOW THRU
1" MINIMUM
2X
GAP = 1"
B
12/14/2015 11:04:35 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
UNIT TYPE
GATE VALVE (TYPICAL)
DRAIN PAN
CLEAN OUT
DRAIN LINE SHALL BE AT LEAST
THE SAME SIZE AS THE NIPPLE ON
THE DRAIN PAN
UNION
(TYPICAL)
DRAIN LINE FULL SIZE OF TAPPING
TO NEAREST FLOOR DRAIN.
BASEBOARD
CHECK VALVE (TYPICAL)
AHA PROJECT NUMBER
FLOOR
G1215-004.00
DATE
OPEN DRAIN BY PLUMBING CONTRACTOR.
SEE PLUMBING DRAWINGS FOR LOCATION.
03 DECEMBER 2015
HOUSEKEEPING PAD
WHERE X = STATIC PRESSURE IN PAN
ISSUE
CONSTRUCTION
DOCUMENTS
NOTES:
1. INSTALL DRYER VENT BOX PER
MANUFACTURER'S RECOMMENDATIONS.
SHEET TITLE
HVAC DETAILS
10
M-501
CONDENSATE DRAIN TRAP
SCALE: N.T.S.
11
M-501
CONDENSATE PUMP DETAIL
SCALE: N.T.S.
12
M-501
DRYER VENT WALL BOX
SCALE: N.T.S.
REVISED
15 DECEMBER 2015
SHEET NO.
M-501
AIR DUCT
DETECTORAND AIR
SAMPLING CHAMBER
1/2" MIS
SPOT WELD ANGLE TO STRUCTURAL STEEL
INTERGRAL WIRE MESH SCREEN PROVIDED BY
UNIT MANUFACTURER
WIRE AND CONDUIT TO FIRE
ALARM SYSTEM AND FMCS,
BY ELECTRICAL
CONTRACTOR.
DUCT
WIDTH
144" MAX
STRUCTURAL STEEL OR
BUILDING STRUCTURE
MOUNTING PLATE
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
DAMPER ACTUATOR 24VDC, FAIL
OPEN (WIRED TO FACP)
NEOPRENE
GASKET
DUCT
HEIGHT
"A" DIM
ANGLES
HANGER
STRAPS
ARCHITECT
MOTORIZED AUTOMATIC DAMPER FURNISHED BY
VENTILATOR MANUFACTURER & INSTALLED BY
HVAC SUBCONTRACTOR.
INTAKE TUBE
C-CLAMP
(TYPICAL)
LOUVERED CAP, 24" HIGH 2 HR FIRE RATING
OPEN CLOSE INDICATOR
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
ROOF CURB, 36" HIGH, 2 HR FIRE RATING
1600 NORTH SECOND STREET
ROOF INSULATION WHERE APPLICABLE
HARRISBURG, PA 17102-2499
RETURN TUBE
SEE NOTE 1
MEP ENGINEER
AHA CONSULTING ENGINEERS
MOUNTING NUTS
STRAP HANGER
1801 OLD ALABAMA RD, SUITE 125
DUCT
ELEVATION VIEW
TRAPEZE HANGER
ROSWELL, GA 30076
NOTES:
1. SMOKE DETECTORS SHALL BE IN ACCORDANCE WITH NFPA 72 AND ELECTRICAL
SPECIFICATIONS. DETECTORS SHALL BE FURNISHED AND WIRED TO THE FIRE
ALARM SYSTEM BY THE ELECTRICAL CONTRACTOR. INSTALLED BY THE HVAC CONTRACTOR
AND WIRED TO THE FMCS BY THE ATC CONTROL. THIS DETAIL APPLIES TO ALL RETURN
SHAFT OPENINGS.
2. INSTALL PER MANUFACTURERS INSTALLATION INSTRUCTIONS.
3. PROVIDE ACCESS DOOR AT SAMPLING TUBES.
NOTES:
1. REFER TO OTHER DETAILS ON THIS DRAWING FOR HIGH VELOCITY DUCTWORK
DETAILS AS REQUIRED.
2. FOR STRAP AND TRAPEZE HANGER SIZE, REFER TO SMACNA DUCT STANDARDS.
3. NO POP RIVETS ALLOWED, USE SELF-TAPPING SHEET METAL SCREWS ONLY.
"A" DIM
36"
72"
96"
120"
144"
# OF SD
1
2
3
4
5
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
NOTE:
1.
33 SOUTH BROAD STREET
LITITZ, PA 17543
ROOF CURB (MIN. 36" HEIGHT) TO BE FURNISHED BY HVAC &
INSTALLED BY GENERAL CONTRACTOR. FLASHING SHALL BE
PROVIDED BY GENERAL CONTRACTOR & COUNTERFLASHING
BY HVAC SUBCONTRACTOR.
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
1
M-502
DUCT HANGER DETAIL (LOW VELOCITY)
2
SCALE: N.T.S.
M-502
DUCT SMOKE DETECTOR DETAIL
3
SCALE: N.T.S.
M-502
STRUCTURAL ENGINEER
ELEVATOR HOISTWAY VENT DETAIL
WBCM
SCALE: N.T.S.
100 STERLING PARKWAY, SUITE 108
NOTE: PROVIDE AUTOMATIC
AIR VENT IN PUMP CASEING
EXTERIOR WALL
PIPE HANGERS (SPRING & NEOPRENE TYPE)
NOTE: 45° ELBOWS SHALL BE CONSIDERED AS
STRAIGHT DUCT
SUPPLY DUCT TO DIFFUSER
CAULK WITH ACOUSTICAL SEALANT
FROM SYSTEM
JACKETED PIPE INSULATION.
REFER TO INSULATION
SPECIFICATION
TIGHTLY PACK ANNULAR
SPACE WITH A FIRE
SAFING MATERIAL
ISOLATION VALVE
1" SOUND LINING FOR ALL LOW PRESSURE
DUCTWORK (45° ELBOWS SHALL BE
CONSIDERED AS STRAIGHT DUCT)
STAINLESS STEEL BRAIDED CONNECTOR
VD
TO SYSTEM
ISOLATION VALVE
1" SOUND LINING
SHALL EXTEND A
MINIMUN OF 36"
FROM TEE (TYP)
CHECK VALVE
STAINLESS STEEL BRAIDED CONNECTOR (INCREASER WHERE REQ'D.)
9" INDUSTRIAL THERMOMETER W/ 3/4" NPT COPPER WELL
MULTIPORT PRESSURE INDICATOR (4-PORT)
1/4" O.D. COPPER TUBING W/ COMP. FITTINGS
SUCTION DIFFUSER WITH STRAINER
BASE MOUNTED END SUCTION PUMP (LONG COUPLED)
PIPE INSULATION. REFER TO
SPECIFICATION FOR INSULATION
REQUIREMENTS
PIPE SLEEVE
FIELD FABRICATED SUPPORT LEG
GROUTABLE FABRICATED STEEL BASE PLATE
DRAIN: TERMINATE NEAR F.D.
4" TYP
END SUCTION (BASE MOUNTED WATER) PUMP DETAIL
5
SCALE: N.T.S.
M-502
SU PPLY CO N N ECTIO N
SCALE: N.T.S.
6
M-502
3/4" HWS (MIN)
STRAIGHT DUCT AT INLET; MIN. 4x(INLET)
FPT
SU PPLY CO N N ECTIO N
SU PPLY CO N N ECTIO N
TEE
RUNOUT
ELBOW
RUNOUT
FAN POWERED TERMINAL UNIT SOUND LINING DETAIL
SCALE: N.T.S.
3/4" HWR (MIN)
ALTERNATE LOCATION
FOR ACCESS DOOR
HANG W/RODS AND VIBRATION ISOLATORS
CEILING
LOW VELOCITY
DUCTWORK, SEE
PLANS
ENCLOSURE FIN
TUBE RADIATION
RUNOUTS TO BOXES SHALL BE 2"
LARGER THAN BOX INLET SIZE
UNLESS NOTED OTHERWISE ON
FLOOR PLANS.
VD
R
HW S
W
H
1
FPT6-16"∅
FPT
STRAIGHT
RUNOUT
EXTERIOR WALL ABOVE GROUND PIPE PENETRATION DETAIL
MAIN SUPPLY DUCT, SEE DETAIL
FOR FITTINGS AT BRANCHES
FLEXIBLE DUCT (3' MAXIMUM)
DUCT HANGERS
FPT6-16"∅
FPT
3" HIGH CONCRETE
HOUSE KEEPING PAD
FINISH FLOOR
4
FPT6-16"∅
CHILLED WATER PIPE
OSHA/ANSI COUPLER GUARD
M-502
1" ACOUSTICAL SOUND
LINING SHALL EXTEND
A MINIMUM OF 36"
FROM FIRST 90°
ELBOW
VD
FLOOR
PITCH DN
ESCUTCHEON PLATE
"S" JOINT COLLAR TO DUCT BOTH
SIDES OF FIRE DAMPER (TYP.)
PET COCK
ONE PIECE ROLL FORMED
GALVANIZED STEEL FRAME
FAN INDUCTION INLET WITH CLEARANCE
DOWN - FEED
1/2" AUTOMATICE CONTROL VALVE
1" THICK ACOUSTICAL SOUND LINING
PERIMETER INDUCTION DIFFUSER
1/2" LINE & PET COCK
FLOOR
2.
FAN POWERED TERMINAL BOX (FPT) IS ILLUSTRATED. INLET DUCT CONDITIONS
AND DUCT DISCHARGE CONDITIONS ARE TYPICAL FOR ALL TERMINAL BOXES.
3.
PROVIDE 1" THICK FILTER
4.
RETURN AIR FROM CEILING PLENUM THROUGH INTERNALLY LINED SOUND
BAFFLE
5.
FOR DUCT SIZES SEE PLAN DRAWINGS.
9/32" DIAMETER GALVANIZED
STEEL PIVOT ROD OR RIVET
PITCH UP
NOTES:
TAKE OFF BOOT W/ MAXIMUM 3' FLEXIBLE DUCT. ALL ELBOWS OF 90° SHALL
BE "HARD" DUCT. PROVIDE QUADRANT DAMPER IN EACH BRANCH.
FASTEN DAMPER TO
SLEEVE BY
WELDING 6" ON CENTER
FLOOR OR WALL
BUILDING
CONSTRUCTION
FUSIBLE LINK
(REPLACEABLE SNAP LINK)
INDUCTION SOUND BAFFLE
4
3
HOT WATER COIL
REFER TO HOT WATER
PIPING DETAIL 1/M-501
1.
STAINLESS STEEL
NEGATOR
CLOSURE SPRING
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
MECHANICSBURG, PA 17050
UP - FEED
ACCESS DOOR (MINIMUM 8"x8" FOR DUCT UP TO
12" WIDE; MINIMUM 12"x12" FOR WIDER DUCTWORK)
PIPE SLEEVE
3/4" HWR (MIN)
3/4" HWS (MIN)
BLADE LOCK
NOTE:
FIRE DAMPER INSTALLATION TO MEET UL REQUIREMENTS.
KEY PLAN
NOTE:
SEE DETAIL 1/M-504 FOR PENETRATION OF CONCRETE FLOORS.
A
7
M-502
FAN POWERED-PARALLEL VAV BOX W/ HOT WATER REHEAT COIL DETAIL
SCALE: N.T.S.
8
M-502
FIN TUBE RADIATION DETAIL
9
SCALE: N.T.S.
M-502
FIRE DAMPER WITH BLADE OUTSIDE OF AIRSTREAM
SCALE: N.T.S.
B
REVISION
NO.
DESCRIPTION
1" MINIMUM TYPICAL
OVERLAP ON ALL
SIDES OF DAMPER
DATE
SHAFT WALL
VENT TO ATMOSPHERE
12/14/2015 11:04:38 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
ITEM.
DUCT
DESCRIPTION
1.
ACTUATOR
2.
FIRESTAT
3.
AUXILLARY OPERATING JACK SHAFT
4.
DAMPER
5.
OVER CENTER LOCK
6
SLEEVE
7.
CAULKING MATERIAL
8.
PFMA OR CONVENTIONAL MOUNTING ANGLES
9.
S-JOINT/DUCT MATE, SLEEVE TO DUCT
LONG ANGLES
1/4" (6) MIN.
FROM HIGH PRESSURE RETURN
7
1
PROVIDE 1/2 TRAP SIZE
5
BY-PASS LINE
4
FLASH
TANK
2
LOW PRESSURE TRAP ASSEMBLY
STRAPS
FLOAT & THERMOSTATIC TRAP
6
DIRT LEG
3
AHA PROJECT NUMBER
TO CONDENSATE RECEIVER
G1215-004.00
MAXIUM FLOOR OPENING
9
DATE
03 DECEMBER 2015
ROOM SIDE
NOTES:
9
SHAFT SIDE
1.
8
DRAIN
SHUT-OFF VALVE
ISSUE
CONSTRUCTION
DOCUMENTS
FLASH TANK ELEVATION SHALL BE FIELD DETERMINED TO ALLOW ADEQUATE PITCH OF
DISCHARGED CONDENSATE. FURNISH AND INSTALL ALL SUPPORTS TO STRUCTURE.
SHEET TITLE
HVAC DETAILS
10
M-502
FIRE/SMOKE COMBINATION DAMPER DETAIL
SCALE: N.T.S.
11
M-502
FLASH TANK DETAIL
SCALE: N.T.S.
12
M-502
FLOOR GUIDE DETAIL
SCALE: N.T.S.
REVISED
15 DECEMBER 2015
SHEET NO.
M-502
GENERATOR EXHAUST PIPE. PROVIDE ANCHORS, GUIDES, AND
EXPANSION COMPENSATORA IN VERTICAL. OFFSET HORIZONTAL
PIPING AS REQUIRED TO ALLOW FOR EXPANSION (TYP)
3/4" SYSTEM RELIEF VALVE
HOT OR CHILLED WATER
PIPE REQUIRING GLYCOL
HEATING COIL
AIR FLOW
SUPPORT FROM STRUCTURE ABOVE
W/VIBRATION ISOLATORS (TYP) BY
HVAC CONTRACTOR
PROVIDE PIPING REDUCER AND DIELECTRIC UNION AT UNIT
COIL CONNECTION WHERE REQUIRED.
ARCHITECT
HKS, INC.
REFER TO GENERATOR STACKHEAD
DETAIL FOR CONTINUATION
HWR
3/4" GLYCOL INJECTION
MANIFOLD W/ BALL VALVE
& CHECK VALVE
COOLING COIL
3/4"
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
HWS
ASSOCIATE ARCHITECT
4" EXHAUST COND. TRAP, 12" LONG
W/PET COCK & TRAP PIPE TO FLOOR
DRAIN
FLEXIBLE CONNECTION
CHWR
REDUCERS AS REQUIRED
FLANGES AS REQUIRED BY HVAC CONTRACTOR
CHWS
55 GALLON SOLUTION
CONTAINER WITH STAND
FOR PUMP, PRESSURE
TANK, GAUGE AND PRV
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
RECOVERY LINE FROM
SYSTEM RELIEF VALVE
TO FLOOR DRAIN
MEP ENGINEER
3/4"
EMERGENCY GENERATOR
(BY ELEC CONTRACTOR)
1/2" DRAIN VALVE (TYPICAL)
AHA CONSULTING ENGINEERS
GLYCOL FEEDER SYSTEM,
GFS-1, SHALL BE BY BELL AND
GOSSETT MODEL GMU60P,
OR APPROVED EQUAL.
D
DRAIN PAN
HARRISBURG, PA 17102-2499
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
1/2"
DRAIN PIPING TRAP MINIMUM 2" HEIGHT
33 SOUTH BROAD STREET
SYSTEM BALL VALVE
LITITZ, PA 17543
GEOTECHNICAL ENGINEER
MUFFLER W/COMPANION FLANGES BY
GENERATOR MANUFACTURER, INSTALLED BY
HVAC CONTRACTOR.
1
M-503
FOUR PIPE FCU PIPING DETAIL
GENERATOR EXHAUST DETAIL
2
SCALE: N.T.S.
M-503
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
GLYCOL FEEDER DETAIL (LARGE GLYCOL SYSTEM)
3
SCALE: N.T.S.
M-503
STRUCTURAL ENGINEER
WBCM
SCALE: N.T.S.
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
RISER
LAST CONNECTION
TEST GLOBE VALVE
1/2"
SET SCREW
PIPE GUIDE
STEAM
PITCH DOWN
FLOW
BOLT
3/4" BYPASS
STEAM
BYPASS
GATE VALVE
6" DIRT LEG
TRAP TEE
NIPPLE
BLANKED FLANGE
CONDENSATE
PIPE
SPICER
FLOW
STRAINER
CHECK VALVE
INVERTED BUCKET TRAP
BUCKET TRAP
BLANK FLANGE
UNION
CONDENSATE RETURN
STRAINER BLOW 1/2" BALL VALVE
1/2" NIPPLE
CHANNEL OR BUILDING STRUCTURE
HIGH OR MEDIUM PRESSURE MAIN
4
M-503
HIGH PRESSURE STEAM TRAP DETAIL
HIGH/MED STEAM RISER TAKE-OFF DETAIL
5
SCALE: N.T.S.
M-503
HORIZONTAL & VERTICAL PIPE GUIDE DETAIL
6
SCALE: N.T.S.
M-503
SCALE: N.T.S.
NOTE:
INSULATION
D + 1"
4D
INSULATED AS SPECIFIED
INSULATION PROTECTION SADDLE
WELDED TO PIPE
1. DUCTWORK RUNOUT SIZE TO LINEAR DIFFUSER
SHALL MATCH THE INLET SIZE TO PLENUM NOTED ON
THE SCHEDULES UNLESS SHOWN OTHERWISE ON
FLOOR PLANS.
VOLUME DAMPER TYP
48" MAX. LENGTH OF FLEXIBLE
CONNECTION TYP. SEE SPECIFICATION
SEE NOTE 2
PIPE ROLL
6"
INLET CENTERED
BOLT (TYP)
INSULATED LOW PRESSURE DUCT
PLENUM LINED W/1" SOUND LINING
THROUGHOUT
PIPE SADDLE ON HOT WATER
D
INSULATION PROTECTION SHIELD
BRACKET UPPER
STACK TO DISCHARGE
DUCT
SPIN-IN DUCT COLLAR
ANGLE IRON SUPPORT BY HVAC
ARCH. SOFFIT OR CEILING
NOTES:
INSULATED FLEXIBLE DUCT FASTENED WITH
BAND CLAMPS, SCREWS ON BOTH SIDES
REFER TO FLOOR PLANS FOR SIZE
1. FOR TYPE OF HANGER AND INSULATION REQUIREMENTS REFER TO SPECIFICATIONS.
2. SERVICE PIPING AS INDICATED IN SPECIFICATIONS SHALL BE INSTALLED ON ROLLER HANGERS.
KEY PLAN
SEE DRAWINGS FOR DIRECTION OF BLOW
A
7
M-503
PIPE HANGER & PIPE ROLLER DETAIL
SCALE: N.T.S.
GENERATOR STACKHEAD DETAIL
8
M-503
LINEAR DIFFUSER DETAIL (TYPICAL)
9
SCALE: 1/8" = 1'-0"
M-503
SCALE: N.T.S.
B
REVISION
NO.
DESCRIPTION
WEATHER-PROOF INSULATION
BUILDING STRUCTURE
REFER TO SPECIFICATION FOR PACKING OF
SPACE BETWEEN PIPE & SLEEVE
DRAW BAND
DATE
MASTIC
PROVIDE A 1" AIR SPACE (MINIMUM) AROUND PIPE.
STEEL PIPE SLEEVE BY HVAC
FLASHING BY HVAC SUB-CONTRACTOR
PIPE
12" MIN.
FLASHING BY GENERAL CONTRACTOR
STANDARD WEIGHT STEEL PIPE SLEEVE
SEE NOTES
ROOF MEMBRANE
12/14/2015 11:04:38 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
ESCUTCHEON AROUND ALL PIPE
PENETRATIONS, SEE SPECIFICATION
NOTES:
AHA PROJECT NUMBER
THICKNESS VARIES
ANCHOR PLATE IMBEDDED IN CONCRETE SLAB OR RESTING ON TOP
OF AND TACK WELDED TO METAL DECKING UNDER ROOF
INSULATION
PIPE SLEEVE SHALL BE LARGE ENOUGH TO ALLOW PIPE & INSULATION
WHERE PIPES ARE COVERED. THEY SHALL ALSO ALLOW EXPANSION &
CONTRACTION.
G1215-004.00
3"
DATE
03 DECEMBER 2015
NOTES:
1.
2.
3.
ISSUE
WEATHER PROOFING OF INSULATION TO BE EXTENDED BELOW COUNTERFLASHING
INSULATION SHALL BE CONTINUOUS THROUGH THE PIPE SLEEVE
CONTERFLASHING TO HAVE MINIMUM CLEARANCE BETWEEN ROOF SLEEVE FLASHING & SHALL EXTEND DOWN A MINIMUM OF 3" BELOW TOP SLEEVE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC DETAILS
10
M-503
PIPE SLEEVE THROUGH WALL DETAIL
SCALE: N.T.S.
11
M-503
PIPE THROUGH ROOF OR WALL DETAIL
SCALE: N.T.S.
REVISED
15 DECEMBER 2015
SHEET NO.
M-503
3
A
3
3
A
5
2
1
4
1
5
1A
SYSTEM NO. F-A-5011
F RATING - 3 HR
T RATING - 1 HR
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)
3
4
2
A
SECTION A-A
SYSTEM NO. C-AJ-1008
(FORMERLY SYSTEM NO. 111)
1. FLOOR-CEILING ASSEMBLY - THE FIRE-RATED UNPROTECTED STEEL DECK FLOOR-CEILING ASSEMBLY SHALL BE
CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL D900 SERIES DESIGNS IN THE UL FIRE
RESISTANCE DIRECTORY AND AS SUMMARIZED BELOW:
A. NORMAL WEIGHT OR LIGHTWEIGHT CONCRETE - CONCRETE THICKNESS ABOVE THE CREST
OF THE DECK SHALL
BE MIN. 3-1/4 IN. NORMAL WEIGHT CONCRETE WITH CARBONATE OR SILICEOUS AGGREGATE, 145 TO 155 PCF UNIT WEIGHT,
MIN. 3000 PSI COMPRESSIVE STRENGTH. LIGHTWEIGHT CONCRETE WITH EXPANDED SHALE, CLAY OR SLATE AGGREGATE,
105 TO 115 PCF UNIT WEIGHT, MIN. 3000 PSI COMPRESSIVE STRENGTH.
B. WELDED WIRE FABRIC - 6x6, W1.4xW1.4
C. STEEL FLOOR AND FORM UNITS*-COMPOSITE OR NONCOMPOSITE 1-5/16 TO 3 IN. DEEP GALV. UNITS OR AS SPECIFIED IN
THE INDIVIDUAL FLOOR-CEILING DESIGNS. MAX AREA OF OPENING IS 300 SQ IN. WITH MAX DIMENSION OF 30 IN.
3A
A
1B
SECTION A-A
1. FLOOR OR WALL ASSEMBLY - REINFORCED LIGHT WEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE HAVING
A MIN THICKNESS AS SPECIFIED IN THE TABLE BELOW (ITEM 3). WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*.
MAX DIAMETER OF OPENNING IS 8 IN. SEE CONCRETE BLOCK (CAZT) CATEGORY IN THE FIRE
RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
2. METALIC SLEEVE - (OPTIONAL) - NOM 8 IN. DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL SLEEVE CAST
GROUNTED INTO WALL OR FLOOR ASSEMBLY, FLUSH WITH FLOOR OR WALL SURFACES.
1. WALL ASSEMBLY - THE 1 OR 2 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL
BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR
U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE
THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL
STUDS. WOOD STUDS TO CONSIST OF NOM. 2 BY 4 IN. LUMBER SPACED 16 IN. OC.
STEEL STUDS TO BE MIN. 3-5/8 IN. WIDE AND SPACED MAX. 24 IN. OC.
B. GYPSUM BOARD* - 5/8 IN. THICK, 4 FT. WIDE WITH SQUARE OR TAPERED EDGES.
THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND
SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES
DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX. DIAMETER OF OPENING IS 9 IN.
THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING
OF THE WLL ASSEMBLY IN WHICH IT IS INSTALLED.
3. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN
THE FIRESTOP SYSTEM. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF
FLOOR OR WALL ASSEMBLY. THE ANNULAR SPACE SHALL BE AS SPECIFIED IN THE TABLE BELOW. THE FOLLOWING TYPES
AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED.
A. STEEL PIPE - NOM 6 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METTALIC TUBING.
C. CONDUIT - NOM 6 IN. DIAM (OR SMALLER) RIGID GALV STEEL CONDUIT.
THE F AND T RATING OF THE SYSTEM IS DEPENDENT UPON THE DIAM OF THE PIPE OR CONDUIT AND ANNULAR
SPACE BETWEEN THE PIPE OR CONDUIT AND THE PERIPHERY OF THE OPENING AS SHOWN IN THE TABLE BELLOW.
2. THROUGH PENETRANTS - ONE METALIC PIPE OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY
OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. PIPE OR TUBING TO BE RIGIDLY SUPPORTED ON
BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALIC TUBING MAY BE USED.
A. STEEL PIPE - NOM. 4 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE - NOM. 4 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
C. COPPER TUBING - NOM. 4 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBE.
D. COPPER PIPE - NOM. 4 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
MAX DIAM.
MIN.
OR
WALL
OR WALL
THCKNS IN.
OF STEEL PIPE
OR CONDIUT IN.
ANNULAR
SPACE IN.
3-3/4
3-3/4
3-3/4
4-1/2
4-1/2
4-1/2
5-1/2
5-1/2
6-1/2
6-1/2
1-1/2
6
6
1-1/2
6
6
1-1/2
6
1-1/2
6
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
2-1/8
1
3/4
1
1
2
2-1/8
1
3/4
1
1
2
2-1/8
1
3/4
1
2-1/8
2
1
2
2-3/4
2-3/4
1-3/4
3-1/2
3-1/2
2-1/2
3-1/2
3-1/2
2-1/2
2-1/2
ANNULAR
SPACE IN.
2
2
2
MIN. FORMING
F RATING
T RATING
METAL
THCKNS IN.
METAL
THCKNS IN.
HR
HR
0
0
0
3
3
3
3/4
3
3/4
1
0
5. FILL, VOID OR CAVITY MATERIAL* - CAULK - MIN THICKNESS OF FILL MATERIAL AS SPECIFIED IN THE ABOVE TABLE
(ITEM 3) APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF THE WALL.
USG INTERIORS INC - TYPE SS
*BEARING THE UL CLASSIFICATION MARK
NTS
2. THROUGH PENETRANTS - A MAX OF TWO METALLIC PIPES OR TUBINGS TO BE INSTALLED WITHIN THE FIRESTOP SYSTEM.
PIPE OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF
METALLIC PIPES, CONDUIT OR TUBING MAY BE USED:
A. STEEL PIPE - NOM. 6 IN. DIAMETER (0R SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE WITH 1 IN. MINERAL FIBER PIPE
INSULATION.
B. STEEL PIPE - NOM. 4 IN. DIAMETER (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE WITH 1 IN. GLASS FIBER OR
MINERAL FIBER PIPE INSULATION.
C. COPPER PIPE - NOM. 4 IN. DIAMETER (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE WITH 1 IN. MINERAL FIBER
PIPE INSULATION.
D. COPPER TUBING - NOM. 4 IN. DIAMETER (OR SMALLER) TYPE L (OR HEAVIER) COPPER PIPE WITH 1 IN. MINERAL FIBER
PIPE INSULATION.
E. COPPER PIPE - NOM. 2 IN. DIAMETER (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE WITH 1 IN. GLASS FIBER PIPE
INSULATION.
F. COPPER TUBING - NOM. 2 IN. DIAMETER (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING WITH 1 IN. GLASS FIBER
PIPE INSULATION.
3. PIPE COVERINGS - ONE OF THE FOLLOWING TYPES OF PIPE COVERINGS MAY BE USED:
A. PIPE AND EQUIPMENT COVERING MATERIALS* - NOM. 1 IN. THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN 3.5 PCF)
GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED WITH METAL
FASTENERS OR FACTORY-APPLIED SELF SEALING LAP TAPE. TRANSVERSE JOINTS SECURED WITH METAL FASTENERS OR
WITH BUTT TAPE SUPPLIED WITH THE PRODUCT. THE ANNULAR SPACE WITHIN THE FIRESTOP SYSTEM SHALL BE MIN. 7/8 IN.
TO MAX 15-1/2 IN. SEE PIPE AND EQUIPMENT COVERING MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS
DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND
BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX
OF 50 OR LESS MAY BE USED.
B. PIPE COVERING MATERIALS* - NOM. 1 IN. THICK UNFACED MINERAL FIBER PIPE INSULATION HAVING A NOM. DENSITY OF
3.5 PCF (OR HEAVIER) AND SIZED TO THE OUTSIDE DIAM. OF THE PIPE OR TUBE. PIPE INSUALTION SECURED WITH A MIN. 8
AWG STEEL WIRE SPACED MAX 12 IN. OC. THE ANNULAR SPACEWITHIN THE FIRESTOP SYSTEM SHALL BE MIN. 7/8 IN. TO MAX
15-1/2 IN.
OWENS CORNING HT INC, DIVISION OF OWENS CORNING - HIGH TEMPERATURE PIPE INSULATION 1200, HIGH TEMPERATURE
PIPE INSULATION BWT OR HIGH TEMPERATURE PIPE INSULATION THERMALOC
L RATINGS NOT APPLICABLE WHEN MINERAL WOOL PIPE COVERING MATERIAL IS USED.
C. SHEATHING MATERIAL*-(OPTIONAL)-USED IN CONJUNCTION WITH ITEM 3B. FOIL-SCRIM-KRAFT OR ALL SERVICE JACKET
MATERIAL SHALL BE WRAPPED AROUND THE OUTER CIRCUMFERENCE OF THE PIPE INSULATION (ITEM 3B) WITH THE KRAFT
SIDE EXPOSED. LONGITUDINAL JOINTS AND TRANSVERSE JOINTS SEALED WITH MATCHING FOIL-SCRIM-KRAFT TAPE. (SEE
SHEATHING MATERIALS (BVDV) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY
SHEATHING MATERIAL MEETING THE ABOVE SPECIFICATION AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME
SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE USED.
0
3
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
2
A
2
A
ASSOCIATE ARCHITECT
1B
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
SECTION A-A
SECTION A-A
HARRISBURG, PA 17102-2499
1. WALL ASSEMBLY - THE 1, 2, 3, OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF
THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL
FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING
CONSTRUCTION FEATURES:
A. STUDS - WALL FRAMING CONSISTS OF STEEL CHANNEL STUDS. STEEL STUDS TO
BE MIN. 3-5/8 IN. WIDE BY 1-3.8 IN. DEEP CHANNELS SPACED MAX. 24 IN. OC.
B. GYPSUM BOARD* - NOM. 5/8 IN. THICK, 4 FT. WIDE WITH SQUARE OT TAPERED EDGES.
THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND
SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES
DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX. DIAMETER OF OPENING IS 13-1/2 IN.
2. PIPE OR CONDUIT - NOM. 12 IN. DIAMETER (OR SMALLER) SCHEDULE 10 OR (OR HEAVIER) STEEL PIPE, NOM. 12 IN. DIAMETER (OR
SMALLER) SERVICE WEIGHT (OR HEAVIER) CAST IRON SOIL PIPE, NOM 12 IN. DIAMETER (OR SMALLER) CLASS 50 (OR HEAVIER)
DUCTILE IRON PRESSURE PIPE, NOM. 6 IN. DIAMETER
(OR SMALLER) STEEL CONDUIT, NOM. 4 IN. DIAMETER
(OR SMALLER) STEEL ELECTRICAL METALLIC TUBING, NOM. 6 IN. DIAMETER
(OR SAMLLER) TYPE L (OR HEAVIER) COPPER TUBING OR NOM. 1 IN. DIAMETER
(OR SMALLER) FLEXIBLE STEEL CONDUIT. WHEN COPPER PIPE IS USED, MAX F RATING OF FIRESTOP SYSTEM (ITEM 3) IS 3 HR.
STEEL PIPES OR CONDUITS LARGER THAN NOM. 4 IN. DIAMETER MAY ONLY BE USED IN WALLS CONSTRUCTED USING STEEL
CHANNEL STUDS. A MAX OF ONE PIPE OR CONDUIT IS PERMITTED IN THE FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE INSTALLED
NEAR CENTER OF STUD CAVITY WIDTH AND TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.
3. FILL, VOID, OR CAVITY MATERIAL*-CAULK- CAULK FILL MATERIAL INSTALLED TO COMPLETELY FILL ANNULAR SPACE BETWEEN
PIPE OR CONDUIT AND GYPSUM WALLBOARD AND WITH A MIN. 1/4 IN. DIAMETER BEAD OF CAULK APPLIED TO PERIMETER OF PIPE
OR CONDUIT AT ITS EGRESS FROM THE WALL. CAULK INSTALLED SYMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY. THE
HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH
IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE. THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON
THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED,
AS TABULATED BELOW:
1. FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. THICK REINFORCED LIGHTWEIGHT
OR NORMAL WEIGHT (100-150 PCF) CONCRETE. WALL ALSO MAY BE CONSTRUCTED
OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIM OF OPENING IS 8 IN.
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR
NAMES AND MANUFACTURERS.
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
2. METALLIC PIPE - MAX 6 IN. DIAM (OR SMALLER) RIGID GALV STEEL CONDUIT,
SCHEDULE 10 (OR HEAVIER) STEEL PIPE OR MAX 4 IN. DIAM (OR SMALLER) STEEL
EMT CONDUIT CENTERED IN THE OPENING. PIPE TO BE RIGIDLY SUPPORTED ON
BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE T RATING OF THE SYSTEM IS
DEPENDENT ON THE SIZE OF THE CONDUIT AND THROUGH OPENING AS SHOWN IN
THE TABLE BELOW. (SEE ITEM 5)
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
3. FORMS - (NOT SHOWN, OPTIONAL) - USED AS A FORM TO PREVENT LEAKAGE
OF FILL MATERIAL DURING INSTALLATION. FORMS TO BE A RIGID SHEET MATERIAL,
CUT TO FIT THE CONTOUR OF THE PENETRATING ITEM. FORMS FRICTION FITTED INTO
THE OPENING OR LOCATED ON THE UNDERSIDE OF FLOOR ON BOTH SIDES OF WALL TO
PREVENT THE LEAKAGE OF FILL MATERIAL. THE FORMS TO BE REMOVED AFTER THE
FILL MATERIAL HAS CURED.
LITITZ, PA 17543
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
4. PACKING MATERIAL - (NOT SHOWN, OPTIONAL) - MINERAL WOOL BATT INSULATION
FIRMLY PACKED BETWEEN THE FORMS AND PENETRATING ITEMS TO PREVENT
THE LEAKAGE OF FILL MATERIAL. THE PACKING MATERIAL MAY BE REMOVED AFTER
THE FILL MATERIAL HAS CURED.
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
5. FILL, VOID, OR CAVITY MATERIAL* - SEALANT - FILL MATERIAL APPLIED WITHIN
ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF
WALL. THE T RATING OF THE SYSTEM IS DEPENDENT UPON THE SIZE OF THE
OPENING, SIZE OF THE PENETRATING ITEM, NOM ANNULAR SPACE WITHIN
OPENING AND THICKNESS OF THE FILL MATERIAL AS SHOWN IN THE TABLE BELOW:
STRUCTURAL ENGINEER
WBCM
100 STERLING PARKWAY, SUITE 108
NTS
PIPE PENETRATION OF FIRE RATED FLOOR
MECHANICSBURG, PA 17050
MAX OPENING
SIZE IN.
MAX PIPE OR
CONDUIT DIAM., IN.
4. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. FORMS-(NOT SHOWN) USED AS A FORM TO PREVENT LEAKAGE OF FILL MATERIAL DURING INSTALLATION. FORMS TO BE
RIGID SHEET MATERIAL, CUT TO FIT THE CONTOUR OF THE PENETRATING ITEM AND FASTENED TO THE UNDERSIDE OF
FLOOR. FORMS TO BE REMOVED AFTER FILL MATERIAL HAS CURED.
B. FILL, VOID, OR CAVITY MATERIAL*-MORTAR-MIN. 3-1/4 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS,
FLUSH WITH TOP OF SURFACE FLOOR. MORTAR IS TO BE MIXED WITH WATER AT A RATE OF 1.9 TO 2.4 GAL. PER 25 LB. BAG IN
ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS.
ANNULAR SPACE
IN.
F RATING
HR.
T RATING
HR.
1
0 TO 3/16
1 OR 2
1
1/4 TO 1/2
3 OR 4
4
0 TO 1-1/2
1 OR 2
0
6
1/4 TO 1/2
3 OR 4
0
12
3/16 TO 3/8
1 OR 2
0
0+, 1 OR 2
3 OR 4
NTS
PIPE PENETRATION OF FIRE RATED WALL
MAX DIAM.
PENETRATION ITEM IN.
NOM ANNULAR
SPACE IN.
MIN FILL MTL.
THK. IN.
T RATING HR
3
1-1/2
9/16
4-1/2
1-1/2
5
3
3/4
4-1/2
1/2
5
1/2
2
3-1/2
3
8
6
11/16
3-1/2
0
8
6
11/16
4-1/2
1/2
*BEARING THE UL CLASSIFICATION MARK
THIS DETAIL SHALL BE USED FOR ALL PENETRATIONS OF MECHANICAL
ROOM 110A AND PENETRATIONS OF OTHER 2 HOUR SEPARATIONS.
*BEARING THE UL CLASSIFICATION MARK
*BEARING THE UL CLASSIFICATION MARK
CONDUIT/STEEL PIPE PENETRATION OF CONCRETE WALL/FLOOR
ARCHITECT
1
SEE ARCHITECTURAL DRAWINGS FOR FIRE RATING OF WALLS.
0
0
3
3
MIN. FILL
4. FORMING MATERIAL* - MIN 4.0 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT
FORM AT THE MIN THICKNESS SPECIFIED IN THE ABOVE TABLE (ITEM 3). FORMING MATERIAL TO BE RECESSED FROM TOP
SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.
THERMAFIBER LLC - TYPE SAF
*BEARING THE UL CLASSIFICATION MARK
INSULATED PIPE PENETRATION OF FIRE RATED WALL
MIN. FLOOR
F
F
F
F
F
F
W
W
W
W
3. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING.
A. PIPE AND EQUIPMENT COVERING MATERIALS* - MAX 2 IN. THICK HOLLOW CYLINDRICAL HEAVY
DENSITY (MIN 3.5 PCF) GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH AN ALL SERVICE
JACKET. LONGITUDINAL JOINTS SEALED WITH MEATL FASTENERS OR FACTORY APPLIED SELFSEALLING LAP TAPE. PIPE COVERING TO BE WRAPPED AROUND THE THROUGH PENETRANT AND
EXTEND A MIN 2-1/2 IN. BEYOND BOTH SURFACES OF THE WALL. THE ANNULAR SPACE
BETWEEN PIPE COVERING AND THE EDGE OF THE THROUGH OPENING SHALL BE MIN. 0 IN.
(CONTINUOUS POINT CONTACT) TO MAX 1/2 IN. SEE PIPE AND EQUIPMENT COVERING MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF
MANUFACTURERS. ANY PIPE COVEING MATERIAL MEETING WITH A FLAME SPREAD INDEX OF
25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE USED.
B. FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 5/8 IN. THICKNESS
MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL.
A MIN 1/4 IN. CROWN OF FILL MATERIAL SHALL BE APPLIED TO THE PIPE
COVERING/GYPSUM WALLBOARD INTERFACE AT THE POINT CONTACT LOCATION
ABD LAPPING 1/4 IN. BEYIND THE PERIPHERY OF THE OPPENING ON BOTH
SIDES OF THE WALL. SPECIFIED TECHNOLOGIES INC - SPECSEAL 100, 101, 102
AND 105 SEALANT.
MAX.
FLOOR
5
A
F RATING - 3 HR
T RATINGS - 0,1/2,1 1/2 AND 3 HR (SEE ITEM 5)
SYSTEM NO. C-AJ-1020
(FORMERLY SYSTEM NO. 165)
F RATING - 2 AND 3 HR (SEE ITEM 3)
T RATING - 0, 3/4, AND 1 HR (SEE ITEM 3)
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ
FT
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT
2
5
UL DETAIL
3
SECTION A-A
3B
M-504
3
A
2
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
A
A
1
1A
F RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 2 AND 3)
T RATINGS - 0,1,2,3 AND 4 HR (SEE ITEM 3)
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT
2
System No. W-L-1101
F Rating - 1&2 Hr (See Item
1)
T Rating - 0 Hr
SYSTEM NO. W-L-1001
(FORMERLY SYSTEM NO. 147)
NTS
CONDUIT/STEEL PIPE PENETRATION OF CONCRETE WALL/FLOOR
NTS
UL DETAILS
SCALE: N.T.S.
DUCT SUPPORT
3/8" FOAM GASKET
FLEX CONNECTOR
SOUND BARRIER
PACKAGE (SEE NOTE 8)
1 1/2" / 3# F.G BOARD AT TOP RAIL
NOTE:
1. ROOF CURB SHALL BE FULLY ASSEMBLED AND SHIPPED IN ONE PIECE. MODEL VIBCURB AS MANUFACTURED BY NAI (NOVIA ASSOCIATES, INC.) OR APPROVED EQUAL.
TOP RAIL AND FLASHING 14 Ga. - Zc.
2. HVAC CONTRACTOR SHALL COORDINATE AND FIELD VERIFY FINAL LOCATIONS OF HVAC UNITS AND DUCT RISERS WITH GENERAL CONTRACTOR BASED ON ACTUAL STRUCTURAL,
ARCHITECTURAL, UNIT, CURB SIZES AND CONNECTION CONDITIONS.
AIR / WEATHER SEAL BOTTOM FLASHING
3. FIELD COORDINATE AND VERIFY FINAL STRUCTURAL STEEL LAYOUT FOR RTU SUPPORT WITH GENERAL CONTRACTOR, HVAC CONTRACTOR & CURB SUPPLIER BASED ON FINAL
APPROVED RTU AND CURB SUBMITTALS.
4. ROOFING MEMBRANE SHALL BE EXTENDED TO THE TOP OF THE SHEET METAL SIDES AND ENDS OF CURB BY THE GENERAL CONTRACTOR.
5. CURB MANUFACTURER SHALL CONSTRUCT THE SHEET METAL SIDES AND ENDS OF CURBS TO CONTINUOUSLY CONFORM WITH ROOF SLOPE. POINT LOADING IS NOT ACCEPTABLE.
WOOD NAILERS
SIDES AND ENDS 12 Ga. - ZC.
3 1/2" R-21 .7 FACED FOAM BOARD
2 LAYERS 1/2" DUROCK (SEE NOTE 8)
6. THE 14" HIGH CURB SHALL BE PROVIDED BY THE HVAC SUB-CONTRACTOR AND SHALL BE FASTENED TO THE ROOF AND UNIT.
THE CURB SHALL NOT INTERFERE WITH THE OPERATING CHARACTERISTICS OF THE UNIT. ALL FLASHING AND COUNTERFLASHING BY ROOF CURB MANUFACTURER.
7. THE ENTIRE FLOOR AREA (ROOF DECK) WITHIN THE ROOF CURB SHALL HAVE ONE LAYER OF 2" - 3# DENSITY RIGID BOARD FIBERGLASS INSULATION AND TWO LAYERS OF
1/2" DUROCK BOARD ON TOP OF THE INSULATION. THE THREE LAYERS SHALL BE FASTENED TO THE ROOF. PROVIDE ONE ADDITIONAL LAYER OF 1/2" DUROCK BOARD
AT TOP FLOATING RAIL OF CURB. HVAC CONTRACTOR SHALL BE REQUIRED TO PROVIDE ALL LAYERS PRIOR TO PLACING ROOFTOP UNITS ON CURBS.
PROTECT ALL LAYERS FROM THE WEATHER UNTIL UNIT IS INSTALLED. OFFSET SEAMS WHEN INSTALLING BOARDS. SEAL ALL JOINTS.
2" - 3# FIBERGLASS BOARD (SEE NITE 8)
ROOFING MEMBRANE *
CANT STRIP *
ROOF INSULATION *
* MATERIALS FURNISHED AND INSTALLED BY GENERAL CONTRACTOR
** MATERIALS FURNISHED AND INSTALLED BY GENERAL CONTRACTOR
METAL DECK **
2
M-504
ERU CURB DETAIL
SCALE: N.T.S.
KEY PLAN
A
B
REVISION
NO.
DESCRIPTION
DATE
AHA PROJECT NUMBER
12/14/2015 11:04:40 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC DETAILS
REVISED
15 DECEMBER 2015
SHEET NO.
M-504
AHU
AIR HANDLING UNIT
CFM
SYMBOL
AHU-G-1
AHU-G-2
AHU-G-3
AHU-1-1
AHU-1-2
SERVICE
LOCATION
KITCHEN
DINING
BOOKSTORE
COMMON
MAIL ROOM
GROUND FL
GROUND FL
GROUND FL
FIRST FL
FIRST FL
SELECTION BASED ON:
SUPPLY FAN WITH VFD
TYPE
SINGLE ZONE-VAV
SINGLE ZONE-VAV
SINGLE ZONE-VAV
MULTI ZONE-VAV
SINGLE ZONE-VAV
EXHAUST FAN WITH VFD
HOT WATER PRE-HEAT COIL
CHILLED WATER COIL
TOTAL
OA
CFM
ESP
TOT.
S.P.
FAN
RPM
BHP
MOTOR
HP
CFM
ESP
TOT.
S.P.
FAN
RPM
BHP
MOTOR
HP
EAT
LAT
GPM
WPD
FT
APD
IN
EWT
LWT
9,000
16,000
12,000
9,500
2,400
1,000
5,100
2,500
1,400
300
9,000
16,000
12,000
9,500
2,400
1.0
1.0
1.0
1.5
0.5
2.51
2.60
2.43
3.29
1.16
1,966
1,110
1,237
1,503
-
7.04
12.09
8.68
9.10
0.88
7.5
15.0
10.0
10.0
1.0
9,000
16,000
12,000
9,500
-
0.5
0.5
0.5
0.5
-
0.83
0.80
0.76
0.79
-
2,036
1,745
1,350
1,127
-
7.02
13.69
6.48
3.88
-
7.5
15.0
7.5
5.0
-
20.0
-
59.3
-
21.5
-
10.9
-
0.05
-
180
-
140
-
EAT
DB
WB
76.2
79.0
77.0
76.2
75.0
LAT
66.8
68.0
66.0
63.8
65.0
DB
WB
56.5
56.5
56.8
52.3
57.6
56.1
56.1
56.5
52.1
57.4
HOT WATER RE-HEAT COIL
FILTERS
MOTORS
REMARKS
GPM
WPD
FT
APD
IN
EWT
LWT
EAT
LAT
GPM
WPD
FT
APD
IN
EWT
LWT
EFF.
V
P
Hz
65.0
129.5
76.6
69.7
12.2
14.6
18.7
6.7
18.7
8.05
0.82
0.70
0.61
0.87
-
44
44
44
44
45
54
54
54
54
55
55
55
55
70
98.7
95.0
96.4
94.2
22.7
37.0
28.7
3.4
10.9
0.9
0.4
4.11
0.11
0.09
0.13
-
180
180
180
180
140
140
140
140
MERV 8
MERV 8
MERV 8
MERV 8
MERV 8
460
460
460
460
460
3
3
3
3
3
60
60
60
60
60
1
1
1
1
1
2
2
2
2
2
3
3
3
3
3
4
4
4
4
4
ARCHITECT
5
5
5
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
5
ASSOCIATE ARCHITECT
JCI/YORK
MURRAY AND ASSOCIATES ARCHITECTS
REMARKS:
1. PROVIDE WITH SINGLE POINT POWER CONNECTION WITH FACTORY MOUNTED AND WIRED DISCONNECT.
2. PROVIDE ALL COILS WITH 2-WAY CONTROL VALVE, SHUT OFF VALVES, BALANCING VALVE, AND STRAINER.
3. PROVIDE WITH WATER LEVEL DETECTION DEVICE FOR CONDENSATE OVERFLOW.
4. CHILLED WATER AND HOT WATER COILS SELECTED WITH 35% PROPYLENE GLYCOL.
5. PROVIDE WALL MOUNTED BAS TEMPERATURE AND HUMIDITY SENSORS (ONE EACH) AS SHOWN ON FLOOR PLANS FOR SUPPLY AIR TEMPERATURE AND HUMIDITY CONTROL.
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
ERU-1
ERU-2
SERVICE
LOCATION
AREA A
AREA B
ROOF
ROOF
SELECTION BASED ON:
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
SUPPLY FAN WITH VFD
SYMBOL
SITE/CIVIL ENGINEER
ERU
ENERGY RECOVERY UNIT (100% OA)
EXHAUST FAN WITH VFD
CFM
ESP
TOT.
S.P.
FAN
RPM
7,800
11,775
2.0
2.0
4.64
4.99
1,922 10.43
1,865 17.08
BHP
ENERGY RECOVERY WHEEL
MOTOR
HP
CFM
ESP
TOT.
S.P.
FAN
RPM
BHP
15.0
20.0
5,000
7,650
2.0
2.0
3.18
3.29
2,154
1,050
8.72
9.45
MOTOR OUTSIDE AIR
HP
DB
WB
10.0
15.0
90.8
90.8
EXHAUST AIR
DB
WB
72.8
72.8
75
75
MBH COOLING
TOTAL SENS.
BASE
EFF.%
63
63
HOT WATER PRE-HEAT COIL
76.3
74.2
137.8
204.6
CHILLED WATER COIL
MBH
HEATING
EAT
LAT
GPM
WPD
FT
APD
IN
EWT
LWT
370.9
550.4
4.5
4.5
39.9
38.6
17.7
25.8
4.6
11.1
0.03
0.04
180
180
140
140
-
EAT
DB
WB
82.2
82.2
LAT
68.0
68.0
DB
WB
54.0
53.4
53.9
53.2
HOT WATER RE-HEAT COIL
FILTERS
MOTORS
LITITZ, PA 17543
REMARKS
GPM
WPD
FT
APD
IN
EWT
LWT
EAT
LAT
GPM
WPD
FT
APD
IN
EWT
LWT
EFF.
V
P
Hz
70.5
109.7
12.3
13.7
0.56
0.74
44
44
54
54
35.0
35.0
76.5
75.4
19.5
28.7
5.5
13.6
0.04
0.05
180
180
140
140
MERV 8
MERV 8
460
460
3
3
60
60
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
1 2 3 4 5 6 7
1 2 3 4 5 6 7
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
JCI/YORK
STRUCTURAL ENGINEER
REMARKS:
1. PROVIDE WITH SINGLE POINT POWER CONNECTION WITH FACTORY MOUNTED AND WIRED DISCONNECT.
2. PROVIDE ALL COILS WITH 2-WAY CONTROL VALVE, SHUT OFF VALVES, BALANCING VALVE, AND STRAINER.
3. PROVIDE WITH WATER LEVEL DETECTION DEVICE FOR CONDENSATE OVERFLOW.
4. CHILLED WATER AND HOT WATER COILS SELECTED WITH 35% PROPYLENE GLYCOL.
5. PROVIDE FACTORY INSULATED ROOF CURB.
6. PROVIDE WALL MOUNTED TEMPERATURE AND HUMIDITY SENSORS (ONE EACH) ON EACH FLOOR AS SHOWN ON FLOOR PLANS FOR SUPPLY AIR TEMPERATURE AND HUMIDITY CONTROL.
7. PROVIDE BYPASS DAMPERS ON ENERGY RECOVERY WHEEL.
MAU-G-1
SUPPLY FAN WITH VFD
LOCATION
KITCHEN
GROUND FL
SELECTION BASED ON:
MECHANICSBURG, PA 17050
TOTAL
OA
CFM
ESP
TOT.
S.P.
3,350
3,350
3,350
1.0
1.23
HOT WATER PRE-HEAT COIL
FAN
RPM
MOTOR
BHP
HP
1,135
1.95
EAT
LAT
GPM
WPD
FT
3
75
16.4
5.4
3.0
FILTERS
STEAM CONDENSATE PUMPS
PUMP
MOTORS
REMARKS
APD
IN
EWT
LWT
EFF.
V
P
Hz
0.08
180
140
MERV 8
460
3
60
1 2 3 4 5
GREENHECK
REMARKS:
1. PROVIDE WITH SINGLE POINT POWER CONNECTION WITH FACTORY MOUNTED AND WIRED DISCONNECT.
2. PROVIDE ALL COILS WITH 2-WAY CONTROL VALVE, SHUT OFF VALVES, BALANCING VALVE, AND STRAINER.
3. HOT WATER COILS SELECTED WITH 35% PROPYLENE GLYCOL.
4. PROVIDE A VFD WITH MAIN DISCONNECT SWITCH, 3 CONTACTOR BYPASS, 120V FUSED CONTROL TRANSFORMER, POWER/CONTROL WIRING, AND TERMINAL STRIP FOR FIELD CONTROL WIRING.
5. INTERFACE CONTROLS WITH BAS.
EXHAUST FAN WITH VFD
SERVICE
LOCATION
CFM
KEF-G-1
KITCHEN
GROUND FL
SELECTION BASED ON:
ESP
5,805
4.25
TOT.
S.P.
FAN
RPM
BHP
4.6
2,310
6.47
PRE-FILTERS
MAIN-FILTERS
FINAL-FILTERS
CH-1
400
EVAP
COND
ENT
LVG
GPM
PD
FT
EFF.
10.0
30%, MERV 8
0.00010
0.00025
52
42
956
15.0
SELECTION BASED ON:
CONDENSER WATER
DEPTH
EFF.
4"
DEPTH
95%, MERV 14
22"
EFF.
DEPTH
95%, MERV 16
V
12"
P
ENT
LVG
GPM
COMPRESSOR DATA
PD
FT QTY VOLT.
KW
PH
85
95
1,127
17.8
460
1
460
3
LBS. OF
REFRIGERANT
REFRIGERATION
TYPE
3
CT-1
SERIES 3000
MAIL ROOM ROOF
SELECTION BASED ON:
DB(ºF) WB(ºF)
85.0
75.8
1,200
228
1,334
85.0
TEMPLATE VERSION: 2.6.8.20141012
12/14/2015 11:04:43 PM
DD-12
-
-
-
-
324
80
-
CENTRAL PLANT
PT3508
-
-
-
-
324
80
-
CENTRAL PLANT
PT3508
-
-
-
-
324
80
-
ARMSTRONG
HXS
R-134A
0.571
0.363
1
20.0
98,800
2
SYMBOL
SERVICE
LOCATION
HXS-1
HEATING HOT WATER
HXS-2
HEATING HOT WATER
PPH
INLET TEMP
CENTRAL PLANT
9,400
324
CENTRAL PLANT
9,400
324
35% GLYCOL SIDE
EWT
LWT
GPM
PD (FT)
MODEL
NUMBER
80
140
180
450
1.8
WS-12
1 2
80
140
180
450
1.8
WS-12
1 2
INLET PRESS
REMARKS
ARMSTRONG
REMARKS:
1. ASME CERTIFIED.
2. HEAT EXCHANGER, RECEIVER, STEAM TRAP, AND PUMP PACKAGE SHALL BE PROVIDED BY THE SAME MANUFACTURER AND SKID MOUNTED.
FINNED TUBE RADIATION (WATER)
SYMBOL
MOUNTING
LENGTH
FTR-A
PEDISTAL
48"
SELECTION BASED ON:
1.
2.
1 2 3 4 5
ELECTRICAL
CONTROL
OPTIONS
WEIGHT
VFD
18,330
9.0
V
PH
460
3
REMARKS
1 2 3 4 5 6 7 8 9 10
OUTPUT (BTU)
PER LINEAR FOOT
638
FTR
AWT
EAT
160
65
GPM
WTD/FT
FINS/FT
FPS
REMARKS
5
0.25
50
3
1 2
MODINE MODEL PA
PROVIDE WITH DOUBLE POLE THERMOSTAT.
THERMAL LIMIT SWITCH.
BT
SYMBOL
SERVES
LOCATION
BT-1
CHILED WATER SYSTEM
CENTRAL PLANT
SELECTION BASED ON:
TANK
TANK
TANK
TANK
VOLUME
DIAMETER
HEIGHT
WEIGHT
2500
84
138
5,340
REMARKS
1 2 3
TACO BTH
REMARKS:
1. MOUNT ON CONCRETE HOUSEKEEPING PAD. REFER TO STRUCTURAL DOCUMENTS.
2. TANK SHALL BE INSULATED PER SPECIFICATIONS.
3. TANK SHALL BE ASME CERTIFIED.
BALTIMORE AIRCOIL
HEAT EXCHANGERS - PLATE & FRAME
HEAD
FT.
NPSHR
BHP
MOTOR
HP
9.375
14.3
21.12
25.0
END SUCTION
9.375
14.3
21.12
75
END SUCTION
9.375
14.3
100
END SUCTION 10.875
9.4
SYMBOL
SERVES
GPM
TYPE
PCHWP-1
PRIMARY CHW
960
75
END SUCTION
PCHWP-2
PRIMARY CHW
960
75
PCHWP-3 (FUTURE)
PRIMARY CHW
960
SCHWP-1
SECONDARY CHW
960
IMP.
DIA.
MOTOR
RPM
V
PH
EMERGENCY
POWER
1,770
460
3
N
1 2 3 4 5
25.0
1,770
460
3
N
1 2 3 4 5
21.12
25.0
1,770
460
3
N
1 2 3 4 5
30.69
40.0
1,770
460
3
N
1 2 3 4 5
REMARKS
SCHWP-2
SECONDARY CHW
960
100
END SUCTION 10.875
9.4
30.69
40.0
1,770
460
3
N
1 2 3 4 5
HWP-1
HOT WATER
450
75
END SUCTION
9.125
7.2
10.39
15.0
1,770
460
3
Y
1 2 3 4 5
HWP-2
HOT WATER
450
75
END SUCTION
9.125
7.2
10.39
15.0
1,770
460
3
Y
1 2 3 4 5
CWP-1
CONDENSER WATER
1,200
75
END SUCTION
9.25
12.1
28.87
40.0
1,770
460
3
N
1 2 3 4 5
CWP-2
CONDENSER WATER
1,200
75
END SUCTION
9.25
12.1
28.87
40.0
1,770
460
3
N
1 2 3 4 5
CWP-3 (FUTURE)
CONDENSER WATER
1,200
75
END SUCTION
9.25
12.1
28.87
40.0
1,770
460
3
N
1 2 3 4 5
BELL & GOSSETT
REMARKS:
1. PROVIDE A VFD WITH MAIN DISCONNECT SWITCH, 3 CONTACTOR BYPASS, 120V FUSED CONTROL TRANSFORMER, POWER/CONTROL WIRING, TERMINAL STRIP FOR FIELD CONTROL WIRING AND INTERFACE
TO SIEMENS DEMAND FLOW CONTROLLER.
2. INVERTER DUTY MOTOR.
3. MOUNT ON CONCRETE HOUSEKEEPING PAD. REFER TO STRUCTURAL DOCUMENTS.
4. SUCTION DIFFUSER WITH INTEGRAL STRAINER.
5. DDC CONTROL TO INTERFACE WITH BAS.
KEY PLAN
HX
SYMBOL
MODEL/
SERIES
SERVES
LOCATION
EWT
(ºF)
HEX-1
HEX-2
A/S PHE
A/S PHE
PRIMARY ECONOMIZER
SECONDARY CHW
CENTRAL PLANT
CENTRAL PLANT
52
54
SELECTION BASED ON:
PUMPS
PLOT DATE:
CENTRAL PLANT
SELECTION BASED ON:
REMARKS:
1. INVERTER CAPABLE, PREMIUM EFFICIENT FAN MOTORS.
2. 3-PROBE ELECRONIC WATER LEVEL CONTROL PACKAGE.
3. ELECTRIC HEATERS W/CONTACTOR FOR HEATER PACKAGE.
4. SUMP SWEEPER PIPING.
5. VIBRATION CUTOUT SWITCH.
6. 304 STAINLESS STEEL COLD WATER BASIN WITH STRAINER.
7. LADDER AND RAILING SYTEM PROVIDED BY MANUFACTURER.
8. DDC CONTROLER WITH BAS INTERFACE.
9. LOW SOUND FAN.
10. PROVIDE VIBRATION ISOLATORS AT EACH CONNECTION TO STEEL SUPPORT.
SELECTION BASED ON:
-
REMARKS
BUFFER TANK
FAN DATA
HEATER DATA
MOTOR HP
#
KW
EWT (ºF) LWT (ºF) # FANS
CFM EA HEATERS
EA
EA
95.0
80
SCP-4
1 2 3 4 5 6 7 8 9 10 11 12
60
100% DUTY
IPLV
KW/TON
KW/TON REMARKS
WATER
GPM
324
PRESS
STEAM SIDE
CT
OUTDOOR AIR
-
SCP-3
Hz
COOLING TOWERS
LOCATION
-
TEMP
SHELL AND TUBE HEAT EXCHANGER
REMARKS:
1. VARIABLE SPEED DRIVE.
2. PROVIDE TOUCH SCREEN INTERFACE.
3. PROVIDE INTERFAC TO BAS.
4. MOUNT ON HOUSEKEEPING PAD WITH NEOPRENE MOUNTS. REFER TO STRUCTURAL DOCUMENTS FOR HOUSEKEEPING PAD.
5. SELECTION BASED ON 0% GLYCOL.
MODEL/
SERIES
-
PPH
REMARKS:
1. HEAT EXCHANGER, RECEIVER, STEAM TRAP, AND PUMP PACKAGE SHALL BE PROVIDED BY THE SAME MANUFACTURER AND SKID MOUNTED.
JCI/YORK MODEL YMC2
SYMBOL
-
SCP-2
CH
CHILLED WATER
DD-12
CENTRAL PLANT
GREENHECK TRIPLE PLAY KITCHEN EXHAUST SYSTEM
FOULING FACTOR
EDR
SCP-1
MOTORS
CENTRIFUGAL LIQUID CHILLER
TONS
GPM
MODEL
REMARKS
MOTOR
HP
STEAM
DISCHARGE
PRESSURE
LOCATION
SELECTION BASED ON:
REMARKS:
1. PROVIDE WITH SINGLE POINT POWER CONNECTION WITH FACTORY MOUNTED AND WIRED DISCONNECT.
2. PROVIDE WITH BONDED ACTIVATED CARBON PANELS AFTER FINAL FILTERS.
3. UNIT SHALL BE ETL LISTED TO UL-710.
4. FAN SHALL BE UL-762 LISTED.
5. FILTERS SHALL BE SEALED AGAINST AIR BYPASS.
6. PROVIDE WITH REMOTE FILTER STATUS INDICATOR FOR PRE, MAIN, AND FINAL FILTERS.
7. PRE-FILTERS SHALL BE PLEATED FILTERS.
8. MAIN- FILTERS SHALL BE BAG FILTERS.
9. FINAL FILTER SHALL BE RIGID FILTERS.
10. FACTORY PIPED ANSUL SYSTEM. ANSUL TANKS AND CONTROLS SHALL BE FIELD INSTALLED.
11. PROVIDE A VFD WITH MAIN DISCONNECT SWITCH, 3 CONTACTOR BYPASS, 120V FUSED CONTROL TRANSFORMER, POWER/CONTROL WIRING, TERMINAL STRIP FOR FIELD CONTROL WIRING.
12. INTERFACE CONTROLS WITH BAS.
SYMBOL
SYMBOL
KEF
KITCHEN EXHAUST FAN WITH SCRUBBER
SYMBOL
SCP
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
CFM
SERVICE
100 STERLING PARKWAY, SUITE 108
MAU
KITCHEN MAKEUP AIR UNIT
SYMBOL
WBCM
HOT SIDE
LWT
GPM
(ºF)
42
44
960
960
WATER PD
(PSI)
EWT
(ºF)
6.64
10.05
40
42
COLD SIDE
LWT
GPM WATER PD
(ºF)
(PSI)
48
52
1,200
960
OPERATING
WEIGHT
10.05
8.96
8,893
8,313
REMARKS
A
1 2
1 3
SONDEX
B
REMARKS:
1. MOUNT ON CONCRETE HOUSEKEEPING. REFER TO STRUCTURAL DOCUMENTS.
2. HEAT EXCHANGER FRAME SHALL HAVE AN EXTRA PLATE CAPACITY OF 200%.
3. HEAT EXCHANGER FRAME SHALL HAVE AN EXTRA PLATE CAPACITY OF 50%.
REVISION
NO.
DESCRIPTION
EXPANSION TANK & AIR SEPARATOR
ET & AS
TANK/ACCEP.
TANK
AIR SEPARATOR
MAX. CAP.
AIR SEPARATOR
VOLUME
DIMENSIONS
MODEL NO.
GPM
DIMENSIONS
SYMBOL
SERVES
ET-1/AS-1
PRIMARY CHW
53
24"Ø X 37"H
RL-12
4,800
-
1 2 3
ET-2/AS-2
SECONDARY CHW
792
48"Ø X 119"H
RL-8
1,900
-
1 2 3
ET-3/AS-3
HEATING HOT WATER
528
48"Ø X 84"H
RL-5
530
-
1 2 3
SELECTION BASED ON:
DATE
REMARKS
BELL AND GOSSETT
REMARKS:
1. MOUNT ON CONCRETE HOUSEKEEPING PAD. REFER TO STRUCTURAL DOCUMENTS.
2. EXPANSION TANK SHALL BE ASME CERTIFIED.
3. EXPANSION TANK SHALL HAVE A PRE-CHARGED BLADDER.
AHA PROJECT NUMBER
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC SCHEDULES
REVISED
15 DECEMBER 2015
SHEET NO.
M-601
VRF - DUCTLESS SPLIT SYSTEMS - INDOOR UNITS
DIFFUSERS, REGISTERS & GRILLES
COOLING
SYMBOL
MODEL
TYPE
CFM
ELECTRICAL
SERVED
BY
SERVES
DSS-A-1
DSS-A-2
DSS-A-3
DSS-A-4
DSS-A-5
DSS-A-6
DSS-A-7
DSS-A-8
DSS-A-9
DSS-A-10
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A
GND FL IDF
1ST FL IDF
2ND FL IDF
2ND FL ELEC
3RD FL IDF
4TH FL IDF
4TH FL ELEC
5TH FL IDF
6TH FL IDF
6TH FL ELEC
FXAQ24PVJU
FXAQ24PVJU
FXAQ24PVJU
FXAQ18PVJU
FXAQ24PVJU
FXAQ24PVJU
FXAQ07PVJU
FXAQ24PVJU
FXAQ24PVJU
FXAQ07PVJU
WALL
WALL
WALL
WALL
WALL
WALL
WALL
WALL
WALL
WALL
635
635
635
500
635
635
260
635
635
260
24.0
24.0
24.0
18.0
24.0
24.0
7.5
24.0
24.0
7.5
18.0
18.0
18.0
13.7
18.0
18.0
6.4
18.0
18.0
6.4
208
208
208
208
208
208
208
208
208
208
1
1
1
1
1
1
1
1
1
1
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
1
1
1
1
1
1
1
1
1
1
DSS-B-1
DSS-B-2
DSS-B-3
DSS-B-4
DSS-B-5
DSS-B-6
DSS-B-7
DSS-B-8
DSS-B-9
DSS-B-10
DSS-B-11
DSS-B-12
CU-B
CU-B
GND FL IDF
GND FL ELEC
FXAQ24PVJU
FXAQ12PVJU
WALL
WALL
635
290
24.0
12.0
18.0
8.9
208
208
1
1
Y
Y
1 2 3 4 5 6 7
1 2 3 4 5 6 7
CU-B
CU-B
CU-B
CU-B
CU-B
CU-B
CU-B
CU-B
CU-B
CU-B
1ST FL MDF
1ST FL IDF
2ND FL ELEC
2ND FL IDF
3RD FL IDF
4TH FL ELEC
4TH FL IDF
5TH FL IDF
6TH FL ELEC
6TH FL IDF
FXAQ24PVJU
FXAQ24PVJU
FXAQ24PVJU
FXAQ24PVJU
FXAQ24PVJU
FXAQ18PVJU
FXAQ24PVJU
FXAQ24PVJU
FXAQ18PVJU
FXAQ24PVJU
WALL
WALL
WALL
WALL
WALL
WALL
WALL
WALL
WALL
WALL
635
635
635
635
635
500
635
635
500
635
24.0
24.0
24.0
24.0
24.0
18.0
24.0
24.0
18.0
24.0
18.0
18.0
18.0
18.0
18.0
13.7
18.0
18.0
13.7
18.0
208
208
208
208
208
208
208
208
208
208
1
1
1
1
1
1
1
1
1
1
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
1
1
1
1
1
1
1
1
1
1
TOT. MBH SENS. MBH
V
EMERGENCY REMARKS
POWER
PH
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
7
7
7
7
7
7
7
7
7
7
SYMBOL
MODEL /
SERIES
FUNCTION
NECK
SIZE
(IN)
FACE SIZE
(IN)
RANGE
(CFM)
MATERIAL
DAMPER
(Y/N)
SD-1
SD-2
SD-3
SD-4
SD-5
TDC-AA
TDC-AA
TDC-AA
TDC-AA
TDC-AA
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY
6"ø
8"ø
10"ø
12"ø
14"ø
24x24
24x24
24x24
24x24
24x24
0 - 100
101 - 230
231 - 380
381 - 500
501 - 640
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
N
N
N
N
N
CEILING
CEILING
CEILING
CEILING
CEILING
1
1
1
1
1
CD-1
TDC-AA
SUPPLY
8"ø
24x24
0 - 230
ALUMINUM
N
CEILING
1 7
KD-1
PAS-AA
SUPPLY
14"ø
24x24
0 - 500
ALUMINUM
N
CEILING
1 8
HARRISBURG, PA 17102-2499
SR-A
SR-1
301FS
301FS
SUPPLY
SUPPLY
18X6
20X20
18X6
20X20
0 - 380
0 - 1300
ALUMINUM
ALUMINUM
Y
N
CEILING
WALL
2
---
MEP ENGINEER
LD-1
LD-2
LD-3
LD-4
TBDI-80
TBDI-80
TBDI-80
TBDI-80
SUPPLY
SUPPLY
SUPPLY
SUPPLY
6"
8"
10"
12"
2 SLOTS, 1x48 EA
2 SLOTS, 1x48 EA
2 SLOTS, 1x48 EA
2 SLOTS, 1x48 EA
0 - 180
181 - 230
231 - 270
271 - 340
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
N
N
N
N
CEILING/WALL
CEILING/WALL
CEILING/WALL
CEILING/WALL
3
3
3
3
TYPE
REMARKS
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
7
7
7
7
7
7
7
7
7
7
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
4
4
4
4
5
5
5
5
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
RD-1
RD-2
RD-3
RD-4
RD-5
PAR-AA
PAR-AA
PAR-AA
PAR-AA
PAR-AA
RETURN
RETURN
RETURN
RETURN
RETURN
8"ø
10"ø
12"ø
14"ø
14x14
24x24
24x24
24x24
24x24
24x24
0 - 230
231 - 380
381 - 500
501 - 640
641 - 1,000
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
N
N
N
N
N
CEILING
CEILING
CEILING
CEILING
CEILING
LITITZ, PA 17543
-----------
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
DAIKIN
RG-1
RG-A
REMARKS:
1. DISCONNECT SWITCH BY ELECTRICAL.
2. PROVIDE WITH CONDENSATE PUMP. ROUTE CONDENSATE TO DRAIN IN NEAREST FAN COIL UNIT CLOSET.
3. PROVIDE UNIT WITH REMOTE WALL MOUNTED THEMOSTAT.
4. PROVIDE ISOLATION VALVES IN REFRIGERANT LINES FOR MAINTENANCE.
5. INSTALL PER MANUFACTURERS RECOMMENDED CLEARANCES AND GUIDELINES.
6. COOLING AND HEATING CAPPACITIES SHALL INCLUDE REFRIGERANT LINE LOSS.
7. PROVIDE WATER LEVEL DETECTION DEVICE (WLDD) IN UNIT SUPPLIED DRAIN PAN AND LOCATE AT A POINT HIGHER THAN THE PRIMARY DRAIN LINE. WLDD SHALL
BE WIRED TO SHUT OFF UNIT IN EVENT THE PRIMARY LINE IS BLOCKED.
PAR-AA
PAR-AA
ER-1
ER-2
ER-3
ER-4
ER-5
COOLING
CU-A
CU-B
REYQ192PBYD
REYQ264PBYD
SELECTION BASED ON:
ELECTRICAL
TOT. MBH
V
PH
192
264
460
460
3
3
IEER
EMERGENCY
POWER
18.7
18.7
Y
Y
REMARKS
1 2 3 4
1 2 3 4
DAIKIN
50F
50F
50F
50F
50F
AIR CONDITIONING UNIT
CRAC-G-1 TRANSFORMER ROOM
CRAC-G-2 TRANSFORMER ROOM
CRAC
CURRENT
CFM
O.A.
CFM
MBH
TOTAL
MBH
SENS.
RH
KW
FAN
HP
V
PH
HTZ
3750
0
102.4
102.4
11.5
2.0
460
3
60
3750
0
102.4
102.4
11.5
2.0
CRCU-G-1
CRAC-G-1
ROOF
95
CRCU-G-2
CRAC-G-2
ROOF
95
0 - 100
0 - 100
101 - 230
231 - 380
381 - 500
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
N
N
N
N
N
CEILING
CEILING
CEILING
CEILING
CEILING
2
2
2
2
2
100 STERLING PARKWAY, SUITE 108
6
6
6
6
6
MECHANICSBURG, PA 17050
TITUS
PRIMARY
AIR CFM
RANGE
INLET
SIZE
FPT-1-1
FPT-1-2
620 - 2,070
16"ø
760 - 2,525
16"ø
FPT-1-3
515 - 1,705
FPT-1-4
360 - 1,195
460
3
60
FPT
FAN
S.P.
FILTER
S.P.
HP
V
PH
EAT
LAT
COIL SIZE
MAX H 2O
GPM
P.D. FT.
0.37
0.35
0.1
1
277
1
68
96.3
3.66
0.38
0.35
0.1
1
277
1
68
94.2
4.21
14"ø
0.40
0.35
0.1
3/4
277
1
68
100.7
12"ø
0.38
0.35
0.1
1/2
277
1
68
102.4
MIN.
OPER. SP
MOTOR
MAX COIL
AIR P.D.
EMERGENCY
POWER
0.69
0.11
N
-
0.9
0.16
N
-
3.44
4.35
0.08
N
-
2.50
2.08
0.06
N
-
REMARKS
12"ø
0.37
0.35
0.1
1/2
1/4
277
1
68
103.3
2.33
1.83
0.05
N
-
12345678
340 - 1,120
12"ø
0.37
0.35
0.1
1/2
1/4
277
1
68
103.0
2.38
1.90
0.05
N
-
MMD96
SELECTION BASED ON
1. NC'S ARE DERIVED FROM SOUND POWER LEVELS, WHICH ARE OBTAINED IN ACCORDANCE WITH ARI STANDARD 880-98 AND ASHRAE STANDARD
130-1996.
2. PROVIDE ECM MOTOR, FACTORY WIRED 24 VOLT TRANSFORMER AND ELECTRIC REHEAT COIL WITH SINGLE POINT POWER CONNECTION AND
DISCONNECT SWITCH.
3. PROVIDE 277 VOLT TO 24 VOLT CONTROL TRANSFORMER.
4. WHERE MEDIUM PRESSURE BRANCH DUCT EXCEEDS TWENTY (20) FEET, INCREASE TO NEXT HIGHER SIZE (i.e. 6" INLET -> 8" DUCT).
REMARKS:
1.
FAN COIL UNITS CHILLED/HOT WATER 4-PIPE
ELECTRICAL DATA
REMARKS
MODEL
WSA
FLA
OPD
V
PH
HTZ
8
19.9
17.4
25
460
3
60
PFH096
1
8
19.9
17.4
25
460
3
60
PFH096
1
FCU
COOLING COIL
SYMBOL
CFM
OA
CFM
ESP
HP
UNIT
STYLE
EDB
FCU-A
350
45
0.5
0.25
VERTICAL
77
64
11.0
EWB TOT.MBH
HEATING COIL
SENS.MBH
GPM
PD EWT
LWT EDB
MBH
GPM
9.2
2.3
7.4
45
55
70
12.0
0.6
ELECTRICAL
PD EWT
EMERGENCY REMARKS
POWER
LWT
V
PH
HTZ
0.14 180
140
277
1
60
N
1 2 3 4 5 6 7
FCU-B
300
30
0.5
0.25
VERTICAL
77
64
10.3
8.4
2.2
6.6
45
55
70
11.5
0.6
0.13 180
140
277
1
60
N
1 2 3 4 5 6 7
FCU-C
900
75
0.5
0.25
VERTICAL
77
64
20.2
18.2
6.0
6.7
45
55
70
22.1
1.2
1.75 180
140
277
1
60
N
1 2 3 4 5 6 7
FCU-D
675
75
0.5
0.25
VERTICAL
77
64
18.0
16.4
3.8
6.7
45
55
70
20.8
1.1
1.66 180
140
277
1
60
N
1 2 3 4 5 6 7
FCU-E
1,350
100
0.5
(2) 0.25
VERTICAL
77
64
32.1
30.0
6.9
6.2
45
55
70
33.8
1.8
0.82 180
140
277
1
60
N
1 2 3 4 5 6 7
FCU-F
1,100
75
0.5
(2) 0.25
VERTICAL
77
64
28.7
25.8
6.2
5.2
45
55
70
29.5
1.6
0.65 180
140
277
1
60
N
1 2 3 4 5 6 7
SELECTION BASED ON:
JCI/YORK
REMARKS:
1. PROVIDE WITH SINGLE POINT POWER CONNECTION WITH FACTORY MOUNTED AND WIRED DISCONNECT.
2. PROVIDE COOLING COIL WITH 2-WAY CONTROL VALVE, SHUT OFF VALVES, BALANCING VALVE, AND STRAINER.
3. PROVIDE HEATING COIL WITH 2-WAY CONTROL VALVE, SHUT OFF VALVES, BALANCING VALVE, AND STRAINER.
4. PROVIDE NETWORKED THERMOSTAT BY BAS MANUFACTURER. SETPOINT ADJUSTMENT RANGE SHALL BE CONTROLLED BY THE BAS.
5. PROVIDE WITH WATER LEVEL DETECTION DEVICE FOR CONDENSATE OVERFLOW.
6. PROVIDE BALANCING VALVE AND MOTORIZED DAMPER IN OUTSIDE AIR DUCT. BALANCE DAMPER TO OA FLOW SHOWN ON SCHEDULE. MOTORIZED DAMPER SHALL OPEN WHEN FAN IS ENERGIZED.
7. CHILLED WATER AND HOT WATER COILS SELECTED WITH 35% PROPYLENE GLYCOL.
ELECTRIC WALL HEATER
EWH
COIL DATA
KEY PLAN
FAN SCHEDULE
KW
STAGES
V
PH
AMPS
MBH
CONTROL OPTIONS
REMOTE THERMOSTAT/
INTEGRAL THERMOSTAT
100
2.0
1
277
1
7.22
6.8
INTEGRAL THERMOSTAT
NO
1 2 3
DEF-1
ENERVEX
BEF500
ROOF
DRYER VENT
3,960
0.981
2,000
-
5.0
208
3
60
1 3 4
AWH4407F
100
2.0
1
277
1
7.22
6.8
INTEGRAL THERMOSTAT
NO
1 2 3
EF-G-1
GREENHECK
CSP-A1410
INLINE
GROUND FL
925
0.375
1,039
-
822 (W)
115
1
60
1 2 5
AWH4407F
100
2.0
1
277
1
7.22
6.8
INTEGRAL THERMOSTAT
NO
1 2 3
EF-G-2
GREENHECK
BSQ-180-30
INLINE
GROUND FL
5,000
0.375
1,484
2.31
3.0
460
3
60
1 2 5
EWH-G-4
AWH4407F
100
2.0
1
277
1
7.22
6.8
INTEGRAL THERMOSTAT
NO
1 2 3
EF-G-3
GREENHECK
CSP-A1050
INLINE
GROUND FL
1,000
0.25
1,090
-
455 (W)
115
1
60
1 2 5
EWH-1-1
AWH4407F
100
2.0
1
277
1
7.22
6.8
INTEGRAL THERMOSTAT
NO
1 2 3
EF-G-4
GREENHECK
CSP-B200
INLINE
GROUND FL
150
0.25
913
-
173 (W)
115
1
60
1 2 5
EWH-1-2
AWH4407F
100
2.0
1
277
1
7.22
6.8
INTEGRAL THERMOSTAT
NO
1 2 3
EF-G-5
GREENHECK
BSQ-240-15
INLINE
GROUND FL
7,000
0.25
765
1.2
1.5
460
3
60
1 2 5
EWH-1-3
AWH4407F
100
2.0
1
277
1
7.22
6.8
INTEGRAL THERMOSTAT
NO
1 2 3
EF-G-6
GREENHECK
CSP-A510
INLINE
GROUND FL
400
0.25
977
-
217 (W)
115
1
60
1 2 5
EWH-1-4
AWH4407F
100
2.0
1
277
1
7.22
6.8
INTEGRAL THERMOSTAT
NO
1 2 3
EF-1-1
GREENHECK
CSP-A700
INLINE
FIRST FL
450
0.375
785
-
350 (W)
115
1
60
1 2 5
EWH-1-5
AWH4407F
100
2.0
1
277
1
7.22
6.8
INTEGRAL THERMOSTAT
NO
1 2 3
EF-1-2
GREENHECK
SP-B110
CEILING
FIRST FL
75
0.25
950
-
80 (W)
115
1
60
1 2
EWH-3-1
AWH4407F
100
2.0
1
277
1
7.22
6.8
INTEGRAL THERMOSTAT
NO
1 2 3
EF-1-3
GREENHECK
SP-B90
CEILING
FIRST FL
50
0.25
586
-
50 (W)
115
1
60
1 2
EWH-3-2
AWH4407F
100
2.0
1
277
1
7.22
6.8
INTEGRAL THERMOSTAT
NO
1 2 3
EF-1-4
GREENHECK
CSP-B200
INLINE
FIRST FL
150
0.25
913
-
173 (W)
115
1
60
1 2 5
EWH-3-3
AWH4407F
100
2.0
1
277
1
7.22
6.8
INTEGRAL THERMOSTAT
NO
1 2 3
EF-1-5
GREENHECK
SP-B150
CEILING
FIRST FL
150
0.25
1,050
-
128 (W)
115
1
60
1 2
EF-2-1
GREENHECK
SP-B150
CEILING
SECOND FL
150
0.25
1,050
-
128 (W)
115
1
60
1 2
EF-3-1
GREENHECK
CSP-B200
INLINE
THIRD FL
150
0.25
913
-
173 (W)
115
1
60
1 2 5
EF-3-2
GREENHECK
CSP-B200
INLINE
THIRD FL
150
0.25
913
-
173 (W)
115
1
60
1 2 5
EF-5-1
GREENHECK
CSP-B200
INLINE
FIFTH FL
150
0.25
913
-
173 (W)
115
1
60
1 2 5
EF-5-2
GREENHECK
CSP-B200
INLINE
FIFTH FL
150
0.25
913
-
173 (W)
115
1
60
1 2 5
SPF-1
GREENHECK
VAD-18H14-16-M30
VANE AXIAL
STAIR PRES.
3,505
2.0
3,500
2.81
3.0
460
3
60
-
SPF-2
GREENHECK
VAD-18H14-16-M30
VANE AXIAL
STAIR PRES.
3,505
2.0
3,500
2.81
3.0
460
3
60
-
SPF-3
GREENHECK
VAD-18H14-16-M30
VANE AXIAL
STAIR PRES.
3,505
2.0
3,500
2.81
3.0
460
3
60
-
EPF-1
GREENHECK
VAD-20H14-23-M75
VANE AXIAL
ELEV. PRES.
8,000
2.0
3,500
6.09
7.5
460
3
60
-
EMERGENCY
POWER
EPF-2
GREENHECK
VAD-20H14-23-M75
VANE AXIAL
ELEV. PRES.
8,000
2.0
3,500
6.09
7.5
460
3
60
-
RF-1-1
GREENHECK
SQ-130-A
INLINE
FIRST FL
2,100
0.25
1,629
0.47
0.75
115
1
60
1 2 5
N
KEF-G-2
GREENHECK
QEI-9-II-3
MIXED FLOW
FIRST FL
650
0.50
1,273
0.13
0.33
460
3
60
1 2 5
SYMBOL
MODEL
CFM
EWH-G-1
AWH4407F
EWH-G-2
EWH-G-3
SELECTION BASED ON:
EMERGENCY
POWER
REMARKS
QMARK
REMARKS:
1. PROVIDE WITH SINGLE POINT POWER CONNECTION.
2. PROVIDE WITH SURFACE MOUNT INSTALLATION KIT.
3. UNIT FINISH SHALL BE DETERMINED BY ARCHITECT DURRING SUBMITTAL PHASE.
WATER FILTRATION SYSTEM
SYMBOL
WFS-1
MODEL
SERVES
PF-63-030
SELECTION BASED ON:
TEMPLATE VERSION: 2.6.8.20141012
12X12
24X24
24X24
24X24
24X24
330 - 1,090
REMARKS:
1. UNIT SHALL BE PROVIDED WITH LOW AMBIENT CONTROLS DOWN TO 0°F.
12/14/2015 11:04:47 PM
6"Ø
6"Ø
8"Ø
10"Ø
12"Ø
FPT-1-6
SELECTION BASED ON: LIEBERT
PLOT DATE:
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
FPT-1-5
CRCU
TONS
STRUCTURAL ENGINEER
12345678
AIR COOLED CONDENSING UNIT
O.A. AMB
-----
MMD96
REMARKS:
1. FACTORY MOUNTED DISCONNECT SWITCH.
2. FACTORY 120V/1PH CONDENSATE PUMP.
3. WALL MOUNTED MICROPROCESSOR CONTROL AND MONITOR PANEL. INTERFACE WITH THE BUILDING BAS.
4. HOT GAS BYPASS CAPACITY CONTROL
5. HIGH TEMPERATURE SENSOR.
6. FILTER CLOG INDICATOR.
7. SUPPLY AND RETURN AIR DISTRIBUTION PLENUM WITH MERV 8 FILTERS.
8. PROVIDE WITH ELECTRIC REHEAT.
LOCATION
CEILING
WALL
REMARKS
GENERAL NOTES: (APPLICABLE TO ALL OF THE ABOVE)
A. R-407C REFRIGERANT.
B. MECHANICAL CONTRACTOR SHALL VERIFY MCA AND MOCP WITH EQUIPMENT MANUFACTURER AND COORDINATE WITH ELECTRICAL CONTRACTOR.
C. SELECTION BASED ON ENTERING AIR TEMPERATURE OF 85 DEG DB/63.6 DEG WB.
SERVES
N
N
MODEL
SELECTION BASED ON: LIEBERT
SYMBOL
ALUMINUM
ALUMINUM
FAN POWERED TERMINAL (HOT WATER) (PARALLEL FLOW)
SYMBOL
SERVICE
0 - 1,500
0 - 1,350
REMARKS:
1. INSULATED BACKPAN.
2. OPPOSED BLADE DAMPER.
3. FACTORY INSULATED PLENUM.
4. VOLUME CONTROL DAMPER KIT W/OPERATOR ACCESSIBLE THROUGH DIFFUSER FACE.
5. CONCEALED FRAME, DRYWALL
6. 1/2"x1/2"x1/2" GRID CORE.
7. PROVIDE TWO WAY THROW ALONG LENGTH OF CORRIDOR.
8. PROVIDE PERFORATED SUPPLY GRILLE WITHOUT PATTERN CONTROLLERS.
REMARKS:
1. PROVIDE WITH FACTORY CONTROLLER WITH BAS INTERFACE.
2. UNIT SHALL BE PROVIDED WITH LOW AMBIENT CONTROLS DOWN TO 0°F.
3. UNIT COMPOSED OF MULTIPLE UNITS MANIFOLDED TOGETHER. INSTALL PER MANUFACTURERS RECOMENDATIONS.
4. CAPACITIES INCLUDE PIPING LOSSES.
SYMBOL
24x24
20x20
GENERAL NOTES: (APPLICABLE TO ALL OF THE ABOVE)
A. COORDINATE FRAME WITH CEILING TYPE AND/OR SUSPENSION SYSTEM. REFER TO ARCHITECTURAL DRAWINGS.
B. FINISH SHALL BE OF THE TYPE AND COLOR SELECTED BY THE ARCHITECT. SUBMIT COLOR/FINISH CHART AS PART OF SHOP
DRAWINGS.
VRF - DUCTLESS SPLIT SYSTEMS - CONDENSING UNITS
MODEL
N/A
N/A
WBCM
SELECTION BASED ON:
SYMBOL
RETURN
RETURN
LOCATION
CT-1
CENTRAL PLANT
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
SELECTION BASED ON:
TYPE
GPM
CENTRIFUGAL
220
HP
GALLONS WEIGHT
7.5
15
ELECTRICAL
V
PH
809
460
3
SYMBOL
MANUFACTURER
MODEL
TYPE
SERVICE
CFM
S.P.
(IN.)
FAN
RPM
BHP
HP
VOLTS
PH
HZ
REMARKS
A
B
REVISION
NO.
DESCRIPTION
REMARKS:
1. PROVIDE WITH SINGLE POINT POWER CONNECTION.
2. PROVIDE WITH FACTORY MOUNTED DISCONNECT.
3. PROVIDE WITH ROOF CURB.
4. PROVIDE WITH VFD, ENERVEX MEC18 CONTROL PANEL, AND REMOTE DUCT MOUNTED PRESSURE SENSOR.
5. PROVIDE SPRING ISOLATORS IN HANGER RODS.
PUROFLUX
PROPELLER UNIT HEATER (HOT WATER)
FAN DATA
AHA PROJECT NUMBER
G1215-004.00
DATE
03 DECEMBER 2015
UH
COIL DATA
ELECTRICAL
DATE
ISSUE
CONSTRUCTION
DOCUMENTS
CFM
HP
RPM
EAT
LAT
EWT
LWT
MBH
GPM
V
PH
HZ
EMERGENCY
POWER
HC165
3,240
1/3
1,075
65
97.5
180
161
103.9
13.6
115
1
60
Y
1 2
SHEET TITLE
HC165
3,240
1/3
1,075
65
97.5
180
161
103.9
13.6
115
1
60
Y
1 2
HVAC SCHEDULES
HC165
3,240
1/3
1,075
65
97.5
180
161
103.9
13.6
115
1
60
Y
1 2
SYMBOL
MODEL
UH-G-1
UH-G-2
UH-G-2
SELECTION BASED ON:
REMARKS
MODINE
REMARKS:
1. PROVIDE WITH SINGLE POINT POWER CONNECTION.
2. PROVIDE WITH WALL MOUNTED THERMOSTAT.
REVISED
15 DECEMBER 2015
SHEET NO.
M-602
EUH
ELECTRIC UNIT HEATERS
SYMBOL
MODEL/
SERIES
SERVICE
MOUNTING
CFM
KW
EUH-G-1
MUH
032 STORAGE
WALL
350
5.0
LENGTH STAGES
(FT)
N/A
1
ELECTRICAL
V
PH
460
3
REMARKS
1 2 3 4 5
ARCHITECT
HKS, INC.
SELECTION BASED ON:
EQUAL PRODUCTS BY:
QMARK
INDEECO, BERKO, CHROMALOX, MARKEL, MARLEY, TRANE
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
REMARKS:
1. INTEGRAL THERMOSTAT.
2. FACTORY DISCONNECT SWITCH.
3. FAN DELAY SWITCH.
4. THERMAL CUTOUT.
5. STEEL FRONT PANEL WITH BAKED ENAMEL FINISH.
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
WALL LOUVERS
WL
MODEL/
SERIES
SERVICE
SIZE
WXH (IN)
MIN FREE AREA
(SQ FT)
CFM
MAX PRESS.
DROP
(IN WC)
WL-G-1
WL-G-2
WL-G-3
WL-G-4
WL-G-5
WL-G-6
WL-G-7
WL-G-8
WL-G-9
WL-G-10
WL-G-11
WL-1-1
WL-1-2
WL-1-3
WL-1-4
WL-1-5
WL-1-6
WL-1-7
ESD-635
ESD-635
ESD-635
ESD-635
ESD-635
ESD-635
ESD-635
ESD-635
ESD-635
ESD-635
ESD-635
ESD-635
ESD-635
ESD-635
ESD-635
ESD-635
ESD-635
ESD-635
MAIN MECHANICAL
EF-G-1
KEF-G-1, G-2
EF-G-2
AHU-G-1, AHU-G-2
EF-G-3
EF-G-5
AHU-G-3
AHU-G-3
EF-G-6
EF-G-6
EF-1-1
AHU-1-1
AHU-1-1
AHU-1-2
RF-1-1
MAU-G-1
AHU-G-1
78 X 36
24 X 24
66 X 36
48 X 36
114 X 66
24 X 24
36 X 60
186 X 24
90 X 48
18 X 18
18 X 18
18 X 18
114 X 30
90 X 42
54 X 24
66 X 18
226 X 28
162 X 24
10.0
1.25
8.25
6.25
31.25
1.25
8.75
15.0
17.25
0.5
0.5
0.75
12.0
13.75
3.5
3.0
22.5
13.0
7,000
925
6,450
5,000
25,000
1,000
7,000
12,000
12,000
400
400
450
9,500
9,500
2,400
2,100
16,250
8,750
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
SELECTION BASED ON:
EQUAL PRODUCTS BY:
OPERATOR INTERLOCK
FRAME
SITE/CIVIL ENGINEER
REMARKS
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
MOD
MOD
-
-
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
3 4
3
3
3
3
3
3
3
3
3 4
3
3
3
3
3
3
3
3
LITITZ, PA 17543
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
STRUCTURAL ENGINEER
WBCM
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
GREENHECK
ARROW, RUSKIN, NAILOR
REMARKS:
1. BIRD SCREEN.
2. BAKED ENAMEL FINISH.
3. INSULATED PLENUM, MINIMUM 24" DEEP, FULL-SIZE OF LOUVER CONNECTION.
4. 120V MOTOR OPERATOR.
RELIEF HOODS
RH
SYMBOL
MODEL/
SERIES
TYPE
SERVICE
THROAT
AREA (SF)
MAX
SP
(IN WC)
RH-R-1
RH-R-2
RH-R-3
RH-R-4
RH-R-5
GRSR
GRSR
GRSR
GRSR
GRSR
RELIEF
RELIEF
RELIEF
RELIEF
RELIEF
STAIRWELL
STAIRWELL
STAIRWELL
ELEVATOR SHAFT
ELEVATOR SHAFT
12.83
12.83
12.83
12.83
12.83
0.013
0.013
0.013
0.066
0.066
SELECTION BASED ON:
EQUAL PRODUCTS BY:
REMARKS
1
1
1
1
1
2
2
2
2
2
3
3
3
3
3
4
4
4
4
4
5
5
5
5
5
GREENHECK
LOREN COOK, PENN BARRY
REMARKS:
1. INSULATED HOOD.
2. ALUMINUM BIRDSCREEN.
3. 120V MOTORIZED DAMPER (FAIL OPEN) TO INTERLOCK WITH FIRE ALARM PANEL.
4. INSULATED ROOF CURB.
5. ADJUSTABLE BAROMETRIC RELIEF DAMPER.
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
SYMBOL
ROSWELL, GA 30076
KEY PLAN
A
B
REVISION
NO.
DESCRIPTION
DATE
AHA PROJECT NUMBER
12/14/2015 11:04:47 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC SCHEDULES
REVISED
15 DECEMBER 2015
SHEET NO.
M-603
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
SPF
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
2
DEF
ASSOCIATE ARCHITECT
1
SPF
60X14 EXHAUST AIR DUCT FROM ERU-2.
SEE M-114 FOR CONTINUATION.
40X16 EXHAUST AIR DUCT TO ERU-1.
SEE M-113 FOR CONTINUATION.
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
34X10 OUTSIDE AIR DUCT. SEE M-114
FOR CONTINUATION.
ROSWELL, GA 30076
44"x18"
18"ø
4"ø
4"ø
TAKEOFF ABOVE FIFTH
FLOOR CEILING.
40"x14"
54X18 SUPPLY AIR DUCT FROM ERU-1.
SEE M-113 FOR CONTINUATION.
22"x22"
10X8 EXHAUST AIR DUCT. SEE M-113
FOR CONTINUATION.
TAKEOFF ABOVE SIXTH
FLOOR CEILING.
12"x44"
PROVIDE TURNDOWN
ABOVE ROOF FOR
DRYER VENT EXHAUST.
6"ø
6"ø
HARRISBURG, PA 17102-2499
MEP ENGINEER
20"x56"
6"ø
1600 NORTH SECOND STREET
70X20 OUTSIDE AIR DUCT DOWN FROM
ERU-2. SEE M-114 FOR CONTINUATION.
60"x14"
6"ø
MURRAY AND ASSOCIATES ARCHITECTS
3
PROVIDE BIRD SCREEN AND
DOWNWARD CAMFER ON DUCT.
PROVIDE BIRD SCREEN AND
DOWNWARD CAMFER ON DUCT.
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
6TH FLOOR
6TH FLOOR
GEOTECHNICAL ENGINEER
14X18 SUPPLY AIR DUCT. SEE M-111
FOR CONTINUATION.
SR-1
1170
22X10 EXHAUST AIR DUCT. SEE M-112
FOR CONTINUATION.
CMT LABORATORIES, INC.
SR-1
1170
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
34X10 OUTSIDE AIR DUCT. SEE M-112
FOR CONTINUATION.
18X10 EXHAUST AIR DUCT. SEE M-111
FOR CONTINUATION.
STRUCTURAL ENGINEER
WBCM
100 STERLING PARKWAY, SUITE 108
6"ø
20"x46"
34X10 OUTSIDE AIR DUCT. SEE M-110
FOR CONTINUATION.
18X10 EXHAUST AIR DUCT. SEE M-109
FOR CONTINUATION.
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
42"x16"
34"x14"
6"ø
22X10 EXHAUST AIR DUCT. SEE M-110
FOR CONTINUATION.
12"x32"
TAKEOFF ABOVE FOURTH
FLOOR CEILING.
14X18 SUPPLY AIR DUCT. SEE M-109
FOR CONTINUATION.
18"x22"
4"ø
4"ø
MECHANICSBURG, PA 17050
10X10 SUPPLY AIR DUCT. SEE M-111
FOR CONTINUATION.
18"ø
34"x18"
6"ø
4"ø
4"ø
TAKEOFF ABOVE THIRD
FLOOR CEILING.
34"x10"
10X10 SUPPLY AIR DUCT. SEE M-109
FOR CONTINUATION.
14X18 SUPPLY AIR DUCT. SEE M-107
FOR CONTINUATION.
6"ø
4TH FLOOR
20"x36"
18"ø
34"x14"
6"ø
40"x14"
6"ø
4TH FLOOR
22X10 EXHAUST AIR DUCT. SEE M-108
FOR CONTINUATION.
SR-1
1170
SR-1
1170
34X10 OUTSIDE AIR DUCT. SEE M-108 FOR
CONTINUATION.
18X10 EXHAUST AIR DUCT. SEE M-107
FOR CONTINUATION.
16"x34"
22X10 EXHAUST AIR DUCT. SEE M-106
FOR CONTINUATION.
TAKEOFF ABOVE SECOND
FLOOR CEILING.
6"ø
12"x22"
18"x10"
14X18 SUPPLY AIR DUCT. SEE M-105
FOR CONTINUATION.
12"x22"
4"ø
4"ø
10X10 SUPPLY AIR DUCT. SEE M-107
FOR CONTINUATION.
18"ø
20"x14"
6"ø
40"x10"
6"ø
34X10 OUTSIDE AIR DUCT. SEE M-106
FOR CONTINUATION.
18X10 EXHAUST AIR DUCT. SEE M-105
FOR CONTINUATION.
6"ø
PROVIDE FIRE SMOKE DAMPER AT
PENETRATION OF SHAFT WALL. (TYP)
4"ø
2ND FLOOR
2ND FLOOR
10"x30"
10X10 SUPPLY AIR DUCT. SEE M-105
FOR CONTINUATION.
18"ø
20"x10"
6"ø
4"ø
20X10 EXHAUST AIR DUCT. SEE M-104
FOR CONTINUATION.
TAKEOFF ABOVE FIRST
FLOOR CEILING.
6"ø
SR-1
1170
SR-1
1170
30X10 OUTSIDE AIR DUCT. SEE M-104
FOR CONTINUATION.
LOCATE SYSTEM DP
SENSOR AT BOTTOM OF
VENT STACK.
PROVIDE FIRE SMOKE DAMPER AT
PENETRATION OF SHAFT WALL. (TYP)
6"ø
6"ø
PROVIDE CLEANOUT AT
BOTTOM OF VENT STACK.
4"ø
4"ø
1
M-701
4" TAKEOFF TO DRYER
VENT BOX. (TYP)
MECH. RISER DIAGRAM - D-3
SCALE: N.T.S.
2
M-701
MECH. RISER DIAGRAM - D-1
SCALE: N.T.S.
3
M-701
MECH. RISER DIAGRAM - D-2
SCALE: N.T.S.
4
M-701
MECH. RISER DIAGRAM - D-4
SCALE:
5
M-701
MECH. RISER DIAGRAM - D-5
SCALE:
KEY PLAN
A
B
REVISION
NO.
DESCRIPTION
DATE
AHA PROJECT NUMBER
12/14/2015 11:04:50 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC RISERS
REVISED
15 DECEMBER 2015
SHEET NO.
M-701
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
ROOF
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
3/4" HWR
3/4" HWS
3/4" SCHWR
3/4" SCHWS
3/4" SCHWS
3/4" SCHWR
3/4" HWS
3/4" HWR
3/4" SCHWS
3/4" SCHWR
3/4" HWS
3/4" HWR
3/4" SCHWR
3/4" SCHWS
3/4" HWR
3/4" HWS
STAE COLLEGE, PA 16801
3/4" SCHWR
3/4" SCHWS
3/4" HWR
3/4" HWS
3/4" SCHWS
3/4" SCHWR
3/4" HWS
3/4" HWR
STRUCTURAL ENGINEER
WBCM
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
6TH FLOOR
3/4" C
3/4" C
3/4" C
3/4" C
3/4" C
3/4" C
3/4" SCHWS
3/4" SCHWR
3/4" HWS
3/4" HWR
3/4" SCHWS
3/4" SCHWR
3/4" HWS
3/4" HWR
1 1/4" SCHWR
1 1/4" SCHWS
3/4" HWR
3/4" HWS
3/4" HWR
3/4" HWS
1 1/4" SCHWR
1 1/4" SCHWS
1" SCHWR
1" SCHWS
3/4" HWR
3/4" HWS
1" SCHWS
1" SCHWR
3/4" HWS
3/4" HWR
3/4" CONDENSATE
FROM FCU (TYP)
1" C
1" C
1" C
1" SCHWS
1" SCHWR
3/4" HWS
3/4" HWR
1" C
1" SCHWS
1" SCHWR
3/4" HWS
3/4" HWR
1" C
1" C
1 1/4" SCHWR
1 1/4" SCHWS
3/4" HWR
3/4" HWS
3/4" HWR
3/4" HWS
1 1/4" SCHWR
1 1/4" SCHWS
5TH FLOOR
1" SCHWS
1" SCHWR
3/4" HWS
3/4" HWR
1" SCHWR
1" SCHWS
3/4" HWR
3/4" HWS
4TH FLOOR
1 1/2" C
1 1/2" C
1 1/2" C
1" SCHWS
1" SCHWR
3/4" HWS
3/4" HWR
1 1/2" C
3/4" HWR
3/4" HWS
1 1/2" SCHWR
1 1/2" SCHWS
1" SCHWS
1" SCHWR
3/4" HWS
3/4" HWR
1 1/2" C
1 1/2" C
3/4" CONDENSATE
FROM FCU (TYP)
1 1/2" SCHWR
1 1/2" SCHWS
3/4" HWR
3/4" HWS
1 1/4" SCHWS
1 1/4" SCHWR
3/4" HWS
3/4" HWR
1 1/4" SCHWR
1 1/4" SCHWS
3/4" HWR
3/4" HWS
3RD FLOOR
1 1/2" C
1 1/2" C
1 1/2" C
1 1/2" C
1 1/2" C
1 1/2" C
3/4" RUNNOUTS
TO FCU (TYP)
3/4" RUNOUTS
TO FCU (TYP.)
1 1/4" SCHWS
1 1/4" SCHWR
3/4" HWS
3/4" HWR
1" SCHWS
1" SCHWR
3/4" HWS
3/4" HWR
1" SCHWS
1" SCHWR
3/4" HWS
3/4" HWR
1" HWR
1" HWS
2" SCHWR
2" SCHWS
1" SCHWS
1" SCHWR
3/4" HWS
3/4" HWR
2" SCHWR
2" SCHWS
1" HWR
1" HWS
2" SCHWR
2" SCHWS
1" HWR
1" HWS
1" HWR
1" HWS
1 1/2" SCHWR
1 1/2" SCHWS
1 1/4" SCHWS
1 1/4" SCHWR
3/4" HWS
3/4" HWR
1 1/4" SCHWR
1 1/4" SCHWS
3/4" HWR
1" HWS
1" HWR
1 1/2" SCHWS
1 1/2" SCHWR
1 1/2" C
3/4" CONDENSATE
FROM FCU (TYP.)
1 1/2" C
3/4" SCHWS
3/4" SCHWR
3/4" HWS
3/4" HWR
1 1/2" C
3/4" HWR
3/4" HWS
3/4" SCHWR
3/4" SCHWS
1 1/2" CONDENSATE TO HUB
DRAIN. HUB DRAIN BY PLUMBING.
2ND FLOOR
1 1/2" C
1 1/2" C
3/4" HWS
3/4" SCHWR
3/4" SCHWS
3/4" HWR
3/4" HWS
3/4" SCHWS
3/4" SCHWR
3/4" HWS
3/4" HWR
3/4" SCHWR
3/4" SCHWS
3/4" HWR
3/4" HWS
1" HWR
1" HWS
2" SCHWR
2" SCHWS
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
3/4" RUNNOUTS
TO FCU (TYP)
KEY PLAN
3/4" RUNOUTS
TO FCU (TYP.)
1 1/2" CONDENSATE TO HUB
DRAIN. HUB DRAIN BY PLUMBING.
1
M-702
SCALE: N.T.S.
1 1/2" CONDENSATE TO HUB
DRAIN. HUB DRAIN BY PLUMBING.
3/4" CONDENSATE
FROM FCU (TYP.)
MECH. RISER DIAGRAM - P-1
3/4" RUNNOUTS
TO FCU (TYP).
3/4" RUNOUTS
TO FCU (TYP.)
1 1/2" CONDENSATE TO HUB
DRAIN. HUB DRAIN BY PLUMBING.
3/4" CONDENSATE
FROM FCU (TYP.)
1 1/2" CONDENSATE TO HUB
DRAIN. HUB DRAIN BY PLUMBING.
1 1/2" CONDENSATE TO HUB
DRAIN. HUB DRAIN BY PLUMBING.
2
M-702
MECH. RISER DIAGRAM - P-2
SCALE: N.T.S.
3
M-702
MECH. RISER DIAGRAM - P-3
SCALE: N.T.S.
4
M-702
MECH. RISER DIAGRAM - P-4
SCALE: N.T.S.
5
M-702
MECH. RISER DIAGRAM - P-5
SCALE: N.T.S.
6
M-702
3/4" CONDENSATE
FROM FCU (TYP).
A
1ST FLOOR
MECH. RISER DIAGRAM - P-6
B
SCALE: N.T.S.
REVISION
NO.
DESCRIPTION
DATE
AHA PROJECT NUMBER
12/14/2015 11:04:53 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC RISERS
REVISED
15 DECEMBER 2015
SHEET NO.
M-702
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
ROSWELL, GA 30076
ROOF
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
3" CHWS/R AND 2" HWS/R
UP TO ERU-1 ON ROOF.
3 1/2" CHWS/R AND 2 1/2" HWS/R
UP TO ERU-2 ON ROOF.
33 SOUTH BROAD STREET
LITITZ, PA 17543
1" CHWS/R AND
3/4" HWS/R TO FCU.
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
3/4" CHWS/R AND
3/4" HWS/R TO FCU.
3/4" HWR
3/4" HWS
2701 CAROLEAN INDUSTRIAL DRIVE
3/4" SCHWS
3/4" SCHWR
3/4" HWS
3/4" HWR
3/4" SCHWR
3/4" SCHWS
3/4" HWR
3/4" HWS
3" SCHWR
3" SCHWS
2" HWR
2" HWS
3 1/2" SCHWS
3 1/2" SCHWR
2 1/2" HWS
2 1/2" HWR
STAE COLLEGE, PA 16801
STRUCTURAL ENGINEER
WBCM
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
3/4" C
1" CHWS/R AND
3/4" HWS/R TO FCU.
3/4" C
3/4" C
1" HWR
1" HWS
1" SCHWR
1" SCHWS
3/4" C
1" HWS/R TO FTR.
3/4" CHWS/R AND
3/4" HWS/R TO FCU.
1" HWR
1" HWS
1" HWR
1" HWS
3/4" C
3/4" RUNNOUTS
TO FCU (TYP)
1 1/4" SCHWS
1 1/4" SCHWR
3/4" HWS
3/4" HWR
1 1/4" SCHWR
1 1/4" SCHWS
1" HWR
1" HWS
3/4" CONDENSATE
FROM FCU (TYP)
3" SCHWR
3" SCHWS
2" HWR
2" HWS
3 1/2" SCHWS
3 1/2" SCHWR
2 1/2" HWS
2 1/2" HWR
1" C
1" C
1" C
3/4" HWS/R TO FTR.
1" CHWS/R AND
3/4" HWS/R TO FCU.
5TH FLOOR
1 1/4" HWR
1 1/4" HWS
1 1/4" SCHWR
1 1/4" SCHWS
1" C
1" HWS/R TO FTR.
3/4" CHWS/R AND
3/4" HWS/R TO FCU.
1 1/4" HWR
1 1/4" HWS
1" C
1 1/4" HWR
1 1/4" HWS
1 1/2" SCHWS
1 1/2" SCHWR
3/4" HWS
3/4" HWR
1 1/4" SCHWR
1 1/4" SCHWS
1 1/4" HWR
1 1/4" HWS
3" SCHWR
3" SCHWS
2" HWR
2" HWS
3 1/2" SCHWS
3 1/2" SCHWR
2 1/2" HWS
2 1/2" HWR
4TH FLOOR
1 1/2" C
3/4" HWS/R TO FTR.
1" CHWS/R AND
3/4" HWS/R TO FCU.
1 1/2" C
1 1/2" C
1 1/2" HWR
1 1/2" HWS
1 1/2" SCHWR
1 1/2" SCHWS
1 1/2" C
1" HWS/R TO FTR.
3/4" CHWS/R AND
3/4" HWS/R TO FCU.
1 1/2" HWR
1 1/2" HWS
3/4" CONDENSATE
FROM FCU (TYP).
1 1/2" C
1 1/2" HWR
1 1/2" HWS
1 1/2" SCHWR
3/4" HWS
3/4" HWR
3/4" CONDENSATE
FROM FCU (TYP)
3" SCHWR
3" SCHWS
2" HWR
2" HWS
3 1/2" SCHWS
3 1/2" SCHWR
2 1/2" HWS
2 1/2" HWR
1 1/2" SCHWS
1 1/2" SCHWR
1 1/2" SCHWS
1 1/2" HWR
1 1/2" HWS
1 1/2" C
3RD FLOOR
1 1/2" C
3/4" HWS/R TO FTR.
1" CHWS/R AND
3/4" HWS/R TO FCU.
2" HWR
2" HWS
2" SCHWR
2" SCHWS
1 1/2" C
2" HWR
2" HWS
2" SCHWR
2" SCHWS
1" HWS/R TO FTR.
3/4" CHWS/R AND
3/4" HWS/R TO FCU.
2" SCHWS
2" SCHWR
2" HWS
2" HWR
2" HWR
2" HWS
3/4" RUNNOUTS
TO FCU (TYP)
2" SCHWR
2" SCHWS
2" HWR
2" HWS
1 1/2" CONDENSATE TO HUB
DRAIN. HUB DRAIN BY PLUMBING.
3/4" HWS/R TO FTR.
1" HWS/R TO FTR.
1" CHWS/R AND
3/4" HWS/R TO FCU.
3/4" CONDENSATE
FROM FCU (TYP).
1 1/2" C
1 1/2" C
1" HWR
1" HWS
1" SCHWR
1" SCHWS
1 1/2" C
1 1/2" CONDENSATE TO HUB
DRAIN. HUB DRAIN BY PLUMBING.
3 1/2" SCHWS
3 1/2" SCHWR
2 1/2" HWS
2 1/2" HWR
3/4" RUNNOUTS
TO FCU (TYP)
3 1/2" SCHWS
3 1/2" SCHWR
2 1/2" HWS
2 1/2" HWR
3" SCHWR
3" SCHWS
2" HWR
2" HWS
3/4" CONDENSATE
FROM FCU (TYP)
1 1/2" CONDENSATE TO HUB
DRAIN. HUB DRAIN BY PLUMBING.
2ND FLOOR
1 1/2" C
3/4" SCHWS
3/4" SCHWR
3/4" HWS
3/4" HWR
1 1/2" C
3/4" SCHWS
3/4" SCHWR
3/4" HWS
3/4" HWR
2" SCHWR
2" SCHWS
2" HWR
2" HWS
3/4" HWR
3/4" HWS
2" SCHWS
2" SCHWR
3/4" HWS
3/4" HWR
1" HWR
1" HWS
2" SCHWR
2" SCHWS
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
3/4" HWS/R TO FTR.
6TH FLOOR
3" SCHWR
3" SCHWS
2" HWR
2" HWS
KEY PLAN
1 1/2" CONDENSATE TO HUB
DRAIN. HUB DRAIN BY PLUMBING.
A
1 1/2" CONDENSATE TO HUB
DRAIN. HUB DRAIN BY PLUMBING.
1ST FLOOR
3/4" HWS/R TO FTR.
B
1
M-703
MECH. RISER DIAGRAM - P-7
SCALE:
2
M-703
MECH. RISER DIAGRAM - P-8
SCALE:
3
M-703
MECH. RISER DIAGRAM - P-9
SCALE:
4
M-703
MECH. RISER DIAGRAM - P-10
SCALE:
5
M-703
MECH. RISER DIAGRAM - P-11
REVISION
NO.
DESCRIPTION
SCALE:
DATE
AHA PROJECT NUMBER
12/14/2015 11:04:56 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
G1215-004.00
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC RISERS
REVISED
15 DECEMBER 2015
SHEET NO.
M-703
PERMANENT VICTAULIC TYPE HARD CONNECTION
FOR FUTURE TEMPORARY/EMERGENCY CHILLER.
LOCATE ON BUILDING EXTERIOR WALL.
FM
PCHWS TO
FUTURE
CAMPUS LOOP
T
12" PCHWS
ARCHITECT
HKS, INC.
TWO LIVE OAK CENTER
12" PCHWS PIPING WITH HIGH
PERFORMANCE LUG TYPE
BUTTERFLY VALVE, SPOOL, AND
BLIND FLANGE FOR FUTURE
CONNECTION. MINIMIZE DEAD LEG.
CH-1
8" PCHWS
ATLANTA, GA 30326
ASSOCIATE ARCHITECT
MURRAY AND ASSOCIATES ARCHITECTS
12" PCHWR
12" PCHWR
8" PCHWR
3445 PEACHTREE ROAD, NE, SUITE 675
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
MEP ENGINEER
AHA CONSULTING ENGINEERS
CH-2
(FUTURE)
1801 OLD ALABAMA RD, SUITE 125
FUTURE 8" PCHWR
ROSWELL, GA 30076
FUTURE 8" PCHWS
SITE/CIVIL ENGINEER
DERCK & EDSON ASSOCIATES
8" CWS PIPING WITH HIGH
PERFORMANCE LUG TYPE
BUTTERFLY VALVE, SPOOL, AND
BLIND FLANGE FOR FUTURE
CONNECTION. MINIMIZE DEAD LEG.
33 SOUTH BROAD STREET
LITITZ, PA 17543
GEOTECHNICAL ENGINEER
CMT LABORATORIES, INC.
CH-3
(FUTURE)
2701 CAROLEAN INDUSTRIAL DRIVE
FUTURE 8" PCHWR
STAE COLLEGE, PA 16801
FUTURE 8" PCHWS
STRUCTURAL ENGINEER
WBCM
100 STERLING PARKWAY, SUITE 108
MECHANICSBURG, PA 17050
CHILLER MINIMUM
FLOW BYPASS
12" PCHWR
12" PCHWS
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
MANUAL BYPASS
VALVE (NC)
HEX-2
HEX-1
VFD
12” PCHWR
8" PCHWR
8" PCHWR
CWP-1
LEAD
VFD
CWP-2
STANDBY
8" PCHWR
12” PCHWR
8" PCHWR
EXPANSION TANK AND AIR SEPARATOR SHALL BE
LOCATED IN CENTRAL MECHANICAL ROOM. PROVIDE
MAKE-UP WATER, DRAIN CONNECTIONS, AND PIPING.
VFD
FUTURE 8" PCHWR
CWP-3
FUTURE
SYSTEM FILL
AIR VENT
AIR SEPARATOR AS-1
FUTURE 8" PCHWR
PCHWR FROM
FUTURE
CAMPUS LOOP
T
12" PCHWR
8" PCHWR PIPING WITH HIGH
PERFORMANCE LUG TYPE
BUTTERFLY VALVE, SPOOL, AND
BLIND FLANGE FOR FUTURE
CONNECTION. MINIMIZE DEAD LEG.
AUTOMATIC AIR VENT
BUFFER TANK BT-1
DRAIN
EXPANSION
TANK ET-1
1
M-801
DICTRICT CHILLED WATER SCHEMATIC
SCALE: N.T.S.
T
COOLING TOWER
BYPASS
14" CWR
14" CWR
14" CWR PIPING WITH HIGH
PERFORMANCE LUG TYPE
BUTTERFLY VALVE, SPOOL, AND
BLIND FLANGE FOR FUTURE
CONNECTION. MINIMIZE DEAD LEG.
CH-1
8" CWS
14" CWS
14" CWR
8" CWS
14" CWR
FUTURE 8” CWR
(TYPICAL 2)
8” CWR
CH-2
(FUTURE)
FUTURE 8" CWS
FUTURE 14" CWR
FUTURE 8" CWS
KEY PLAN
2 POSITION AUTOMATIC CONTROL
VALVE (TYPICAL INLETS AND OUTLETS)
8" CWS PIPING WITH HIGH
PERFORMANCE LUG TYPE
BUTTERFLY VALVE, SPOOL, AND
BLIND FLANGE FOR FUTURE
CONNECTION. MINIMIZE DEAD LEG.
A
CH-3
(FUTURE)
FUTURE 8" CWS
FUTURE 8" CWS
B
REVISION
NO.
DESCRIPTION
CT-1
HEX-1
14" CWS
CT-2
(FUTURE)
DATE
CT-3
(FUTURE)
14" CWS
VFD
14" CWS
8" CWS
COOLING TOWER DUNNAGE. SEE
STRUCTURAL DRAWINGS.
VFD
12/14/2015 11:04:58 PM
CWP-2
STANDBY
8" CWS
VFD
FUTURE 8" CWS
CWP-3
FUTURE
ROUTE 2” OVERFLOW AND 2” DRAIN
TO FLOOR DRAIN IN CENTRAL PLANT.
AHA PROJECT NUMBER
G1215-004.00
14" CWS
TEMPLATE VERSION: 2.6.8.20141012
8" CWS
PLOT DATE:
VIBRATION ISOLATION.
8" CWS
CWP-1
LEAD
1-1/2” MAKE-UP WATER PIPING
WFS-1
8” CWS
FUTURE 8” CWS
(TYPICAL 2)
14" CWS
FUTURE 8" CWS
DATE
SYSTEM
FILL
03 DECEMBER 2015
ISSUE
FUTURE 14" CWS
CONSTRUCTION
DOCUMENTS
TO FLOOR DRAIN IN
CENTRAL PLANT
T
14" CWS
2
M-801
DICTRICT CONDENSER WATER SCHEMATIC
SCALE: N.T.S.
8" CWS PIPING WITH HIGH
PERFORMANCE LUG TYPE
BUTTERFLY VALVE, SPOOL, AND
BLIND FLANGE FOR FUTURE
CONNECTION. MINIMIZE DEAD LEG.
SHEET TITLE
14" CWS
HVAC
SCHEMATICS
REVISED
15 DECEMBER 2015
SHEET NO.
M-801
VFD
SEE STEAM TO WATER HEAT EXHCHANGER DETAIL
FOR PIPING LAYOUT AND TRIM REQUIRED.
6” HWS
T
HWS TO
BUILDING
HWP-2
STANDBY
FM
6” HWS
6” HWS
ARCHITECT
VFD
HKS, INC.
TWO LIVE OAK CENTER
3445 PEACHTREE ROAD, NE, SUITE 675
6” HWS
HWP-1
LEAD
6” HWS
6” HPS
ATLANTA, GA 30326
HXS-1
ASSOCIATE ARCHITECT
HPS FROM
CAMPUS LOOP
MURRAY AND ASSOCIATES ARCHITECTS
1600 NORTH SECOND STREET
HARRISBURG, PA 17102-2499
6” HPS
MEP ENGINEER
AHA CONSULTING ENGINEERS
1801 OLD ALABAMA RD, SUITE 125
HXS-2
ROSWELL, GA 30076
SITE/CIVIL ENGINEER
LPC TO
CAMPUS LOOP
DERCK & EDSON ASSOCIATES
33 SOUTH BROAD STREET
LITITZ, PA 17543
T
GEOTECHNICAL ENGINEER
HWR FROM
BUILDING
6” HWR
CMT LABORATORIES, INC.
2701 CAROLEAN INDUSTRIAL DRIVE
STAE COLLEGE, PA 16801
STRUCTURAL ENGINEER
WBCM
100 STERLING PARKWAY, SUITE 108
HEATING HOT WATER SCHEMATIC
1
SCALE: N.T.S.
BLOOMSBURG UNIVERSITY
RESIDENCE HALL
& BOOKSTORE
M-802
MECHANICSBURG, PA 17050
VFD
8” SCHWR
T
SCHWR FROM
BUILDING
SCHWP-2
STANDBY
8” SCHWR
PCHWR TO
CAMPUS LOOP
8” SCHWR
VFD
8” SCHWR
SCHWP-1
LEAD
8” SCHWR
8” SCHWR
8” PCHWR
HEX-2
MANUAL BYPASS
VALVE (NC)
MANUAL BYPASS
VALVE (NC)
8” SCHWS
T
SCHWS TO
BUILDING
8” PCHWS
FM
PCHWS FROM
CAMPUS LOOP
8” SCHWS
SECONDARY CHILLED WATER SCHEMATIC
2
M-802
SCALE: N.T.S.
LUZERNE HALL
HX
KEY PLAN
NEW RESIDENCE HALL
LYCOMING HALL
BEN FRANKLIN HALL
A
FROM DISTRICT
CHILLED WATER PLANT
HX
HX
CAPPED VALVES IN SERVICE
TUNNEL. SEE FLOOR PLANS
FOR LOCATION.
B
REVISION
NO.
DESCRIPTION
DATE
ELWELL HALL
HX
12/14/2015 11:04:59 PM
PLOT DATE:
TEMPLATE VERSION: 2.6.8.20141012
3
M-802
DISTRICT CHILLED WATER SITE SCHEMATIC
AHA PROJECT NUMBER
G1215-004.00
SCALE: N.T.S.
DATE
03 DECEMBER 2015
ISSUE
CONSTRUCTION
DOCUMENTS
SHEET TITLE
HVAC
SCHEMATICS
REVISED
15 DECEMBER 2015
SHEET NO.
M-802