__________________________________________________________________________ http://waterheatertimer.org/Intermatic-Defrost-timers-and-manuals.html DTMV40 Time Initiated, Temperature, Pressure or Time Terminated Multi-Voltage Defrost Timers Input Voltage Switch (S2) INSTALLATION Mode Selection Switch (S1) Bracket Mount NEMA 3R Enclosure STARTUP PROCEDURE 1. Determine model to be replaced (Grasslin or Competitors) from table below. Fig. A 2. Set Mode Selection (S1 BLUE DIP Switch – Fig. A) See table below and instructions on page 5. 3. Apply corresponding Terminal Identification and Door labels –see retrofit kit instructions. 4. Set correct input voltage (S2 RED DIP Switch – Fig. B). 5. Follow installation and programming instructions. Fig. B The DTMV40 can be configured for either 120 or 208/240VAC. Locate RED DIP Switch to the right of timer module. For: • 120VAC slide DIP switch UP • 208/240VAC slide DIP switch DOWN Paragon n n n n n n n Precision Mode Selection Wiring Diag. TIME INITIATED, TIME TERMINATED 8045/8046 8041 8043 8047 6045 6041 6043 6047 A A B B Note: For outdoor locations, Raintight, or wet location conduit hubs that comply with requirements of UL 514B (standard for fittings for conduit and outlet boxes) are to be used. 1. Open door and then remove interior protective cover by releasing spring clip on bottom. 2. Remove timer mechanism by releasing spring clip on bottom. 3. Select knockouts to be used. Remove inner 1/2” knockout by inserting a screwdriver in the slot and carefully punch knockout loose. Remove slug. If 3/4” knockout is required, remove the outer ring with pliers after removing the 1/2” knockout. Smooth edges with knife if necessary. 4. Place enclosure in desired mounting location and mark the three mounting holes (refer to diagram). Start by placing set screw on top and attaching enclosure over keyhole; then screw in remaining two screws on bottom. 5. Connect conduit hubs to conduit before connecting the hubs to the enclosure. After inserting hubs into enclosure, carefully tighten hub lock nut. Do not over-torque. 6. Verify voltage selection. 120VAC – position switch UP; 208/240VAC – position switch DOWN (refer to Fig. B). 7. Wire in accordance with National and Local Codes. 8. Grounding: Terminate all ground wires to ground lug on bottom of enclosure. 9. Replace interior protective cover. Interior Protective CAUTION: Do not Cover check circuits by “sparking” wires to terminals. Damage to the defrost timer may result. 1 2 3 4 Step 1 TIME INITIATED, REMOTE TEMPERATURE OR PRESSURE TERMINATED 8145 8141 8143 6145 6141 6143 A A B 5 7 8 Timer Mechanism 6-1/8” TIME INITIATED, PRESSURE TERMINATED n n n n n n n (Separate Pressure Switch Required (see instructions) 8245 8243 8247 6245 6243 6247 Grasslin DT040 DT140 DTMV DTSX A B B 10 11 12 A A A A 5 5 5 5 2-1/2” Ground Lug Step 2 Model Designation DTMV40 TROUBLESHOOTING GUIDE A MODE Models Enclosure Mount DTMV40 24-hour, Outdoor NEMA 3R Enclosure DTQMV40 24-hour w/Battery Backup, Outdoor NEMA 3R Enclosure DTMV40-IM 24-hour, Indoor Metal NEMA 1 Enclosure (See page 1) In Refrigeration Mode Arrow on timer points to current time. Trippers are “IN” Indicates Refrigeration “Green” LED ON DTQMV40-IM 24-hour w/Battery Backup, Indoor NEMA 1 Enclosure Models “1 & F” Make “1 & 3” Break Non-Enclosure Mount F DTMV40-M 24-hour, Mechanism Only DTQMV40-M 24-hour w/Battery Backup, Mechanism Only DTMV40-P 24-hour, Panel Mount TIMER RELEASE RELAY TIMER 3 1 2 4 L1 N L2/N In Defrost Mode TIMER DTQMV40-P 24-hour w/Battery Backup, Panel Mount DTMV40-B 24-hour, Bracket Mount DTQMV40-B 24-hour w/Battery Backup, Bracket Mount “2 & 4” Make X TIMER RELEASE RELAY Arrow on timer points to current time. F 3 1 2 4 L1 N F 3 1 2 TIMER RELEASE RELAY 3 L1 1 2 4 L1 X TIMER RELEASE RELAY TIMER “1 & F” Break “1 & 3” Make PROGRAMMING (Synchronous and Quartz Electromechanical Models) N 4 “Red” LED ON F Trippers are “OUT” Indicates Defrost L2/N TIMER Note: All units with Battery Backup provide up to a week of reserve carryover. X L2/N N X L2/NTIMER RELEASE RELAY TIMER “2 & 4” Break F 3 1 2 4 TIMER N F 3 L1 1 2 4 TIMER RELEASE RELAY X L2/N N X Setting the Time: L1 Turn the minute hand clockwise until the time of day (and AM or PM) on the outer dial is aligned with the triangle marker on the inner dial. L2/N TIMER RELEASE RELAY TIMER DTMV40 TROUBLESHOOTING GUIDE 3 1 3 1 L1 F MODE F TIMER RELEASE RELAY N X B2 (See4 page 1) TIMER 2 4 N L2/N Arrow on timer time. L2/N L1 points to current TIMER Setting Defrost Initiation Time: Move a white tab (tripper) on the outer dial outward at each desired initiation time. For example, to set defrost initiation times at 6:00AM, 11:30AM, 4:30PM and 11:00PM, move the tab adjacent to the “M” in AM on the dial (6:00AM), the tab that lies between 11:30AM and 11:45 AM, the tab between 4:30PM and 4:45PM, and the tab adjacent to the 11:00–11:15PM marks. (See note for 8243/6243 replacement.) Both LED’s ON F 3 1 2 4 F 3 L1 1 2 4 L1 TIMER RELEASE RELAY TIMER TIMER RELEASE RELAY N “1 & F” Make “1 & 3” Break TIMER RELEASE RELAY TIMER RELEASE RELAY 3 1 2 4 TIMER N X F 3 L1 1 2 4 X L2/N N 3 1 “2 & 4” Break L2/N TIMER 8 X F F Trippers are “IN” Indicates Refrigeration L2/N L1 Different defrost durations may be set for each defrost initiation setting. Each white tab (tripper) provides a 15 minute interval. The tabs that set the initiation time provide a minimum of 15 minutes of defrost. For longer defrost duration, move additional tabs (following in time) from the initiation tab. For example, if a 45 minute defrost is to start at 7:00AM, move the tab outward that lies between 7:00 and 7:15 on the AM side of the dial, and the tabs adjacent to 7:15-7:30 and 7:30-7:45. (3 tabs moved outward). The defrost will initiate at 7:00AM and time terminate at 7:45AM (if temperature termination does not occur first.) X L2/N N TIMER Setting Maximum Defrost Duration: For electronic models, refer to separate programming instructions. X In Refrigeration Mode DO NOT ROTATE MINUTE HAND COUNTER-CLOCKWISE 2 TIMER RELEASE RELAY TIMER RELEASE RELAY 4 TIMER N In Defrost Mode X Arrow 1 2 to current 3 timer 4 Ntime. X L1points L2/N F on L1 L2/N TIMER TIMER RELEASE RELAY Trippers are “OUT” Indicates Defrost Both LED’s OFF F 3 1 2 4 L1 N L2/N “1 & F” Break “1 & 3” Make TIMER F 3 1 L1 X 2 4 TIMER RELEASE RELAY N “2 & 4” Make X L2/N Note: It is necessary to apply power across terminals 1&N in order to perform electrical test. 7 A M 2 TYPICAL WIRING DIAGRAMS All switch positions are shown in refrigeration cycle operation, and change position upon initiation of a defrost. DTMV40 Time/Time –Electric DefrostDefrost WiringWiring Diagram DTMV40 Time/Time–Electric DefrostDefrost WiringWiring Diagram DTMV40 Time/Time –Electric Diagram DTMV40 Time/Time–Hot Gas Defrost WiringWiring Diagram DTMV40 Time/Time –Electric Defrost Wiring Diagram DTMV40 Time/Time–Electric Diagram DTMV40 Time/Time–Hot GasGas Defrost Diagram DTMV40 Time/Time–Electric Defrost Wiring Diagram 8045 Replacement DTMV40 Time/Time–Hot Defrost Wiring Diagram DTMV40 Time/Time –Electric Defrost Wiring Diagram 8041 Replacement 8045 Replacement 8043 Replacement 8045 Replacement DTMV40 Time/Time–Electric Defrost Wiring Diagram DTMV40 Time/Time–Hot Gas Defrost Wiring Diagram 8041 Replacement 80438043 Replacement 8041 Replacement Mode A with 8045 Label Applied Replacement DTMV40 Time/Time –Electric Defrost Wiring Diagram Replacement 8045 Mode A with 8041 Label Applied DTMV40 Time/Time –Electric Defrost Wiring Diagram Mode A with 80458045 Label Applied Mode B with B 8043 Label Applied DTMV40 Time/Time–Electric Defrost Wiring Diagram Mode A with Label Applied 8041 Replacement DTMV40 Time/Time–Hot Gas Defrost Wiring Diagram Time/Time–Electric Defrost Wiring Diagram DTMV40 8043 Replacement Mode A with 8041 Label Applied DTMV40 Time/Time–Hot Gas Defrost Wiring Diagram Mode with 8043 Label Applied Time/Time –Electric DTMV40 Mode A with 8041 Label Applied Mode B with 8043 Label Applied 8045 Replacement DTMV40 Time/Time–Electric Wiring Diagram Mode A with 8045 LabelDefrost AppliedWiring Diagram DTMV40 Time/Time–Hot Gas Defrost 8045 Replacement 8041 A withReplacement 8041 LabelDefrost Applied 8041 Mode Replacement B8043 with Replacement 8043 Label Applied Wiring Diagram TIMER Replacement 8043Mode TIMER 8045 Replacement DTMV40 Time/Time –Electric Defrost WiringDiagram Diagram TIMER TIMER Mode with 8045 Label Applied TIMER TIMER RELEASE 8041 Replacement DTMV40 Time/Time –Electric Defrost RELEASE Wiring DTMV40 Time/Time–Electric Defrost Wiring Diagram 8043 Replacement TIMER 8045ALabel Applied Mode A with TIMER DTMV40 Time/Time–Hot GasDefrost DefrostWiring Wiring Diagram RELEASE Mode A with 8041 Label Applied TIMER Diagram Time/Time–Electric Defrost Wiring DTMV40 B with 8043 Label Applied Mode RELEASE DTMV40 Time/Time–Hot Gas Diagram RELAY RELEASE A with 8041 Label Applied Mode RELAY TIMER RELEASE Mode B with 8043 Label Applied RELEASE RELEASE RELAY Mode A with8045 Label Applied TIMER 8045Replacement Replacement RELEASE TIMER RELAYRELAY TIMERRELAYRELAY TIMERTIMER Mode A with Label Applied TIMER RELAY 8041 Replacement TIMER Mode B with 8043 Label Applied TIMER Replacement RELAY RELEASE TIMER RELEASE 8041 Replacement 8043 Replacement RELEASE TIMER TIMER RELAY TIMER ModeAAwith with8045 8045Label Label Applied RELAY TIMER TIMER TIMER RELAY TIMER TIMER TIMER Applied Mode ModeAAwith with8041 8041Label Label TIMERApplied RELEASE ModeBBwith with8043 8043Label Label Applied RELEASE RELEASE Mode Applied RELEASE RELEASE TIMER TIMER Mode Applied TIMER RELEASE DTMV40 Time/Time –Electric Defrost Wiring Diagram RELAY TIMER RELAY TIMER 8045 RELAY RELAY RELAY TIMER 8041 TIMER RELEASE DTMV40 Time/Time–Electric Defrost Wiring Diagram RELEASE RELAY Diagram TIMER RELEASE 2–Electric 8043 8045 8045 4 X F Replacement 1-N 8041 8041 DTMV40 Time/Time–Hot Gas Defrost Wiring 2 N TIMER Time/Time –Electric Defrost Wiring Diagram RELAY 4 X 3 1 LABEL RELAY TIMER LABEL TIMER TIM DTMV40 Time/Time Defrost Wiring Diagram TIMER 2 8043 TIME RELAY 3 8045 TIMER 4 X 1 2 F3DTMV40 4 1-N DTMV40 Time/Time–Electric Defrost Wiring Diagram 3 N F LABEL TIMER N N 1Time/Time–Electric 2 804 3 4 4 Wiring X XDiagram 4 X TIMER Defrost Diagram LABEL F8045 Replacement 1-N Replacement 8041DTMV40 RELE 1 3 3 2 2Defrost Time/Time–Hot Defrost Wiring Diagram RELEASE TIMER 1 1 Gas 2 8043DTMV40 Replacement 4 4Gas TIMER2 3 Time/Time–Hot 8045 LABEL LABEL FDTMV40 NWiring LABEL 8041 RELEASE LABEL RELEA 3Replacement F 8043 N LAB RE 2 8043 3Replacement RELAY X TIMER 4 RELEASE TIMER RELEASE 8045 1-N THERMOSTAT 2Applied N A with Mode F A with 8045 Label Applied RELAY 4 X TIMER 3Label TIMER LABEL 1 8041 8041 Replacement LABEL RELA RELAY Replacement 8041 1 2 RELAY 8041 THERMOSTAT 4 Mode 3 F N LABEL 8043 Replacement 8045 L1 B with 8043 Label Applied Mode TIMER 8045 L1 8041 2 8043 Label 3 A 2with 4 XLABEL8045 TIMER THERMOSTAT F Mode 1-N8045 L1 THERMOSTAT 2THERMOSTAT 8043 Mode with 8045 Label Applied 3 48041 4AppliedXLABEL 4 4 XApplied 1 2A with LABEL THERMOSTAT LABEL F F L13 L1 N NL11L1NMode Label Mode X 8041 B with 1 8043 2 L1 L1 F 1Mode NLABEL Label Applied LABEL B3with Applied 2 24Label 3 3Mode F F N Applied COMPRESSOR 2THERMOSTAT 8043 3 1-NA1-N FAN X THERMOSTAT 2 SOLENOID 4OR VALVE X L1 1 3 3A with 8041 LABEL COMPRESSOR LABEL TIMER TIMER L1 COMPRESSOR FAN FAN 1 48043 4 Label TIMER N RELEASE LABEL MOTORRELEASE COMPRESSOR OR COMPRESSOR 8045 FAN OR 8041L1 HOT COMPRESSOR OR MOTOR RELEASE 8045 SOLENOID VALVE OR THERMOSTAT 2 8041 3 OR 4 X TIMER SOLENOID VALVE MOTOR L1 THERMOSTAT DEFROST F 1-N LINE OR RELAY HOT HOT CONNECT ACROSS COMPRESSOR TIMER TIMER DEFROST RELAY 4 4 TIMERXX TIMER L1FAN FAN TIMER 1 THERMOSTAT LABEL TIMER SOLENOID VALVE L1 LABEL FAN 2MOTOR 3CONTACTOR XRELEASE OR 1-N SOLENOID VALVE GAS RELAY 4 F THERMOSTAT TIMER L1 CONTACTOR RELEAS NN 1DEFROST 22ORCONTACTOR COMPRESSOR 33 L1 VALVE F GAS33COMPRESSOR SOLENOID VALVE LABEL LINE HEATER LABEL ORCOIL OR DEFROST RELEASE RELEASE L1 THERMOSTAT COIL OR CONNECT ACROSS LINE DEFROST 11 CONNECT 22 NN RELEASE HEATERDEFROST 44 ACROSS CONTACTOR COIL L1 THERMOSTAT FGAS L OR TIMER RELEASE OR SOLENOID VALVE L1 HEATER HOT VALVE FAN CONTACTOR COIL COIL RELAY RELAY COMPRESSOR COIL RELAY RELAY HEATER TIMER FANTIMER HEATER SOLENOID VALVE L1 CONTACTOR COMPRESSOR OR RELAY RELAY TIMER TIMER HEATER COMPRESSOR DEFROST FAN LINE VALVE DEFROST OR COMPRESSOR COMPRESSOR OR COMPRESSOR ACROSS CONNECT THERMOSTAT TIMER GAS OR CONTACTORSOLENOID COIL MOTOR ORFAN THERMOSTAT TIMER COMPRESSOR VALVE MOTOR L1 THERMOSTAT HEATER OR HOT FAN CONTACTOR COIL THERMOSTAT L1 SOLENOID VALVE HEATER THERMOSTAT COMPRESSOR SOLENOID VALVE HOT FAN VALVE L1 THERMOSTAT THERMOSTAT OR OR COMPRESSOR DEFROST L1 L1 SOLENOID VALVE LINE L2 DEFROST SOLENOID OR MOTOR DEFROST L2 OR L2 LINE CONNECT ACROSS 8045 OR GAS DEFROST VALVE CONTACTOR COIL L1 8041 CONNECT ACROSS HOT FAN OR HEATER THERMOSTAT HEATER L2 L1 L2 CONTACTOR COIL OR CONTACTOR COIL THERMOSTAT HEATER COMPRESSOR COMPRESSOR OR OR VALVE SOLENOID SOLENOID ORVALVE OR CONTACTOR COIL CONTACTOR COIL 8041 8041 LABEL LABEL L2 L1 LINE LINE L2F LINE HEATER 2 4 X LABEL FAN N 32 24 4X X 1 3DEFROST N HEATER FAN1 DEFROST L21L2HEATER 3 DEFROST L2 LINE LINE LINE LINE LINE LINE N 8045 8045 LABEL LABEL COMPRESSOR OR OR VALVE SOLENOID SOLENOID ORVALVE OR CONTACTOR COIL CONTACTOR COIL GAS L2VALVE L2GAS L2 THERMOSTAT 8043 COMPRESSOR 1VALVE COMPRESSOR 2ACROSS 4CONNECT 3VALVE N 1–4 LABEL HOT THERMOSTAT COMPRESSOR Bridge Between HOT 1 4Bridge 2 N 1–4 4Bridge 3THERMOSTAT N1–4 F NOTE: 1 2 ACROSS CONNECT GAS 3Remove FNOTE: Remove Between THERMOSTAT NOTE: Remove Between CONNECT ACROSS GAS VALVE LINE LINE OR CONTACTOR COIL LINE FAN FANLABEL MOTOR X F LINE 1-N 2 2 4 4 X MOTOR 3 3 1-N F HEATER DEFROST DEFROST LINE L2 3 33 333 3 3 3 3 33 LINE LINE L2 L1 L23L2 HEATER VALVE 2SOLENOID CONTACTORX COIL 1-N CONTACTOR HEATER DEFROST COIL 4 COMPRESSOR LINE L2 LINE F LINE LINE 2 22 222 2 2 2 2 22 LINE 1 11 111 1 1 1 1 11 8043 80 LABEL LA L2 L2Remove NOTE: Bridge Between 1-N –2 Remove Bridge Between Remove Bridge Between 1-N –21-N –2 *See NoteNOTE: 2 NOTE: *See*See NoteNote 2 2 3 L2 LINE 120V 120V 240V 120V 120V 120V 120V 120V 240V 240V LINE LINE LINE LINE LINE LINE LINE LINE LINE LINE LINE LINE LINE LINE LINE LINE LINE LINE L2 L2 240V 240V 240V 240V 120V 240V120V 240V 240V 240V LINE 1212 12 1212 12 12 12 12 12 1212 LINE L2 LINE L2 LINE LINE LINE LINE LINE LINE 111111 11 11 11 1111 11 11 1111 LINE LINE LINE 9 99 999 9 9 9 9 99 LINE LINE LINE LINE LINE LINE LINE LINE LINE 120V LINE LINE LINE LINE LINE LINE LINE 120V 120V 240V 6 66 666 6 6 6 6 66 5 55 555 5 5 5 5 55 1010 10 10 10 10 10 10 10 10 1010 LINE L2 LINE THERMOSTAT THERMOSTAT COMPRESSOR OR SOLENOID VALVE COMPRESSOR COMPRESSOROR OR OR CONTACTOR COIL SOLENOID VALVE SOLENOID VALVE OR DEFROST OR DEFROST CONTACTOR COIL CONTACTOR COIL LINE L2 L2 DEFROST FAN FAN HEATER LINE LINE L1 L1 FAN 8 88 888 8 8 8 8 88 LINE LINE LINE LINE LINE 7 77 777 7 7 7 7 77 LINE L2 LINE LINE LINE LINE LINE LINE 4 44 444 4 4 4 4 44 THERMOSTAT THERMOSTAT FAN COMPRESSOR MOTOR OR FAN SOLENOID VALVE COMPRESSORFAN COMPRESSOROR OR MOTORMOTOR OR SOLENOID VALVE CONTACTOR COIL SOLENOID DEFROST VALVE DEFROST OR OR HEATER CONTACTOR COIL HEATER CONTACTOR COIL LINE L2 L2 DEFROST HEATER LINE LINE LINE L1 L1 LINE VALVE Remove COMPRESSOR Between 1–4 COMPRESSOR THERMOSTAT THERMOSTAT Bridge Between NOTE: Bridge L1 L1 NOTE: NOTE: Remove 1–4 Remove Bridge Between 1–4 L2 HOT L2 NOTE: Remove Bridge Between 1–4 CONNECT ACROSS GAS HOT HOT VALVE COMPRESSOR NOTE:CONNECT Remove Bridge Between 1–4 ACROSS CONNECT Time/Time–Electric DefrostDefrost WiringWiring Diagram DTMV40 DTMV40 Time/Temp.–Electric Defrost Wiring Diagram ACROSS GAS GAS NOTE: Remove Bridge Between 1–4 HEATER Defrost Wiring Diagram DTMV40 Time/Time–Electric Diagram DTMV40 Time/Temp.–Electric THERMOSTAT DTMV40 Defrost Wiring Diagram VALVE HEATER COMPRESSOR DTMV40 Time/Time–Electric Defrost Wiring Diagram DTMV40 Time/Temp.–Electric Defrost Wiring Diagra VALVETime/Temp.–Electric COMPRESSOR DTMV40 Time/Temp.–Electric Defrost Wiring Diagram DTMV40 Time/Temp.–Electric Defrost Wiring Diagram 8047 Replacement–Double Pole Switching 120V Fan & Fan Defrost Heater; 240V Compressor THERMOSTAT L2 DTMV40 Time/Time–Electric Defrost Wiring Diagram L2 L2 DTMV40 Time/Temp.–Electric Defrost Wiring Diagram THERMOSTAT 8047 Replacement–Double Pole Switching 8145 Replacement 120V & Defrost Heater; 240V Compressor 8047 Replacement–Double Pole Switching 120V Fan & Defrost Heater; 240V Compressor DTMV40 Time/Temp.–Electric Defrost Wiring Diagram 81458145 Replacement L2 Replacement Mode B with 8047 Label Applied L2 L2 Mode A No Label Required L2 DTMV40 Time/Time–Electric Defrost Wiring Diagram L2 DTMV40 Time/Temp.–Electric Defrost Wiring Diagram L2 8047 Replacement–Double Pole Switching 120V FanMode &ADefrost Heater; 240V Compressor DTMV40 Time/Time–Electric Defrost Wiring Diagram B with 8047 Label Applied Mode DTMV40 Time/Temp.–Electric Defrost Wiring Diagram Mode A - NoALabel Required Mode - Bridge No Required DTMV40 Time/Temp.–Electric Defrost Wiring Diagram Mode B with 8047 Label Applied A - Label No Label Required 8145 Replacement NOTE: Remove Between 1–4 DTMV40 Time/Temp.–Electric Wiring Diagram Mode - No Required DTMV40 Time/Time–Electric Defrost Wiring DTMV40 Time/Temp.–Electric Defrost Wiring Diagram A - Label No Defrost Label Required Mode 8047 Replacement–Double PoleDiagram Switching Fan & Required Defrost Heater; 240V Compressor Mode B with 8047 Label Applied DTMV40 Time/Temp.–Electric Defrost Wiring Diagram TIMER A120V - NoNOTE: Label 8047 Replacement–Double Pole Switching 120VMode Fan & Defrost Heater; 240V Compressor Remove Bridge Between 8145 A - NoReplacement Label Required NOTE: Remove Bridge Between TIMER 1–4 1–4 TIMER Replacement 8145 Mode RELEASE 8047 Replacement–Double Pole Applied Switching TIMER DTMV40 Time/Time–Electric DefrostWiring Wiring Diagram 120V Fan & Defrost Heater; 240V Compressor DTMV40 Time/Temp.–Electric Defrost Wiring Dia TIMER RELEASE Mode B with 8047 Label RELEASE TIMER DTMV40 Time/Time–Electric Defrost Diagram RELAY Mode A No Label Required TIMER Diag DTMV40 Time/Temp.–Electric Defrost Wiring 8145 Replacement RELEASE DTMV40 Time/Temp.–Electric DefrostTIMER WiringDiagram Diagram 120V Mode B with 8047 Label Applied Mode A No Label Required RELEASE A No Label Required Mode TIMERRELAYRELAY RELAY DTMV40 Time/Temp.–Electric Defrost Wiring RELEASE 120V RELEASE Mode A No Label Required TIMER TIMERHeater; Mode B with8047 Label Applied TIMER Pole 120V 8047Replacement–Double Replacement–Double PoleSwitching Switching LabelFan Required Mode A - No120V TIMER 120V Fan Defrost 240V RELAYCompress RELEASE RELAY RELEASE RELAY TIMER RELEASE &&Defrost Heater; 240V Compresso Mode A - No8145 LabelReplacement Required TIMER TIMER Replacement 8145 TIMERTIMERRELAY TIMER TIMER RELEASE TIMER RELAYRELAY 120V TIMER TIMER TIMER RELEASE ModeBBwith with8047 8047Label LabelApplied Applied TIMER RELEASE ModeAA- -No NoLabel Label Required TIMERRELAY TIMER TIMER RELEASE Mode Mode Required RELEASE NoLabel LabelRequired Required ModeAA- -No TIMER RELAY TIMER 120V RELEASE TIMER RELAY RELAY TIMER Mode RELEASE 120V Wiring RELAY DTMV40 Time/Time–Electric Defrost Wiring Diagram RELEASE DTMV40 Time/Temp.–Electric Defrost Diagram 8047 RELAY TIMER RELEASE TIMER RELAY TIMER TIMER DTMV40 Time/Temp.–Electric Defrost Wiring Diagram 120V NRELEASE 2 TIMER RELAY 4 F 3 TIMERDefrost TIMER X 1 8047 TIMER 3 2 4 2 1 N LABEL RELAY TIMER RELAY 8047 DTMV40 Time/Time–Electric Wiring Diagram RELEASE DTMV40 Time/Temp.–Electric Defrost Wiring Diagr TIMER 2 F 3 4 RELEASE N XTIMER 1 TIMER DTMV40 Time/Time–Electric Defrost Wiring Diagram 1 2 3 Time/Temp.–Electric Defrost 8047 Replacement–Double 4 Switching 2 2 2 2 8047 LABELRELEASE N N 1 1 120VDTMV40 Fan F & Defrost F DTMV40 4 Wiring 3 Heater; X N Diagram 1 240V2Compressor Diagram 3Pole 4 TIMER LABEL RELEASE Time/Temp.–Electric Wiring TIMER RELAY 3 Time/Temp.–Electric 8145 Replacement 4NDefrost NXWiring F3DTMV40 XTIMER 120V 2Defrost 3 1 1 24 TIMER 4RELAY NDiagram RELEASE F8145 X RELAY 2& THERMOSTAT 8047 Replacement–Double Switching RELAY F A -3120V 4 Heater; 120V N 240V X 1 Required RELEASE 120V Fan Defrost Compressor 3 Applied 2 PolePole 4 2Switching 18047 LABEL 8047 Replacement–Double TIMER Fan & Defrost Heater; 240V Compressor ModeNB with Label RELAY No Label Mode RELEASE TIMER Replacement 1 2 3 RELAY TIMER 4 N TIMER L1 8047 F X 8145 Replacement TIMER Mode A No Label Required THERMOSTAT L1 8047 RELAY TIMER THERMOSTAT 2 Required 4 X N TERMINATION 3 - No X 1No 4Label B with 3 8047 2 2LABEL8047 LABEL L1 L13 Mode N 2A -2 F L1F L13 3FMode 1 Mode Mode B1 Applied 3Mode 2 24Label 2 Applied NL1N L11 1 Label Required 1 Label 2Required A THERMOSTAT - No THERMOSTAT X THERMOSTAT DEFROST TIMER A3 Required N 4 X N TERMINATION 4 NN F F L13F 1Mode X THERMOSTATTERMINAT 1ADEFROST 3with48047 4 Label 2 RELEASE LABEL L1 TER L1 SOLENOID FAN TIMER 1- No2Label 2 4 DEFROST 4THERMOSTAT THERMOS FAN N TERMINATION X W/FAN DELAY THERMOSTAT FANHEATER 8047 L1 TH THERMOSTAT TERMINATION COMPRESSOR RELEASE VALVE SOLENOID THERMOSTAT TIMER RELAY HEATER TIMER TIMER8047 FAN TERMINATION SOLENOID FAN 120V THERMOSTAT 2 HEATER MOTOR W/FANX THERMOSTAT 4 F 3 TIMER L1 N 1 OR DEFROST FAN RELEASE COMPRESSOR DEFROST W/FAN DELAY N VALVE VALVE L1 LABEL W/F THERMOSTAT TIMER L1 OR RELEASE COMPRESSOR 4 RELEASE F 3 THERMOSTAT XDEL NRELEASE 1 TIMER 2 RELAY L1 THERMOSTAT TERMINATION MOTOR 33 TIMER 44 22 22 RELEASE SOLENOID VALVE 11DEFROST N OR LABEL 1THERMOSTAT 2VALVE 3 COMPRESSOR FAN 4 N W/FANX DELAY TIMER MOTOR SOLENOID DEFROST F OR LINE L1 OR CONTACTOR HEATER RELAY 4 HEATERDEFROST W/FAN DELAY TIMER TIMER RELAY RELAY TERMIN L1 THERMOSTAT L1 FAN 1 2 OR 3 N OR SOLENOID VALVE 120V 120V W/FAN DELAY F X L1 THERMOSTAT TERMINATION RELAY DEFROST RELEASE SOLENOID VALVE LINE DEFROST CONTACTOR HEATER RELAY HEATER TIMER DEFROST RELEASE CONTACTOR LINE DEFROST CONTACTOR MOTOR THERM TIMER TERMINATION HEATER L1 THERMOSTAT ORCOIL OR DEFROST TIMER OR W/FAN DELAY FAN THERMOSTAT RELAY TERMINATION TERMINATION TIMER TIMER OR SOLENOID N HEATER THERMOSTAT HEATER CONTACTOR COIL FAN N L1HEATER RELAY TIMER SOLENOID FAN HEATER SOLENOID VALVE DEFROST CONTACTOR COIL W/FAN THERMOSTAT THERMOSTAT DEFROST FAN COMPRESSOR LINE CONTACTOR VALVE L1 W/FAN DELAY HEATER THERMOSTAT THERMOSTAT TERMINATION COMPRESSOR N OR L1 L2 VALVE FAN MOTOR SOLENOID L1 DEFROST ORFAN DEFROST HEATER COMPRESSOR W/FAN DELAYL2 MOTOR L1 HEATER OR THERMOSTAT OR CONTACTORSOLENOID COIL THERMOSTAT W/FANTHERMOSTAT DELAY 8047 COMPRESSOR VALVE L1 VALVE COMPRESSOR L21 CONTACTOR DEFROST SOLENOID VALVE LINE DEFROST 2OR L2 4COMPRESSOR FNL2 L23 HEATER MOTOR X W/FAN DELAY N 1 FANSOLENOID 3SOLENOID OR NOTE: Move Bridge to 2–2 DEFROST LINE L2 DEFROST 2to 2–2 4 OR 22–2 NORL2 VALVE OR CONTACTOR LABEL W/FAN DELAY TERMINATION HEATER DEFROST OR OR OR HEATER VALVE 1 CONTACTOR 2SOLENOID TERMINATION HEATER NOTE: Move Bridge 3L2HEATER L2 OR SOLENOID 4CONTACTOR NCOIL X MOTOR VALVE VALVE FAN 8047 8047 F LINE DEFROST FANCONTACTOR COMPRESSOR NOTE: Move Bridge to COIL SOLENOID CONTACTOR THERMOSTAT 2 SOLENOID HEATER 4 3 COMPRESSOR HEATER NF F 3 VALVE 1 3 OR 2 4 L2 FAN COIL1 2 N OR 2OR LABEL 4 N NX X 1 N THERMOSTAT 3 NOTE: OR 2 4 2 1 COMPRESSOR N LABEL VALVE OR HEATER DEFROST W/FAN DELAY CONTACTOR COIL 1 2 L2 3 COIL COIL 4 MOTORN X X W/FAN OR Move BridgeDEFROST to 2–2 SOLENOIDCONTACTOR VALVE 1DEFROST 2 SOLENOID L2 NOTE: NOTE: 3 OR CONTACTOR 4ORVALVE F FLINE SOLENOID VALVE N THERMOSTAT COMPRESSOR L2 OR NOTE: DEFROST LINE CONTACTOR COMPRESSOR OR HEATER L1 DELAY N L2 L1 L2 OR L2 CONTACTOR HEATERto 2–2 OR CONTACTOR COIL L2 OR HEATER NOTE: Move Bridge CONTACTOR COIL THERMOSTAT NOTE: COMPRESSOR SOLENOID VALVE L2 L1 THERMOSTAT NOTE: Move Bridge to 2–2 THERMOSTAT HEATER SOLENOID VALVE L2 TERMINATION L1 CONTACTOR COIL N OR L1 OR L1 DEFROST OR N CONTACTOR L2 L1 NOTE: Bridge to 2–2 THERMOSTAT SOLENOID VALVE CONTACTOR COIL TERMINATION L1 THERMOSTAT L2 Move FAN NOTE: COIL SOLENOID T L1 THERMOSTAT COMPRESSOR NOTE: OR FAN L2 W/FAN DELAY TERMINAT L2HEATERFAN DEFAULT (Out of the Box) DEFROST THERMOSTAT COMPRESSOR COMPRESSOR VALVE OR DEFROST CONTACTOR COIL T TERMINATION L2 L2 NOTE: MOTOR THERMOS TERMINATION SOLENOID OR DEFROST OR VALVE NOTE: Move Bridge to 2–2 W/FAN DELAY SOLENOID HEATER FAN OR SOLENOID FAN L2 HEATER W THERMOSTAT NOTE: Move Bridge to 2–2 SOLENOID VALVE SOLENOID COMPRESSORFAN VALVE ORVALVE W/FAN DE THERMOSTAT DEFROST LINE COMPRESSOROR CONTACTOR VALVE HEATER MOTOR OR DEFROST OR CONTACTOR COIL W/FAN DELAY MOTOR OR NOTE: OR DEFROST W/FAN DELAY HEATER OR CONTACTOR COIL SOLENOID VALVE CONTACTOR COIL DEFROST NOTE: SOLENOID VALVE CONTACTOR HEATER N DEFROST LINE LINE OR CONTACTOR DTMV40 Time/Temp.–Electric Defrost WiringWiring Diagram HEATER DTMV40 Time/Temp.–Hot Gas Defrost Wiring Diagram OR HEATER CONTACTOR COIL Time/Temp.–Electric Defrost Diagram HEATER L2 DTMV40 CONTACTOR COIL DTMV40 Time/Temp.–Hot Gas Defrost Wiring Diagram DTMV40 Time/Temp.–Electric Defrost Wiring Diagram N COMPRESSOR DTMV40 Time/Temp.–Hot Gas Defrost Wiring Diagram N Time/Temp.–Electric L2 8141 NOTE: Replacement OR 8143 DTMV40 Defrost WiringWiring Diagram L2 Replacement L2 DTMV40 Time/Temp.–Electric Defrost Wiring Diagram Move Bridge to 2–2 DTMV40 Time/Temp.–Hot Gas Defrost Wiring Diagram SOLENOID VALVE COMPRESSOR 8141 Replacement L2 8143 Replacement 8141 Replacement COMPRESSOROR L2DTMV40 Time/T emp.–Electric Defrost Diagram 8143 Replacement OR Time/T emp.–Electric Defrost Wiring Diagram L2 DTMV40 OR L2Label Applied Mode A with Label Applied NOTE: Move Bridge to Wiring 2–2 Diagram DTMV40 CONTACTOR COIL Mode B withL2 8143 SOLENOID VALVE DTMV40 Time/Temp.–Electric Defrost 8143 Replacement–Double Pole Switching 8141 Replacement NOTE: NOTE: Move Bridge to Diagram 2–2 DTMV40 Time/Temp.–Hot Gas Defrost Wiring Diagram SOLENOID VALVE DTMV40 Time/Temp.–Electric Defrost Wiring 8143 Replacement Mode A8141 with 8141 Label Applied DTMV40 Time/T emp.–Electric Defrost Wiring Diagram Time/Temp.–Hot Gas8143 Defrost Wiring Diagram OR Pole Mode B with 8143 Label Applied Mode A with 8141 Label Applied 8143 Replacement–Double Switching OR Mode B with Label Applied 8143 Replacement–Double CONTACTOR COIL Pole Switching DTMV40 Time/Temp.–Electric Defrost Wiring Diagram DTMV40 Time/Temp.–Hot Gas Defrost Wiring Diagram NOTE: CONTACTOR COIL 8141 Replacement NOTE: Mode B with 8143 Label Applied Mode A with 8141 Label Applied TIMER 8143 8141 Replacement DTMV40 Time/T emp.–Electric Defrost Wiring Diagram B withReplacement 8143 Label Applied TIMER 8143 Replacement–Double Pole Switching 8143 Mode Replacement DTMV40 Time/T emp.–Electric Defrost Wiring Diagram Mode B with 8143 Label Applied Mode B with 8143 Label Wiring AppliedDiagram TIMER RELEASE 8141 Replacement DTMV40 Time/Temp.–Electric Defrost Wiring Diagram 8143 Replacement TIMER TIMER DTMV40 Time/Temp.–Hot GasDefrost Defrost Wiring Diagram DTMV40 Time/T Defrost RELEASE Mode with 8141 Label Applied TIMER Diagram DTMV40 Time/Temp.–Electric Defrost Wiring RELEASE Mode with 8143 Label Applied DTMV40 Time/Temp.–Hot Gas Wiring Diagram RELAY Mode A with 8141ALabel Applied Replacement–Double Pole Switching RELEASE B8143 withemp.–Electric 8143 LabelPole Applied Mode B with 8143BLabel Applied TIMER 8143Mode Replacement–Double Switching RELAY RELEASE TIMER RELEASE TIMER RELAYRELAY Mode A with8141 Label Applied TIMERRELAY TIMER 8141Replacement Replacement RELEASE TIMERTIMER Mode B with8143 Label Applied TIMER 8143Replacement Replacement 8143 Replacement–Double Pole Applied Switching TIME RELAY DTMV40 Time/T emp.–Electric Defrost Wiring Diagr RELEASE RELEASE RELEASE Mode BLabel with 8143 Label TIMERTIMER DTMV40 Time/T emp.–Electric Defrost Wiring Diagra RELAY RELEA Mode B with 8143 Applied RELAY TIMER TIMER RELAYRELA TIMER RELAY TIMER TIMER ModeAAwith with8141 8141Label Label TIMERApplied RELEASE Mode B with 8143 Label Applied Mode B with Label Applied 8143 Replacement–Double Pole Switching TIMER RELEASE RELEASE Mode Applied RELEASE TIMER TIMER Mode B with 8143 Label Applied 8143 Replacement–Double Pole Switching RELEASE RELAY TIMER TIMER RELAY TIMER RELAY RELAY TIMER TIMER 8141 RELEASE DTMV40 Diagram TIMER RELAY DTMV40 Time/Temp.–Hot Gas Defrost Wiring Diagram TIMER Wiring RELEASE 8143 RELEASE ModeBBwith with8143 8143Label Label Applied 8141 8141 N Time/Temp.–Electric 2 Defrost TIMER RELAY 3 Time/Temp.–Electric LABEL RELEASE TIMERX TIMER TIMER TIMER 8143 TIMER Mode Applied RELAY Defrost Diagram 1 DTMV40 TIMER N1 DTMV40 RELAY 8143 X Time/Temp.–Hot Defrost Diagram LABEL 4X 4 Wiring Diagram N 1Time/Temp.–Electric 2 Defrost RELAY 8141 DTMV40 Replacement XWiring RELEASE 1 3 3 24 TIMER Time/Temp.–Hot Defrost Diagram RELEASE TIMER 34 3 42Gas 2 8143 Replacement TIMER2 Wiring 1NDTMV40 X Wiring N3 N LABEL DTMV40 Time/Temp.–Electric Defrost Wiring Diagram 8141 RELEASE LABEL 4 Gas RELEASE 1 8143 X LABEL 8143 LABEL RELAY 8143 RELAY TIMER 2 N RELAY 3 X TIMER XDefrost TIMER RELEASE 1 LABEL 4 8143 TI8T 8141 Replacement RELAY 3 2 4 1 Replacement LABEL N 8141 Replacement DTMV40 Time/T emp.–Electric Wiring Diagram 3 2 RELAY THERMOSTAT 4 A with 8141 Label Applied THERMOSTAT TIMER 1 X LABEL N 8143 Replacement RE Mode B with 8143 Label Applied 8141 DTMV40 Time/T emp.–Electric Defrost Wiring Diagram TIMER 3 8143 Replacement–Double Pole Switching 2 4 1 L1 Mode X N LABEL TIMER 8141 3 4 2 REL 8143 1 N LA X TIMER THERMOSTAT 2Label R 8143 8143 3 48141 1 2A with LABEL L1 4AppliedXLABEL N NL11L1NMode Mode X 8141 B4with Applied RE 3 8143 2 4Label L1 N 1 3Mode XLABEL Label Applied 8143 Replacement–Double Pole Switching LABEL 3 BN with 8143 Label Applied 2 2 4 L1 Mode 1 1 X TERMINATION COMPRESSOR X N LABEL 8143 Replacement–Double Pole Switching 8143 Mode B with 8143 Label Applied THERMOSTAT 2 SOLENOID TIMER X 1 3 3A with 8141 LABEL TERMINATION 4OR VALVE TIMER L1 TERMINATION COMPRESSOR 8143 3 2 TIMER 4 L1 THERMOSTAT TIMER 1 X LABEL TERMINATION N TERMINATION COMPRESSOR 8143 L1 OR RELEASE 8141 Mode B with 8143 Label Applied 3 HOT FAN 4 2 1 THERMOSTAT L1 THERMOSTAT N LABEL X OR TERMINATION RELEASE Mode B with 8143 Label Applied 3 W/FAN DELAY THERMOSTAT 2 4 1 TIMER 8143 8141 L1 THERMOSTAT X N LABEL8143 OR SOLENOID VALVE VALVE THERMOSTAT 2 N RELAY HOT TERMINATION COMPRESSOR TIMER DEFROST 3 X TIMER L1FAN FAN THERMOSTAT 1 LABEL 4 SOLENOID 8143 ACROSS CONNECT TIMER GAS W/FAN DELAY DELAY RELAY 4 TIMER TIMER CONTACTOR COIL THERMOSTAT OR RELEASE N 2VALVE 3 3 SOLENOID XTHERMOSTAT XDELAY 1 HOT N CONNECT 4 2 1DEFROST LABEL 1 OR N X RELEASE LABEL TERMINATION OR RELEASE RELEASE W/FAN L1 LABEL FANL1 VALVE THERMOSTAT L1 SOLENOID ACROSS GAS FAN FAN1 33 CONNECT 22 W/FAN W/FAN DELAY HEATERDEFROST 44 ACROSS CONTACTOR COIL COIL RELEASE X LABEL TIMER RELAY DELAY L1 CONTACTOR HOTVALVEGASN COMPRESSOR FAN THERMOSTAT RELAYW/FAN TERMINATION COMPRESSOR RELAY HEATER COMPRESSOR VALVE SOLENOID W/FAN DELAY L1 RELAY TIMER TIM TERMINATION OR RELAY TIMER TIMER SOLENOID COMPRESSOR VALVE THERMOSTAT DEFROST HEATER OR TERMINATION DEFROST COMPRESSORTIMER RELE 3 TIMER 4 ACROSS CONNECT TIMER 1 DEFROST VALVE VALVE FAN GAS L1 NDEFROST W/FAN DELAY OR CONTACTOR COIL THERMOSTAT TERMINATION OR L1 TERMINATION THERMOSTAT COMPRESSOR SOLENOID VALVE THERMOSTAT 3 22TERMINATION 4 1 XX RELEASE N HOT FAN THERMOSTAT L1 HEATER THERMOSTAT SOLENOID VALVE SOLENOID OR THERMOSTAT CONTACTOR W/FAN DELAY HOT FAN VALVE HEATER THERMOSTAT THERMOSTAT RELAY REL OR OR TERMINATION COMPRESSOR OR L1 L1 W/FAN DELAY L1 THERMOSTAT DEFROST SOLENOID OR L2 FANL2 DEFROST VALVECONTACTOR L2 CONNECT ACROSS W/FANTHERMOSTAT FAN GASCONNECT ACROSS TERMINATION W/FAN DELAY HEATER VALVE CONTACTOR COIL L1 8141 THERMOSTAT HOT CONTACTOR FAN GAS TERMINATIO DELAY TIMER HEATER CONTACTOR COIL DEFROST W/FAN DELAY THERMOSTAT 8143 TERMINATIONL2 L2 COMPRESSOR TIMER OR SOLENOID N 2 CONTACTOR THERMOSTAT VALVE COMPRESSOR 3 HEATER X COMPRESSOR 1L2HEATER LABEL 4 DEFROST SOLENOID OR COMPRESSOR TERMINATION CONNECT ACROSS THERMOST VALVE FAN GAS OR TERMINATION W/FAN DELAY COIL 8141 3 2 4 1 X 3–4 LABEL CONTACTOR L1 VALVE HEATER DEFROST THERMOSTAT TERMINATION NVALVE 8141THERMOSTAT L2 VALVE 8143 SOLENOID VALVE SOLENOID L1 L2 HOT FAN N THERMOSTAT THERMOSTAT 8143TERMINATION 3 2 2 4 SOLENOID X 1 3DEFROST LABELL2 4OR OR COMPRESSOR DEFROST W/FAN DELAY THERMOSTAT NOTE: Bridge Between THERMOSTAT N HEATER 8143 OR XVALVE HOT LABELW/FAN FAN1 THERMOSTAT 3 4Bridge 2 X 3–4 4Bridge VALVE 1FAN X3–4 LABEL L2N CONTACTOR N LABEL DELAY DELAY 3 2Between CONNECT ACROSS OR GAS FAN W/FAN NOTE: Remove HEATER NRemove CONTACTOR COIL 3SOLENOID NOTE: Remove Bridge Between 3–4 3–4 DEFROST 4 2Bridge DEFROST 1ORL2 TERMINATION LABEL TERMINATION X THERMOSTAT NOTE: Remove Between HEATER CONNECT ACROSS OR W/FAN DELAY THERMOSTAT L2 CONTACTOR COIL L2 1 HEATER NOTE: Remove Bridge Between L2CONTACTOR L2 VALVE 1 *See Note 1GAS COMPRESSOR 8143 NOTE: Remove Between 3–4X THERMOSTAT THERMOSTAT SOLENOID CONTACTOR HEATER TERMINATION HEATER VALVE L1 L2 VALVE N 3 2 4 NOTE: Remove Bridge Between 3–4 COMPRESSOR 1 *See Note 1 3 NOTE: Connect Bridge Between 2–X L2 THERMOSTAT 2 4 1 LABEL X N VALVE *See Note 1 DEFROST THERMOSTAT THERMOSTAT THERMOSTAT ORConnect NOTE: Remove Bridge Between 3–4 L2 TERMINATION COMPRESSOR NOTE: Bridge Between 2–X DEFROST L1 L1 THERMOSTAT L1 L2 OR NOTE: Connect Bridge Between 2–X CONTACTOR L1 NOTE: TERMI NOTE: Remove Bridge Between 3–4 OR HEATER TERMINATION *See Note 1Bridge L1 L2 THERMOSTAT Remove Between 3–4 CONTACTOR TERMINA HEATER L2 L2 SOLENOID VALVE TERMINATION COMPRESSOR HOT NOTE: Remove Bridge Between 3–4 THERM FAN NOTE: Connect Bridge Between 2–X THERMOSTAT TERMINATION COMPRESSOROR L2 L2 W/FAN DELAY NOTE: Remove Bridge Between 3–4 NOTE: Remove Bridge Between 3–4 OR TERMINATION THERMO L1 THERMOSTAT DEFROST OR NoteACROSS 1 CONNECT FAN GAS W/FAN DELAY TERMINATION L1 NOTE: THERMOSTAT CONTACTOR COIL SOLENOID VALVE *See Note 1*See Remove Bridge Between 3–4 FAN THERMOSTAT SOLENOID VALVE L2 W/FAN DELAY DTMV40 Time/Pressure–Compressor Shutdown NOTE: Connect Bridge Between 2–X HOT HOT FAN THERMOSTAT SOLENOID HEATER OR VALVE W/FAN DELAY NOTE: Connect Bridge Between 2–X DEFROST COMPRESSOR OR *See Note 1 L2 DTMV40 Time/Pressure–Electric Defrost Wiring Diagram NOTE: Remove Bridge Between 3–4 CONNECT ACROSS FAN GAS DTMV40 Time/Pressure–Compressor Shutdown W/FAN DELAY DEFROST CONTACTOR COIL VALVE CONNECT ACROSS FAN GAS DTMV40 Time/Pressure–Compressor Shutdown W/FAN DELAY CONTACTOR COIL NOTE: Remove Bridge Between 3–4 DTMV40 Time/Pressure–Electric Defrost Wiring Diagram NOTE: Connect Bridge Between 2–X SOLENOID HEATER DEFROST NOTE: Remove Bridge Between 3–4 DTMV40 Time/Pressure–Electric Defrost Wiring Diagram THERMOSTAT VALVE ORDTMV40 T ime/Pressure–Electric Defrost Wiring3–4 Diagram SOLENOID HEATER 8243 Replacement VALVE NOTE: Remove Bridge Between COMPRESSOR VALVE DTMV40 Time/Pressure–Compressor Shutdown 8245 Replacement *See Note 1 COMPRESSOR DTMV40 T ime/Pressure–Electric Defrost Wiring Diagra 8243 Replacement CONTACTOR TERMINATION VALVE HEATER DTMV40 T ime/Pressure–Electric Defrost Dia DTMV40 Time/Pressure–Electric DEFROST Bridge Between 8243 Replacement *See Note 1Reversed THERMOSTAT 82458245 Replacement OR NOTE: 2 DEFROST L2 Connect 2–XWiring THERMOSTAT Replacement Defrost Wiring Diagram OR THERMOSTAT 8247 Pole Switching Mode with NOTE: Connect Between 2–X CONTACTOR TERMINAT DTMV40 Time/Pressure–Compressor Shutdown HEATER Bridge DTMV40 TReplacement–Double ime/Pressure–Electric Defrost Wiring Diagram 8243B Replacement Mode A with Label Applied CONTACTOR Shutdown TERMINATION 8247 Replacement–Double Pole Switching HEATER Mode BTrippers with Trippers Reversed DTMV40 Time/Pressure–Electric Defrost Wiring Diagram DTMV40 L2 Time/Pressure–Compressor 8247 Replacement–Double Pole Switching 8245 Replacement Mode B with Trippers Reversed DTMV40 Time/Pressure–Electric Defrost Wiring Diagram THERMOS L2 L2 L2 DTMV40 Mode A8245 with 82458245 Label Applied L2 THERMOSTAT Mode A with Label Applied Time/Pressure–Compressor Shutdown Mode B withTBime/Pressure–Electric 8247 Label Applied DTMV40 Defrost Wiring Diag 8243 Replacement DTMV40 Time/Pressure–Electric Defrost Wiring Diagram NOTE: Remove Bridge Between 3–4 8247 Replacement–Double Pole Switching Mode B with Trippers Reversed DTMV40 T ime/Pressure–Electric Defrost Wiring Diagram 8243 Replacement Mode with 8247 Label Applied Replacement Mode B with 8247 Label Applied Mode8245 A with 8245 Label Applied L2 Remove 8245 Replacement NOTE: Bridge Between 3–4 L2 TIMER 3–4Shutdown DTMV40 T ime/Pressure–Electric Defrost Wiring Diagram 8243 Replacement DTMV40 Time/Pressure–Compressor NOTE: Remove Bridge Between TIMER Replacement–Double Pole Switching Remove Bridge Between 3–4 TIMER Mode B Time/Pressure–Compressor with Trippers Reversed Note 1DTMV40 8245 DTMV40 Replacement Shutdown Mode B8247 with 8247 Label Applied DTMV40 Time/Pressure–Electric Defrost WiringDiagram Diagram *See RELEASE TIMER 8247 Replacement–Double Pole Switching Mode BNOTE: with Trippers Reversed TIMER NOTE: Remove Bridge Between Mode with 8245 Label Applied TIMERWiring Defrost RELEASE NOTE: Connect Bridge 2–X NOTE: Remove Bridge Between 3–4 3–4 Mode A with 8245ATime/Pressure–Electric Label Applied TIMER T TIMER RELAY RELEASE RELEASEWiring TIMER RELEASE 8247 Replacement–Double Pole Applied Switching Mode*See B with Trippers DTMV40 TBetween ime/Pressure–Electric Defrost *See Note 1 Reversed 8243 Replacement RELAY RELEASE TIMER TIMER RELAYRELAY Note 1 Replacement RELEASE RELEASE TIMER Mode B with 8247 Label Mode A with8245 Label Applied DTMV40 T ime/Pressure–Electric Defrost RELAYWiring 8243 8245Replacement Replacement RED TIMER Mode B with 8247 Label Applied TIMERRELAYRELAY NOTE: Connect Bridge Between 2–X TIMERTIMER RELEASE TIMER NOTE: Connect Bridge Between 2–X RELAYR RELEASE Mode B with Label Applied 8247 Replacement–Double Pole Switching TIMER ModeBBwith withTrippers Trippers Reversed RELAY TIMER RELEASE TIMER TIMER 8247 Replacement–Double Pole Switching Mode Reversed Mode A with 8245 Label Applied RELAY TIMER TIMER TIMER RELEASE RELAY TIMER TIME TIMER Mode A with 8245 Label AppliedRELEASE RELEASE TIMER TIMER DTMV40 Time/Pressure–Compressor Shutdown RELAY RELEASE RELEA TIMER Mode B with 8247 Label Applied 8243 TIMER RELAY RELEASE TIMER DTMV40 Time/Pressure–Electric Defrost Wiring Diagram 8245 RELEASEp TIMER RELAY TIMERApplied Mode B with 8247 Label TIMER Xp 8243 8243 2 RELAY RELA TIMER RELEASE p F 8245 8245 RELAY RELEASE Xp LABEL Diagram 2 p8243 3DTMV40 Xp Shutdown DTMV40 Shutdown TIMER DTMV40 T ime/Pressure–Electric Defrost Wiring Diagram F8245 31-N Time/Pressure–Compressor 8243 Replacement Defrost pLABEL F3DTMV40 Xp LABEL RELAY 8247 2 4 4RELAY pTIMER 3 1-N 1-N 24 TIMER LABEL DTMV40 Wiring Diagram F Time/Pressure–Compressor Xp TIMER TIMER 31-N Time/Pressure–Electric RELAY Replacement TIMER pLABEL LABEL F RELEASE XpWiring pWiring 2 4Defrost Xp 3 1-N 1-N 24 TIMER 4 824 F Time/Pressure–Electric 3ime/Pressure–Electric 4 2TIMER 2 3 2Pole 8245 N 1 LABEL RELEASE RELEASE DTMV40 T ime/Pressure–Electric Defrost Wiring D p 8243 Replacement Xp 2 p 3 Xp RELAY 4 TIMER DTMV40 T Defrost Diagra LABEL F 8243 Replacement 1-N 3 8247 Replacement–Double Switching 4 RELEASE Mode B with Trippers Reversed N p p 1 LABE TIMER Xp 8245 Replacement Xp LABEL 2 3 RELAY 4 RELAY TIMER N 8247 TIMER 1 Replacement–Double F A with 8245 Replacement 1-NLabel Mode 8245 Applied4 8243 8247 L1 TIMER 8243 8245 p XpLABEL 8245 RELAY p Pole Switching Xp L1 THERMOSTAT 2 Mode B with Trippers Reversed 3 4 LABEL L1 3 p F 4 2 1-N Xp N 1 LABEL 8247 Replacement–Double Pole Switching 2 p Mode B with Trippers Reversed 3 4 Mode B with 8247 Label Applied L1 F Xp LABEL 1-N 8243 2 Mode A with 8245 Label Applied 3 TIMER 4 p L1 THERMOSTAT F 1-N Xp LABEL8245 2 282454Label Applied 8 THERMOSTAT F F 3 L13 Mode 1-N 1-NA with p TIMER p L1 Xp 2 8247 3 4 LABEL F 1-N PRESSURE Xp p L1 LABEL 2 Label N Mode p TIMER 1 2 B 3with Xp 4Applied TIMER 4 MOTOR FAN Xp PRESSURE Label 3 Mode 48247 NL1N L11 1 PRESSURE L1 THERMOSTAT COMPRESSOR 8243 TIMER SWITCH FAN FAN 8245 pLABEL8247 L Xp 8243 OR COMPRESSOR pPRESSURE 3B with PRESSURE Xp 4 Applied 28247 SWITCH PRESSURE 2RELEASE 3 COMPRESSOR RELEASE 4 TIMER TIMERSWITCH 8245 LABEL L1 COMPRESSOR FCOMPRESSOR 1-N LINE L1 p MOTOR p SOLENOID RELAY 4 COMPRESSOR RELEASE LABEL TIMER 2 Xp SOLENOID VALVE SWITCH L1 OR Xp LABEL 2 3 3 PRESSURE TIMER 4 LABEL MOTOR SWITCH THERMOSTAT F DEFROST F 1-N 1-N LINE L1 OR p RELEASE RELAY TIMER LINE TIMER L1 THERMOSTAT SWITCH Xp LABEL FAN 2 SOLENOID 3 PRESSURE OR SOLENOID VALVE VALVE 4 RELEASE F RELAY Xp TIMERp LINE 1-N COMPRESSOR SOLENOID RELEASE L1 SOLENOID VALVE LINE HEATER RELAY DEFROST DEFROST RELEASE CONTACTOR COIL OR LINE DEFROST N 11DEFROST VALVE VALVE L1 MOTOR COMPRESSOR L1 THERMOSTAT OR OR RELAYSWITCH RELEASE pR TIMER TIMER OR PRESSURE L1 RELAY 33 TIMER 22 PRESSURE 44 Xp HEATER N CONTACTOR COIL COIL LINE PRESSURE RELAYSWITCH SOLENOID OR TIMER FANTIMER HEATER SOLENOID VALVE PRESSURE CONTACTOR CONTACTOR HEATERDEFROST RELAY DEFROST FAN OR LINE PRESSURE L1 L1 COMPRESSOR OR COMPRESSOR VALVECONTACTOR PRESSURE SWITCH MOTOR HEATER SWITCH ORFAN CONTACTOR PRESSURE L1 MOTOR L1 HEATER THERMOSTAT COMPRESSOR COMPRESSOR TIMER HEATER OR PRESSURE SWITCH CONTACTOR COILTHERMOSTAT LINE PRESSURE SWITCH L2 TIMER SWITCH OR SOLENOIDDEFROST COMPRESSOR SOLENOID VALVE 8243 L1 LINE SOLENOID DEFROST SWITCH SOLENOID VALVE LINE 8245 L2 MOTOR L2 p LABEL OR LINE L2 DEFROST Xp OR CONTACTOR L1 VALVE HEATER DEFROST 2 Between SWITCH 4 1-N F NOTE: 1-NCOMPRESSOR OR VALVE PRESSUREL2 PRESSURESWITCHSWITCH LINE 3L2 p FAN SOLENOID HEATER L1 Xp LABEL VALVE 2SOLENOID 8243 COIL 4CONTACTOR F FAN HEATER OR 1-N CONTACTOR DEFROST PRESSURE DEFROST LINE 3L2 COIL 8243 PRESSURE 8245 8247 Remove –2 1-N OR VALVE 8245PRESSURE L21 CONTACTOR 2Between L2 3 1-NBridge SWITCH SWITCH LABEL F LINE 1-N p LABEL Xp –2Xp p pLABEL COMPRESSOR MOTOR Xp COMPRESSOR HEATER 2Between 3 Bridge NOTE: Remove 4 4–2 3SOLENOID NOTE: Remove Bridge Between 3–4 DEFROST 2 4Bridge Xp p pLABEL LABEL F NORL2 2COMPRESSOR L2 PRESSURE SWITCH SWITCH HEATER 4 MOTOR NOTE: Remove Bridge 1-N F LINE OR 1-NCOIL2 SOLENOID COMPRESSOR PRESSURE 3 3CONTACTOR OR 4OR F HEATER SOLENOID VALVE Xp 1-N SWITCH NOTE: Remove Bridge Between 3–4 3–4 L2CONTACTOR DEFROST 824 LINE *See Note 2 NOTE: Remove Between SOLENOID CONTACTOR HEATER Xp p pLAB L2 ORVALVE VALVE 3 4 2 DEFROST PRESSURE N 1 LINE NOTE: Remove Bridge Between 1-N –2 Xp SWITCH L2 L1 SWITCH 3 *See*See NoteNote 2 2 NOTE: Connect Bridge Between 4–Xp 4 2 L2 N 1 OR HEATER VALVE DEFROST CONTACTOR COIL L2 L1 THERMOSTAT OR NOTE: Remove Bridge Between 3–4 L2 HEATER NOTE: Connect Bridge Between 4–Xp DEFROST L2 CONTACTOR COIL SWITCH 4–Xp L2 OR NOTE: Connect Bridge Between L1 CONTACTOR L2 HEATER NOTE: Remove Bridge Between 1-N –2 L1 *See Note 2 L1 PRESSURE THERMOSTAT NOTE: Remove Bridge Between 1-N –2 CONTACTOR HEATER PRESSURE L2 L1 L1 THERMOSTAT PRESSURE NOTE: Remove Bridge Between 3–4 NOTE: Connect Bridge Between 4–Xp FAN PRESSURE NOTE: Remove Bridge Between 3–4 L2COMPRESSOR COMPRESSOR NOTE: Remove Bridge Between 1-N –2 SWITCH L1 SWITCH *See Note 2 L2 L2 MOTOR PRESSURE SWITCH L1 NOTE: OR Remove Bridge Between 3–4 SWITCH PRESSURE FAN L2 PRESSURE *See LINE Note 2 L2 NOTE: Connect Bridge Between 4–Xp SOLENOID SOLENOID VALVE COMPRESSORFAN PRESSURE NOTE: Connect Bridge Between 4–Xp DEFROST L2 LINE COMPRESSOROR *See Note 2LINE NOTE: COMPRESSOR Remove Bridge Between 1-N –2 COMPRESSOR SWITCH SWITCH OR VALVE MOTORMOTOR OR NOTE: Connect Bridge Between 4–Xp SWITCH SWITCH HEATER SOLENOID DEFROST SOLENOID VALVE NOTE: Remove Bridge Between3–4 3–4 CONTACTOR COIL SOLENOID LINE NOTE: Remove Bridge Between 1-N –2 OR SOLENOID DEFROST VALVE NOTE: Remove Bridge Between LINE LINE DEFROST OR VALVE *SeeNote Note22 CONTACTOR OR VALVE HEATER HEATER DEFROST Bridge PRESSURE CONTACTOR COIL *See OR NOTE: HEATER DEFROST Connect Between4–Xp 4–Xp CONTACTOR COIL OR NOTE: Connect Bridge Between CONTACTOR L2 HEATER CONTACTOR HEATER HEATER L2 Remove Bridge Between 3–4 NOTE: L2 SWITCH PRESSURE PRESSURE SWITCH SWITCH NOTE: Remove Bridge Between NOTE: Connect Bridge Between 4–Xp NOTE: Remove Bridge Between 3–4 3–4 NOTE: Connect Bridge Between NOTE: Connect Bridge Between 4–Xp4–Xp WIRING LEGENDS Precision GRASSLIN Paragon Model Model Model TIME INITIATED, TIME TERMINATED 8045 6045 DTMV40 DTMV40 8046 S1 Mode Selector Terminal Ident. Label Typical Wiring Diagram A A None None 1 F 2 3 4 N 1 3 F 3 8041 6041 DTMV40 A 8041 8043 6043 DTMV40 B 8043 8047 6047 DTMV40 B 8047 TIME INITIATED, REMOTE TEMPERATURE OR PRESSURE TERMINATED 8145 6145 DTMV40 A None 8141 6141 DTMV40 A 8141 8143 6143 DTMV40 B 8143 5, 6 7 8, 9 6243 DTMV40 B 8243 8247 6247 DTMV40 B 8247 4 X NO CONNECTION 2 4 X NO CONNECTION 1 4 2 N NO CONNECTION N 1 3 4 2 NO CONNECTION F 3 1 2 4 N X N 1 3 2 4 X 1 N 3 4 2 X 3 1-N 2 2 See Note 1 TIME INITIATED, PRESSURE TERMINATED (Separate Pressure Switch Required - see instructions) 8245 6245 DTMV40 A 8245 8243 Terminal Layout (see note below) 10 F 3 1-N 2 4 Xp p 11 F 3 1-N 2 4 Xp p See Note 2 12 N 1 3 2 4 Xp p NOTE: In “Terminal Layout,” the connecting lines between terminals indicate the correct positions of the bridges for each model. The heavy line indicates the bridge must be installed as shown. The light line indicates the bridge may be removed if different voltages are used at each switch. APPLICATION though the defrost programmed termination time has not been reached. The time termination functions as a fail-safe and will terminate the defrost if the temperature or pressure switch fails to do so. The temperature or pressure switch on the refrigeration coil has contacts which close on a temperature or pressure rise above freezing, indicating that frost and ice have melted from the coil. Typically a wide differential SPDT temperature switch is used with it’s normally closed contacts wired to the fans thereby delaying the fans from coming on until the coil temperature has dropped back to below freezing. In most applications, the contacts at terminals 2 and 4 are normally closed (when timer is energized) and control the fans and refrigeration equipment or compressor. For hot gas defrost, or for double pole switching, contacts 2 and 4 may be configured as normally open by selecting mode “B.” Refer to wiring diagrams 1 thru 12 for additional detail. The DTMV40 Defrost Timer is equivalent in function, terminal identification, and wiring to the Paragon 8140 and Precision 6140 series Defrost Timers. The DTMV40 may also be used to replace Paragon 8040 and Precision 6040 series time terminated defrost timers. With the addition of a remote pressure switch, the DTMV40 can replace the Paragon 8240 series and Precision 6240 series pressure terminated defrost timers.Defrosts will be initiated by programming the timer, which will accept from 1 to over 24 defrost initiation settings per day at 15 minute intervals (8:00AM, 8:15AM, 8:30AM, etc.) Defrost duration is settable in 15 minute intervals from a minimum of 15 minutes up to several hours (15 minutes, 30 minutes, 45 minutes, 1 hour, 1 hour-15 minutes, etc.) The defrost duration determines the termination time. In standard configuration, the contacts between terminals 1 and 3 are normally open and close during a defrost to energize defrost heaters; the contacts between terminals 2 and 4 are normally closed (when timer is energized) and open during a defrost to deenergize refrigeration and fans. “F” Terminal: The DTMV40 contains a normally closed contact between terminals 1 and F. This terminal may be used to switch the fans off during a defrost rather than terminals 2 and 4. For hot gas defrost applications, with the mode switch set to position “B”, the fans may be connected to terminal “F.” DTMV40 Time Initiated, Remote Temperature, Pressure or Time Terminated: Used in electric or hot gas defrost applications where the defrost is terminated when the coil is frost free, as sensed by a temperature or pressure switch, even Note: The DTMV40 is configured by default (out of the box) to replicate the 8145 wiring. For replacement of other models refer to page 3. 4 REPLACING EXISTING DEFROST TIMERS IMPORTANT: When replacing a Grasslin DT-040 model with a DTMV40, the power connections must be made to terminals N and 1 on the DTMV40. No connection must be made to the X terminal or damage to the unit will result. Disconnect the power wire from terminal X on the DT-040 and connect it to terminal N on the DTMV40. Disconnect the other power wire from terminal N on the DT-040 and connect it to terminal 1 on the DTMV40. All other wires should be connected to the DTMV40 the same as on the DT-040. The DTMV40 will replace all models of Paragon 8040, 8140, 8240 Series or Precision 6040, 6140, 6240 Series. TERMINAL IDENTIFICATION: The standard DTMV40 terminal identification is identical to the Paragon 8145 with the addition of the “F” terminal. Terminal identification labels are provided for the other models to be placed over the printed numbers on the printed circuit board. From the table on page 4, select the proper label, apply to printed circuit board, and wire per the original wiring or the wiring diagrams indicated. MODE SELECTION (Light Blue DIP Switch): First determine what model is being replaced (Grasslin or Competitors). The mode selector DIP switch (located at lower right side of the board) determines the configuration of terminals 2&4. In position “A”, the terminals are normally closed (only when the timer is energized), and will open during a defrost. In position “B”, terminals 2&4 are normally open, and will close during a defrost. Select proper position from table below and wiring diagrams indicated. To select mode simply slide the switch as follows: Mode A – position switch to left; Mode B – position switch to right the DTMV40 must be configured for 120V application (RED DIP Switch Down) with 120V power connected to 1N and X, and the bridge jumper between 1-N and 2 must be removed. Note 1 – (8143 Replacement): When replacing a Paragon 8143 or Precision 6143, wire the termination thermostat to terminal N of the DTMV40 and the adjacent blank terminal. The Paragon and Precision timers are wired to terminal N and the blank terminal. If the termination thermostat is wired to terminal N of the DTMV40 (with the 8143 label attached), temperature termination will not occur and may result in burnout of the DTMV40. See wiring diagrams 8 & 9. 8240/6240 SERIES REPLACEMENT: The DTMV40 may be used to replace the Paragon 8240 or Precision 6240 series defrost timers with integral pressure termination by the addition of a remote pressure switch wired to terminals Xp and p of the DTMV40 (with an 8240 series terminal label applied). There must be no external voltage connected to the pressure switch. Set pressure switch cut-in to the same value as set on the Paragon or Precision defrost timer being replaced. Set cut-out 6 to 14psi below cut-in. See wiring diagrams 10, 11, and 12. Recommended Pressure Switches: Johnson/Penn P170, Ranco 010 series, or Danfoss KP1 series. Pressure range approximately 35-110psi, CUT-IN ON PRESSURE RISE. NOTE 2 – (8243 Replacement): When replacing a Paragon 8243 or Precision 6243, the DTMV40 white tabs (trippers) for setting defrost time and defrost duration must be reversed. Pull ALL tabs outward for refrigeration. Press the tabs inward at the desired defrost initiation times, and for desired duration. Please Note: The DTMV40 replaces all prior Grasslin defrost timer models such as DT040, DT140, DTMV, and DTSX. Note: When Mode “B” is selected the DTMV40 will operate as follows: Refrigeration Mode – RED & GREEN LED’s will turn OFF (1&3 and 2&4 break while 1&F make) SPECIFICATIONS Defrost Mode – RED & GREEN LED’s will turn ON (1&3 and 2&4 make while 1&F break) 8045 REPLACEMENT: The DTMV40 with 8045 terminal ID label applied differs from the 8045 in that terminals 1 and N are combined. This means that the DTMV40 model must be the same voltage as the defrost circuit (defrost heater, contactor coil, or hot gas valve). If used in an application where the defrost circuit is 120V and the refrigeration circuit is 240V, 5 Switch Rating: 40A Resistive @ 120VAC, 208~240VAC 2HP @ 208~240VAC; 1HP @ 120VAC 16FLA, 90LRA @ 120VAC 12FLA, 52LRA @ 240VAC “F” Terminal: 30A Resistive @ 120~240VAC 1HP @ 120VAC; 2HP @ 208~240VAC Wiring Connections: Screw box lug terminals. Environmental Ratings: Operating Temperature Range: –40°F to 131°F (–40°C to 55°C) Operating Humidity: 0 to 95% non-condensing Dimensions: 8.795” x 6.631” x 2.935” (H x W x D) Shipping Weight: 2 lbs. DTMV40 INSTALLATION INTO EXISTING ENCLOSURE SETUP PROCEDURE 1. Disconnect power. 2. Disconnect wiring from existing defrost timer. 3. Remove Paragon mechanism from enclosure. 4. Remove Grasslin DTMV40 printed circuit board from it’s enclosure (gray plastic). 5. If necessary, adjust DIP switches and apply terminal identification label as indicated in the DTMV40 operating instructions. 6. Engage tabs on left side of printed circuit board into enclosure, and swing PCB into place. 7. Apply extra DTMV40 label to existing enclosure door. 8. Reconnect wires to DTMV40. 9. Attach gray faceplate over PCB and secure using existing enclosure locking latch as illustrated. 10. Reapply power. DTMV40 Installation into Old Paragon Enclosure/Bracket ***Note: Grasslin Recommends replacing Old Paragon Enclosure/Bracket entirely with the DTMV40 NEMA3R Enclosure or DTMV40-B Bracket Mount *** SETUP PROCEDURE 1. Disconnect power (turn breaker OFF). 2. Disconnect wiring from existing Paragon timer. 3. Remove and save the 6-32 screw. Remove and discard two metal posts retaining Paragon mechanism. 4. Remove Paragon mechanism from enclosure. 5. Remove Grasslin DTMV40 mechanism from it’s enclosure (if applicable) and with pliers break off the 3 tabs on left side of printed circuit board. 6. Remove contents of plastic hardware bag. 7. Refer to DTMV40 operating instructions for procedures on setting voltage and mode DIP switches. 8. Refer to installation diagram below. CAUTION: If the DTMV40 mechanism is not assembled to the old Paragon enclosure/bracket exactly as shown below, a short circuit may occur which will destroy the DTMV40 defrost timer. 9. Reconnect wires, tighten terminal screws securely. Reapply power (turn breaker ON). 10. Follow the programming/setup procedure (refer to DTMV40 operating instructions). Old Paragon Enclosure Existing Paragon #6-32 Screw #6-32 x ¼” Screw 3/8” Nylon Standoffs #6-32 x ¾” Threaded Standoff #6-32 Nylon Posts Paragon Bracket 3/8” Nylon Standoffs From Bag