AC Power for Business-Critical Continuity™ MEDIA 6000VA Parallelable Rack-Mounted Inverter System Key Features Hot Swappable disconnect Distributed Static Transfer Switch (STS) function – eliminates single point of failure Triple port inverter with distributed transfer switch eliminates single point of failure concerns. Parallelable for redundancy and increased reliability Automatic load sharing when paralleled System sound handling of internal or load generated short circuits >Tool-less installation – configured with standard Nema or Twist Lock receptacles The MEDIA 6000VA is a parallelable, rack-mounted inverter system that provides a pure AC sine wave output at 120 or 240Vac (60 or 50Hz) with a THD <3% for any kind of load. These high density systems range from 1500VA to 6000VA at 48Vdc and can be mounted in a 19 in open relay rack or conventional box bay. U U I I AC Source DC Source Load Communication Fig: TSI-MEDIA platform 3000VA 5 6 1 7 8 2 9 10 3 11 Description The feature-rich MEDIA inverter system has an AC-AC “Enhanced Power Conversion” (EPC) mode, that double filters and isolates the AC input. When operated in this EPC mode, overall efficiency is increased to 94% without compromising the quality and stability of the output wave form. Unlike hard transfers between energy input sources, MEDIA’s “soft-switching” method is disturbance free. Pure power is delivered to your critical load despite normal disturbances such as harmonics, surges, glitches, voltage fluctuations, etc. Compact MEDIA inverters enable you to deliver maximum power in limited space, offering pure sine wave output and ideal power factor input without drawing any energy from your DC supply source. Your future power demands are likely to be unknown and unpredictable. With the MEDIA 6000VA, there is need to size a single static switch for future power demand. Instead, system capacity can be gradually increased as your load demands grow. The MEDIA 6000VA is compatible with standard TSI monitoring devices, offering massive power density up to 3kVA in a 2U package or 6kVA in a 4U package, with built-in STS function, DC and AC distribution, and output PDU. This cutting edge inverter sets the standard for “true redundant systems”. 4 1 PDU (at rear) 2 Access to AC terminal blocs 3 Open relay rack fixture 4 Box bay fixture 5 Access to DC terminal blocs (at side) 6 DC in protection 7 T2S monitoring unit 8 Inverter modules 9 AC distribution box 10 AC MBP 11 Surge arrestor (behind front cover) 1 ESLID102en-MEDIA / 0910 MEDIA 6000VA Parallelable Rack-Mounted Inverter System Technical Specifications General EMC (immunity) EMC (emission) Safety Cooling MTBF Efficiency (MAX) IEC 1000-4 FCC PART 15 UL 1778 (Ed.4) Forced >200 000 hrs On Line Enhanced Power Conversion (EPC) Dielectric Strength DC/AC (@ 0.6mA) True Redundant Systems 90% 93% 4300Vdc Compliant AC Output Specifications Nominal Voltage (AC)* Protected against reverse current Crest Factor at Nominal Power Compliant Terminal block Or NEMA receptacle Or Twist Locks Or combo AC output receptacles Protected against reversed polarity Self adaptive to wide operating conditions AC Output Power Nominal Output Power** Output Power (resistive load)** Short Time Overload Capacity Permanent Overload Capacity Load Power Factor Available while Mains is available at AC input port With magnitude control and management *Operation within lower voltage networks leads to derating of power performances. **“n” stands for Number of Modules in parallel. Transfer Performance Total Transient Voltage Duration Environment Altitude Above Sea Ambient Temperature** <1500m n x 1500VA -20 to 50 °C Storage Temperature Relative Humidity 48 V 40 - 60 V n x 34 A n x 42 A <1mV -40 to 70 °C 95%, non condensing **“n” stands for Number of Modules in parallel. Signaling & Supervision Display Alarms Output (optional) Supervision Input voltage boundaries user selectable **“n” stands for Number of Modules in parallel. Synoptic LED Dry contacts on shelf Use optional devices Comprehensive table of troubleshooting codes AC Input Specifications Nominal Voltage (AC) Voltage Range (AC) (each phase) Conformity Range Power Factor Frequency Range (selectable) Synchronization Range Emerson Network Power Energy Systems Calle 10 No 145, Col. San Pedro de los Pinos CP 01180, Del. Alvaro Obregon, Mexico, D.F. Toll Free: 01.800.9262.777 Tel/Fax: +52-55-5809 5250 Web: EmersonNetworkPower.com/EnergySystems 0s (transient free) Pmax at 100% LOAD Derating up to 65°C DC Input Specifications Nominal Voltage (DC) Voltage Range (DC) Nominal Current (at 40Vdc)** Maximum Input Current (for 5 sec.)** Voltage Ripple (resistive load @ 54Vdc) The global leader in enabling Business-Critical Continuity™. 10 x In for 20m sec Short Circuit Clear Up Capacity **“n” stands for Number of Modules in parallel. Emerson Network Power. 2.2 With short circuit management and protection n x 1500 VA n x 1200W 150% 15 second 110% @ 40°C Full power rating from 0 inductive to 0 capacitive Internal temperature management and cut off 90 – 130 V 2% 50 – 60 Hz 0.03 % <3 % 0.4 ms 30 s n x 12.5 A Voltage Accuracy Frequency Frequency Accuracy Total Harmonic Distortion (resistive load) Load Impact Recovery Time Turn on Delay Nominal Current** 3 disconnection levels on AC(out) and DC(in) power ports 4 disconnection levels on ACin port/2 communication bus RoHS-6 Connection I/O 120V or 240 V (Single or dual phase selectable at order) Voltage Range (AC) (adjustable) 120V 1P or 2P 83 – 140 V Adjustable >99% 50 - 60 Hz 47 – 53 Hz / 57 – 63 Hz AC Power Connectivity DC Power Embedded Computing Weight & Dimensions Width 19" or 23" open relay rack and box bay compatible 12.5-inch - 300 mm 2U (1500VA) / 4U (3000VA) 7.9 Kg + n x 2.4 Kg Coated steel Depth Height Weight Material (casing) Embedded Power Infrastructure Management & Monitoring Outside Plant Power Switching & Controls Precision Cooling Racks & Integrated Cabinets Services Surge Protection © 2010 Emerson Network Power Energy Systems, North America, Inc. All rights reserved. Emerson®, Emerson Network Power™, Business-Critical Continuity™, NetReach™, NetSpan™ and NetXtend™ are trademarks of Emerson Electric Co. and/or one of its subsidiaries. Printed in USA 2 ESLID102en-MEDIA / 0910