Precision Cooling for Business-Critical Continuity™ Liebert HPM Dual Circuit Floor Mount Chilled Water Units for High Redundancy Redundancy To Secure Your Business Liebert HPM R-type units are dual circuit chilled water units for business critical applications. Equipped with two independent chilled water circuits they are able to take cooling fluid from two independent sources. The models are available in the cooling capacity range 24 - 120 kW for each circuit; each equipped with 3 or 2 Port valves. These units provide additional security for your critical environment. With primary and secondary chilled water circuits the units provide mandatory back up in terms of cooling capacity. Liebert HPM Dual CW Circuit Hydraulic System Schematic Liebert HPM Dual CW Circuit units are specifically designed for buildings with primary and secondary chilled water circuits. A typical application is for polyfunctional buildings where a larger cooling source operates during the day, serving offices, technology and datacentres; while at night when cooling is only required for the technology and datacentres we can use a smaller chilled water source, maximizing obvious energy savings. CW1 CW2 Availability 100% redundancy CW circuits Dual CW circuits with double power supply maximize availability. Flexibility Simplified design layout: • power cables • condensate drain • supply/drain for humidifier Secondary CW circuit can provide additional cooling in the event of increased heat loads 2 Low Total Cost of Ownership: Reduced footprint compared to two separate units Lower investments in airconditioners Lower cost for the installation iCOM - Keep it under control Control The sophisticated control logic of the units offers several options to satisfy the chilled water system requirements and valve management. Parallel mode The chilled water valve management and positions are the same for both CW circuits. Safe mode First circuit and valve managed utilizing 70% of proportional temperature band, and then second valve starts to open (Requires same inlet fluid temperature on both circuits). Alternate mode With an external input to the iCOM controller it is possible to manage which of the two chilled water circuits / valves is duty and which is standby. In parallel and safe modes both CW circuits can run together maximizing the cooling capacity. Liebert HPM R-type - Technical Data Model M241 upward downward M451 upward downward M601 upward downward L851 L111 L132 downward downward downward Total cooling capacity at max airflow4 kW 24.8 48.4 63.5 86.1 108.1 127.4 Total cooling capacity4,6 kW 24.2 46.9 60.7 80.3 99.7 118.6 118.6 Sensible cooling capacity kW 24 43.1 54 68.3 89.1 Water flow rate6 l/s 1.15 2.24 2.89 3.83 4.76 5.66 Number of fans n 1 1 2 2 3 4 7050 11500 13900 17150 23900 32700 4,6 Air delivery Max ESP downward/upward delivery Sound pressure level5 m3/h 3 Pa dB(A) 190/210 100/100 120/140 180 210 180 54.4 65.4 64 64.2 66.1 69.3 Width mm 1000 1750 1750 2050 2550 3350 Depth mm 850 850 850 850 850 850 Height mm 1950 1950 1950 1950 1950 1950 kg 335 540 610 640 865 1020 Net weight * * 1 2 3 4 5 6 All the data refer to: one circuit working and G4 air filter 20 Pa ESP for downward delivery version, 50 Pa ESP for upward delivery version Air inlet @ 24° C, 50% RH, water in/out 7/12° C, ESP 20 Pa, G4 air filter Air inlet @ 24° C, 45% RH, water in/out 7/12° C, ESP 20 Pa, G4 air filter Max. ESP available for the indicated air delivery For downward version 1.5 m height, 2 m front distance; free field; fan (s) working with indicated air delivery, downward delivery version. At nominal/indicated air delivery 3 Ensuring the High Availability Of Mission-Critical Data And Applications. Emerson Network Power, a business of Emerson Locations (NYSE:EMR), is the global leader in enabling Business-Critical Continuity™. The company is a trusted source of custom, adaptive and ultra-reliable solutions designed to enable and protect its customers’ business-critical technology infrastructures. Backed by the largest global services organization in the industry, Emerson Network Power offers a full range of innovative power, precision cooling, connectivity and embedded Emerson Network Power - Headquarters EMEA Liebert Business Via Leonardo Da Vinci 16/18 Zona Industriale Tognana 35028 Piove di Sacco (PD) Italy Tel: +39 049 9719 111 Fax: +39 049 5841 257 marketing.emea@emersonnetworkpower.com products and services for computer, communications, healthcare and industrial systems. Key product brands within the Emerson Network Power family include Liebert, Knürr, ASCO, Astec and Lorain. Emerson Network Power - Service EMEA Via Leonardo Da Vinci 16/18 Zona Industriale Tognana 35028 Piove di Sacco (PD) Italy Tel: +39 049 9719 111 Fax: +39 049 9719045 service.emea@emersonnetworkpower.com United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Tel: +1 614 8880246 Asia 7/F, Dah Sing Financial Centre 108 Gloucester Road,Wanchai Hong Kong Tel: +852 2572220 Fax: +852 28029250 While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and accepts no liability for damages resulting from use of this information or for any errors or omissions. ©2008 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. Emerson Network PowerTM The global leader in Business-Critical Continuity™. AC Power Embedded Computing Outside Plant Rack & Integrated Cabinets Connectivity Embedded Power Power Switching & Control Services DC Power Monitoring Precision Cooling Surge Protection Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of EmersonElectric Co. ©2009 Emerson Electric Co.