O-BBS 24-080 and 48-540 Outdoor Battery Backup System Key Features Description

advertisement
O-BBS 24-1080 and 48-540
Outdoor Battery Backup System
Key Features
•High capacity passive hydrogen
ventilation system — reliable
ventilation capacity exceeding
industry standards to minimize risk
of hydrogen build up
•Two separate compartments,
battery and electronics — no
risk for arcs or sparks to ignite
hydrogen gas as electronics
compartment is located below
batteries
•Outer skin made of 1/8" thick
powder coated aluminum —
corrosion resistant and shot gun
resistant
•Heavy duty foil backed
insulation in battery
compartment — minimizes
environmental impact and cooling
requirement
•Multiple and flexible cable inlet
positions — simple adaptability to
site conditions
Outside Plant for
Business-Critical Continuity
Description
The system includes innovative temperature control for the ultimate in reliability and long
life time. The O-BBS is state of the art engineering with extensive software analysis as well
as extensive agency testing and verification to the highest industry standards. Further
engineering focus was on installability/serviceability and cost.
DC Power
• +24VDC or –48VDC configurations — flexibility to connect to all common DC power
voltages
• Integrated Battery Breaker Module, BBM — flexibility to choose up to four feeds with
circuit breakers up to 200A each
Cooling and Heating
•Thermoelectrical cooling/heating
(Peltier) — high reliability and low maintenance cost
•No refrigerants used — environmental friendly and no requirement for specialized
refrigerant service technicians
•DC operated cooling/heating, i.e. no AC power routing required — saves site installation cost and time
•Low Voltage Disconnect device — automatic disconnect and reconnect of Peltier unit maximizes backup time and minimizes recharge time
•Thermostatically controlled by solid state circuit — high reliability and precise control
Application
Emerson Energy Systems’ O-BBS is a high
performance battery backup system for
outdoor applications. Usage can be for, but
not limited to:
•Extended RBS/BTS/data/telecom outdoor
battery backup
•Replacement of diesel generator sets
•Replacement of existing battery backup
solution to increase system reliability and
battery life
•Outdoor enclosure and shelter sites
OSPDS-124100 / 0207
O-BBS 24-1080 and 48-540 Outdoor Battery Backup System
Specifications
System Characteristics
Nominal system voltage +24VDC or -48VDC
Backup capacity
Up to 4h at 6kW and 1.75V/cell
Up to 1080Ah (+24VDC version)*
Up to 540Ah (-48VDC version)*
Agency approvals
Telcordia GR-487-CORE and UL 50
Grounding, single point
2-hole lug for 1/4" screw and 5/8" spacing
Environmental Classification
Operating temperature (nominal)
Maximum: 115°F (46°C) with 753 W/m2 solar load
Minimum: -40°F (-40°C)
Sound level
55 dB(A) at 5’ (1.5m)
Hydrogen outgassing capacity
500 cc/min (less than 2% H2 concentration)
Degree of protection
NEMA 4 (electronics compartment)
NEMA 3R (battery compartment)
Earthquake
Telcordia GR-63-CORE, Zone 4
Environmental Control Unit, ECU
Technology
Thermoelectrical (TE) modules (Peltier), forced air, closed loop, filterless, non-refrigerant
Cooling and heating capacity
Cooling 200W, heating 250W
Thermostat control (solid state)
Cooling, set point 77°F (25°C), +/- 3.5°F (2°C)
Heating, set point 50°F (10°C), +/- 3.5°F (2°C)
Low Voltage Disconnect (LVD) with disconnect/reconnect of ECU
25.0 / 26.0V, +/- 0.5V (+24VDC version)
50.1 / 51.0V, +/- 0.5V (-48VDC version)
Repair time
< 10 minutes (non-specialist)
Power consumption11.2A (+24VDC version)
5.6A (-48VDC version)
Enclosure
Dimensions (H x W x D)
57" x 36" x 30" (1448 x 914 x 762mm)
Weight
880 lbs / 400 kg (excluding batteries)
2700 lbs / 1200 kg (including batteries)
Lock system
3-point, padlockable
Alarms
Open door (NC)
High/low temperature (NO or NC)
Circuit breaker tripped (NO or NC)
Access
Front access (rear access not required)
Bug screens (on all openings)
0.1" (2.5mm) mesh hole size
External material
Aluminum 5052-H32, 1/8" thick
External color, powder coating
Medium gray, polyester semi gloss hytex
Cable inlets
Exchangeable cable inlet plates
Conduit connections, ø11/4", ø2", ø4" etc.
Cable grommets and glands, various sizes
Roxtec, CF16
Safety Compliance
UL
UL50
CSA
C22.2 60950-00
Telcordia
GR-487-CORE
NEMA NEMA 4 for electronics compartment and NEMA 3R for battery compartment
OSPDS-124100 / 0207
O-BBS 24-1080 and 48-540 Outdoor Battery Backup System
Battery Specifications
Optional Equipment *
Top terminal type
GNB
Front terminal type, 22" deep
GNB
M12V155FT
C&D
FA 12-150
EnerSys12V165F
Fiamm®12 FAT 155
East Penn-Deka12AVR-150ET
Northstar
NSB170FT
M12V90F
Installation
Factory installed and pre-wired
Battery acid drip prevention
Plastic tray for each battery
Battery Breaker Module (BBM)
Circuit Breakers (CB)
Up to 4 CBs, 100 to 200A each
Lug size (external side)
Up to 4/0, 2-hole lug for 3/8" screw and 1" spacing
Interrupt current
50 kAIC
Safety Compliance
Telcordia
GR-487-CORE
* Additional equipment types can be fitted.
OSPDS-124100 / 0207
O-BBS 24-1080 and 48-540 Outdoor Battery Backup System
State of the art engineering with extensive software analysis,
testing and verification
Emerson Network Power.
The global leader in enabling businesscritical continuity.
Emerson Network Power
Energy Systems
701 N. Glenville Drive, Richardson, TX
Telephone: 866-851-2565 Fax: 972-367-0066
www.EmersonNetworkPower.com/EnergySystems •
•
•
•
AC Power
Connectivity
DC Power
Embedded Computing
•
•
•
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
•
•
•
•
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection