Liebert LTS (10A & 16A) Power Redundancy for One-way Power Supply

advertisement
AC Power
for Business-Critical Continuity™
Liebert LTS (10A & 16A)
Power Redundancy for One-way Power Supply
The LTS is an automatic transfer device, designed to provide fast automatic transfers between two independent, synchronous AC power
sources to provide continuity of AC power to critical equipment, such as information technology equipment, despite irregularities in
either of the two AC input power sources. The transfer is accomplished with sense and transfer times of less than 6 milliseconds typically.
The LTS is available as a 2 pole device, with capacities of 10, and 16 amps in a rack mount package.
Features
„ Redundancy of design for key components.
„ Preferred and Alternate Source modes.
„ Digital Signal Processor (DSP) ensuring increased
processing capability, including sensing and
operational functionality.
„ Optional SNMP card for remote monitoring
capability.
Designed For Reliability
„ Break-before-make switching eliminates
connecting together of the independent power
sources, even under faulted conditions.
„ Switched neutrals maintain isolation of the two
power sources and simplify grounding.
„ Diagnostics and transfer tests detect potential
switch failures, before the problem becomes
critical.
Fast Operation
„ Less than 6 milliseconds typical transfer time is
invisible to sensitive electronic equipment, and
well within CBEMA and ITIC curves.
„ Automatically transfers from the failing power
source to the good source immediately upon
detection of a problem.
„ Manual transfer allows you to switch power
sources at your convenience for scheduled
source shutdowns or maintenance.
The Liebert LTS Is Ideally Suited For:
„
„
„
„
Computer equipment rooms
Internet data centres
Telecom & »nancial data centres
Industrial process control centres
Liebert LTS Specifications
Model Number
02352247
02352244
02352190
Input
C14 x 2
Input Connectors
IEC309 x 2
IEC-C20 x 2
220 /230VAC
Rated Voltage
50 / 60Hz
Rated Frequency
Voltage Range
150 to 300VAC
Frequency Range
50 / 60Hz ± 5Hz
Voltage Distortion
< 10%
C13 x 6
C13 x 6 + C19 x 1
Power Factor
0.75 to 1 lead or lag
Overload Capacity
125% for 30 minutes
Transfer
2 poles
Number of Poles
Victoria
Tel. No.: +61 3 9535 2700
Fax No.: +61 3 9543 5170
< 6ms typical, < 11ms max
Automatic Transfer Interval
Environmental Parameters
0 to 40°C
Operating temperature
Western Australia
Tel. No.: 1 800 065 345
Fax No.: +61 8 9240 0730
-40 to 70°C
Storage temperature
5 to 95%; no condensation
Relative humidity
3000m
Elevation
New Zealand
Auckland
Tel. No. 64-9-443 5496
Fax No. 64-9-444 0066
Email: marketing.ap@emerson.com
Mechanical Parameters
44 × 430 × 250
Dimension H × W × D (mm)
4.5kg
Net weight of standard
equipment
Christchurch
Tel. No. +64 3 339 2060
Fax No. +64 3 339 2063
Email: marketing.ap@emerson.com
5kg
Gross weight with options
Transfer Button
Queensland
Tel. No.: 07 3633 3117
Fax No.: +61 7 3633 3100
Australian Capital Territory
Tel. No.: 1 800 065 345
Fax No.: +61 2 6280 0661
99%
Efficiency
Australia
Head Office
Block P, Regents Park Estate, 391 Park Road
Regents Park, NSW 2143, Australia
Tel No.: 61-2-9743 8555
Fax No.: 61-2-9743 8737
Email: marketing.ap@emerson.com
New South Wales – North Ryde
Tel. No.: 1 800 065 345
Fax No.: +61 2 9805 9550
Output
Output Connectors
Emerson Network Power Australia and New Zealand
Failure Status
USB Port
Input Power Status
Output End Status
While every precaution has been taken to ensure the
accuracy and completeness of this literature, Emerson
Network Power assumes no responsibility and disclaims
all liability for damages resulting from use of this
information or for any errors or omissions.
Silence Button
Front Panel Schematic Diagram
Source 1 Input Cable (ex-factory delivery)
Source 2 Input Cable (ex-factory delivery)
Emerson, Business-Critical Continuity and Emerson
Network Power are trademarks of Emerson Electric Co.
or one of its af»liated companies.
©2012 Emerson Electric Co.
All rights reserved throughout the world. Speci»cations
subject to change without notice.
Source 1 Input Switch
SNMP Card Slot
Source 2 Input Switch
One 16A Output Socket
Six 10A Output Socket
Back Panel Schematic Diagram
Emerson Network Power.
The global leader in enabling Business-Critical Continuity™.
www.EmersonNetworkPower.Asia
AC Power
Embedded Computing
Infrastructure Management & Monitoring
Precision Cooling
Connectivity
Embedded Power
Industrial Power
Outside Plant
Power Switching & Controls
Racks & Integrated Cabinets
Services
DC Power
AU12-PWR-LTSV1-BR
Download