VFD-Motor Package INSIGHT Lenntech info@lenntech.com Tel. +31-152-610-900 www.lenntech.com Fax. +31-152-616-289 Overview RTD Temperature Probe Marley offers a complete VFD and motor upgrade aftermarket package for cooling towers that can significantly reduce energy costs compared to single or two-speed starters. This package provides a singlesource solution, it’s easy to purchase and has a longer warranty than individually purchased components. Primary Benefits • • • ignificantCostSavings–TheVFDpackage S can lower operating costs as much as 30% compared to a two-speed motor system, or 70% compared to a single-speed motor system, while also qualifying for state and utility rebates in some regions EaseofPurchase–Marleywillassistby identifying both mechanical and electrical towerby components required to make your single purchase order a smooth experience Support/Warranty–Approvedandsupported Marley and backed with a 3-year warranty that is twice the length of many VFD manufacturers Benefit Detail Cost Savings: • • • • NEMA Premium Efficiency Motor FIVE YEAR AVERAGE ENERGY COST* $300,000 $200,000 nergyCosts–upto30%savingsvstwo-speed E or 70% vs single-speed* ProcessCosts–VFDsmaintaintightercoldwater set-point temperature control than thermostats to minimize your process cost Rebates–Multipleutilitiesproviderebatesof up to 50% of the drive cost as an energy saving incentive Payback–Thepaybackconsideringthetotalcost savings associated with the VFD package can be aslowastwoyearsorless—useMarley’sUPDATE program to calculate your savings today! more VFD $100,000 MARLEY SINGLE TWO SPEED MOTOR SPEED MOTOR VFD SYSTEM Reducing Fan Speed 20% Reduces Fan Horsepower 50% * Based on UPDATE selection for a three-cell NC8405TAN with 40hp motor per cell running 24/7 for 5 years. Total water flow over the tower is 4500 GPM. Cost is $0.10 per kWh with an assumed annual interest rate of 3%. Cold water set point is 75°F, with an average wet-bulb temperature of 50.7°F, (average seasonal value for Cincinnati, OH). VFD-Motor Package INSIGHT Ease of Purchase: • Single-sourcesuppliervsmultiplepurchaseorders • Coolingtowerspecificcomponentsidentified by Marley • MarleyOEMqualityandsupport • CertifiedVFDstartupassistancefromABB Marley Support and Enhanced Warranty: • ExtensiveServiceRecorddatabasetoidentify needs • Three-yearmaterial-onlywarrantythatcoversthe entire package • AdditionalVFDwarrantycoveragewithcertified startup assistance—material, labor and travel for VFD repair or replacement included • Applicationandtroubleshootingassistancefrom experiencedMarleyControlsteam • • • • • • TYPICAL VFD COMPONENTS SOLD SEPARATELY SOLD SEPARATELY andorAutooperationallowsoperatordirect H control of motor speed Softstartofmotor—enableslesswearto mechanical equipment and less noise than using across-the-line starters DV/DToutputfilteroptionisavailableforlong lead lengths between VFD and fan motor Tripless-designdriveeliminatesmostnuisance faults (under-voltage, over-voltage, flying start, downdraft back drive) keeping the tower running Reducedfanspeedsextendmotorbearinglife and pulls less airborne contaminants into the tower, minimizing maintenance shutdowns— overall sound levels of the tower are also reduced • tandalonesystemmatched S external controller required—status indicators and withRTD:No keypad display provide easy tower control CustomerBMScontrolsspeed theBuildingManagementSystem ofVFD:Let process temperature and control the VFD monitorthe -4-20mA,0-10VDCanalog signals -ModbusRTU,JohnsonControls speed FLN(p1)andBACnet(MS/T) N2,Siemens communications fieldbus Features and Options • • • • • • • LListed U PWMdrivewithIGBTswitching bypass design andintegrated NEMA12indoororNEMA 208through575VACpower choices 3Routdoorenclosure 5%lineimpedancestandard Maincircuitbreakerdisconnect lock-out tag-out padlocks withprovisionsfor SwitchtoisolateVFDfrom servicing voltagesupplywhen | Lenntech info@lenntech.com Tel. +31-152-610-900 www.lenntech.com Fax. +31-152-616-289 MARLEY VFD SYSTEM Methods of Operation pto150hppackageincludestheMarleyCooling U Tower Duty Motor 200hpandhigherincludesaNEMAPremium Efficiencysingle-speedmotor Special Design Considerations 24 12 • Application Range • WARRANTY 36 MONTHS Benefit Detail In the interest of technological progress, | | Printedmaterial all products are subject to design and/or in USA change without notice. ©2011 SPX Cooling Technologies, Inc. IN-VFDM-10