THE DRYING OF AIR CONTINUOUSLY 25 OCT1943 BY AIR-BORNE SILICA GEL By Arthur W. Plummer B.S. University of Kentucky 1939 Submitted in Partial Fulfillment of the Requirements for the Degree of Master of Science in Chemical Engineering from the Massachusetts Institute of Technology Signature of Author Depart ment of Chemical Engineering Signature of Professor in Charge of Research Signature of Chairman Department Committee on Graduate School I / 2~3 A C K N 0 W L E D G M E N T The author wishes to acknowledge the great assistance rendered by Professor C. A. Stokes during the experimental and early writeup stage of this investigation. The use of apparatus and auxiliary equipment previously built by him made it poasible to complete the experimental work at night while on duty at the CWS Development Laboratory. His analysis and conversion of data from the literature and his willingness to cooperate in taking readings during the experiments enabled the author to complete considerably more work in the small time available. Suggestions made throughout the investigation were very helpful and are hereby gratefully acknowledged. 261435 TABLE OF CONTENTS Page No. LOCATION OF TABLES LOCATION OF FIGURES I. II. III. IV. V. VI. VII. VIII. ii- SUMMARY 1 INTRODUCT ION 4 PROCEDURE 22 RESULTS 24 DISCUSSION OF RESULTS 27 CONCLUSIONS 44 RECOMMENDATIONS 47 APPENDIX 48 A. Expansion of Procedure 49 B. Summarized Data 59 C. Sample Calculations 62 D. Results: 73 Plots and Tables E. Location of Original Data 79 F. Calibration Data: 81 Plots and Tables G. Nomenclature 84 H. Literature Citations-. 86 i. LOCATION OF TABLES Table No. Title Page No. Original Data 59 (f)* Temperature of the Surroundings During Runs 1-19, Inclusive 60 Data for Comparison of Gravimetric and Psychrometric Methods of Measuring Humidity 61 IV Table of Calculated Data and Results 73 (f) V Variation in Residual Water Content of Silica Gel with Time of Reactivation in Air at 178 0C. 74 Comparison of Water Balances Calculated From (1) Difference in Weight of Inlet and Outlet Gel and (2) Difference in Humidity of Inlet and Outlet Air 75 Comparison of Gravimetric and Psychrometric Methods of Determining the Humidity of the Outlet Air 76 Percent Fines Produced During Use of Silica Gel 77 Estimated Heat Losses From Column 78 Calibration of 00-550C. Thermometers Used to Measure the Inlet and Outlet Air Temperatures (Ice Point, 00C. Used as Standard). 82 Calibration of Triple Beam Balance Used in Weighing Inlet and Outlet Gels 83 I II III VI VII VIII IX X XI *Indicates that Table follows page number given -iiLOCATION OF FIGURES Figu re No. Title 1 2 3 Follo wing Page No. Equilibrium Data For System, Silica Gel-Water Vapor 11 A. Integrated Heat of Wetting of Silica Gel By Liquid Water 15 B. Partial Heat of Wetting of Silica Gel By Liquid Water 15 A. Integrated Heat of Wetting of Silica Gel By Liquid Water 15 B. Partial Heat of Wetting of Silica Gel By Liquid Water 15 4 Elevation Diagram of Apparatus 58 5 Assembly of Apparatus 58 6 Assembly of Column, Funnel and Flasks 58 7 Sharp-Edge Orifice Flowmeter 58 8 Component Parts of Apparatus 58 9 Residual Water Content of Silica Gel vs. Temperature of Activation 78 10 Inlet Water Vapor Adsorbed vs. Air Velocity 78 11 Inlet Water Vapor Adsorbed vs. Mass Rate of Air Flow 78 Variation in Water Balance Error With Air Flow 78 Variation in Water Balance Error With us/ug 78 Variation in Water Balance Error With L /G 78 Variation in Slip Velocity With Superficial Air Velocity 78 Variatioh in Silica Gel Concentration in Column With Mass Rate of Air Flow 78 a2 13 14 15 16 -Iii- LOCATION OF FIGURES (Cont'd.) Figure No. Title Following Page No. 17 Operating Diagrams for Runs 1-19, Inclusive 78 18 Variation in Adsorption Coefficient, KRHa, With Rate of Air Flow 78 Variation in Adsorption Coefficient, K a, With Rate of G61 Feed 78 Variation in (K a)(G/1000) With Rate of Gel Feea 78 Calibration of Air Orifice Flowmeters 83 19 20 21 -1- I. SUMMARY Although most air conditioning is done by refrigeration, two methods gaining in popularity are absorption and adsorption dehumidification. The latter has been applied in the form of static beds of silica gel which do not offer ideal conditions for adsorption. Furthermore, methods of design for such dehumidifiers are more or less empirical. A system capable of steady state operation has been investigated and conventional methods of design for absorption columns proposed for the system. The drying of air continuously by air-supported silica gel was investigated by passing air and gel (-28 + 48 mesh) at known rates and water content into- an insulated glass column through which the gel was carried by the air. The amount of water adsorbed was determined by (1) difference in weights of the inlet and outlet gel, (2) air rate and difference in the humidity of the inlet and -outlet air, (3) gel rate and analysis of the inlet and outlet gels for water content and (4) calculations employing thermal data, i.e., air and gel rates, air temperature rise and heat of adsorption data. The operating data were correlated in terms of overall mass transfer coefficients, KRHa and Kga, based on driving forces of percent relative humidity of the air and useful water concentration of the gel, respectively. It was found that KR1ja decreased slightly with increase in air rate, which -2is attributable entirely to decrease in "a" because of lower gel concentration in the column at the higher air rates. An equation- derived for Kga involving both air and gel rates is (Kga)(G/lOOO) = 0.0013L1 + 0.35 These coefficients were calculated using equilibrium data determined in the same column by the same method of operation. Lower Useful Water Concentrationsat equilibrium were obtained at a given Percent Relative Humidity than those reported in the literature. This was attributed to (1) a lower rate of approach to equilibrium due to the presence of air or (2) loss of heat from the column. During the experiments it was discovered that a gravimetric method could not be used to measure the humidity of air in the presence of finely divided solid adsorbent due to additional adsorption of water vapor in the lines leading to the drying tubes. A psychometric method was found to be satisfactoty. Percent error in the water balance calculated from thermal data (assuming the average of the other three to b e correct) was attributed to a lower temperature reading at the top of the column than that corresponding to the water adsorbed. The low temperature was due to either loss of heat from the column or insufficient time of contact between gel and air for the heat effect to become fully developed. Temperature measurements at a point three inches above the gel inlet indicated that adsorption occurred almost instantaneously since this temperature was almost equal to that at the top of the column. Recommendations for closer temperature control were made for determination of equilibrium data in any future investigation. It was also recommended that operating data taken on different size gels at various gel and air rates be correlated in terms of overall adsorption coefficients. -4II. INTRODUCTION In the past it has been desired to adjust and control the humidity and temperature of air to be used in homes, commercial establishments and factories for comfort, and in industrial areas where manufacture or storage of certain materials requires narrdwly defined humidity and temperature conditions. Although the methods by which this control is ob- tained are several, most air conditioning is accomplished by refrigeration. Two other general methods which are gaining in popularity, however, are absorption and adsorption dehumidification. These two methods offer excellent control of the humidity but may not offer desired temperature regulation. The latter is obtained by a cooling system installed subsequent to and in series with the dehumidification systems. Both methods have the advantage that air of approximately the same temperature and humidity may be obtained even though the inlet air varies over a considerably wide range provided the dehumidifying agent is introduced into the system at a constant rate, temperature and water concentration. The absorption dehumidification method involves the use of certain salt solutions which are capable of absorbing water vapor from the atmosphere when the vapor pressure of the solution is less than the vapor pressure of water vapor in the air. As the concentration of salt decreases and the temperature increases the vapor pressure of the solution increases until it equals that of the water vapor in the -5Before this point is atmosphere and absorption ceases. reached the solution is withdrawn, concentrated by evaporation and returned to the system. Usually temperature rise rather than decrease in concentration determines the point at which the liquid absorbent shall be withdrawn. absorption system is efficient, excellent control over humidity. The liquid very flexible and offers However, a part of the equipment required must generally be corrosion resistant (unless an air concentration method is used) since evaporation of water from the salt solution necessarily occurs at an elevated temperature. Adsorption dehumidification is accomplished by adsorption of water vapor from the air on the surface of certain solids such as activated alumina or silica gel. It is well known that most solids are capable of adsorbing small quantities of gas or vapor on their surface and that it is retained by a considerable attractive force. It follows that any solid possessing very large surface area exposed to the gas or vapor should be a good adsorbent. Activated alumina and silica gel are known to possess extremely large surface area per unit weight of solid in the form of submicroscopic pores throughout the solid body (7, 10, 23); these two have been used extensively for dehumidification of gases and air. When in use for this purpose the large surface area exerts an attraction for water molecules in the vicinity and adsorbs and condenses them by a tremendous force of attraction. The condensed water is carried by capillary action to the recesses -6of the individual pores. According to Lewis, Squires and Broughton (12) the rate at which the water is transferred to the innermost parts of the gel particle is the controlling factor in the adsorption. This action continues until the adsorbed liquid exerts a vapor pressure equal to that of the water vapor in the surrounding inert gas, at which point equilibrium is reached. These solids have remarkable adsorptive capacities, for example, normal commercial silica gel will adsorb 50 percent of its weight of water from saturated air (4). From this result it has been estimated that the exposed surface area of one cubic inch of silica gel is about fifty thousand square feet. Both of these solids are used in much the same way commercially. Silica gel is a dehydrated colloidal gel produced under closely controlled conditions from sulfuric acid and sodium silicate solutions. chemicals. It is a hard substance inert to most As in the case of activated alumina, adsorption of water by silica gel is purely a physical action, i.e., the particles do not change in shape, size or appearance even at equilibrium. When equilibrium is reached, the adsorbed water may be driven off by heating the gel to at least 300 Fahrenheit and the same gel can be used again with adsorptive capacity unimpatred. Silica gel has been used extensively in industry for dehumidification of air. However, its uses have been confined largely to batch or semi-continuous operations. The types of apparatus generally employed in dehumidification systems are -7- varied but may be represented schematically by the diagram below. .ETAIR A rART RO DSOR13LC ' H TEI aLI DRY Alt ACT IVATING- AIR OUT WAIME AC-IVATIMCr AiI I 1N It is clear that this system operates on the same general principle as certain types of catalytic cracking units used in petroleum refining, i.e., alternately, reaction and regenerative cycles. Cell A above dehumidifies air passed to it while cell B is being reactivated with hot gases. When the latter operation is complete and the gel cooled, cell B is shifted to dehumidify air and the gel in cell A is reactivated. In this way conditioned air is obtained continu- ously from a system operated batchwise. This system is em- ployed in several small dehumidification units commercially available (2). Another system available on the market consists of a rotating cylindrical bed of silica gel arranged in such a way that one half the bed dehumidifies air while the other half is being reactivated by hot gases. As the gel moves from the reactivation zone it is cooled and then passes to the dehumidifying zone. The two zones are separated by baf- fles sliding closely on the surface of the cylindrical shell holding the gel. publications (2). This system is described in the manufacturer's -8These two systems have the disadvantage that the best gel-water vapor contact is not obtained, inasmuch as a static bed is employed during both the dehumidification and reactivaIn such a bed the points of contact between the tion cycles. gel particles are probably untouched by the humid air and thus are ineffective in removing water vapor therefrom. The ideal gel-water vapor contact would be obtained in a system where the individual gel particles were moving about in and were completely and continuously aurrounded with the air to be dehumidified. Mass transfer of water vapor could then take place from the air to the entire surface of the particle and, furthermore, motion of the particle itself would induce local turbulence which would improve the transfer. This could be realized only in a system where the gel particles were in continuous motion in the air without striking neighboring particles. This condition can be approached closely, how- ever, by keeping the gel in motioh in the air with only momentary collisions of the particles. With a system in which these conditions are approached the weight of silica gel required per unit of air for dehumidification to a certain point will be less than that required where a static bed of gel is used. Such a system has been designed (13, 14) for utilizing solid adsorbents such as silica gel for separation of gases. Here the gel is fed into the gas stream at the bottom of a colun, is carried upward in the gas and is separated therefrom at the top by a cyclone separator. As the gel passes to -9the top the particles move about in random motion sidewise and "jiggle" in the gas stream, thereby effecting aimost perfect gel-gas contact. Another system (15) has been designed to give very nearly the same conditions. However, here the gel is fed at the top of the column, flows countercurrent to the gas stream and is removed at the bottom. Both of these systems have been commercially used for dehumidification and separation- of various gases with widely varying boiling points. It is the purpose of this investigation to conduct experiments with air-borne silica gel in a small laboratory column, collecting operating data and correlating it in such a way that design of larger columns may be accomplished. Literature Survey Before proceeding with experimental work efforts were made to locate in the literature, equilibrium and thermal data for the system silica gel-water vapor. Although con- siderable data were found, they were not readily applicable to the present problem since in most cases the experiments were conducted by either passing water vapor through static beds of silica gel or permitting water as vapor or liquid to remain in contact with the gel for long periods of time until equilibrium was obtained. The present investigation employed an entirely dynamic method, i.e., both the silica gel and an air-water vapor mixture were constantly in motion. Furthermore, in many cases previous experiments were performed -10- in the absence of air. According to other investigators this will affect greatly the adsorption of water vapor. Patrick and Cohen (16) have found that the rate of adsorption of water on silica gel is independent of permanent gas only when the latter is present at a pressure less than 0.5 millimeters of mercury and that the rate is inversely proportional to the molecular weight and partial pressure of the inert gas if the latter exceeds 0.5 millimeters. Patrick and McGavack (19) have shown that in adsorption of SO2 by silica gel, a pressure of air over the gel'too small to materially affect the calculated pressure of S02 would increase by several hours the time required for equilibrium to be attained. They found also that a higher degree of evacuation was required in the system for water vapor than for S02 in order that equilibrium might be established in the same time. Thus, any data obtained by a static method in the absence of air would not be applicable to the present investigation. From the standpoint of academic interest, however, data obtained by the several different methods are given in Figure 1 for comparison with data taken during this investigation. Ray and Ganguly (21) conducted a series of experiments to test the validity of the Patrick adsorption equation V = K(P /P)l/n. A discussion of this equation is given in the original article. Data were obtained by contacting air- free water vapor and silica gel until equilibrium was reached. The gel used was obtained from the Silica Gel Corporation -11and was teeated carefully to remove all acid and air. Percent residual water in the gel was found to be 5.04 per cent (basis not definitely stated). The data were recalculated and plotted on Figure 1 as Percent Useful Water Concentration (Grams Water Adsorbed per Gram Initial Wet Gel) versus Percent Relative Humidity. This method of treatment for equilibrium data, reported by Dehler (5), tends to bring all data together which were obtained at different temperatures falling within a fairly narrow range (40-1000F.). The data of Ray and Ganguly do not agree particularly well with other data except at low Percent Relative Humidity. Ewing and Bauer (6) permitted silica gel to stand over concentrated sulfuric acid out of contact with air at 15, 25, 40 and 60 degrees Centigrade until equilibrium with the water vapor had been established. The equilibrium water con- tent of the gel was determined by Tasting to dryness; results were expressed as percent water (wet basis). These data plotted on Figure 1 are in good agreement with others up to Useful Water Concentrations of approximately 25 percent. Above that point however, Ewing and Bauer obtained higher Useful Water Concentrations at a given Percent Relative Humidity than did other investigators. Patrick and Greider (17) obtained equilibrium water contents of gel used in heat of wetting measurements in the absence of air. These agree reasonably well with other data but the shape of the curve at high Percent Relative Humidity is quite different from all others (see Figure 1). PS 4j, 44. +~I -~~~~... - + .. 1. .. I .. ~ to 94 .. .. .. 0 - .. . ...... .. I 14 ...... ... ... . . . . .. ... . ii wimuld 0R Ma 0 .... H :- :: :: -- - to 0111 2 0 I0 0 U -12Experiments performed with presence of air included those of Patrick and Opdycke (20) who mixed air saturated with water vapor with dry air and passed the mixture over static beds of silica gel prepared three years previously by Patrick and McGavack (21). The gel was kept sealed in air tight containers and analyzed to give a water content of 3.57 percent (dry basis). They found that "it was sometimes necessary to continue the flow of (water) vapor for so long as three days" in order to obtain equilibrium and the results indicated that equilibrium was still not established in some cases. Figure 1 it From is evident that the data of Patrick and Opdycke agree with other data although they obtained slightly higher Useful Water Concentration than did other investigators at a given Percent Relative Humidity. Considering the fact that the equilibrium data mentioned above were taken by several techniques on various gels prepared by different methods, the curves drawn through these data on Figure 1 fall fairly close together. It is true that even though two silica gels are prepared by the same method they will probably possess a different number of capillaries of different diameter. This obviously will cause a difference in the internal volume, surface area, capillary force exerted on the adsorbed water and consequently differences in the equilibrium data of the two gels. Therefore the agreement between data taken at random from the literature appears to be even more remarkable. As mentioned above none of the data found in the literature -13was applicable to the present investigation. However, it was found that data were available from the Davison Chemical Corporation on the actual gel used. These data were obtained by passing mixtures of water vapor and air through static beds of silica gel (Designation No. 659528-2000) and after equilibrium was attained the percent useful water concentration was obtained by blasting the gel to dryness (the initial water content of the gel, wet basis, was approximately 5 percent). These data are also given in Figure 1 and are seen to be in fair agreement with other data. Even though the latter data were taken on the same gel as used in this investigation it was felt advisable to obtain more data on the same gel using the dynamic rather than the static method. Throughout these determinations it was felt unnecessary to control the temperature closely from one experiment to another because of the fact that the method of plotting tends to bring together all data taken at temperatures falling within a reasonably narrow range. The data so obtained gre also given in Figure 1. Thermal Data When water vapor is adsorbed by silica gel a certain amount of heat is evolved dependent upon the initial water content of the gel and the temperature at which adsorption occurs. Considerable controversy has existed in the past concerning the cause of this heat evolution. It is a gen- erally accepted fact that when water vapor is adsorbed by solids possessing extremely minute pores condensation occurs -14and the heat of condensation is given off. However, the amount of heat evolved during adsorption is generally somewhat greater than the latent heat of condensation at the temperature of adsorption. This additional amount, called the heat of wetting, is the main subject of controversy. Lamb and Coolidge (11) have felt that this heat is evolved aa the result of liquid compression in the capillaries of the gel and by the forces of molecular attraction. Harkins and Ewing (8) have called it heat of spreading and have claimed it is due to changes in surface energy involved. In agreement with the latter, Patrick and Grimm (18) have found it possible to calculate quantitatively the heat of wetting from changes in the surface energy. Patrick and Greider (17) have shown by heat of adsorption determinations at 0 degrees Centigrade that the heat of wetting is probably not due to compression of water at the surface and have pointed out that if the water were compressed the principle of LeChatelier would call for absorption rather than evolution of heat. They also point out that since the change in surface energy is negligible from 0 to 25 degrees Centigrade, if the heat of wetting at equilibrium is the same at the two temperatures, it is probably due to surface energy. In order to use temperature increase data in this investigation for calculation of material balances around the column sources of heat of wetting data were sought. were found but only the following could be applied. Several -15Ewing and Bauer (6) determined the heat of wetting of several silica gels with different water contents. Their data, given as the observed heat evolved per unit weight of initial wet gel when this gel was permitted to come to equilibrium with liquid water, were plotted in Figure 2A to give an integrated heat of wetting curve. The slopes of this curve plotted in Figure 2B against the initial water content of the gel give the partial heat of wetting per unit weight of water adsorbed. At an initial water content of 5-6 percent (dry basis) the partial heat of wetting was approximately 250 Btu per pound of water adsorbed. Thd data of Patrick and Greider (17) was treated similarly (Figures 3A and 3B) and gave a partial heat of wetting of approximately 275 Btu per pound of water adsorbed. Design of Silica Gel Dehumidifiers Methods of design for silica gel dehumidifiers in the past have been largely applied to static beds of gel. The methods for the most part have been empirical and have been based upon assumptions which are probably not entirely true. For example, one empirical method reported (5) was used to calculate the size of the adsorber necessary to dry a certain volume of air, a definite amount. It was assumed that at the end of the adsorption period, (1) the gel in the bottom of the bed would be in equilibrium with the inlet air and (2) that that at the top of the bed would be in equilibrium with the outlet air. In the first place, to satisfy this condition the adsorption must necessarily be instantaneous T I:: - t. * . .. - 1:: .1:;:: op Lit 0# ~tti±~+f H I I R, :f::.: ~1T ~ I I Firh I T-A __ 4 . I i. 15t1''1 iii .... ~~~~~~~ ~zi~1 441 s-4 i I. III i T- T '':1.1. .~ 0 I I .111 I S iJlRLLli....L.LIam _________ If i 117FT 4d 44~4Jflhi I-Al :4: +4++4 ................ I j I T 1#1 2H 1-u lIIIl1lLin1IEWT'~'1TI'-iTT~ -T- I i++- 4-1-T HIiTTFI'1..~, -l ,H; 44- 44 YT jiT!JiTT1if4 iu~innI 1u11.nHIPI>IfT jiT IE1 I .4- I I I 1111II Ilili~i.LI!IrIIIIIIIIlIIIli..liltII ... iiv S-9-qI.IA~9 59*99 II I.IIflIl.lllflH. I ...... 7ii~ 4- * LIJ..L..1.-.XL I 2LJLi1 iLI{ ~iIiP.IitflhTitIi111.III1IL1iJitt FVfJ'flJ-J1..L2.I~I..2!11UiiI! hJit~IIUIJ 4HII 44-4 mIJ -V ii: 9:4 Ii. I j~i I 11111. T I 1-7 4f~4444444.-~ ; 44 j- - 44;* ... F.1.. .. ... vti ira n~iiJ..1I~i~i~itII~v~riii: ~ui~I n ......i..ALILL 7 * 1 , 1 , i H i 114444-4 T 49-+- 1 TIT'l II ttt.m*it 11.511 liii [~b444f~T~ z'~ 1 4 4- ' -fL~1 + ti I-, 44 I,. ;:i:'::it' I fSISJIIIT 44*4 W A ...-, jil .......... -t-t - i ....... 1111 fifffiH i 4- u + U ~1t -S A -4-4 f -P t jr .... ... .... I ..... son l I .. . 4 LL~~4..L4 :::lU~ 71 ~1~44P44trht~ t I-. .. .... ... .... ot ................. ... .... ... . .... ... . .. . ... . .... .. .. . ... . .... .. .. .. . .... ... .... ... . .... . .. . .. .... ... '..: .. :., :.'* * *, T . . . . . .... ... .... .... .... . . . . . . . . .. .. . . . . .... T ... . . ... I.... . . a .... .... ... .... .. . .... . .... .... . ... ... . . . . . .... .. ... ... .. .. .... ... .... ... .... . .. . .... . . .... .. . .. .. .... .... .... ... . ..... .... ... . .... .... .... .. . . . . .... .... .... .... ..... .... .... .. .... .. ... . .... .......... ... .. .. .... . . . . . ... ... .. .. . ... .... . . .. .... .... . .. .. . . . . .. .. .. .. .... ... . .... .. . .. . . . .. . . . ... .. . . . . . ol .. ........... ... .... .... ... . .... ... ... .. ... .... . .... .... .... ...... ... . . ... . . .. Aw .... ... ... . ... . . . . . . . .... ... . . . .. ... .... .... .... .... .... ... . . .. .. .... . . . . . .. .. .. .. . .. .... .. .... .. .. ... . .. . ... . .. .. . .. .. . . ... . Owl . . . . .... . ... .... .. . . ... .... .. 7 lium Iwwlww .... ... .... ... .... ....I.:. . ... . .... .. ... . ... .... .... . .. .. . ......... .... ..... .... .... ... .. . ... .... .... ... .... .... .... .... .... ... .. .... .... .7 ...... . .. ... ....... ... .... .... .... .... .... .... .. .. .... .... .... .... . .... .... .... .... ... ... .... .... . ... ....... .. ... .... ... ... ... .... .... .... .... .... .... .... .... .... f .... .... .... .. .... .. .... .... .... .... .... .... ...... P . . .... .... .. . .... . ... .... .... .... .... .... .... .... ..... ..... .... .. ... .... .... .... .... .... . 4O.F .... ... " .... .... .... .... .... .... .. .. .. IT mr, ... . ... .. . . 'T . . ..... .... .... .... .... . .... ... ...- 1 ::. .... .... .... .... ........ "a ....... ......... . . .. .... : ... . .. .. . .. 7--7= 4- + . ... .... .... .. ....... .... .... .... . .... .... .. .. .... .... .... ... ... ... ... .... .... .... .... ... .... ... .... .... .... .... ... ...... . .. .... .. ... 1w. .. .... .... .... .... .... ... .... .. : . TO Rat irl FAN a .... .... .......... .... ... .... ... COW . .. .... . .. . .. .... .... ..... .. L I . . .. . .... : : :: .-: ... . . .... . .. .. .. . ... -16even when the gel and air passing through are near equilibrium. Obviously, this is probably not true for the system water vapor - silica gel due to extremely low driving forces near equilibrium and it certainly will not be true for the system encountered above, namely, water vapor - air - silica gel. Secondly, the mass of gel calculated to adsorb the required total amount of water would adsorb rapidly at first but the rate would decrease as equilibrium were approached and the humidity of the effluent air would change. It seems therefore, that some more rigorous method of design should be projected for static beds of gel or for some other system into which fresh gel could be fed and in which a steady state of operation would be reached soon after adsorption began. The lat- ter procedure appears to offer more promise inasmuch as the system investigated during the present experiments is the type which could be operated under steady state conditions. Several analogies can be drawn between this system and the usual type of-absorption column. When absorbing a gas from a stream of air in a liquid absorbent, both liquid and gas-laden air are passed at constant rates into a column so arrangedthat the mass transfer area, i.e., the liquid surface will be essentially constant and large per unit volume of the column. After a short per- iod of operation the column reaches steady state and the inlet and outlet conditions remain the same so long as the rates of feed and other factors remain the same. The operat- ing data of such a system can usually be correlated in terms -17- of mass transfer coefficients which account for the diffftsivity of the gas in air, the temperature and the pressure in the column. The equations for such a system are given in The Principles of Chemical Engineering (22) and are discussed fully. It is noteworthy that from equations 5 and 6 on pages 486 and 487, respectively, of this same reference (22) G(Y - Y2) = K'aV(Y* - Y)av.. L(X 2 - Xl) = KLaV(X* - X)av. (1) (2) a value of an overall capacity coefficient Kla or KLa can be calculated if the inlet and outlet conditions, liquid and air rates and equilibrium relatibns for the system are known. With a value of this coefficient it is clear that the volume of a column could be calculated for certain specified inlet and outlet conditions. This would be very desirable in the silica gel type dehumidifier investigated. The analogies between the above absorption system and the "jiggling" of silica gel are as follows: (1) A solid adsorbent is fed to the column at a certain definite rate. (2) Humid air is also passed through the column at a constant rate. (3) Although the gel concentration is not constant throughout the column, the overall weight concentration is the same at a given air rate for a given gel particle size and the gel will probably be distributed in the same manner throughout the column during a single and during each successive operation. Thus, an apparent constant concentration and gel surface area exist. (4) Steady state operation is possible. (5) Equilibrium data for the system are known or may be determined. Thus, it appears that it may be possible to calculate from sufficient operating data a mass transfer coefficient which could beused in subsequent calculations to determine the size of column necessary to adsorb a certain amount of water with a given gel particle size at a specified air rate. Since the equilibrium data for the system silica gelwater vapor-air are given in terms of percent relative humidity and useful water concentration it would be desirable to obtain a coefficient also in terms of relative humidity or useful water concentration driving forces. The former could be written as follows: KRHa = G(Hl - H2 ) V(RH - RHe)av. (3) &nd the latter K~a = L (UWC2 - UWc 1 ) V(UWCe - UWC)av. Remembering that % RH = H = [(p)/(n -P) 100 (p)/(ps) and (Mw/Ma) (5) then the percent relative humidity becomes RH = H (0.62 + H8 ) Hs(0.62 + H) (6) RH = (100)(H)/(Hs) approximately (7) or -19Substituting this value in equation (3) there is obtained a/H K RH = G(Hl - H 2 ) s V(H - He)av. (8) which is equivalent to the usual equation given for dehumidification, namely, G(Hl - H 2 ) = k'aV(H - He)av. (9) Thus, the operating data could be used to calculate a value of K § RH which would be constant for isothermal operation but would vary~ during normal operation which is essentially adiabatic. However, by expressing driving forces in terms of relative humidity (which seems justified in view of the fact that the equilibrium data correlate well over a reasonably narrow temperature range using percent RH and useful water concentration) an overall coefficient of mass transfer may be calculated which should be constant throughout the column for a given set of operating conditions. The coefficient, KSa, defined by equation (4) is immediately equivalent to the usual overall liquid side coefficient, KLa given on page 487 in The Principles of Chemical Engineering (22) and can be calculated from operating and equilibrium data available. As is well known, the path of absorption in the isothermal case can be rppresented by a straight line on the appropriate equilibrium diagram. It is interesting to note that a similar "operating line" can be drawn for the adsorption column used during this investigation, even though the operation was not isothermal. The equilibrium diagram used is a plot of -20UWC against RH so that the slope of a straight line on this plot would be represented by the equation (UWC)2 (RH)1 - (UWC1 ) slope (RH)2 (10) Remembering that RH = (100)(H)/(Hs) approximately, (Uwc)2 - (UWC)1 100 [(H/Hs)1 - (H/H5 ) = (11) slope If the adsorption were isothermal say at a temperature t1 , then slope1 = (UWC) 100(Hi - (WC)(12) - H 2 )/Hs( 1 - or (100)(slope1 )/H. (UWC)2 - (UWC)1 (H 1 - H 2 ) (13) Now from a water balance around the column (L 1 /100) (Uwc)2 -- (UWC)1 j = G(H - H2 ) (14) or (UWC)2 - (UWC)l (Hl - H2) (100)(G)/(L 1 ) and substituting from equation (13), the slope of the operating line at the bottom of the column becomes slope1 = (G)(Hsl)/(L1 ) (15) and. at the top of the column the slope of the operating line is slope 2 In this way, = (G)(H )/(L 1 ) (16) the operating line can be placed if the inlet and outlet temperatures, are known. 5 humidities and useful water concentrations It is clear also that from equation (4) the overall transfer coefficient, K a could be obtained by graphical integration -21of the area between the operating line and equilibrium curve. With these coefficients, determined (by direct calculation or by graphical integration) at different gel and air rates for various mesh size gels, they could be used in all subsequent design calculations. Summarizing, the purposes of this investigation are (1) to determine operating data at several air and gel rates for a given size gel, (2) to determine equilibrium data for the system silica gel-water vapor-air at the same conditions under which the operating data were collected and (3) to correlate the data if possible in some manner which could be utilized for future design calculations, perhaps in the form of overall mass transfer coefficients. -22III. PROCEDURE Silica gel (used in previous runs) containing a small percentage of useful water was reactivated by heating in air at 1780 Centigrade from 2 to 72 hours. Upon removal from the oven the gel was permitted to cool to room temperature in a dessicator after which a portion was weighed out in a long neck glass flask for the run. The humidity of the inlet air, taken from the dompressed air line, was determined by means of a et- and dry-bulb psychrometer and the flow through the column was adjusted to the desired quantity (from 1 to 2 cubic feet per minute) as shown by the pressure difference across a sharp-edge orifice. Silica gel was fed to the column from the long neck flask through a simple feed device and the following readings were taken at five-minute intervals. (a) Temperatures of the inlet and outlet air. (b) The air temperature three inches above the gel inlet point. (c) The wet- and dry-bulb temperatures of the outlet air. (d) Flowmeter reading. When steady state had been reached in Runs 1-7 a small stream of air was passed through magnesium perchlorate drying tubes by means of a siphon arrangement. At the completion of these runs the increase in weight of the tubes was determined by weighing on an analytical balance and the humidity of the outlet air was calculated. The wet- and dry-bulb temperature of the outlet air was not measured during these runs. -23At the completion of all other runs the outlet gel was weighed to 0.1 gram and samples of both inlet and outlet gel were taken for analysis for water content. Equilibrium runs were made by recirculating the gel in the column continuously with the air flow adjusted to approximately 2 cubic feet per minute. 'When the inlet and outlet temperatures of the air were equal or the outlet temperature remained constant with and without the gel in the column it was assumed that equilibrium had been reached and samples of gel were taken for analysis for water content. The absolute humidity of the air was determined with a wet- and dry-bulb psychrometer and the relative humidity calculated from known saturation pressures of water at the temperature observed at the top of the column. The temperature of the inlet air was controlled (in a given run) by a water to air heat exchanger and the humidity of the inlet air was adjusted by passing the air through a bubbler designed to humidify at least 3 cubic feet per minute up to 90 percent relative humidity at the humidifier.. The calculations performed for each run and a detailed .description of the operation and construction of the apparatus used are given in Appendices A and C, respectively. -24IV. RESULTS The results obtained during this investigation are listed below. Plots and tables of results are located in Appendix D, Results: Plots and Tables. 1. The residual water content of the silica gels heated 2-72 hours in air at 178 degrees Centigrade agree well with other data obtained from the literature (6, 2L). These results are plotted on Figure 9. 2. Time of reactivation (2-72 hours) of the silica gel in air had no effect on residual water content. Table V gives the values obtained after various timesof reactivation. 3. Humidity of the effluent air could not be measured satisfactorily by the gravimetric (drying tube) method without further provisions for removing gel fines from the air stream. Comparison of values of Water Adsorbed/(hr)(ft.i)calculated from data taken by this method, by gel weight difference and by the psychrometric (wet- and dry-bulb temperature) method is given in Table VI. 4. The psychrometric method of determining outlet air humidity agrees with the gravimetric method when silica gel is not in the colurgn; howeer when gel is "jiggling" the latter method consistently gives lower values of humidity than the former. A comparison of values obtained by the two methods with and without gel "jiggling" is reported in Table VII. 5. Silica gel fines produced by use of the gel from Run No. 7 to No. 15 is approximately 10 percent (see Table VIII). -256. Estimated heat losses from the column are slightly greater at the lower values of the mass rate of air flow, G, (Runs 1-13, inclusive). Table IX gives the estimated heat loss from the column for Runs 1-19. 7. The air temperature three inches above the gel inlet point was almost equal to the outlet air temperature for Runs 15-19, inclusive. 8. The percent of the inlet water vapor adsorbed by the silica gel varied inversely with the superficial air velocity. Figure 10 gives the relationship which can be represented by the equation Percent inlet water vapor adsorbed = 213/(us) 1 .0 3 The same relation is shown on Figure 11 for percent inlet water vapor adsorbed and G, the mass rate of air flow. 9. The percent error in the value of the Water Adsorbed/ (hr)(ft2) calculated from heat of wetting, air and gel rates and temperature rise data was greater at higher rates of air flow, greater at lower values of the ratio u./ug, and went through a minimum as the value of L /G increased. Figures 12, 13 and 14 indicate the manner in which'the percent error changes with the variables mentioned. 10. The slip velocity, us - ug, increased with increase in air velocity up to approximately 6.5 feet per second and then decreased (see Figure 15). 11. The concentration of silica gel in thle column varied inversely as the mass rate of air flow, G. Figure 16 indicates the exponent on G to be approximately -8.4. -2612. Operating lines for all runs placed on an equilibrium diagram (see Figure 17) were either very close to straight lines or were definitely S-shaped. 13. Values of the overall adsorption coefficient, KRHa, (lbs. of water vapor adsorbed per hour per cubic foot per unit RH difference) became smaller as the mass rate of air flow, G, increased. The change in coefficient with air rate is given on Figure 18. 14. The overall adsorption coefficient Kga (lbs. of water vapor adsorbed per hour per cubic foot per unit % UWC difference) increased with increase in the gel feed rate. The value at a given gel rate depends on the mass rate of air flow, G, the higher values being obtained at lower rates of air flow (see Figure 19). 15. Values of (Kga)(G/1000) plotted against the gel feed rate, Ll, give a straight line represented by the equation (Kga)(G/1000) = 0.0013L1 + 0.35 (see Figure 20) 16. Equilibrium data obtained during Runs 20-28, inclusive, indicated that lower values of Percent Useful Water Concentration were obtained at a given Percent Relative Humidity than those found in the literature. Figure 1 gives the curve plotted from the experimental data and also the data obtained from the literature. -27V. DISCUSSION OF RESULTS The residual water content of the reactivated silica gel when plotted against temperature of activation gives a point or small spread of points which fall near the curve obtained when data from the literature are treated similarly even though the latter were obtained largely under vacuum. The time of reactivation had no apparent effect on the residual water content of the silica gel (the water content varying from 4.71 to 4.88 percent, dry basis, see Table V) probably because of the fact that the amount of water left on the silica ge.l even after short time of reactivation is held by very strong attractive forces which could be overcome only by elevating the temperature considerably or evacuating the system. It might also be possible that the presence of even small amounts of air would increase the time of transfer of water from the inner portions of the gel to the surface and thus preclude the possibility of detecting any effect of time of reactivation on residual water content. The former explanation is probably more nearly the correct one, however, inasmuch as the amount of water left in the gel may form a monomolecular layer in the large part of the capillaries and thus be held strongly on the surface or it may rest in the apex of the conical pores and at this point be held by strong attractive forces or very high surface tension. Considerable difficulty was experienced during Runs 1-8, inclusive in measuring the humidity of the outlet air by passing a small stream through drying tubes containing magnesium -28perchlorate. In all cases, the water balances calculated by usibg the value of the humidity, H2 , obtained by this method were higher than calculated from the difference in weights of the inlet and outlet gels. In other words, the humidity observed by this method was lower than the probable true value existing at the top of the column. This can probably be explained by the fact that small amounts of gel powder carried into the air line leading to the drying tubes adsorbed additional water vapor from the air stream thus permitting smaller quantities to reach the tubes. The increase in weight of the tubeswould, therefore, be less and the calculated humidity would be lower than that existing at the top of the column. This explanation is substantiated by the fact that deposits of powdery gel were observed in the small air line leading to the drying tubes. It is easy to visualize how the gel might be transferred to the air line and deposited. The amount of air withdrawn through the drying tubes was very small, varying from 5 to 12 liters total, and thus the air velocity through the tubing was low. Under these conditions any gel passing the small glass wool filter in the air line would settle out before reaching the tubes and would adsorb additional water. Beginning with Run 8, attempts to determine the humidity of the effluent air by #eans of the gravimetric method were discontinued and the psychrometric method adopted. Before proceeding with measurements using this method, however, it was checked against the gravimetric method with no silica gel -29"jiggling" in the colunn. It was found that the two methods gave the same results, 0.00808 for the gravimetric and 0.00810 for the psychrometric method. Thus, it was shown that the latter method would give accurate values of the humidity. The question immediately arises as to the effect of silica gel fines in the air stream passing over the wet- and drybulb thermometers, i.e., why will not the silica gel fines adsorb additional water from the air stream thus causing low values of the humidity to be observed also by this method. It is probably true tha.t some additional water vapor is adsorbed by the gel fines in the air passing to the psychrometer but the amount of air withdrawn is much greater than that passed through the drying tubes and thus the velocity in the air line was sufficiently high to permit (1) no gel deposition therein and (2) very low time of contact between the air and gelfines before it reached the psychrometer. Thus, the amount of water vapor adsorbed would ptobably be small. Furthermore, the gel passing to the psychrometer in the air stream would strike the wet-bulb of the thermometer, adsorb water, liberate heat of wetting and thus cause a somewhat higher temperature to be observed than would be normally. Obviously, then these two effects are offsetting and it may be that values of the humidity very near the true value at the top of the column were observed. The magnitude of these effects were not in- vestigated. The perdent gel fines produced by using the gel from Runs 7-15, inclusive was approximately 10 percent. Inasmuch as -30the amount of silica gel screened to -28 + 48 initially was approximately twice the amount used in most runs, the gel rescreened before Run 7 and after four runs only. Run 15 was used in It is probably true that the "jiggling" operation produced most of the fines, for it was during this time that the gel particles were spinning violently in the air stream, striking each other many times as they passed through the columb. Unfortunately, no other data were taken to indicate how long a given silica gel could be used before the fines produced prohibited its further use. is an important point and should be investigated in This the future. Heat losses from the column were calculated by estimating heat transfer coefficients from appropriate empirical At the lower rates of flow equations obtained from (22). where G was approximately 1000, the Reynolds number, DG/u, indicated the flow to be in the streamline region; the inside film coefficients were calculated using an equation for the streamline region (equation 18, page 125 in (22) ). With these coefficients, the overall coefficient of heat transfer, U, was found to be approximately 0.26-0.27 and the heat losses calculated were found to be greater than at the higher rates of air flow where G was near 2000. At the latter rates the flow through the column was close to turbulent (Re above 2100 and less than 7000) and the values of U were 0.29-0.30. How- ever, the mean temperature difference existing for Runs 14-19 (G approx. 2000); thus, the estimated heat losses were greater. -31Another point to be considered is the fact that at the lower air rates the gel concentration in the column was greater and in spite of the fact that the flow according to the Reynolds number was streamline, it was probably definitely turbulent due to motion of the gel particles. Thus, the coefficients calculated at the low air rates are probably low and the heat loss from the column is actually greater than that estimated as given in Table IX. Furthermore, at the greater gel con- centrations (lower air velocities) most of the gel was concentrated three inches above the gel inlet point and the air temperature at that point was almost equal to that at the top of the column. Thus, the temperature driving force between the air and surroundings was somewhat greater over more of the column than was calculated in the heat loss estimations. Again, then the heat losses at low values of G were probably greater than those estimated and may have Peen considerably greater than the heat losses at higher values of G. As mentioned in the preceding paragraph, the air temperature at a point three inches above the gel inlet was almost equal to that at the top of the column. This seems to indicate that initial adsorption of water vapor occurs almost instantaneously inasmuch as the time required for the gel to traverse this small distance at the higher rates of air flow is extremely small. This may be explained at both high and low air rates by the fact that at the gel inlet the air velocity is higher than at any point above and due to the inertia of the gel particles, the slip velocity at that point is probably greater than it is farther up the column. At low air rates, in addition to the probable greater slip velocity the concentration of igel at the bottom of the column was greater than in the upper portions. Thus, the conditions for transfer of water vapor from the air to the surface of the gel were more nearly ideal than at any other point in the column. However, this does not explain how the gel itself was capable of adsorbing water vapor more rapidly at that point. This may be explained in the following manner which is in accord with most theories of adsorption of water vapor by silica gel. The residual water on the freshly reactivated gel probably lies near the apex of the conical pores or along a portion of the surface thereof in a monomolecular layer, thereby leaving the inlet to the pore or capillary relatively free of water and capable of rapid adsorption up to the point of local saturation (that is, up to the point where the inlet to the capillaries were filled with condensed water). When this condition was reached the rate of transfer of the water from the surface of the gel to the center became controlling and not only did the rate of adsorption of water vapor from the air decrease but the amount of heat eVolved from that time was the heat of condensation of a very small amount of adsorption plus the heat of wetting of the gel surface by the total liquid water as the water was transferred toward the apex by capillary action. This amount of heat was relatively small compared with that evolved during the f irst -33stages of adsorption, i.e., heat of condensation of a large percentage of the total water vapor adsorbed in the coluon. Thus, in this way the temperature rise of the air within three inches above the gel inlet was almost equal to the total rise throughout the entire length of the column. The fact that the percent of the inlet water vapor adsorbed by the silica gel decreased as the superficial air velocity increased may be attributed to the fact that (1) the gel concentration in the column became progressively smaller, (thereby decreasing the transfer area) and (2) the time of contact between the gel and air was progressively less. Even though the rate of transfer of water vapor from the air to the gel may have been equal in all runs, if the area of transfer and the time of contact were smaller, the absolute amount of water vapor adsorbed would be smaller. However, since the total amount of water vapor passed through the column at superficial velocities of 7-8 feet per sedond was approximately twice that at velocities of 4 feet per second and the percent inlet water vapor Adorbed was only half then the absolute amount of water vapor adsorbed was nearly the same at both velocities. This appeared to indicate that the rate of adsorption at the higher velocities was considerably greater per unit area of gel surface. This is substan- tiated somewhat by calculations of overall transfer coeffidients discussed later in this section. The water balances calculated by four independent methods are in very good agreement when consideration is taken of the -34fact that the amount of water vapor adsorbed in all runs was small and that two of the values (gel weight difference and gel water content determinations) were obtained by taking the difference between relatively large numbers. (see Table IV) that in all runs except 4, 6, 9, It is clear and 17 the value of the water adsorked/(hr)(ft 2 ) calculated from heat of wetting, gel and air rate and temperature rise data are smaller than any other. This could be doe to (1) a smaller indicated temperature rise than that corresponding to the amount of water vapor adsorbed, (2) to an error in the total heat effect calculated per pound of water adsorbed or (3) to errors in measurement of the gel aid air rates. The former is the most likely cause for the discrepancy since the temperature rise of the air depends on the transfer of the heat of adsorption from the gel to the air and if' the time permitted for this to occur is not sufficiently great, the full temperature rise corresponding to the water adsorbed will not be observed. From an examination of Table IV and also Figure 12 it is evident that the percent error in the water balance calculated from thermal data (assuming the average of the three other values to e nearly the correct) was greater at the higher air rates. This might be due to smaller heat transfer coefficients at the higher air velocities or to insufficient time of contact between the gel and air. The former seems unlikely although it will be pointed out later in the discussion that such a condition might exist. It is more likely that insufficient time of contact is the main reason for the larger percent error since it is well known that particularly in the presence of air the time required for the full heat of adsorption to be developed and re-transferred to the air is extended considerably. Most certaihly then the smaller the time of contact between the gel and air, the greater will be the observed percent error. In an effort to develop a more complete and definitive picture of the cause for the discrepancy in this water balance, the percent error was plotted against the ratio of the superficial and gel velocities, us/u i(Figure 13) and also against the ratio L1 /G (Figure 14). By the former method the percent error appeared to be somewhat greater at the lower values of the ratio, us /u 9 i.e., when the superficial and gel velocities were nearly equal or approached each other the error was greater. This appeared to be a point in favor of lower heat transfer coefficients since the closer the two velocities, the lower the slip velocity. However, it so happens that only at the higher air rates were the velocities approaching each other and at the higher velocities the time of dontact was small. The second method of plotting indicated a minimum in the percent error as the value of L /G increased. Examina- tion of the data in Table IV will indicate that the low values of Ll/G (0.14-0.20) were obtained with (1) both G and Ll and (2) average values of Li. low values of high values of G and both high and The points so calculated placed the left end of the curve shown in Figure 14. Obviously, at high values of G and both average and high values of Ll the gel concentration is low in the column and the time of contact between the gel and air is small. Thus the error observed for these runs could be attributed to the time factor. When both Ll and G were low, the gel concentration in the column was relatively high and therefore, the gel velocity was low. Although this means that the time of contact between gel and.air was relatively great, it also means that if approximately the same degree of turbulence existed as at higher gel rates, the heat loss to the surroundings was probably greater and thus a low outlet temperature was recorded. Other than this, there appears to be no reason to explain why the error should be greater for runs where the values of L and G were both low. The right end of the curve in Figure 14 was placed by using values of Ll/G obtained from low values of G and high values of Ll. Since the gel con- centration was approximately the same at equal air velocities and independent of the gel rate, the slip velocity existing during these runs was somewhat lower and conditions for heat transfer not quite as good. Furthermore, since the gel rate was high and the gel concentration in the column essentially unchanged, the gel velocity was greater and the time of contact between gel and air in the column was becoming progressively smaller. Again there is a point in favor of both low heat ttansfer coefficients and low time of contact. The middle pdrtion of the durve in Figure 14 was placed using values of L1 /G calculated from low values of G and average values of Ll. Under these conditions the slip velocity was -37intermediate between that existing at low and high values of L1 /G. Summarizing, it appeared that (1) when the tiite of contact between air and gel was great, the heat of adsorption was fully developed but was partially transferred to the surroundings, (2) when the time of contact was intermediate, the heat effect was developed but heat losses to the surroundings were not as great and (3) at low times of contact the heat effect was not fully developed. In this way a minimum in the percent error as Ll/G increased might be possible. However, it should be pointed out that the data are few and that perhaps if more runs had been miade covering a greater range of gel and air rates the curve could have been placed more definitely. Then, too, the fact should not be overlooked that the average of the water balances calculated by the other three methods may be in error more for some runs than for others. The slip velocity, us - ug, plotted on Figure 15 against the superficial air velocity appears to go through a maximum as the air velocity increases. This has not been explained satisfactorily as yet. The concentration of gel in the column decreased rapidly as the mass rate of flow G increased. The data plotted on logarithmic paper (Figure 16) gave a line with slope eoual to -8.4. The data at the higher air rates were very difficult. to obtain inasmuch as the gel concentration was extremely low. Thus, the value of -8.4 is not particularly reliable, since all points on the upper portion of the curve fall aknost together The data are sup- and do not aid inlacing it definitely. ported in part by visual observation of the gel concentration in the column during operation. At low air rates the column appeared to be almost filled with gel but at values of G-around 2000 it was difficult to see a single gel particle as it passed through the column. The difficulty in measuring the gel holdup in the column at the conclusion of a run was caused by the inability to shut down the air momentarily at the right time to permit the gel to fall from the column through the constriction. Obviously, at higher air rates, a very small fraction of a second error in shutting down the air would cause a large error in the gel concentration determination. For example, in Runs 14 and 19 the air valve was closed too late and the column was swept free of gel; for these runs it was necessary to assume that the velocity of the gel was the same as that of the air and calculate the concentration existing in the column. The results of the calculation were close to those obtained by actual measurement. In an attempt to develop a method of design for such silica gel drying columns an operating line was calculated for all runs. The equation for the slopes of these lines at the bottom and top of the column is given in the Introduction. It was hoped that some sort of picture of the adsorption path in the column -might be obtained. 'curves for all runs. Figure 17 gives the In all cases, the curves were very near straight lines or were definitely S-shaped. The majority -39of them were of the S-shape type. The curves are not to be taken as representing the actual path of adsorption but only as an indication of the form of the path because of the fact that there was no method by which a middle point could be placed with the data available. The shape of the curves seemed to indicate that as the gel entered the column instantaneous adsorption occurs but a slight lag in development of the heat effect caused the Useful Water Concentration to appear to increase more rapidly than the Percent Relative Humidity decreases. As soon as the heat of adsorp- tion was transferred the Percent Relative Humidity decreased rapidly but the Useful Water Concentration went up slowly because the absolute water adsorbed in this part of the column might have been small; perhaps during this part of the process, the water adsorbed initially was being transferred to the inner portion of the gel particle by capillary attraction. The upper portion of the curve has not been explained unless it may be aaid that the cycle was repeated. It is believed that further data are needed in order to place curves representing the path of adsorption through the column. Such curves placed properly could be used to calculate transfer coefficients by graphical integration. Pursuing the same idea projected in the preceding paragraph the data from the operating runs were used in calculating overall adsorption coefficients from equations 3 and 4 in the Introduction. Inasmuch as the eduilibrium data gave a single line over a reasonably narrow temperature range when -40plotted as Useful Water Concentration against Percent Relative Humidity, it was thought that perhaps a coefficient of mass transfer based on a unit difference in Percent Relative Humidity could be correlated with air or gel rate. It was found that such a coefficient, KRHa, calculated from equation (3) decreased as the air rate increased. Since the gel concentra- tion in the column decreased rapidly as air rate increased, the term "a" in KRHa must have decreased rapidly and the value of KRH must increase rapidly as the air rate increased. As mentioned before, the data are few and the gel concentrations at high air rates are not considered too reliable, therefore, no definite statement can be made as to the extent of the increase of KRH with air rate. However, it is believed that the values given on Figure 18 plotted against the air rate can be used for design purposes within the temperature range covered by the equilibrium data and with this particular gel size (--28 + 48 mesh). The overall coefficient, KSa, was also calculated from equation 19. (4) and plotted against the gel feed rate in Figure It was found that the values of Ksa increased as the gel rate increased and fell along two straight lines one for the low air rates and the other for the high. The points for runs with intermediate air rates fell generally between these two lines. The lower values of KSa fell along the line for the higher air rates. In order to bring the data together the values of KSa were multiplied by G/L000 and the results, (K a)(G/1000) were plotted against the gel feed rate -41on Figure 20 to give a straight line with slope equal to 0.0013 and an intercept of 0.35. Thus, for a given value of G, K a increases as the gel feed rate increases. The only explanation for this appeared to be the following; since at constant G, the gel concentration in the column remained very nearly the same, the gel velocity and therefore, the turbulence might be sufficient to cause an improvement in the mass transfer coefficient. Referring to Figure 20 it is clear that the points for Runs 16, 18 and 19 lie below the straight line drawn through a majority of all points. Exam- ination of the water balances calculated for these runs and reported. in Table IV will show how this can be explained. Run 16 The water balances calculated from L2 - Ll, G(Hl - H 2 ) and gel water content determinations check well but that calculated from thermal data is much lower. This indicates that the top temperature might be low and that the percent relative humidity calculated therefrom would be too high. If this were true, then the UWCe would be too high and the mean driving force calculated would be high. This would give a lower value of K 8 a than that which actually existed during this run. Run 18 The water balance calculated from thermal data for this run is also lower than the others and thus the same reasoning holds as for Run 164 Furthermore, since the water balances calculated from G(H1 - H2 ) and gel water content determinations -42check reasonably well but that calculated from L 2 - L is high, the air rate, G might be too low or the water content of the outlet gel, C., may be low (if this is low then UWC2 is low,AUWC is low and the UWC driting force calculated would be too high). This would tend to give low values of Kga. Run 19 Both the water balances from gel water content determinations and thermal data are lower than the other two. Thus the same reasoning may be followed for Run 19 as for Run 18. It is believed that a more reliable correlation could be obtained if a series of experiments were run using gel of different sizes and collecting operating data as was done in the present investigation and using that data to calculate the adsorption coefficients. several gel and air rates. This should be done at For the particular gel size used, however, it is believed that the values of Kga given on Figure 20 can be employed for design calculations for this type of silica gel dehumidifier. Referring to Figure 1 it is clear that the equilibrium data obtained during this investigation show consistently lower values of the Useful Water Concentration at a given Percent Relative Humidity than do the data taken from the literature. This may be attributed to at least two differ- ent factors, namely, (1) presence of air extended the length of tite required to reach true equilibrium beyond the actual duration of the equilibrium runs and (2) the use of large quantities of gel which while setting in the funnel outside -43the column cooled down to some temperature below that in the column and when passed into the column absorbed any small quantities of heat of adsorption which may have been evolved, thus preventing any rise in temperature of the air.which would have been observed normally. The first fac- tor was known to exist to such an extent that it would probably have taken three or four days to reach the true equilibrium point. However, with the system used it was impos- sible to judge when equilibrium had been reached except by equality of inlet and outlet temperature or by constancy of outlet temperature with and without the gel "jiggling" in the column. Probably, the presence of air so decreased the rate of adsorption that small amounts of heat evolved as the gel passed through the column were' not observed. The sedond factor, although shown in some runs to have little effect by the constancy of outlet temperature with and without the gel in thb column, must have been a contributing factor, inasmuch as it was known that the funnel at the top of the column was generally lower in temperature than the inside of the column. It is believed that during any future investigations undertaken to determine equilibrium data for the system silica gel-water vapor-air by the "jiggling"method, special care should be taken to control the temperature of the whole system or to prevent heat loss to the surroundings from either the gel or the air. It is also believed that smaller quantities of gel should be used and consequently, a greater number of cycles per unit time. -44VI. CONCLUSIONS The following conclusions have been reached as a result of the data obtained during this investigation. 1. The time of reactivation of silica gel at 178 degrees Centigrade in air has little or no effect on the residual water concentration. 2. Residual water contents of freshly reactivated gel u"ed during the experiments agree well with those obtained by other investigators, even though reactivation was carried out in the presence of air at atmospheric pressure. 3. Humidity of air cannot be measured satisfactorily when a small stream is passed to drying tubes through lines filled partially with an adsorbent soli4,- nor can the method be used when the velocity of the air being passed to the drying tubes is so low that long time of contact is permitted with the suspended or depositied solid. However, humidity of air can be measured satisfactorily by the psychrometric method under the conditions prevailing during this investigation. 4. Further work should be done in determining the extent of powdering of silica gel in the type system used. 5. Heat loss from the column was greater at low than at high rates of air flow. Future investigators should tkke steps to prevent this heat loss or else construct a column which will operate isothermally. 6. The rise in air temperature is almost as great in the -45three inches above the gel inlet point as throughout the entire length of the column. 7. The percant of the inlet water vapor adsorbed can be correlated with rate of air flow. 8. The percent error in the water balance calculated from thermal data is large at both high and low times of contact between the gel and air passing through the column and is relatively small at intermediate times of contact. It is concluded that this is probably due to the fact that at large times of contact in the column the opportunity for heat loss to the surroundings is great even though the full heat of adsorption is developed, that at intermediate times of contact the full heat effect is developed but the heat losses are less and that at low times of contact the heat effect is not fully developed. 9. The slip velocity passes through a maximum as the air velocity increases. The reaeon for this should be investigated. 10. The gel concentration in the column decreases rapidly as the air rate increases. Determination of the gel concen- tration at high air rates is inherently difficult. Consider- able work should be done in any future investigation in determining gel concentrations for different size gels at various air and gel feed rates. 11. The end conditions of the gel and air can be pictured on an equilibrium diagram by an operating line which represents the form of the path of adsorption through the column. The shape of these operating lines is inherently S-shaped. -4612. The operating data taken during Runs 1-19 can be correlated with air and gel feed rates in terms of overall adsorption coefficients. These adsorption coefficients can be used for future design work provided the same size gel is to be used £nrthe rangd6ofcz:tempsitatures covered by the equilibrium data given on Figure 1. 13. Equilibrium data taken during Runs 20-28, inclusive, give lower Useful Water Concentrations at a given Percent Relative Humidity than other data taken from the literature. It is concluded that this is due to the presence of air or to improper technique employed in taking these data. It is believed that extreme care should be taken to prevent heat losses from the entire system in all future investigations undertaken to determine equilibrium data for the system silica gel-water vapor-air by the "jiggling" method. Otherwise, steps should be taken to make the system isothermal in operation. -47VII. RECOMMENDATIONS It is believed that if the recommendations list6d below are followed, considerable data of Value would be obtained. 1. The extent of powdering of the silica gel when used in the "jiggling" operation should be determined. 2. For all future investigations in which a system similar to that used here is proposed, care should be taken to prevent heat loss to the surroundings or the apparatus should be constructed for isothermal operation. 3. The change in slip velocity with superficial air velocity should be investigated so that observed variations in adsorption coefficients might be more easily explained. 4. The gel concentration in the column should be determined accurately for different size gels at various air and gel feed rates. This should also include a study of the gel distribution in the column at different air rates. 5. Attempts should be made to correlate all operating data taken by the "jiggling" method in terms of adsorption coefficients which could be used for future design calculations. 6. Extreme care should be taken during determinations of equilibrium data for the system silica gel-water vapor-air to insure that heat losses to the surroundings by any mechanism are reduced to a minimum. If possible the system should be designed to operate isothermally under controlled conditions of temperature. -48- VIII. A P P E N D I X -49A. Expansion of Procedure The description of the experimental procedure employed in this investigation will be included with a description of the operation and construction details of the apparatus. Ini order to clarify the description a cross-sectional elevation diagram of the apparatus (Figure 4 following page 58) has been included in which the details of the construction are shown clearly. The apparatus is pictured whild operating on air of normal moisture content; the conditions of the operation will be discussed in the body of the present section. Certain advantages are gained by separating the experimental procedure into four phases of operation, namely: A. Preparation for Run B. Operations During Run C. Operations at Conclusion of Run D. Operations During Equilibrium Run A. Preparation for Run Silica gel (screened to -28 +48 mesh) used in a previous run was reactivated by heating in air at 1780 Centigrade until the residual water content dropped to 4.7-4.8 percent on a dry basis. The reactivation was carried out in an electric oven equipped with a bi-metallic temperature control. The reactivated gel was placed then in the dessicRtor pictured at the extreme right of Figures 4, allowed to cool to room temperature. , 6 ane. e and Calcium chloride was -50used as the dessicant. Over the total period of the experi- mental work the time of reactivation was varied purposely in order to determine the relation between time of reactivation and residual water content of the silica gel. The reservoir supplying water to the wet-bulb wick of the wet- and dry-bulb psychrometer (top left, Figures 4 and 8) was filled to insure thorough wetting of the wet bulb. Screw clamps 51, S2 and 55 were opened, in the order given, to permit inlet air to flow over the wet- and dry-bulb. The type of psychrometer used consisted of two U-tubes fitted with fractional thermometers reading from 0-55 Centigrade by 0.1 degree. The upper part of each U-tube in which the thermometers were seated were covered with tinfoil and asbestos tape to prevent heat transfer between the bulb and the surroundings. The leg of the U-tube housing the wet-bulb thermometer was relatively short to permit the use of a short wick. This type of psychrometer possessed a particular ad- vantage in that the air after contacting the wet-bulb flowed over the water reservoir and cooled it to the wet-bulb temperature; this helped to eliminate the possibility that the correct temperature was never reached at the wet-bulb. The wet- and dry-bulb method of determining humidity was checked against a gravimetric method employing magnesium perchlorate as the drying agent.and found to be in excellent agreement therewith at the humidities encountered in this investigation. When this check was made the air was not passing through silica gel in the column. -51In preparation for Runs 1-7, inclusive, U-tubes containing magnesium perchlorate were weighed accurately on an analytical balance and placed in an air line leading from the top of the jiggler column to alfive gallon bottle previously filled completely with water. The bottle was connected by means of water filled glass and rubber tubing to another five gallon bottle placed at a lower level on a platform balance, 55 pounds capacity; flow of water to the lower level was prevented by a screw clamp. the bottle on the balance was recorded. The weight of The drying tubes and bottles are not shown in Figure 4 since they were eliminated from the apparatus after and 8, following page Run 7; they are shown in Figures 5 58. A one liter volumetric flask, fitted with aluminum funnel and pinch clamp, Pl, was connected directly to the dessicator outlet and a sample of activated gel withdrawn (out of contact with moist air) through S13 and Pl. P1 was closed immediately, the gel was mixed thoroughly by shaking, and a sample of gel was taken for determination of moisture content. The weight of the flask and gel content was determined on a triple beam balance (previously calibrated against brass analytical weights) to the nearest 0.1 gram and the flask was mounted as indicated in Figures 4, 5 and 6. An empty one liter volumetric flask was weighed and mounted to receive the wet gel from the column. At this point the apparatus was ready for the beginning of a run. -52B. Operations During a Run The wet- and dry-bulb temperatures of the inlet air were recorded and S5 closed. Air flow was adjusted to the desired quantity by adjusting either 81 or 82. The quantity of air flow was determined by a sharp edged orifice flowmeter (Figure 7) constructed of two sections of 14 millimeter Pyrex glass tubing ground smooth at the pressure tap ends. A brass circular plate with orifice opening of 0.199 inches diameter was machined with outer diameter equal to that of the glass tubing but with a concentric shoulder on one side to slip inside the tubing and thereby center the orifice opening exactly. The two sections of tubing with orifice plate in place were held together with pressure tubing. The orifice was calibrated against a dry test meter over the range from 0.8 to 3.5 cubic feet of air per minute. The taps of the orifice were connected directly to a differential water manometer. The manometer reading in Figure 4 is 11 centimeters of water which corresponds to an air flow of approximately one cubic foot per minute. The air passed from the flowmeter through a water cooled condenser tube (used for temperature control) and thence to the column (no temperature control was used during runs made to obtain operating data). After adjusting the air flow, pinch clamps P2 and Pl were opened in the order given; the run was timed from the instant P1 was opened. The dry (4.7-4.8% water, dry basis ) gel flowed by gravity through Pl into a feed device consisting simply of a glass tube constricted at the downstream -53The end with minimum elongation and thence into the column. concentration of gel in the column as pictUred in Figure 4 was characteristic of an air flow of one cubic foot per minute or a superficial velocity of approximately four feet per second and was built up in less than five minutes. The column itself was construdted of 22 millimeter I.D. Pyrex tubing. A Venturi constriction above the air inlet and between the air and silica gel inlet points converted pressure energy of the air to kinetic energy, providing an air stream of high velocity at the silica gel-inlet. As the silica gel was whisked into the body of the column and "jiggled" in the- air stream, water vapor was adsorbed, heat of adsorption given off'and the air temperature increased. Felted hair insulation around the upper and lower portions of the column together with a dead air space provided by a glass jacket and annular cardboard ring spacers around the body of the column eliminated decrease in air temperature due to heat losses to the surroundings. Fractional thermometers read- ing from 00-550 Centigrade by 0.1 degrees recorded the increase in air temperature between the inlet point and the top of the column. In both cases, heat transfer between the thermometer bulb and surroundings was reduced by insulation; at the inlet point tinfoil and asbestos tape was used while felted hair was used at the top of the column. A 0*-2204 Centigrade thermometer recorded the air temperature at a point three inches above the silica gel inlet. After jiggling up the length of the column, the silica gel fell over into a -54tin funnel and thence to the volumetric flask receiver. The column was seated tightly in a hole through the side of the tin funnel by means of heavy rubber tubing. Light galvanized iron sheet soldered to the top of the funnel sealed the system effectively. Holes were cut in the funnel top for insertion of thermometers and air outlet. A small air outlet (through this outlet in Figure 4, the 0*-220O Centigrade thermometer in the column was supported by copper wire), directly above the column and protected by glass wool filter, led to the drying tubes; a larger outlet protected by copper screen and glass wool filter led to the atmosphere and in later runs to the wet- and dry-bulb thermometers. The screen and filter were installed -to eliminate as far as possible, the gel fines formed during operation. After reaching steady state (usually less than five minutes) the following readings were taken at five minute intervals: 1. Manometer readings (all runs) 2. Inlet air temperature (runs 9-19, inclusive; the drybulb temperature was taken as the inlet temperature for runs 1-8, inclusive) 3. Temperature three inches abbve the silica gel inlet (runs 15-19, inclusive) 4. Outlet air temperatures (all runs) 5. Wet- and dry-bulb temperature of outlet air (runs 7-19, inclusive) In Runs 1-7, inclusive, after steady state was reached, -55a small stream of outlet air was turned through the drying tubes and thence to the water filled bottle. Water flowed from the upper bottle to that resting on the balance, thereby drawing air through the drying tubes. The weight of water displaced, the temperature of the water in the upper bottle, the head of water in the tubes connecting the bottles and the barometric pressure were recorded. The volume of air drawn through the drying tubes varied from 5-12 liters per run. In these runs, the wet- and dry-bulb temperatures of the outlet air were not measured. At the conclusion of all runs (usually 20-80 minutes) as the last particles of silica gel fell through the feed device, the air flow was discontinued immediately for a moment to permit the silica gel holdup in the column to drop below the air inlet point. The wet- and dry-bulb temperatures of the inlet air were determined again. C. Operations at Conclusion of Run The operations at the conclusion of a run can best be described by numerical listing. 1. The empty feed flask and the filled receiver flask were weighed on the triple beam balance. 2. The silica gel holdup in the column wazs removed through Sll and S12 and weighed accurately on an analytical balance. 3. In Runs 1-7, inclusive, the magnesium perchlorate tubes were weighed accurately on an analytical balance. -564. The time of the run as observed by stopwatch wes recorded. 5. A sample of outlet silica gel was taken after thorough mixing by shaking, weighed accurately on an analytical balance, transferred to a crucible, and heated to constant weight with a Meker burner. The sample of inlet gel taken before the run was analyzed for moisture content similarly at the same time. D. Operations During Equilibrium Run Air flow was adjusted as before to approximately two cubic feet per minute. Reactivated gel contained in the flask controlled by Pl, was passed into the column through Pl; pinch clamp P2 was closed during this operation thereby holding the gel in the tin funnel. After all gel had passed through the column, the feed flask was removed and connection made by rubber tubing from the outlet of the tin funnel to the gel inlet. P2 was opened partially permitting the gel to flow into the column, back to the tin funnel, and again to the column continuously. The gel was fed to the column until the inlet and outlet air temperature remained constant with and without the gel jiggling. The equality of the inlet and outlet temperatures or the constancy of the outlet temperature indicated that no water vapor was being adsorbed and therefore, that equilibrium had been reached for that particular percent relative humidity. At that point, duplicate samples of gel were withdrawn from the total quantity after thorough mixing by shaking and the moisture content -57determined by heating to constant weight with a.Meker burner. The results were plotted as Percent Useful Water Concentration (based on the weight of initial wet gel) against the percent relative humidity (see Figure 1). In order to control the temperature of the air, a watercooled condenser tube was placed in the air line. The water supply was taken from a reservoir into which steam (through B7) and cold water '(through 56) were introduced. in quantities depending on the desired temperature; a large part of the water ran to waste from the reservoir through S8, the remainder flowed to the condenser tube jacket. In this way, the temperature of the air could be controlled to 0.20 Centigrade over a considerably long period of time. With constant room temperature the control was better over longer periods of time. Since it was desired to determine equilibrium data at very high percent relative humidities it became necessary to construct an air saturator to handle a large volumetric flow of air, for the relative humidity of the inlet air seldom exceeded 35 and was never greater than 40 percent. Ordinary bubbling apparatus proved unsatisfactory due to low capacity; a fritted glass plug in a glass column eighteen inches in length was tried first but the flooding velocity was reached at low volumetric flow. In order to approach saturation closely it was necessary to pass the air as relatively fine bubbles through water and at the same time handle at least two cubic feet of air per minutes. A simple device -58was constructed to meet these requirements. Two types of B. & W. Kaolin Brick, No. 28 and 26 were cut in half, one half of each was carved out so that the remaining walls were one inch in thickness. A small hole was cut in the top of the No. 28 brick and a short length of 12 millimeter glass tubing was sealed therein with Plicene cement. The two halves of brick were also sealed together with Plicene cement and placed in water contained in a heavy Pyrex jar twelve inches in diameter and twelve inches in height. A circular steel plate fifteen inches in diameter with a groove, one eighth inch in depth cut to fit over the glass jar was sealed thereon with litharge and glycerine cement. One huddred pounds of steel weights were placed on the steel plate. ELEVATION DIAGRAM OF APPARATUS FIG.407-55-C. THERMOMETER WET- AND DRY-BULB THERMOMETERS. OUTLET AIR VAL VE OPEN VAL VE CLOSED - TINFOIL AND ASESTOS TAPE VAL VE PARTIAL LY OPEN -7& S9 HEAVY RUBBER TUBING TO WET- AND DRYBULB THERMOMETERS WATER MANOMETER GLASS WOOL FILTER OUTLET AIR COPPER SCREEN / WOOL TIN FUNNEL NSULATION ALUMINUM FUNNEL WATER WICK WET-BULB P2 S14 GLASS JACKET-- MM PYREX TUBING - STO PRESSURE TUBING S4 SI S3 - ANNULAR CARDBOARD RING WASTE pi REACTIVATED SILICA GEL - -- - 100 POUNDS WEIGHT BRASS SHARP-EDGED ORIFICE PLATE CIUM SHLORIDE -- COLD--WATER GLASS WOOL FILTER S13 STEEL PLATE STEAM 58 LITHARGE AND GLYCERINE )-SC I LITER VOLUMETRIC FLASK THERMOMETER S7 HEAVY PYREX ------------------- - WATER - PLICENE CEMENT B&W K-28 BRICK CO AIRD WOOL INSULATION 58 JAR B & W K- 2 6 B RIC- -- - - - TINFOIL AND ASBESTOS TAPE TO~ WASTE Sil Sl 2 A W.P 12-17-41 r WI L 2: FIGURE 5 ASSEKBLY OF APPARATUS r - 1 ,-AG m MA FIGURE 6 ASSEMBLY OF COLUMN, FUNNEL AND FLASKS A. Disassembled B. Assembled C. Placed for Operation FIGURE 7 SHARP-EDGE ORIFICL FLCWETER I 4" B. A. Psychrometer C. FIGURE 8 MgC10 4 Dessicr tor Drying Tubes COM'PONLNT PARTS OF THi APPARATUS -59B. Summarized Data All data taken during Runs 1-28, inclusive are given in Tables I, II and III of the present section. Table I includes all operating data for both normal runs and also those during which equilibrium data were determined. At the bottom of Table I will be found the calibration data for the various flowmeters used during the experiments. Calibration curies of this data are to be found in Appendix F. Table II gives the surrounding temperature for Runs 1-19, inclusive. These were used in calculating the heat losses from the column. Table III gives the data taken when the psychrometric method of determining humidity of air was being ehecked against the gravimetric method. These data were taken without silica gel "jiggling" in the column. Similar data for comparison of the two methods with gel in the column may be found in Table I under Runs 2 and 7. TABLE I ORIGINAL DATA I 2 3 34.0 12.0 31.1 26.6 24.1 16.1 32.0 20.1 19.9 16.9 1I.0 16.60 oo. Rum 4 5 16 9 -7 1 3 14 2+.10 17.25 15.55 16.30 1 'A 10 2.1 5 27 s6 I to 10.15 24.15 25.20 20.900 2146 22.1 11.80 '1.90 14 13 13.11 14.30 14.11 12.75 13.10 12.15 16.45 7.45 13.16 392 0.1461 0.1411 0,45 0.11L6 0.6318 a1.g 33.5w 48.50 10.00 15.15 26.33 12.90 32.05 41.0 21.iS 15.45 21.20 1.10 14.40 2(.60 1.31 1i.016 o0.1165 12.6110 17 Is 21 24 It 6 Is as INLslAII TIMPItATUht,*C, My VUL9 W&T SuwL 1aNPPATUIDrC. PO4IF6O 6.p e 4.07351 s.0. AIR/mINUII Y6IIPIIATUSI,*C, KAmannsthO R*6 0414,tt T, C 31.0 I8l 26.4 10 41.8 "A10IEgTYA KCACA4.46MTIC'i H,0 +7.7 CUSIC F1IT AIR /MINUITL 41.1 47.4 1.01 .05 TIMtPIIt*u66 OuTIt' As : ovistl ru6 ,C- em se36, mSA9OIW*YW OUT6JT.TAI 1'ST. vuess, 30 49.3 49.5 16.61 3.1 11.1 11.4 49.3 1.%&1 .63 0.9 4904 .111116 6"I 1.11 -. 11.15 49.7 49.3 LO @0779 6.21 28.43 2.5.42. 25.13 4.06 21.67 23.51. 59.4 61.6 6+.5 67.7 66. 66.6 51.6 GS.3 48. 48.6 34.0 36.4 38.1 41.3 43.7 403 S.15 X2.56 57.6 51.+ 46.5 1.00 3.9s 4.01 LGI 1.10 1.07 (.931 1.00 1.11 1.91 30 764 al 23 30 762 12.06 17.0 15.2 14.6 25.3 11.+9 25.45 0.0477 0.0(11 76 26 30 30 14.70 17.00 6..00 13.75 11.40 0.20 765 li.60 "4.4 1.79 24.5 30 30 ST.68 16.70 13.04 12.49 41.1 +64 .3 610.4 3.3 39.16 TS6 36.1 16.11 25.19 26.59 12.14 10.91 26.01 a6.61 23.28 23.26 2696 1901 9.90 10.69 11.44 1+.61 12.00 .113 4.99 0.116 32.12 28.16 27.32 15.93 21.3 11.97 11.14. 34.906 32.37 34.48 33.01 19.35 19.13 34.46 SILICA *"1 IN bAS 1.13 ,MS. 404.6 630.3 61.5 634.6 191.l 3SI.9 392.9 312.2 317 194.6 118.9 315.9 413.5 2W1.0 6413.9 639.1 6".6 5-IT. 35-51 67-2. 7s-u4t,- 9.66 to.9 11.7l 632. 81181te3 1.09 1110140 SILICA *I. 110OLUP IN C8LPR 1.7 1i.19 .36 t.+o 314.4 190.4 318.3 16o0.1 51.-51 52 it.11 9-m0 51-5 i.9+ lOl 42-9 19-5 10.17 i1.57 132.6 12.21 S1i9. 26-34 9.33 442.1 4 34.9 . 3+9 4127 466.0 419.7 +-4S 44-4 0.079 0.0 94.1 341.6 429.6 4.6- 1 I.10 47-10 41-9 0.27 0.05 0.200 0T.061 0.09+ WOOL P11.161, .81. -11 POR ANALYSm51.ifS;: 1T+534 1.1641 1ILST OUTL9SSAAPVLS* I 6.0i15 G.9299 6.1106 .3101 6.-I S.A10 .3.00 7.1741 9WL90 6.6616 6.6143 st.L 9 .6a 9.496+ 163 6.6300 6.6616 6.6199 8.6914 6.0837 1.jSS 9.06097 mL ourTLgT, 9.0421 @2. I4a11.1651 6.6195 61140 10.271 IS. 6.-7013j106051 11.111 9." 491.s A"92e BLAS""a,90%6 SIA *1L~ .11 7.1 6.f01 7.9144 6.14 OUT36T,9 6.04916.7176 5A0011.29 DE p""MentTsat RmtqIr6,ArC" W.0 53 , 144 MAWSPEY*A 51AbI46,*i9trCf414,O OPFL.w, Poky rgser£Mq S SCON O ltAble s P1 .7?57 8.2902 .1494 8.1471 6.1007 9.9673 0.910 1.441) 6.1660 0.15 6.450 1 U I 0206 0. : 9 peg. ATOICACVP3SVA0)*h*A #.5 .1"6 OUTL9T, SAM K4*2 CA6I DRATION Ad I.3 14.10 765 2.8 16.1 Me T.rC.umm'leMo. ,eS093U81, Toe 12510 .65 T.00 27.9 13.0 ,C. SILICA ORL 90s6ICSe,6MS. DUV I.51 11.4 a eulSi SILICA 69 116asumI SlICcA 6SI-TAK 57. 4.90 IA5 1.0 AN5-Sll 8151810 itnpsATM a,*c .aL 010013 0S4 754 1 11. 9 20.7 GAM 0.01.0 V6S6TULDYApSStArUMS,'C- SILICA 16.10 ,C. 29.7 s cot 03v IuSLU11AvG4xu1 OUTLET I 26.69 1197 1.62 766.3 M 06 BSUw ma1n34,WCMUS VoLung ceSN5is46d gt. -ASOOS6g 1.56 AOS009 16 MjCI6O*UWSS,6MI W36t .6.4 1,.1 k.07 29.9 605 04 OILACS OT AIR eAmommm 49.5 1.06 25.15 12.20 mai3oo WAVSUOiSPLA.SSSVAM, IMP. WAU 14.1 In.9 9 87. 5.1 1+4.60 21.45 21.50 2 .V *"0 .09 11.4 97.9 Mso 6.4 17.25 i. 1.37 217.1 2.5 So s+2 5+.4 55.1 49.5 5S 49.9 498 1.95 1.9 I 1 V%.& 197.9 IS11. I 5 1 5 1 .5 57.0 60.1 61.9 44.1 41.9 19.I 1.10 2.1* s 44.1 60.1 +4+9 6. 2.5 I 1.s 7S.0 611., 2.5 2.5 3a 6 ,. e 66.6 1-1.+ 10 1-31.1 11.0 it 31.1 IS2 1.0 jIG 1 55.0 56.1 51.0 49.6 +9.4 MTC.t +6.1 O 51.9 46 I 61.6 1a JIl IS8.3 I'LS.S 163.9 o2.0 j 2.0 I a . 2.0 I 2.0 I .0 2.0 2.0 £ g 2 0 64.4 4.3 0 11.0 IFICE 55.9 A1e.6 41.0 121.3 1.90 134.3 1e w.$ 104.' 12..S 1.0 OLO IFLOW 6a4C I 9.0l3 8.532 D. 71-1 174.t @(.f 5.4 131.7 41.6 IX316 890 , o a 2 5 0 O.3 - 0.5 19. 1.0 -. 111,.6 2.9 3. - 9.I2.I 714 7.53 0.199 W.1, 7.2197 3.131 mtEs (SIA P 16 99.5 __.3 . 9.2 . #&' 10 ups IMsa- IN 46.9 +*.a _4_ L,4 - -70- a 5.0 4.5 16.0 1 9.0 9.557 1.40 I:'S.g 10.1 6.0 4(.9 A 9.7 1 .96 .6993 44.9 1.0 5'1. -. 19.6 '17.4 p.2. 3.7 a e~ + 2. 5 1-7. 5 1 .0 AwP 9/441 94+4 54.1 -60TABLE II TEM1PERATURE OF THE SURROUNDINGS DURING RUNS 1-19, INCLUSIVE Run No. Su r r o u n d i n g T e m p e r a t u r e Degrees Centigrade Degrees Fahrenheit 1 34.0 93.1 2 32.0 89.6 3 31.2 88.2 4 26.6 79.8 5 24.2 75.6 6 26.1 79.0 7 26.4 79.6 8 22.7 72.9 9 22.8 73.0 10 23.8 74.8 11 21.5 70.6 12 21.1 70.0 13 24.1 75.4 144 27.3 81.1 15 20.3 68.5 16 23.4 76.2 17 25.2 77.4 18 20.9 69.6 19 21.5 70.7 -61TABLE III DATA FOR COMPARISON OF GRAVIMETRIC AND PSYCHROMETRIC METHODS OF MEASURING HUMIDITY Gravimetric Method No. 1 Weight of drying tube + adsorbed water Weight of drying tubes Weight of adsorbed water Total weight of adsorbed water 60.5305 gms. 60.5292 0.0013 gms. 31.81 lbs. 12.25 191.56 lbs. Temperature of water in bottle 29.4000. Head of water below gas receiver 26.0 inches Volume of connecting tubeP. 30.0 ml. 754.0 mm. Hg Psychrometric Method Wet-bulb temieratur, 17.35 17.42 17.38 17.20 . Dry-bulb temperature, 27.75 27.85 27.80 27.50 2 70.2852 gms. 70.2224 0.0627 gms. 0.0741 gms. Weight of bottle + water Weight of bottle Weight of water displaced Barometric pressure No. 00. -62C. Sample Calculations The calculations performed for Run No. 10 are representative of those performed for all other runs except the first seven; the calculations for those runs are the same as all others except for those performed to determine the outlet air humidity by the drying tube method. Run No. 10 INLET AIR Dry Bulb Temperature = 24.600. = 76.3 0 F. Wet Bulb Temperature = 14.90. = 58.8 0 F. From a humidity chart covering the normal temperature range at atmospheric pressure, H1 = 0.0068 lbs. H2 0 vapor/lb. b.d. air RH, = 31% s1 = 0.243 Btu/(lb.)(OF.) Average Air Inlet Temperature = 25.250C. Temperature, Time 8:45 p.m. 8:50 8:55 9:00 9:05 9:10 9:15 9:20 9:25 9:30 Average = 77.4 0 F. 0 0. 25.00 25.10 25.50 25.40 25.52 25.70 25.25 25.15 25.00 24.85 25.25 From the humidity chart again at a temperature of 77.4 0 F. and 31% RH, the specific volume of the inlet air is v = 13.60 cu. ft./lb. b.d. inlet air Rate of inlet air flow: Manometer Readings, cm. water Left Right Time 8:45 p.m. 8:50 8:55 9:00 9:05 9:10 9:15 9:20 9:25 9:30 Average 49.35 49.00 49.10 49.25 49.40 49.10 48.95 49.55 49.15 49.35 49.22 57.30 57.60 57.50 57.35 57.20 57.50 57.60 57.00 57.45 57.20 57.37 Manometer Differential = 57.3,? - 49.22 = 8.15 cm. water From Figure 21, 8.15 centimeters of water corresponds to an air flow of 1.01 cubic feet of air per minute. Then 1.01 13.60 = 0.0743 lbs. of b.d. inlet air flowing/minute To convert this quantity to one more useful for design calculations it is necessary to know the tower cross sectional area. Since the tower measured 22 mm. I.D., the cross sectional area of flow is S= LTrT(22/25.4)a /(144)(4) = 4.09 x 10-3 ft.2 Then the rate of air flow, G, becomes G ='(o.0743)(60)/(4.09 x 10-3) = 1090 lbs. b.d. air/(hr)(ft2) The superficial air velocity, us, at this mass rate of air flow is us = (1.01)/(60)(4.09 x 10-3) = 4.15 feet/ second -64OUTLET AIR Humidity and temperature of the outlet air: Time p.m. Wet Bulb Temp. 00. OF. 8:45 8:50 8:55 9:00 9:05 9:10 9:15 9:20 9:25 9:30 Ave. 12.80 12.35 12.75 12.70 12.60 12.80 12.75 12.95 12.95 13.00 12.97 55.04 54.40 54.95 54.90 54.70 55.00 54.95 55.60 55.60 55.40 55.05 Dry Bulb Temp. 0F. 00. Outlet Temp., OC. 25.30 26.10 26.45 26.70 26.55 26.85 26.85 27.00 27.00 27.05 26.59 31.20 32.60 32.70 33.00 33.30 33.35 33.50 33.25 33.35 33.05 33.02 (91.400F.) 77.60 79.00 79.60 80.00 79.80 80.40 80.40 80.60 80.60 80.70 79.87 H* 0.0044 0.0036 0.0036 0.0035 0.0036 0.0035 0.0035 0.0039 0.0039 0.0038 0.0037 *H lbs. of water vapor per lb. of b.d. air The values of H above were obtained from a standard humidity chart. Using the same chart and the average wet- and dry-bulb temperatures, the percent relative humidity, RH 2 and humid heat, S2, were found to be RH 2 = 11% s= 0.242 Btu/(lb.)(OF.) The temperature rise, t. - ti, of the air in passing through the column is 91.4 - 77.4 = 14.04F., and the water adsorbed is G(Hi- H2 ) = 1090(0.0068 - 0.0037) = 3.4 lbs. water vapor adsorbed/ (hr)(ft2) The percent of the inlet water vapor adsorbed by the silica gel is 100(0.0068 - 0.0037)/0.0068 = 45.5% SILICA GEL MEASUREMENTS Rate of Gel Flow, Ll and L2 : -65- Inlet Outlet 747.88 gms. 641.07 gms. 335.21 435.68 305.76 gms. gms. 312.20 Weight of Reservoir + Silica Gel Weight of Reservoir Weight of Silica Gel Silica Gel Holdup in Column: Weight of Bottle + Silica Gel 32.448 gms. 19.878 Weight of Bottle Weight of Silica Gel Holdup Weight of Inlet Gel, gms. 12.57 gms. 312.20 318.33 Weight of Outlet Gel, gms. Since the elapsed time of the run was 49 minutes and 20 seconds or (49 + 20/60)/(60) = 0.82 hours, L1 and L2 are L1 = (312.2)/(454)(4.09 x 10-3)(0.82) = 205.3 lbs. of silica gel/(hr)(fta) I" L2 = (318.3)/(454)(4.09 x 10- 3 )(Q.82) = 209.2 and the amount of water adsorbed by the gel is 209.2 - 205.3 = 3.9 lbs. of water adsorbed/(ht)(ft2) Water Content of the Silica Gel: The gel was sampled at both the inlet and outlet points and each sample heated to dryness over a,Meker burner. Inlet Weight of Bottle + Fresh Gel Weight of Bottle Weight of Fresh Gel Outlet 27.5593 gms. 26.9279 gms. 20.0199 18.5578 7.5394 gms. 8.3701 gms. Weight of Crucible + Gel, After Blasting: Weighing No. 1 36.1571 gms. 35.7438 gms. Weighing No. 2 36.1557 35.7434 27.9070 28.9631 Weight of Crucible 7.8364 gms. gms. 7.1926 Weight of Dry gel Water content of the inlet gel is equal to C1 = (7.5394 - 7.1926)(100)/(7.1926) = 4.83% (dry basis) Water content of the outlet gel is equal to 02 = (8.3701 - 7.8364)(100)/(7.8364) = 6.81% (dry basis) -66The amount of water adsorbed by the silica gel can also be calculated from the rate of gel feed and the water content of the inlet and outlet gel. __ For example, C2 __ /21 [(C2 - 01)/100= ) + Loo+c2)J .- 10 lbs. H20 adsorbed/(hr)(ft2) For Run No. 10 [205.3(l.0 - 4.83 2181 + 209.2(1.0 - 10 l0+6.8i (6.81 - 4.83)/1001 = 3.9 lbs. of water vapor adsorbed/(hr)(fta) F.E2100;4.83 CALCULATION OF WATER BALANCE FROM THERMAL DATA Inasmuch as the measured increase in air and silica gel temperature up the column is caused by evolution of heat of condensation of the water vapor and heat of wetting of the gel by the water adsorbed, it is possible to calculate the quantity of water vapor adsorbed in the column from thermal data for silica gel and heats of condensation. The partial heat of wetting of silica gel, expressed as Btu per pound of water adsorbed is given in Figures 2B and 3B as a function of initial water content. Since the change in water content of the gel in all runs was small, the partial heat of wetting at the average water content can be used satisfactorily for calculating the water balance. The pertinent data are G = 1090 lbs. of b.d. air/(hr)(ft2 L*. av. = ) 206.7 lbs. of -gel/(hr)(fta) a* = 0.2 Btu/(lb. of gel)(OF.) *Lav. represents the arithmetic average (weight) of the inlet and outlet gels. SPecific heat of 0.2 for b.d. gel can be. used here since the gel water content is low. -670 aV = 5.82% hw (FigureB)- 250 Btu/lb. of water adsorbed 74 + 91.4)/2 = 84.4 0 F. tav.hv = (at 84.4 0 F. ) =-1046 Btu/lb. of water condensed Sav. = 0.243 Btu/(lb. b.d. air)(OF.) At = 14.04F. ha = 250 + 1046 = 1296 Btu/lb. of water vapor adsorbed Heat Evolution Observed: (1090)(0.243)(14.0) (206.7)(0.2)(14.0) = Total = 3710 Btu 579 Btu 4289 Btu Water adsorbed = 4289/1296 = 3.31 lbs./(hr)(ft2) DETERMINATION OF OUTLET AIR HUMIDITY BY GRAVIMETRIC METHOD Since the perchlorate drying tube method was not used in Run No. 10 for determining the humidity of the effluent air, the data taken during Run No. 3 will be used t6 illustrate the calculations. Weight of water and five gallon bottle Weight of five gallon bottle Weight of water displaced by air 39.00 lbs. 12.31 26.69 lbs. Temperature of Water in Bottles = 29.6500. No. 1 No. 2 Weight of drying tubes and ads. water 60.5292 gms. 70.2224 gms. 70.2033 60.5279 Weight of drying tubes 0.0013 gms. 0.0189 gms. Weight of adsorbed water Barometric Pressure, mm Hg = 29.67 inches = 754 mm. Head of water Lbelow gas receiver bottle = 23 inches = 42.8 mm Hg 3 Volume of connecting tubes = 30 cm Room temperature = 30'C. -68Vapor pressure of water at 29.650. = 31.2 mm. Hg Density of water at 29.65C. = 0.9957 gms/cm3 Then the pounds of bone dry air passed through the tubes may be calculated as follows: (26.69)(454)(1/0.9957) 30][ (75 4 (273/302.7)(1/22,400)(29/454) - 42.8 - 31.2)/(760) = 0.02792 lbs. The humidity of the outlet air then is (0.0013 - 0.0189)/(454)(0.02792) = 0.00159 lbs. water vapor! lb. b.d. air. By wet- and dry-bulb temperature measurements on the inlet air the humidity was found to be 0.0100 lbs. water vapor/lb. b.d. air. The water vapor adsorbed by -the gel per lb. of b.d. air is then 0.0100 - 0.00159 =- 0.00841 lbs. and since the b.d. air rate for Run No. 3 was found to be 1110 lbs./(hr)(ft2) the Lbs. of water vapor adsorbed/(hr)(ft 2 ) = (1110)(0.00841) = 9.33 It will be observed from Table VI that' this value is g'eater than that obtained from a difference in inlet and outlet gel weights. The proposed explanation for this is given in the Discussion of Results. CALCULATION OF OUTLET AIR HUMIDITY FOR RUNS 1-7 FROM DIFFERENCE IN INLET AND OUTLET-GEL WEIGHTS Since determination of the outlet air humidity by the magnesium perchlorate drying tube method was found to be unreliable during Runs 1-7 this quantity was calculated from the difference in the weights of inlet and outlet gel as follows: -69- L2 - Li = 357.5 - 352.0 = 5.5 lbs. of water vapor adsorbed/ (hr)(ft2) G = 1110 lbs. b.d. air/(hr)(ft 2 ) G(Hl - H2 ) = 5.5 1110(0.0100 - H2 ) = 5.5 0.0100 -H = 5.5/1110= 0.00495 = 0.0051 lbs. water vapor/lb. H2 b.d. air CALCULATION OF WATER BALANCE FOR RUNS 1-8 USING THEMIAL DATA Inasmuch as the water content of the silica gel was not determined experimentally during Runs 1-8 it was not possible to calculate a water balance from thermal data directly4. ever, How- subsequent runs indicated that the water content of freshly activated gel was sufficiehtly constant so that an initial water content could be assumed for the first eight runs. The final water content of the gel could then be cal- culated from the difference in weight of inlet and outlet gel. In this way heat of wetting data could be used to calculate a water balance for these runs. Run No. 3 Assume the initial water content of the gel to be 4.8 percent (dry basis). The final water content of the outlet gel is then (see Table I for original data) 100 E (357.5 - 352.0) + (352.0)(4.8)/(104.8) /(352.0) (1.0 - 0.048) = 6.42% Average water content = (4.8 + P.42)/2 = 5.61% Heat of wetting (Figure 2B) = 250 Btu/lb. of water adsorbed. A calculation similar to that on page 66 can now be performed. -70The result is Lbs. of water adsorbed/(hr)(ft2) = 3.8 CALCULATION OF GEL CONCENTRATION IN COLUMN FROK GEL FEED RATE AND AIR VELOCITY ASSUMING ZERO SLIP Inasmuch as the gel holdup in the column at higher superficial air velocities was very small, measurement thereof was difficult. Consequently, for Runs 14 and 19 the gel con- centration in the column was calculated from the gel feed rate and the superficial air velocity assuming the gel velocity to be equal to the air velocity. Run No. 14 Gel concentration in column, lbs./ft 3 = (lbs)(hr)/ (hr)(ft2)(ft) (hr)/(ft) = (sec/ft)(hr/sec) = (1/u,)(1/3600) Therefore, Gel concentration = Ll/(3600)(us) = 387.0/(3600)(7.92) = 0.0136 lbs/ft3 CALCULATION OF SLIP VELOCITY IN THE COLUMN The slip velocity in the column is the difference between the gel and air velocities and may be calculated from the gel feed rate and gel concentration in the column as follows: Slip velocity = Air velocity, ft/sec = U B- - b(bs Ll/(gel concentration)(3600) Run No. 10 L Gel concentration = 205.3 lbs. = of gel/(hr)(ft 2 ) 4.52 lbs./ft3 us =4.15 ft/sec gel)(fta) (h)f2 )( lbs .gel) -71Slip velocity = 4.15 - 205.3/(4.52)(3600) = 4.14 ft/sec CALCULATION OF ADSORPTION COEFFICIENTS, KRHa, Kaa AND (Kga)(G/1000) Run No. 10 KRHa = (G)(AH)/(h)(RH - RHe)M ARH = 35 - 13 = 22 (RH RHe)m = - (35 - 0) - (13 - /ln(35/4) = 31/2.17 = 14.3 9) G = 1180 lbs. b.d. air/(hr)(ft2) h = 1.5 feet H = 0.0035 lbs. water vapor/lb. b.d. air KRHa = (1180)(0.0035)/(1.5)(14.3) = 0.193 lbs. water vapor adsorbed/(hr) (ft3) (unit RH difference) K a = (L )(AUWC)/(l00)(h)(UWC - UWCe)m L = 205.3 lbsl of gel/(hr)(ft2) AUWC = 1.89% (dry basis) (UWC - UWCe)M = [(11.5 - 0) - (3.16 - 1.89)1 /ln(11.5/l.27) = 10.23/2.2 = 4.65 Kga = (205.3X1.89)/(100)(1.5)(4.65) = 0.556 lbs. of water vapor adsorbed/ (hr) (fts) (unit UWC difference) (K a)(G/1000) = (0.556)(1180)/1000 = 0.606 Values of KRHa are plotted against the mass rate of air flow, G, on Figure 18. Kga and (Kga)(G/1000) are plotted against rate. of gel feed, Ll, on Figures 19 and 20, respectively. CALCULATION OF PERCENT RELATIVE HUMIDITY FOR EQUILIBRIUM RUNS 20-2g. INCLUSIVE Run No. 20 Temperature in column = 22.9*0. -72p8 at 22.900. = 20.95 mm Hg .H = 0.0048 lbs. of water vapor/lb. b.d. air p = (29)(760)(H)/(18 + 29H) p = 5.82 mm Hg = 27.9% relative humidity 100p/p8 The water content of the outlet gel was calculated as for Runs 1-19, inclusive. CALCULATION OF AN OPERATING LINE ON THE EQUILIBRIUM DIAGRAM FOR A GIVEN RUN The slope of the operating line at the bottom of the column for any given run was shown in the Introduction to be (slope) 1 = GH s5 / L1 and similarly for the top of the column the slope was shown to be (slope), = GHS Then for Run No. / L1 10 where G = 1090 lbs. of air/(hr)(ft2) L = 205.3 lbs. of gel,/(hr)(ft 2 H = 0.0208 lbs. of water vapor/lb. of b.d. air H5 1 = ) 0.0323 lbs. of water vapor/lb. of b.d. air the slopes of the operating line at the top and bottom of the column are (slope) 1 = (1090)(0.0208)/(205.3) (slope) 2 = = 0.111 (1090)(0.0323)/(205.3) = 0.172 Obviously, since the slope of the operating line at the top of the column is greater than that at the bottom the curve must be S-shaped to pass through the points representing the terminal conditions with the slopes calculated. The results of such calculations for Runs 1-19, inclusive are plotted in Figure 17. j~ D. Results: Plots and Tables Table IV of this section gives all operating data calculated to a more useful form for design purposes. Also given are the calculated water balances obtained by four independent methods, namely, (1) air rate and humidity difference, (2) silica gel weight difference, (3) silica gel analysis for water content and silica gel rate of flow and (4) temperature rise and heat of wetting data. All other tables given in this section have been mentioned in Results in the main body of the report. Similarly, all plots given here have been mentioned under Results. TABLE M TA1LE Of CALCULATED DATA AND R[5ULT5 U,4 010. 4 3 a 1 6 s 0 0 a it 6 is 1+ IS I is is 17 I 20 14 11 1 as 1 26 As ILCET AIR: RATE OfPLOW,6, LS SUPERFICIAL ARA/("0XFTa) V90CIT,frT./SEc.,A, 19,IiZRATUEt,* hlUMIDIST,M, LII 1O/LS. 5.0. RELATIVE MUNSOTV,m%.PScEM Ait 1096 4.31 93.2 s.& $ILI 6.0110 0e.000 3S 33 r MuMID5 MEAT, 6, +.16 a 1100 1010 1066 5090 1160 1190 4.39 4.60 413 # +. +.S6 4.1s +.40 4.1t 19.0 1s.6 19.0 ,9.6 72.9 19.9 17.4 72.6 12.2 1,60 1140 1160 1043 +.23 21 36 .&+ 0.144 0.S44 155.1 101.6 1.4 0.t4e 6A". 0* 06 0.a*S 100 46 30 06 27 40 a.666 35 OUT"CTAIR.I A9E 49L ,./L. HUMI0ITYM5,4L6S. 90.1 04.0 91.1 99.5 'o0., 04.0 703 2045 AI50 .92 #.a 83.. 10 L00 79L 71 10 4.91 s15.3 *6+ 10 .0 4 d0 43 55 TO 0.L43 .143 0.243 0.0&43 94.0 89.6 St T? 13 0.00 O O650 1910 6S 8+4 +3 05066 10.0.o 30 SS 36 16 0.345 0.141 0.43 96-7 7T6 9.0. PIAT 1.4 0 1s.3 63.0 77.4 91.1 11.0 1 096 0..640 O.243 II 4.8 91.4 APPRA -5137 110 0.66 __ o0.6 04 . SIM 69.9 0 76.9 P6.4 0.011301, 6 I 05 1%4 89.7 13.1 101.1 70.9 0.9 69.9 76.3 0.0 TI.7 81.3 o.6 95.+ 16.1 77.3 INLInIto1,1 AlEt 0.66SS 9.637 0.6644 0.01 S0, 0.41 0.0030 6.6644 0636 0.6 0AO6+ 0.6611113 a66 064139 0.241 .S10 0. 141 o41 0.241 0.241 0.141 0.2*+ .145 0.1 .065 06015 It IMs 0 .8 9 1 RLtATiVMussiTY,s,,.aRCISP SUMID MILAT, 0.41 -39 l40.0616 II T9MP9RATUS,tg.P TampaxwTuAs" 0.06f as 31 0.143 0..L*+ 0.14+ 0.141 0.4+ 0.4 0.0074 %14,0 I 16-s 1 4614L 0.14 .ocul 13 I1 0.141 1 0 .645 0.00ST 004 10 16 to I1 11 1o 6.141 0143 0.144 0.0046 .0049 00 20 a L1.9 15 0-001Z 13.1 14.4 11 13 0.00 31.2 6604 +1.7 060 0 15.4 00130 6063+ .osaS 66.0 17.6 79.+ 46 46 46 0.143 INLE.T SILCA OIL :II AAISOPPSSO,L,,S0s.GEh/(SSRXK'T') rt5ILoSACTIVATION, MOISTURS COITEST, 3640 154.0 11.1 246.3 205.3 231.6 1+5.6 4.0 3 4.69 3.60 5.0 0oleu tklLTIMs11 4.12 4.1 5.95 3.47 6.0 391.0 321.7 216.5 25.1 is.+ 13 13 36 1 3 3 +651 .33 +.1? 4.09 4.01 4.9 36.14 4.41 4.52 +.60 4.76 +.71 3.3 0.04 +.63 ------ ------- ------- ------- 4L35 NA../V,b in O 271.6 @ASIS),% % CPR E9UILSSRSUMIAnCIUMtH,*---1" conc. 304.0 119.5 AS.0 3WO 4S. 0.06 0.012 0.4O 0609 %$*.( T1 +.75 0 13 +.60 0 0 0 0 13 46 0 a 0 0 0 0 0.0111 OUL.3T S6LSC^A 41. RATE OF FLOv,LAS. OL/(KRXFT "),L& OiSTRu acow"TEA(0R4 61.1 367.2 357.5 369.3 2G.S 109.0 216.3 UASIS),c 6 P133S3T WAI09AP6N AOM 3ELO ToEM RU,111S. s m*AVaVnO6.616 .t.- 6.1 0.66 ,r 0A 59 1 54A7 ,.1 4(4,-Ma) F-t. 65.0 49.0 0-93 0.93 S.5 10.0 14.2 .M ,S.. 5.6 66.5 45.0 5.0 132.6 44.3 45.5 52.0 47.3 0.71 0."0 0.01 0.85 1.21 1.20 O.S6 0.81 11.2 11.2 51.3 14.5 5.o I.2 15.1 19.7 15.3 143 0.143 .14L 0.141 0.um43 0143 0.130 0.243 0.*1 .142 .141 4.3 av-s..cITV AMRsINmG Ia A CALcULAT69 PON PONS -? , MEASURID0 149.t0AFTMA T"5S0 K5N6T 8 16 W6.54E6 a I.e iFSET *cALCuaATEo 6 7.0 5.2 1.8 4.7 POW50 ssUaMCIA.At ToWa COSS AsEcTI6O - w (11/2S.4)r3A/s4x4) a 4.091 T0wAa VOL~UME * (.5X4.09 x so-')s 6.54x 3 ~ri. 3 RAVES OPAIS NPW ( LOS. .D.AIR/tMW.)(6O/4.-91-) [/4.O91 (PT'/M) #UPS9.PSCSAL AiR VELOCITY 0 . r3 +.5 1.1 4,0 4.7 ((4 .La-ss.4,4 .61-566.o4a$L,-c, (L 4 ,.1)(,tt,)-)/.. .3 2 +6.5 5.5 7.2 6.3 6.05 4 ks"Ls~sU' MU"A"EAT RM2 ELAPSSOTIP&OP 1096.1 340.6 1+9.3 391.0 391.6 13.6 290.0 121.1 113.0 293.1 117.0 149. 7.6 it MOLDUP) GEL COAC:ISTRAT0e,16 sM 904.11M x (M5S.GL. RAT901114ILL. Puslo efns. %.9)/(4r4))(s/oMis OP aus) 4.1 4.0 3.7 49i 6.19 1.3 cO 5.9 1.44 5.0 0.6 3.3 .215 5.95 .1 0.6- 14.6 25.0 2,6.3 45.t 0.4+ 0.76 0.78 0.65 0.79 0.79 14.7 6.6 4.9 4.0 214 6.6 5.1 0.243 0.4 243 0.3.411 4.1 3.5 T. 4.6 4.9 -3.7 3.3 6.5 -3.0 4.1 6.6 3.1 3.2 a.3 2.1 6.14S 1.143 -3.9 3.2 +.s 6.0 2.9 4.1 4.1 3.7 3.9 3.4 5.6 F.9 9.0 1.1 3.0 4.0 1.9 +.6 .343 4.4 1., 32.1 5.7 I.+ 14.9* 11.14 9.23 56.54 12.90 19.35 36.10 4.99 30.0 12.3 54.0 0.21 3.4 1.3 6.&0 161IP 10-1 o-'X 6.9 3.5 1A 1.6 6.33 .l,6106XL8. S.0. AtI/MIlot) - (4.I)(FTI/M4) /(+54X415 /+.01 sO-@) XIO-0), (o.s9 (O.93flXQs. )(sPIS. S' OGL/ RS 5L'OUP) OP Mul) AW p Ao/+P 31.15 -74wTABLE V VARIATION IN RESIDUAL WATER CONTENT OF SILICA GEL WITH TIME OF REACTIVATION IN AIR AT 178 0 C. Time of reactivation, hrs. 2 Percent residual water, dry basis 4.85 4.83 4.80 13 4.76 4.72 23 4.80 36 4.83 72 4.75 -75TABLE VI COMPARISON OF WATER BALANCES CALCULATED FROM (1) DIFFERENCE IN WEIGHT OF INLET AND OUTLET GEL and (2) DIFFERENCE IN HUMIDITY OF INLET AND OUTLET AIR Run No. P o u n a so0 Gravimetric f W a t e r A d s o r b Gel Wt. Difference /r)(ft) Psychrometric % Error 2 8.6 7.2 3 9.3 5.5 69.0 4 7.9 4.3 84.0 5 9.1 7.0 30.0 6 7.3 4.0 82.5 7 6.9 4.7 Note: 5.6 4.8 19.5 47.0 The percent error above is that for the lbs. of water adsorbed/(hr)(ft2 ) calculated by the gravimetric method assuming the values calculated from the gel weight difference to be correct. -76TABLE VII COMPARISON OF GRAVIMETRIC AND PSYCHROMETRIC METHODS OF DETERM1INING THE HUMIDITY OF THE OUTLET AIR Run No. A bsolute Humidity, Gravimetric Outlet Ps ychrometric -With gel "jiggling" in column2 0.0022 0 .0049 7 0.0017 0.0038 -With no gel "jiggling" in column0.00808 Note: Units of Absolute Humidity, of water vapor/lb. b.d. air 0.00810 Outlet Air are lbs. Air -77TABLE VIII PERCENT FINES PRODUCED DURING USE OF SILICA GEL Silica gel through #48 screen, Silica gel unscreened, gms. % fines produced gms. 63.0 636.6 Note: This gel was screened before Run No. 7 and used through Run No. 15 before rescreening. 3 9.9 -78TABLE IX ESTIMATED HEAT LOSSES FROM COLUMN Run No. Heat Losses, Percent 1 5.0 2 4.2 3 4.0 4 4.4 5 4.1 6 4.3 7 4.5 8 4.6 9 6.8 10 5.0 11 4.5 12 4.7, 13 4.5 14 3.7 15 9.5 16 3.7 17 3.8 18 3.9 19 5.8 .........I .......... - - ----.l.-w w KV i + + .... .... .. 44 : TN t .... . .... ......... .... .... .... .. + - + .. .. t- wo 300 - f ++t7t 400 F" 0" 9" .. ... . .. . ... .... . ... .... .... ... ... t... 'I ... iL . .... .... .. WIN ... . .... . ... EM lk-U3QR 971 1. ... . . .. .... .... .... .... .... .... ...... .... . .. .... .... ..... 777.... ... .... .... .... .... ......... .... ... ... .. .... .... ... .... .... .... .... .... .... . ........ ... .... ... .... ... VJ A _T .... ..... .... .. ........ ..... .... .... .... .... . ... .... .... .... .... .... ....... .... .... ... ... .... .... .... .... 1-7: --:7:7 - ...:. . . . ... ... . .... .... .... .. 4H H l M ; ++ 4 -- 44. + :Tit .. . t TI 1 T--- V4 44! +Jti . .. . 4 -JIL- .... ...... + ++ I ++4-- + Ti T + ..Aa 4 mm F11 l 1: 1 ! 1 E so 40 ill1i so SA 11; FT:M 0 I 9 I illiji .. ........ -- 4-i-f r I I of I 11 -+- 1 i T III jjjj,_j__4 H Ira, 4 i ..... ..... ......... .... .... .. ......... + + . . . . .4- - ... 71 .... .... .... .... .. ..... .... +t TIT- , -- T- .... _4_44 ' .. .... ..... ......... .... .... .... .... ... 7 110 ... .... . . . . . . .. . -1 t t 14- too .... .... .... .. :::, ... -- : ..... . - :: ....... . ... H-H ... . .. ... .... .... .... .. .... .... . : : . .... :.: .... . ... .... .... ..... ... . .... . .. . .... ... .. 14. .... . .. . .. .. . ... ... .. ... ::*: -: . . . .... ... I - 7 .. .. .. .... . : . : : : *:: .... . ... .... .... a a . .. . . . . . . . . . . . . . . ... . . . .. . . . . . ... . ......... . . . .. .... . .. . .. .... .... ... . . . . . . . . . ... .... .... .... .... .... .... .... .... ..... f .. ... .. .... .... . 147t . . . .. ... .. . . .... .... .... .... -': .. .... .... . . .... . . . . . . . . . . . . . . . . . . . T . . . . . . . .... . . . . . . . so 14 =-- .. . . .... . ... .. 40 + + + + t .. :' : + .... : : : : ... : ... .... .... . . . ... ... .... .... .... ... .... .... ......... ... .... . . . . 30 -I -+++ 11 4- . . . . + . . . . . . . . . .... . .... .... . .. . . . . . . . . . . . . . .. . . . ........ . . . . . . . .. . . . . . . . . . . . .. . .............. .... . . . . . . . .... ... .... .... . + + .... .... ... .... 10 .. . . . . . .. . . . . .. . .... . .. .... .... .. :: +..--.. .... .... .. ... . . . .. . .... .... ... . . . .. .... 1+ -tit tat .... .... .. IL" 4" 6 low so" am I" Aw .. . . . . . . . . . . .. . . . . . . . . . . . . . . . .... . . . . . . . . . . . .t . . . . ... .... .... "..... I ....:... . . . . ... .... ... I :7-~{1A$4tt;tttdlltt4T T77 :I* ITFIW;tIm4h4 I t±Tttiii HF- Boo 'S I I El::2 -E .- up" fif 14 - FF-- rtt: =141.41=11t- rjd M0 I p.- LW" tiZ :I I I ttt-i -.. 4Kit: 4i)4P #27 , f 4; 7'1± 22 I -, --- 27 ft-f-- :4~ ITiYIPII I:4: *.{~j[:~.jj:j f II t f I0 0 10400 G0M0 W" 1400 940 IW "o ansi ~ 12"0 amni sinS 004 IEmfIEEIIIEIinIImEIiiiiuE7miimmmiimmiimmmmmiiiu on +r41W4 7fftt~~~a~~jw:Att~~~wI :4 -;4 -"4 1- PPPRP Ti7 I~ 0 i~~hVf4 KKV+.. i2IPkdU§tTUUIiPI 2TfW +~ImE ++t5 f+ 71 MiMil Mil " P-77771 0 01 II! livii ft of .1. ~. . . . t:fltt lat iihi .... 4 ttttt4t4Ptt444tVA: 0* 4 + 44 t 4 .1l -1 ft a ~ ~~ -~i Of 4 -.-.-44.-- 1 Ii "1 .{ ... . . ... :u I: I: Iu t It I:Tt I:: Ta II i I. ::: :t 7+ 4 + I T- 1-24444 !a -"4 - 6 -"t -t-I H - !+-"--44 MI-IH-. 60 -4-+44. -4 +t ~4~4~4 -4 so1 tt- 401 4 =T- -4 TT -+4-, 1 -4-4 4 4 + 4 ... 4 .... + .... ..... ::4 + . . . . . . . . . . . .. .. . . . . . . .. . . . - . . . . . . . I .... ... "W30 + + to 1 TT = 4t 4 + T + 0 + = . . .. . . ... .. . . . :j. + 1 -4. + . . . . . . . . . . . . . . . 4 + 4 r . . - 4 .. . . . . . . . . . . . . . . . +: 10 + + + ... + .... H . ::* . . .. I + t ,77.1 0.1 .. + . . . . . . . . . . . . . . . .. . . . . . .- . - . , . . ;. . . I i . . . . =--4 + . +~J 1ltIFvrrL O-Z 0.3 I TT ITT I 'AMR .9 I r - 4--t . . .. .... .... . .. . .. .... ... .... .... ... + .... ..... ... .... .... .... ... .... .... .... T +_ .... .... .... .... .. Z:7: !t+ +44. '14 - .... .... .... T ... . .... ... ... .... .... .... :-A .... IT .... .... IT of- . .... ... ... I - + -4 am . ......... ... ..... It ... .9 ......... . 4 ...... . ... -4wILI - ---- ---- ... . .. .. .. .... +4 .... .... .... .... .. . -lie -t-r+ .. .... .... . .... .... .... ... .... .... . .. -------... .... .... .... .... ..... .... .... 71T t .. .... ..... .... .... .... .... .. .... .... ......... .. . .... .. ...... .... .. .... .... .... .... .... .... .... . .... ....... .... T - - -4 t, .... ... T+ 4 .......... .. .... .. 4 4- .. T 44 _, .... .... .... .... .... .... .... ... .. .. t .... .... ... -1 1+ 4 .1 + .... .... .... . .. .... .... .. ... .... 1. t + .... . . .. . . . IT . . . . .. .... .... .... 1 4 . ... - -,4 . ....... .. .. . . ... .. .. .... .... -------- 71 4-4- . . . . +: 41 . . . . . . . . . . . . .. . . . .... SAM -Ld. . ... T . .. .... .... ... ...... ....... J .: t lk ... ..... 1 If %FA .... ....... ..... I ftf T 1 t t- f - '44- 3 61, 4 2 o 8 5 (S 3 4 36'8 1) 3 5 1 L Ir GO I I -- 56_- 7I 7 a_ Fi: ___ - - - - - - - - - __ ---- 3 ... ...-.. . ... ... T.. 02 -~~~~~-- ,. 4----- 4.L. r -1 L -1Z ~i -r - 2 a 4 5 07 so a 4 a 5-7 89 JT 1060 6o MSS RMA1 OP AIR fP1.0W, LAAqU 41j1 mmums 2 1 3 p ... .... ... .... .... .... .... ......... .... .... .... ... .... .... . ... ... .... + I-t .. .. .... ' :4 .. ... . 7 .... . ..... .... ..... ...... .. .... .... .. . . .. .... .... .. + ..... .... .... . .... .... . ... .... .... .... .. . .... .... .... ... . ... ir.... ... .... ... . . . . . . . .. . . . . . . . . . . . . . .. .. .... + + . ... if 04 .. A- :4 -r T77-T T WOO" rI .... -4 i I , I I I ....... 4 ++ T- -7 Ti , 7 + . . + + + .... . . T + +4 -44 - .44 + .. ...... .... + ; ++ TTTTT 1 777 i Ti I 1 T I I I I 4- T I r I I T I I TT 1 7 I 4 I + ++ + =.jT + --- r + ++, +: I +I 1 .... .... ..... 1 1+ - + 17 7-:: .I I I -+++ + ++ ++ + -4 *4 4 rl, + 4-L . . . . .... . . . .... 7f . . . . .... + .... + t -+ + + 4 .. 0 00S9 00CM "r M"no . .. . .. ... .. . .... .... .. .... ... . .... .. .... .... .... .... . Ile .. ......... ... .... .... ... .. .... .---.... ....... ... ..... .... . .. ......... A. M ro ......... .... .......... . .... .... ..... .. . .. . . . . . . .. .... ... . .. .. t .... .... . . . . .. . . . . . .. . . . . . . .. . .. . . .. . . . . .. . -llc= .. . . . . . . r . .. . .... .... . . . . . .. . . .. . . f .... . . .. f too ... . . . t . . . Ht . . . . . . .. .. .... .... .... .. . .. too .. +i 0*0 TT .... .... .. 1 I JIP ALAAA " -*4pppl-- lp" . I - 4 1 1 1 . . . TI . . 4 , ++- V- 1. 4 i i 1 11 - I t -T, - - - . I . TT I I f 14Z I I kv , ............ I- T -V t ........... -1 JEW-1 .... .... 4 t -44+441''li 44 4 i Ut4- --4-+ +-1 t I . I . i4 4 -t 'w I - ---- ---- .~ . 00n . 74-.t an *of - u- N- I~ I~ q~ ~ y,,, I ~. aI I0 ~a K7Ftm~~~~t4E~t,+l~~EFFsLt .t Igo El4 .I'j 4+ 44- t- 4 14- + t4 -. - -wM T-:~~ + +4- 4- t t4l 4-" *+t- i +4 i7i ++ + 4 T -4 . .. .... . t .. + .. . . . . . . I. . . . . . . . 4-+ 900 + - Pt-Pt: 1. 2 A4tt4t442-.f.~.4..4-,-~ __ 4224stp2z~:2f:2plu 41 t:: +7 ,-. . .-. +i - 4-+7 fH - A.O to :fflfttilThi t t; -4 4: LHV{ I II 4t 44- 4-u- 44i44-4-4-P4-4-.44-44-t--t4 -f-4- 4j11!11 44+4-4 44- 4 M,-+--A444r-4 HI +P~4.-.t t -I- 4--t 4A44 + + Ui4itit ~T.fl~ZZt.Z.LLZt'~1tttiutt~n:t:: It I -~L; .t 7 ~ '4t off S. H httt±t-rt!tt±tiAI±tuttzs. jt t -* i 8IIVREM7U- ttl ti4LI A i H I. *.. +4 24 I:tt= IISMTYEU tfl IIEEinIinmnmnmIahmaInhamnmnmnEEEm I-El---'- .- , I-- L M d 11 11 1 1- , f- I -- f - F2 I i 1 , , " rt 7t; -It4- 4 -:::+44k j 1 n !j = '; Days0 000 -77777--.- +4 t7:,- t :M!r; !trrm 0 : 1 1 1 1 1 , !1i:T:i1":! m 11 ; 11 1 111 11 11 L m 11 , '. -!I!:: * t! . . - . . - - . . . . , - -- .... .......... 0 . , - . - . -i i 94 ~~E1 4~, 4 + +;-4-- 4-+ 4, -Htttt--i-' J'i'r=77 - 4i +++4+i i i i 1 ; ; ; i 4 H i i Ft+-4 4- j 1 1 i i i i i i I i 7i ; ; i ., 1- !. ~1~*~~~ 1 1 1 1 lot iii 061 4--74-,'!* *---i-A-V ++-+4 + t-- -r I j + A I - I ~ . - ... ________ ... -29E. Location of Original Data The original data for all runs will be found in Research Notebook Number 1 on the following pages. Run No. Page No. 1 6 2 9-10 3 11-12 4 14-15 5 22-24 6 25-26 7 27-28 8 30-31 9 33 10 34 11 35 12 37 13 39 14 40 15 41 16 43 17 44 18 45 19 46 20 48 21 49 22 50 23 51 -80Run No. Page No. 24 52 25 53 26 54 27 55 28 56 Miscellaneous original data are found in Research Notebook Number 1 on the following pgges. Nature of data Page No. Comparison - Psychrometric and Gravimetric Methods of Determining Humidity Resereening Silica Gel 13 29, 42 Calibration Data: Thermometers 1 Triple Beam Balance 13 Air Orifice Flowmeters 17-21 -81F. Calibration Data: Plots and Tables Before any experiments were initiated the thermometers used for temperature measurement were calibrated at the icepoint. The data obtained are given in Table X. Similarly, the triple beam balance was calibrated against brass -analytical weights during the course of the experiments. Data obtained at four points are given in Table XI. Three different flowmeters were used in Runs 1-19, inclusive. Calibration data for these flowmeters ranging from 0.5 to 5.0 cubic feet per minute are given in Figure 21. -82TABLE X CALIBRATION OF 00-5500. THERMOMETERS USED TO MEASURE THE INLET AND OUTLET AIR TEMPERATURES (ICE POINT, OCC., USED AS STANDARD) Thermometer No. 2 Note: T e m o e r a t u r e, 00. Trial No. Trial No. 2 Trial No. 1 0.10 0.10 0.10 0.10 0.10 0.10 0.12 0.15 0.15 3 Calibration trial No. 1 was carried out in a mixture of ice and water in a towel wrapped beaker. No. Trials 2 and 3 were made in a small Dewar flask in a mixture of ice and water. -83TABLE XI CALIBRATION OF TRIPLE BEAM BALANCE USED IN WEIGHING INLET AND OUTLET GELS Brass Weight, gms. Weight by tritole beam balance, gims. 50 50.25 70 70.50 80 80.50 90 90.50 CAWRR ___o G. 4. -4-0 2. o > 4 o0 ______ OP ... _.... _______- ____ - - - ____ 0-0000"- _ _ _ _ _ _ (~ _ _ _ _ _ _ 0. -1 I A 2" 3 0 6 8 10 10 0 so 4 40 Go so m _ _ _ -84G. Nomenclature a square feet of surface area of the silica gel per cubic foot of tower volume silica gel concentration in the column, lbs. of gel/ b (ft3 ) 01, 02 water content of the inlet and outlet silica gels, percent (dry basis) C av. the arithmetic average of the water contents o f the inlet and outlet silica gels E error in the water balance calculated from thermal data, percent G mass rate of air flow, lbs./(hr)(ft 2 ) h height of column, ha heat of adsorption, water vapor on silica gel, Btu/lb. of hv ft. Tnter vapor adsorbed latent heat of condensation, Btu/lb. of water vapor condensed hy1 heat of wetting of silica gel by liquid water, Btu/lb. of liquid water adsorbed H1 , H 2 absolute humidity of inlet and outlet air, lbs. of water vapor/lb. of b.d. air H5 absolute humidity of air at saturation, lbs. of water vapor/lb. of bid. air KRHa adsorption coefficient, lbs. of water vapor adsorbed/ (hr) (ft3 ) (unit RH difference) Kga adsorption coefficient, lbs. of water vapor adsorbed/ (hr) (ft3 ) (unit % UWC difference) -85Li, L 2 mass rate of flow of inlet lbs./(hr) L av.1 and outlet silica gel, (ft2 ) the arithmetic average of L and L2 p partial pressure of water vapor in air, mm Hg pS partial pressure of water vapor in air at saturation', mm Hg RH1 , RH2 relative humidity of the inlet and outlet air, percent RHle RH2e relative humidity of the air in equilibrium with silica gel at a given UWC, perdent L'S s2 humid specific heat of the inlet and outlet air, Btu/(lb. of air) (OF.) sav * the arithmetic average of s l and S2 S cross-sectional area of the column, 'ft2 ti, t2 , ts temperature oC thet inletIL andi outle tair.-and,-of-they, air three inches above the gel inlet point, respectively, At temperature increase of the air passing through the column, or t 2 U - tl = At, OF. the overall coefficient of heat transfer based on the inside heat transfer area of the column, Btu/(hr)(ft 2 )(OF.) u velocity of the gel passing through the column, ft/sec g u superficial velocity of the air, ft/sec UWc , UWC2 useful water concentration of the silica gel, or UWC = 100(C2 - C 1 )/(100+0), or lbs. of adsorbed water/ lb. of initial wet gel, expressed herein as percent U0C le, UW e useful water concentration of the silica gel in equilibrium with moist air at a given percent relative humidity, percent v specific volume of humid air, ft?/lb. of b.d. air -86H. Literature Citations 1. Bartell, F. E. and Almy, E. G. 475 (1932) 2. Bryant, Silica Gel Dehumidifier, Engineering Bulletin No. 334 and 336, AlA File. No. 30-F, The Bryanl Heater Co. 3. Chem. and Met. Report on Conditionibg of Gasea and -Air, May 1940 4. Dehler, F. C., Silica Gel Adsorption, reprinted from Chem. and Met., May 1940 5. Dehler, F. C., Silica Gel, Its Uses as a Dehydrating Agent, presented at George Washington University, Washington, D. C., June 23, 1941, Distributed by the Davison Chemical Corporation, Silica Gel Department, Baltimore, Md. 6. Ewing, D.T. and Bauer, G. T., J. Am. Chem. 59, 1548 (1937) 7. Fells, H. A. 241 (1925) 8. Harkins, W. D. and Ewing, D. T., Sci., , 49 (1920) 9. Industrial and Commercial Air Conditioning, Committee Report, 1939, Working Committee of the Committee of Executives on Air Conditioning, American Gas Association, 420 Lexington Ave., New York City and Firth, J. B., J. Phys. Chem., 36 J. Phys, Soc., Chem., 29 Proc. Nat. Ac'ad. 10. -Jones, D. C., J. Phys, Chem., 29, 327 (1925) 11. Lamb, A. B. and Coolidge, A. S., 42, 1146 (1920) 12. Lewis, W. K., Squires, L, and Broughton, G. Industrial Chemistry of Colloidal and Amorphous Materials, The MacMillan Co., New York City, 1942. 13. Miller, E. B., U.S. Patent 1,557,534, March 23, 1926 14. Miller, E. B., U.S. Patent 1,799,858, April 7, 1931 15. Miller, E. B., U.S. Patent 1,825, 707, October 6, 1931 16. Patrick, W. A. and Cohen, L. H., J. Phys. Chem., 41, 437-43 (1937) J. Am. Chem. Soc., -8717. Patrick,. W.A. -and Greider, C. E., J. Phys, Chem., 29, 1035 (1925) 18. Patrick, W. A. and Grimm, F. V., J. Am. 43, 2144 (1921) 19. Patrick, W. A. and McGavack, John, J. Am. Chem. Soc., 42, 946 (1920) 20. Patrick, W.A. and Opdycke, L. H., J. Phys, Chem., _29, 601 (1925) 21. Ray, R. C. and Ganguly, P. B., Trans.. Faraday Soc., 30, 997-1007 (1934) 22. Walker, W. H., Lewis, W. K., McAdams, W. H. and Gilliland, E. R., Principles of Chemical Engineering, 3rd Edition, 1937, McGraw-Hill Book Company Inc. New York City, N.Y. 23. Zigmondy, R., Z. anorg. chem., 71, Chem. Soc., 356 (1911)