MEDIA Inverter MEDIA is a compact and scalable inverter providing

advertisement
DC Power for
Business-Critical Continuity™
MEDIA Inverter
1500VA – 48Vdc
Key Features
nDual input sources (AC & DC)
MEDIA is a compact and scalable inverter providing
a pure sine wave supply of AC power.
nCompact and lightweight solution
Description
nHigh efficiency
In conjunction with a DC power system, the MEDIA inverter delivers a reliable backup energy solution for AC applications. Using the latest Twin Sine Inverter (TSI)
technology, this inverter provides superior energy efficiency in a compact size.
nFull scalability and expandability
nNo single point of failure
The MEDIA inverter is designed to work from 230Vac and 48Vdc sources through
AC/AC and DC/AC conversions. Unlike traditional inverters, this inverter features an
AC to AC conversion process, known as Enhanced Power Conversion (EPC), that
double filters the output wave form. EPC mode operates offline, assuring high efficiency of 95% without any compromise in quality or stability. By filtering current
and voltage offline, EPC mode is able to operate like an online rectifier and inverter
but deliver significantly better efficiency. Compared to a UPS operating in offline
mode without current and voltage filtering, efficiency is the same but the rejection
of grid disturbances is much higher.
nTotal modularity as no external
static-switch required
MEDIA inverters have an in-built static switch function. Because no external static
switch is needed, the inverter system is smaller, more reliable and easy to expand.
As many as 32 inverter modules can be used in parallel.
nHot swappable
nPure sine wave on AC output
nTransfer time reduced to naught
An online mode is available for use during the occasional mains outage when inverters are fed by batteries. Since these inverters will almost constantly provide an
efficiency of 95%, they offer the most reliable AC backup solution in the industry!
Application
Inverter systems are normally used for AC backup requirements in a telecom / datacom site or anywhere a highly reliable AC power back up source is needed.
EN312DRA-Media / 1112
1
MEDIA Inverter
Inverter Power Flow Diagram
Standard Feature – Offline Mode
AC in
➡
DC in
AC
Backup Feature – Online Mode
➡
AC in
AC out
AC
➡
DC
Output power comes from AC in – Inverter is fed from AC commercial grid
AC
AC out
DC in
➡
AC
DC
➡
➡
Output power comes from DC in – Inverter is fed from the DC Power system
Technical Specifications
General
EMC (immunity)
EMC (emission)
Safety
Cooling
Isolation
MTBF
Efficiency (Typical)
Dielectric Strength
True Redundant Systems
RoHS
Connection
Trouble-Free Operation
EN61000-4
EN55022 (Class A in system)
IEC 60950-1
Forced
Doubled
>200,000 hrs
Enhanced power conversion 95%
On line 91%
DC/AC 4300Vdc
Compliant: 3 disconnection levels on AC out and DC in
Power ports: 4 disconnection levels on AC in port
Compliant
I/O terminal block protected against inversion
of polarity
Self adaptive to wide operating conditions and
comprehensive table of troubleshooting codes
AC Output Power
Nominal Output Power
Output Power (resistive load)
Short Time Overload Capacity
Permanent Overload Capacity
Admissible Load Power Factor
Internal Temperature Mgmt.
1500VA
1200W
150% 5 second
110%
Full (power rating from 0 inductive to 0 capacitive)
Switch off
DC Input Specifications
Nominal Voltage (DC)
Voltage Range (DC)
Current (at 40Vdc)
Maximum Input Current
Recommended Protection
Voltage Ripple
Input Voltage Boundaries
48 V
40 - 58 V
34A
48A
50A circuit breaker per inverter
<2mV
User selectable
AC Input Specifications
Nominal Voltage (AC)
Voltage Range (AC)
Current (at 185Vac)
Conformity Range
Power Factor
Frequency Range (selectable)
Synchronization Range
230 V
185 - 265 V
28A per shelf
Adjustable
>99%
50 - 60 Hz
47 - 53 Hz, 57 - 63 Hz
AC Output Specifications
Nominal Voltage (AC)*
Voltage Range (AC)
Voltage Accuracy
Frequency
Frequency Accuracy
Total Harmonic Distortion (resistive load)
Load Impact Recovery Time
Turn On Delay
Nominal Current
Crest Factor at Nominal Power
(with short circuit mgmt. and protection)
Short Circuit Clear up Capacity**
230 V
200 - 240 V
2%
50 - 60 Hz
0.03 %
<3%
0.4 ms
40 s
6.6A (protected against reverse current)
2.8:
1
10 x In for 20msec
* Operation within lower voltage networks leads to derating of power.
** Available while Mains is available at AC input port,
with magnitude control and management.
Transfer Performance
Maximum Voltage Interruption
0s
Total Transient Voltage Duration (max) 0 s
Environment
Altitude Above Sea
Ambient Temperature
Storage Temperature
Relative Humidity
<1500m
-20 to 50 °C
-40 to 70 °C
95%, non-condensing
Signaling & Supervision
Display
Alarms Output
Supervision
Synoptic LED
Dry contacts on shelf
Use optional devices
Weight & Dimensions
Width x Depth x Height
Weight
Material (casing)
19" x 2U rack x 380mm depth
N x 2.4kg (inverter) + 5.5kg (rack)
Coated steel
EmersonNetworkPower.com/EnergySystems (North America)
EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power Energy Systems North America 2012.
Business-Critical Continuity™, Emerson Network Power™, the Emerson Network Power logo, Emerson® and Consider it Solved are service marks and trademarks of Emerson
Electric Co. EnergyMaster ™, eSure™, NetPerform™, NetReach™, NetSpan™, NetSure® and NetXtend™ are trademarks of Emerson Network Power Energy Systems North America.
2
EN312DRA-Media / 1112
Download