LIEBERT® HIPULSE U™ 3-PHASE UPS: 80-500KVA, 50HZ, 380VAC - SITE PLANNING DATA
General Specifications
INPUT
The Liebert® Hipulse-U offers a
reliable, scalable and userfriendly solution to ensure
availability of various types of
networks.
Hipulse-U offers protection to
your investment and lower cost of
ownership through its digital
architecture and range of options
which you can customize
specifically for your needs.
Voltage
Voltage Range w/o derating
380VAC, 50Hz, 3-phase 3-wire plus ground
+15%, -15%
Frequency Range
45-65Hz
Current Distortion with filter
10% maximum reflected THD for 6 pulse & 5% for 12 pulse at full load
Current Limit
115% of full load input current
Power Factor
>0.9 lagging at full load; >0.9 lagging at half load
Surge Protection
Sustains input surges without damage, per criteria listed in IEC 60664-1
OUTPUT
Voltage
Voltage Adjustment Range
380VAC, 50Hz, 3-phase 3-wire plus neutral and ground
±5%
Voltage Regulation
1% for balanced load, 1% for 100% unbalanced load
Dynamic Regulation
±5% deviation for 100% load step;
Transient Response Time
Recover to ±5% of output voltage within 1 cycle
Voltage Distortion
For linear loads, 1% THD; Less than 3.5% THD for 100% nonlinear loads without kVA/kW
derating
Phasing Balance
120° ±1° for balanced load; 120° ±2° for 100% unbalanced load
Frequency Regulation
±0.05Hz for free running frequency
Load Power Factor Range
0.5 lagging to 1.0 without derating
Overload
125% of full load for 10 minutes; 150% for 1 minute, with true sinusoidal waveform
ENVIRONMENTAL
Operating Temperature
Non-Operating Temperature
UPS: 32° to 104°F (0-40°C); Battery: 68° to 86°F (20-30°C)
-13° to 158°F (-25° to 70°C)
Relative
H
idit Altitude
Operating
0-95% non-condensing
Up to 1,000m without derating
Acoustical Noise (full load)
80kVA/100kVA/120kVA
<67dB at 80-104°F (27-40°C) ambient
160kVA
<69dB at 80-104°F (27-40°C) ambient
200kVA
<70dB at 80-104°F (27-40°C) ambient
300kVA
<72dB at 80-104°F (27-40°C) ambient
400kVA
<72dB at 80-104°F (27-40°C) ambient
500kVA
<74dB at 80-104°F (27-40°C) ambient
STANDARDS:
EMI requirement: IEC/EN 62040-2 C2 or C3 level. (Consult to product manager for detail. )
Electric Specification: IEC 62040-3(Uninterruptible power systems (UPS) -Part 3); IEC62310-3(Static Transfer Systems- Part 3)
Site Planning Data - Single Input, 80-500kVA, 50Hz, 380VAC
Site Planning Data - Single Input, 80-500kVA, 50Hz, 380VAC
UPS Rating
Voltage
AC Input
Battery
Current (A)
kVA
Input
kW Nom.
Output
Nom.
Nom. Max.
Rec.
OCPD
Nom.
VDC
AC Output
Battery
Max.
Disconnect
Discharge
Rating
Mechanical Data
Current (A)
Nom.
Dimensions
W x D x H (mm)
OCPD
Weight
lb. (kg)
Heat
Dissipation
BTU/hr
(kWH)
Cooling
Airflow
CFM
(m3/hr)
72
90
108
380
380
380
380
380
380
145
181
217
159
199
238
250
250
250
384
384
384
237
296
355
NA
NA
NA
121
151
181
250
250
250
900x855x1900
900x855x1900
900x855x1900
900
900
900
5.04
6.3
8.24
1890
1890
1890
120(12P) 108
380
380
212
236
250
384
355
NA
181
250
1540x855x1900
1400
8.92
2250
384
80(6P)
100(6P)
120(6P)
160(6P)
160(12P)
200(6P)
200(12P)
300(6P)
300(12P)
400(6P)
400(12P)
144
144
180
180
270
270
360
360
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
500(12P) 450 380
See Notes for Table (below):
289
282
362
353
542
529
723
706
318
315
397
394
596
591
795
788
400
400
400
400
630
630
800
800
474
474
592
592
888
888
1184
1184
NA
NA
NA
NA
NA
NA
NA
NA
243
243
304
304
456
456
607
607
400
400
400
400
630
630
630
630
1250x855x1900
384
384
384
384
384
384
384
1640x855x1900
1240x855x1900
1740x855x1900
1640x855x1900
2280x855x1900
2280x855x1900
2280x855x1900
1200
1750
1200
1850
1600
2550
2200
2400
9.63
11.89
11.12
13.91
19.33
21.8
28.2
31.6
2590
2750
3180
2910
5250
5350
6150
6150
882
985
1000
480
1182
759
800
2640x855x1900
2900
36.2
8205
1
2,3,7
5
4
625
—
—
—
1,3,7
Notes for Table
1.
2.
3.
4.
5.
6.
7.
8.
1,3,7
5
Additional Notes
• If site configuration includes a backup emergency generator, it is recom- mended that the
Nominal (Nom) current is based on full rated output load at nominal input voltage.
Maximum (Max) current is short duration for battery recharge conditions.
UPS input cables must be run in separate conduit from output cables.
Nominal battery voltage is shown at 2.0 volts/cell per
OCPD = Overcurrent Protection Device. Recommended AC input and AC output
overcurrent protection represents 115% of nominal full load current (continuous) plus
100% of recharge current (non-continuous) per NEC 215.
Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground
conductors are recommended.
Wiring requirements: AC Input:
3-phase, 4-wire, plus ground
AC Output: 3-phase, 4-wire, plus ground
All wiring is to be in accordance with national and local electric codes.
Control wiring and power wiring must be run in separate conduit.
engine generator set be properly sized and equipped for a UPS application
• If site configuration requires an external isolated maintenance bypass circuit, it should be
noted that utility AC input might not be in phase with the UPS AC output. Consult an Emerson
Network Power sales representative or applica-tions engineer.
• Input and output 4 poles external breaker will be used for the UPS use with impedancegrounded systems, corner-grounded or high leg delta systems.
© 2013 by Emerson Network Power CO., Ltd
All rights reserved. The contents in this document are subject to change without notice.
Emerson Network Power provides customers with technical support. Users may
contact the nearest Emerson local sales office or service center.
2
Emerson Network Power CO., Ltd
Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057,
Shen zhen China
Web site: www.emersonnetworkpower.com.cn
E-mail: overseas.support@emerson.com
Download