LIEBERT® HIPULSE U™ 3-PHASE UPS: 80-500KVA, 50HZ, 380VAC - SITE PLANNING DATA General Specifications INPUT The Liebert® Hipulse-U offers a reliable, scalable and userfriendly solution to ensure availability of various types of networks. Hipulse-U offers protection to your investment and lower cost of ownership through its digital architecture and range of options which you can customize specifically for your needs. Voltage Voltage Range w/o derating 380VAC, 50Hz, 3-phase 3-wire plus ground +15%, -15% Frequency Range 45-65Hz Current Distortion with filter 10% maximum reflected THD for 6 pulse & 5% for 12 pulse at full load Current Limit 115% of full load input current Power Factor >0.9 lagging at full load; >0.9 lagging at half load Surge Protection Sustains input surges without damage, per criteria listed in IEC 60664-1 OUTPUT Voltage Voltage Adjustment Range 380VAC, 50Hz, 3-phase 3-wire plus neutral and ground ±5% Voltage Regulation 1% for balanced load, 1% for 100% unbalanced load Dynamic Regulation ±5% deviation for 100% load step; Transient Response Time Recover to ±5% of output voltage within 1 cycle Voltage Distortion For linear loads, 1% THD; Less than 3.5% THD for 100% nonlinear loads without kVA/kW derating Phasing Balance 120° ±1° for balanced load; 120° ±2° for 100% unbalanced load Frequency Regulation ±0.05Hz for free running frequency Load Power Factor Range 0.5 lagging to 1.0 without derating Overload 125% of full load for 10 minutes; 150% for 1 minute, with true sinusoidal waveform ENVIRONMENTAL Operating Temperature Non-Operating Temperature UPS: 32° to 104°F (0-40°C); Battery: 68° to 86°F (20-30°C) -13° to 158°F (-25° to 70°C) Relative H idit Altitude Operating 0-95% non-condensing Up to 1,000m without derating Acoustical Noise (full load) 80kVA/100kVA/120kVA <67dB at 80-104°F (27-40°C) ambient 160kVA <69dB at 80-104°F (27-40°C) ambient 200kVA <70dB at 80-104°F (27-40°C) ambient 300kVA <72dB at 80-104°F (27-40°C) ambient 400kVA <72dB at 80-104°F (27-40°C) ambient 500kVA <74dB at 80-104°F (27-40°C) ambient STANDARDS: EMI requirement: IEC/EN 62040-2 C2 or C3 level. (Consult to product manager for detail. ) Electric Specification: IEC 62040-3(Uninterruptible power systems (UPS) -Part 3); IEC62310-3(Static Transfer Systems- Part 3) Site Planning Data - Single Input, 80-500kVA, 50Hz, 380VAC Site Planning Data - Single Input, 80-500kVA, 50Hz, 380VAC UPS Rating Voltage AC Input Battery Current (A) kVA Input kW Nom. Output Nom. Nom. Max. Rec. OCPD Nom. VDC AC Output Battery Max. Disconnect Discharge Rating Mechanical Data Current (A) Nom. Dimensions W x D x H (mm) OCPD Weight lb. (kg) Heat Dissipation BTU/hr (kWH) Cooling Airflow CFM (m3/hr) 72 90 108 380 380 380 380 380 380 145 181 217 159 199 238 250 250 250 384 384 384 237 296 355 NA NA NA 121 151 181 250 250 250 900x855x1900 900x855x1900 900x855x1900 900 900 900 5.04 6.3 8.24 1890 1890 1890 120(12P) 108 380 380 212 236 250 384 355 NA 181 250 1540x855x1900 1400 8.92 2250 384 80(6P) 100(6P) 120(6P) 160(6P) 160(12P) 200(6P) 200(12P) 300(6P) 300(12P) 400(6P) 400(12P) 144 144 180 180 270 270 360 360 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 500(12P) 450 380 See Notes for Table (below): 289 282 362 353 542 529 723 706 318 315 397 394 596 591 795 788 400 400 400 400 630 630 800 800 474 474 592 592 888 888 1184 1184 NA NA NA NA NA NA NA NA 243 243 304 304 456 456 607 607 400 400 400 400 630 630 630 630 1250x855x1900 384 384 384 384 384 384 384 1640x855x1900 1240x855x1900 1740x855x1900 1640x855x1900 2280x855x1900 2280x855x1900 2280x855x1900 1200 1750 1200 1850 1600 2550 2200 2400 9.63 11.89 11.12 13.91 19.33 21.8 28.2 31.6 2590 2750 3180 2910 5250 5350 6150 6150 882 985 1000 480 1182 759 800 2640x855x1900 2900 36.2 8205 1 2,3,7 5 4 625 — — — 1,3,7 Notes for Table 1. 2. 3. 4. 5. 6. 7. 8. 1,3,7 5 Additional Notes • If site configuration includes a backup emergency generator, it is recom- mended that the Nominal (Nom) current is based on full rated output load at nominal input voltage. Maximum (Max) current is short duration for battery recharge conditions. UPS input cables must be run in separate conduit from output cables. Nominal battery voltage is shown at 2.0 volts/cell per OCPD = Overcurrent Protection Device. Recommended AC input and AC output overcurrent protection represents 115% of nominal full load current (continuous) plus 100% of recharge current (non-continuous) per NEC 215. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground conductors are recommended. Wiring requirements: AC Input: 3-phase, 4-wire, plus ground AC Output: 3-phase, 4-wire, plus ground All wiring is to be in accordance with national and local electric codes. Control wiring and power wiring must be run in separate conduit. engine generator set be properly sized and equipped for a UPS application • If site configuration requires an external isolated maintenance bypass circuit, it should be noted that utility AC input might not be in phase with the UPS AC output. Consult an Emerson Network Power sales representative or applica-tions engineer. • Input and output 4 poles external breaker will be used for the UPS use with impedancegrounded systems, corner-grounded or high leg delta systems. © 2013 by Emerson Network Power CO., Ltd All rights reserved. The contents in this document are subject to change without notice. Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center. 2 Emerson Network Power CO., Ltd Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shen zhen China Web site: www.emersonnetworkpower.com.cn E-mail: overseas.support@emerson.com