LIEBERT® NX™ 3-PHASE UPS: 250-800KVA, 50/60HZ, 380/400/415VAC - SITE PLANNING DATA General Specifications The Liebert NX is a true on-line, double conversion, three-phase UPS system .It delivers the best combination of availability, reliability and energy-efficiency. INPUT Voltage 380/400/415VAC, 50/60Hz, 3-phase 3-wire+N+ ground Voltage Range w/o derating +25%, -15% Frequency Range 40-70Hz Current Distortion 3% maximum reflected THD at full load Current Limit 125% of full load input current Power Factor >0.99 lagging at full load; >0.98 lagging at half load Surge Protection Sustains input surges without damage, per criteria listed in IEC 61000-4-5 OUTPUT Voltage 380/400/415VAC, 50/60Hz, 3-phase 3-wire+N+ ground Voltage Adjustment Range ±5% Voltage Regulation 1% for balanced load 5% for 100% unbalanced load Dynamic Regulation ±5% deviation for 100% load step; Transient Response Time Recover to ±5% of output voltage within 1/2 cycle Voltage Distortion For linear loads, 2% THD; Less than 5% THD for 100% nonlinear loads without kVA/kW derating Phasing Balance 120° ±1° for balanced load; 120° ±1.5° for 100% unbalanced load Frequency Regulation ±0.05% single module; ±0.25% paralleled modules Load Power Factor Range 0.7 lagging to 0.8 leading Overload 125% of full load for 10 minutes; 150% for 30 seconds, with true sinusoidal waveform ENVIRONMENTAL Operating Temperature UPS: 32° to 104°F (0-40°C); Battery: 68° to 86°F (20-30°C) Non-Operating Temperature -4° to 158°F (-20° to 70°C) Relative Humidity 0-95% non-condensing Operating Altitude Up to 3,250 ft. (1,000m) without derating Acoustical Noise (full load) 250kVA/300KVA/400KVA <74dB at 80-104°F (27-40°C) ambient; 600KVA/800KVA <76dB at 80-104°F (27-40°C) ambient; STANDARDS General and safety requirements for UPS used in operator access areas EN62040-1/IEC62040-1 EMC requirements for UPS EN62040-2/IEC62040-2/AS62040-2 (Category C3) Method of specifying the performance and test requirements of UPS EN62040-3/IEC62040-3/AS62040-3 (VFI SS 111) 1 Site Planning Data - 250-800kVA, 50/60Hz, 400VAC Site Planning Data - 250-800kVA, 50/60Hz, 400VAC UPS Rating AC Input Voltage kVA kW Input Nom. 250 225 400 Current (A) Output Nom. Nom. Max. 400 343 381 Battery Rec. OCPD 630 AC Output Battery Current (A) Max. Disconnect Nom. Rating VDC Discharge Nom. OCPD 480 628 630*2 379 300 400 400 458 503 630 480 829 630*2 455 630 400 360 400 400 549 610 630 480 995 630*2 606 630 600 600 400 400 916 1006 1250 480 1658 1250 910 1250 480 1990 1250 1212 1250 720 400 400 1098 1220 1250 Dimensions WxDxH in. (mm) 630 300 800 Mechanical Data 900 x 1200 x 1900 900 x 2400 x 1900 Heat Dissipation Cooling Airflow Weight lb. (kg) BTU/hr (kWH) CFM (m3/hr) 800 11.3 6609 850 13.5 6609 900 18 6609 1850 27 13218 1950 36 13218 See Notes for Table (below): — Notes for Table Additional Notes 1. • If site configuration includes a backup emergency generator, it is recommended that the engine generator set be properly sized and equipped for a UPS application Nominal (Nom) current is based on full rated output load at nominal input voltage. 2. Maximum (Max) current is short duration for battery recharge conditions. 3. UPS input cables must be run in separate conduit from output cables. 4. Nominal battery voltage is shown at 2.0 volts/cell 5. OCPD = Over current Protection Device. Recommended AC input and AC output over current protection represents 125% of nominal full load current (continuous) plus 100% of recharge current (non-continuous) per NEC 215. 6. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground conductors are recommended. 7. Wiring requirements: AC Input: 3-phase, 4-wire, plus ground AC Output: 3-phase, 4-wire, plus ground 8. All wiring is to be in accordance with national and local electric codes. 9. Top or bottom cable entry through removable access plates. Punch plate to suit conduit size, then replace. 10. Control wiring and power wiring must be run in separate conduit. 11. Dimensions and weights in table do not include external battery cabinet. • If site configuration requires an external isolated maintenance bypass circuit, it should be noted that utility AC input might not be in phase with the UPS AC output. Consult an Emerson Network Power sales representative or applications engineer. © 2013 by Emerson Network Power CO., Ltd All rights reserved throughout the world. Specifications subject to change without notice. Emerson Network Power CO., Ltd Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen China Please contact to local Emerson network power representative for any further details . Web site: www.emersonnetworkpower.com.cn E-mail: overseas.support@emerson.com 2