Liebert HPC-S™ Freecooling Chiller ®

advertisement
Liebert ® HPC-S™ Freecooling Chiller
Designed for the Efficient Cooling of Small Data Centers
Getting To A PUE Of 1.2
Freecooling data center chillers are designed to efficiently
supply chilled water to indoor data center thermal
management equipment.
The Liebert iCOM control system is easily networked to
The integrated freecooling technology used by the Liebert®
HPC-S™ Freecooling Chiller allows it to cool water when the
external ambient temperatures are below the chilled water
return temperature.This reduces annual energy consumption
of the entire chilled water system by over 30% in most
applications, while improving system availability at the
same time.
Additionally, coupling the Liebert CRV™ Optimized Aisle
The Liebert® HPC-S Freecooling Chiller provides reliable
year-round capacity, regardless of the environmental
working conditions, with extended high ambient
capability and freecooling functionality that eliminates
the need for low ambient compressor starting. The
unit is equipped with the latest technology by using EC
condenser fans, Copeland® scroll compressors and Liebert
iCOM™ control system.
provide efficient control of the chiller plant without the
need for a separate building automation system.
Control™ with cold aisle containment and the Liebert
HPC-S Chiller creates a system capable of achieving a
mechanical PUE of 1.20. This configuration thus ensures
that each watt of power is used to cool the servers,
hence delivering maximum availability.
The chiller operates with R410A refrigerant to meet
today’s data center demands by enabling businesses to
operate with maximized availability and efficiency.
Liebert HPC-S Chiller features:
EC Fans
High efficiency EC motors
deliver a 25% reduction
in energy consumption
compared to traditional
AC motors.
Scroll Compressor
Liebert HPC-S Chiller is
equipped with Copeland
digital scroll compressors
to improve efficiency and
reliability of performance.
Liebert iCOM control
Advanced unit and teamwork
control to maximize energy
efficiency.
Fast Start Ramp
Liebert HPC-S Fast Start Ramp
ensures full restoration of
chiller capacity after 100
seconds from power re-start.
Operation
It operates at extreme
ambient and water
temperature conditions.
Freecooling
Integrated freecooling
functionality delivers
additional energy savings
and greater reliability.
Refrigerant
Optimized for
R410A refrigerant.
2
High Efficiency
High efficiency design
resulting from the use of
a combination of the best
technologies on the marketintegrated economizer, wide
operating range, and EC
condenser fans.
Extremely Low Noise
Audible noise is minimized as
a result of low-noise, HyBlade
EC Fans.
Achieving Efficiency And Environmental Responsibility
Today, environmental responsibility is becoming increasingly fundamental for many organizations.
Liebert® HPC-S™ Freecooling Chiller enables data centers to achieve increased efficiency while reducing environmental impact,
through its ability to work in freecooling mode. This operation leverages the external environmental conditions to cool
the water, thus requiring compressor operation only when the outside temperature exceeds the temperature of the water
returning to the chiller. This occurs during more than 50% of the annual operating hours for most of the US.
18,000
16,000
14,000
12,000
10,000
8,000
6,000
4,000
2,000
0
-10
$50,000
Std Chiller 45˚F-55˚F
Annual Operations Cost ($)
Annual Power Consumption (kW-hr)
Compressor operation is also used as partial back up during the partial freecooling mode. The total combined effect of the
Liebert HPC-S unit’s leading technologies delivers up to 40% annual energy savings over standard industry cooling chillers.
HPC-S Chiller 45˚F-55˚F
HPC-S Chiller 54˚F-66˚F
HPC-S Chiller 66˚F-78˚F
$40,000
$30,000
$20,000
$10,000
$0
0
10
20 30
40 50
60
70 80
90 100
Ambient Temperature (˚F)
Std Chiller
45˚F-55˚F
HPC-S Chiller
45˚F-55˚F
HPC-S Chiller
54˚F-66˚F
HPC-S Chiller
66˚F-78˚F
Ambient Temperature (˚F)
Depending on local ambient temperatures and operating temperature, Liebert HPC-S Chiller could consume thousands of kilowatts
less energy than a standard chiller. This higher efficiency operation could result in thousands of dollars of energy savings every year.
FG0052
FG0080
FB0110
192 kW (55) tons
285 kW (81) tons
362 kW (103) tons
61 kW
99 kW
150 kW
Ambient Temperature for 50% freecooling
54°F (12°C)
51°F (10.7°C)
48°F (9°C)
Ambient Temperature for 100% freecooling
39°F (4.2°C)
35°F (1.9°C)
30°F (-1°C)
Chicago
$12,000
$16,300
$22,600
Minneapolis
$11,100
$15,100
$20,900
Denver
$12,700
$17,300
$24,100
St.Louis
$8,700
$11,700
$16,200
Capacity1
Power Consumption, kW
Annual savings with
freecooling2
1
2
Capacity at 95°F ambient air, 56°F (13.3°C) leaving fluid temperature, 12°F (6.7°C) fluid temperature rise, and 20% ethylene glycol
Assumes electrical power cost of $0.10 / kWh blended rate
3
Emerson Network Power
Global Headquarters
Liebert® HPC-S™ Freecooling Chiller
FG0 080 & FB0 110 with Integral Freecooling and Without Buffer Tank
51.2in
1300mm
Right Side
Left Side
Electrical Panel and
Control Unit Panel
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43229
800 877 9222 Phone (U.S. & Canada Only)
614 888 0246 Phone (Outside U.S.)
Contact@EmersonNetworkPower.com
Emerson Network Power
Caribbean and Latin America
Office – United States of America
+1-954-984-3452 Phone
Ask.Cala@Emerson.com
Emerson Network Power Canada
88.2in
2240mm
226.4in
5750mm
Front View
Refrigerant Circuit
Rear View
Condenser Coil
Air Inlet
3580 Laird Rd Unit 1
Mississauga
Ontario L5L 5Z7
+1 905 569 8282
Ask@EmersonNetworkPower.com
liebert.com
24 x 7 Tech Support
Piping
Connection
800 222 5877 Phone
614 841 6755 (outside U.S.)
EmersonNetworkPower.com
FG0 052 with Integral Freecooling and Without Buffer Tank
51.2in
1300mm
Left Side
Right Side
Electrical Panel and
Control Unit Panel
While every precaution has been taken to ensure
accuracy and completeness in this literature,
Liebert Corporation assumes no responsibility, and
disclaims all liability for damages resulting from use
of this information or for any errors or omissions. All
names and logos referred to herein are trade names,
trademarks or registered trademarks of their respective
owners. ® Liebert is a registered trademark of the
Liebert Corporation.
© 2014 Liebert Corporation. All rights reserved
throughout the world. Specifications subject to change
without notice.
Emerson Network Power and the Emerson Network
Power logo are trademarks and service marks of
Emerson Electric Co.
©2014 Emerson Electric Co.
SL- 17600 (R01/14)
88.2in
2240mm
Front View
Refrigerant Circuit
187in
4750mm
Rear View
Condenser Coil
Air Inlet
Piping
Connection