NetSure 4000 Series 400V DC Battery Tray Add backup power to a NetSure

advertisement
NetSure™ 4000 Series
400V DC Battery Tray
Key Features
n9 minutes backup at 10 kW,
per tray
nOne string in each tray; 336 VDC
nominal, 378 VDC float charge
nDesigned for easy and safe
installation with (6) battery
sub-trays in parallel and
connectorized cable assembly
nRemote trip breaker for low
voltage protection
n4U high, 19" mounting
Add backup power to a NetSure™ 4000 Series
power system with 400V DC Battery Trays.
Description
The 400V DC Battery Tray is specifically designed for use with NetSure™ 4000
Series DC power systems. Simple assembly on site can be accomplished by
a single person; (6) battery sub-trays reduce the initial installation weight of
the tray.
Using standard 35 watt/cell 12 V VRLA batteries, each battery tray holds
28 blocks configured in (1) 336 V nominal string. A single string can supply
approximately 9 minutes of backup time at 10 kW load. Refer to the battery
backup table on the following page for available backup times.
All battery trays take up only 4U of rack space and fit into a standard
19" IT rack.
nUL Recognized (US & Canada),
CE Marked
Additional Information
n EmersonNetworkPower.com/400VDC
n NetSure™ 4015 System Data Sheet
n Power & Control Sub-Rack Data Sheet
n Load Distribution Sub-Rack Data Sheet
n System Application Guide
n NetSure™ 4015 Pre-Quote Form
EN612DRA-BatryTray / 0913
1
400V DC Battery Tray
Battery Backup Time (minutes)
Load
5 kW
10 kW
15 kW
20 kW
25 kW
30 kW
1
15
9
2
50
18
10
7
5
Number of Strings/Trays
3
>60
31
18
12
8
6
Overview
4
>60
44
27
18
13
10
5
>60
50
32
24
18
13
NOTE: Backup times based on 25 ˚C ambient with fully charged batteries.
1
2
Technical Specifications
Rating
Nominal Voltage
Float Voltage, Recommended
Capacity
Cells
Protection
Type
Design Life
Battery Tray – Front View
336 VDC
378 VDC
35 Watt/cell (15 min. rate), see battery backup table above
28 x 12 V blocks; Enersys DataSafe® NPX-35TFR or equivalent
40 A shunt trip circuit breaker
High rate discharge lead acid (VRLA), flame retardant (V0) case
3-5 years @ 25 °C (77 °F)
3
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
Elevation
Cooling
RoHS
Range: -5 °C to +35 °C; Recommend 20 °C to 25 °C
-20 °C to +50 °C
0% to 95% non condensing
Up to 3000 m (10,000') at full power
Convection
RoHS compliant (pending)
Mechanical
Hardware Interface
Tray Dimensions (H x W x D)
Battery Dimensions (H x W x D)
Tray Weight (installed)
Sub-Tray Weight (ea)
Power and control cables to Power and Control Sub-Rack included
4 RU x 483 mm x 838 mm (4 RU x 19" x 33")
98 mm x 65 mm x 151 mm (3.8" x 2.6" x 5.9")
118 kg (260 lbs) with batteries
18 kg (40 lbs) with 6 batteries
1
Battery Tray – Rear View
(6) sub-trays in parallel for safe
1
isolation and ease of assembly
Breaker with remote trip for LVD
2
(low voltage disconnect) and
system shutdown
Quick connects on each sub-tray
3
Safety
Safety Agencies
UL Recognized per UL 60950 (cUR for Canada)
CE Marking per low voltage directive (EN 60950) and the EMC directive
for easy assembly
Ordering Information
List Number
91
92
Part Number
584000300
58400030091
58400030092
Description
NetSure™ 4015, 30kW 400V DC Power System
Battery Tray - HRMG
Battery Tray - NPG
Email NetSure4000Series@Emerson.com
for more information.
Note: HRMG = High Resistance Mid-point Ground and NPG = Negative Pole Ground.
EmersonNetworkPower.com/EnergySystems (North America)
EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power, Energy Systems, North America, Inc. 2013.
Business-Critical Continuity™, Emerson Network Power™, the Emerson Network Power logo, Emerson™ and Consider it Solved are service marks and
trademarks of Emerson Electric Co. EnergyMaster ™, eSure™, NetPerform™, NetReach™, NetSpan™, NetSure™ and NetXtend™ are trademarks of Emerson
Network Power, Energy Systems, North America, Inc. Any other product, brand, or company names or logos are the property of the respective owner.
2
While every precaution has been taken to ensure accuracy and
completeness herein, Emerson Electric Co. assumes no responsibility,
and disclaims all liability, for damages resulting from use of this
information or for any errors or omissions. Specifications subject to
change without notice.
EN612DRA-BatryTray / 0913