NetSure™ 4000 Series 400V DC Battery Tray Key Features n9 minutes backup at 10 kW, per tray nOne string in each tray; 336 VDC nominal, 378 VDC float charge nDesigned for easy and safe installation with (6) battery sub-trays in parallel and connectorized cable assembly nRemote trip breaker for low voltage protection n4U high, 19" mounting Add backup power to a NetSure™ 4000 Series power system with 400V DC Battery Trays. Description The 400V DC Battery Tray is specifically designed for use with NetSure™ 4000 Series DC power systems. Simple assembly on site can be accomplished by a single person; (6) battery sub-trays reduce the initial installation weight of the tray. Using standard 35 watt/cell 12 V VRLA batteries, each battery tray holds 28 blocks configured in (1) 336 V nominal string. A single string can supply approximately 9 minutes of backup time at 10 kW load. Refer to the battery backup table on the following page for available backup times. All battery trays take up only 4U of rack space and fit into a standard 19" IT rack. nUL Recognized (US & Canada), CE Marked Additional Information n EmersonNetworkPower.com/400VDC n NetSure™ 4015 System Data Sheet n Power & Control Sub-Rack Data Sheet n Load Distribution Sub-Rack Data Sheet n System Application Guide n NetSure™ 4015 Pre-Quote Form EN612DRA-BatryTray / 0913 1 400V DC Battery Tray Battery Backup Time (minutes) Load 5 kW 10 kW 15 kW 20 kW 25 kW 30 kW 1 15 9 2 50 18 10 7 5 Number of Strings/Trays 3 >60 31 18 12 8 6 Overview 4 >60 44 27 18 13 10 5 >60 50 32 24 18 13 NOTE: Backup times based on 25 ˚C ambient with fully charged batteries. 1 2 Technical Specifications Rating Nominal Voltage Float Voltage, Recommended Capacity Cells Protection Type Design Life Battery Tray – Front View 336 VDC 378 VDC 35 Watt/cell (15 min. rate), see battery backup table above 28 x 12 V blocks; Enersys DataSafe® NPX-35TFR or equivalent 40 A shunt trip circuit breaker High rate discharge lead acid (VRLA), flame retardant (V0) case 3-5 years @ 25 °C (77 °F) 3 Environmental Operating Temperature Storage Temperature Relative Humidity Elevation Cooling RoHS Range: -5 °C to +35 °C; Recommend 20 °C to 25 °C -20 °C to +50 °C 0% to 95% non condensing Up to 3000 m (10,000') at full power Convection RoHS compliant (pending) Mechanical Hardware Interface Tray Dimensions (H x W x D) Battery Dimensions (H x W x D) Tray Weight (installed) Sub-Tray Weight (ea) Power and control cables to Power and Control Sub-Rack included 4 RU x 483 mm x 838 mm (4 RU x 19" x 33") 98 mm x 65 mm x 151 mm (3.8" x 2.6" x 5.9") 118 kg (260 lbs) with batteries 18 kg (40 lbs) with 6 batteries 1 Battery Tray – Rear View (6) sub-trays in parallel for safe 1 isolation and ease of assembly Breaker with remote trip for LVD 2 (low voltage disconnect) and system shutdown Quick connects on each sub-tray 3 Safety Safety Agencies UL Recognized per UL 60950 (cUR for Canada) CE Marking per low voltage directive (EN 60950) and the EMC directive for easy assembly Ordering Information List Number 91 92 Part Number 584000300 58400030091 58400030092 Description NetSure™ 4015, 30kW 400V DC Power System Battery Tray - HRMG Battery Tray - NPG Email NetSure4000Series@Emerson.com for more information. Note: HRMG = High Resistance Mid-point Ground and NPG = Negative Pole Ground. EmersonNetworkPower.com/EnergySystems (North America) EmersonNetworkPower.eu/EnergySystems (EMEA) © Emerson Network Power, Energy Systems, North America, Inc. 2013. Business-Critical Continuity™, Emerson Network Power™, the Emerson Network Power logo, Emerson™ and Consider it Solved are service marks and trademarks of Emerson Electric Co. EnergyMaster ™, eSure™, NetPerform™, NetReach™, NetSpan™, NetSure™ and NetXtend™ are trademarks of Emerson Network Power, Energy Systems, North America, Inc. Any other product, brand, or company names or logos are the property of the respective owner. 2 While every precaution has been taken to ensure accuracy and completeness herein, Emerson Electric Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications subject to change without notice. EN612DRA-BatryTray / 0913