KEY NOTES: 1 . PANELBOARDS INDICATED ON ONE LINE DIAGRAMS DO NOT SHOW ALL BRANCH CIRCUITS. REFER TO PANELBOARD SCHEDULE(S) 2 . CIRCUIT BREAKER TRIP FUNCTION: L=LONG TIME S=SHORT TIME I=INSTANTANEOUS G=GROUND FAULT CONDUCTORS [ 4 4# 350 AL A1000.4 A100.4 G PROVIDE (3) 4" SLEEVES THROUGH FLOOR FOR FUTURE PHOTOVOLTAIC SYSTEM FEEDER. REFER TO FLOOR PLAN FOR PROPOSED SLEEVE LOCATION. COORDINATE PENETRATION WITH THE STRUCTURAL CONTRACTOR PRIOR TO ROUGH-IN. 2 4 . PROVIDE SEPARATE INSULATED GROUNDING CONDUCTOR IN ALL FEEDER, HOMERUN AND BRANCH CIRCUITS. 5 . INSTALL CONDUIT CONCEALED IN FINISHED AREAS UNLESS OTHERWISE NOTED. PAINT EXPOSED CONDUIT TO MATCH EXISTING FINISHES WITHIN THE SURROUNDING AREA. 6 . DO NOT ROUTE CONDUIT WITHIN STRUCTURAL OR TOPPING SLABS OF FLOORS UNLESS SPECIFICALLY NOTED OTHERWISE AND WRITTEN APPROVAL IS OBTAINED FROM THE STRUCTURAL ENGINEER. 3 AT THE CONTRACTOR'S OPTION, THIS PANELBOARD MAY BE PROVIDED AS A SINGLE SECTION UNIT. 4 SINGLE POINT CONNECTION. COORDINATE WITH THE MECHANICAL CONTRACTOR AND EQUIPMENT SUPPLIER FOR CONNECTION TO MULTIPLE VFD'S. VFD'S FURNISHED WITH THE EQUIPMENT. 5 COORDINATE METER REQUIREMENTS WITH COLORADO SPRINGS UTILITIES PRIOR TO ROUGH-IN. 6 6 PROVIDE (1)1"C. WITH PULL STRINGS. 7 7 EXTERIOR PHOTOCELL ON ROOF. PROVIDE LOW VOLTAGE CONNECTION TO THE LIGHTING CONTROL SYSTEM AS INDICATED. REFER TO ROOF POWER PLAN, LIGHTING CONTROL SCHEDULES AND SPECIFICATIONS FOR ADDITIONAL INFORMATION. 7 . FIRE SEAL ALL FIRE RATED WALL AND FLOOR PENETRATIONS. REFER TO ARCHITECTURAL DRAWINGS FOR FIRE RATED WALLS. 8 8 8 . COORDINATE EXACT REQUIREMENTS AND LOCATIONS OF MECHANICAL EQUIPMENT WITH MECHANICAL DRAWINGS AND MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN AND ORDERING MATERIALS OR EQUIP 9 9 4# KEY (6) "C , 1/0 AL 1# 6 AL G 1# 250 AL G 2 1 REFER TO MECHANICAL EQUIPMENT SCHEDULE. REFER TO TRANSFORMER SCHEDULE. XFMR NOTE: HV PROT (1) CCT BRKR SWITCH HIGH VOLTAGE FEEDER (3) 480 V 208 V T15 18.0 41.6 25 A 3 P 3# 10 ,1# 10 G 3/4 50 A 3 P 4# 6 ,1# 10 T30 36.1 83.3 45 A 3 P 3# 6 ,1# 10 G 1 100 A 3 P 4# 1 ,1# 8 T45 54.1 1.) 124.9 70 A 3 P 3# 4 ,1# 8 G 1-1/4 150 A 3 P 4# 1/0 ,1# 6 FUSE CONDUCTORS "C CONDUCTORS SECONDARY O.C. PROTECTION PER NEC 450. ALL CONDUCTORS ARE COPPER. SEE PLANS FOR INCREASED CONDUCTOR SIZES DUE TO VOLTAGE DROP ETC. ENGINEER APPROVED EQUIVALENT). 4.) 5.) BONDING AND GROUNDING CONDUCTOR PER NEC 250. DIMENSIONS, WEIGHTS & BTUH OUTPUT SHOWN ARE FOR REFERENCE ONLY. ACTUAL DIMENSIONS MAY VARY FROM MANUFACTURER TO MANUFACTURER. 6.) CONDUIT 40% FILL RATIO BASED ON EMT. PC PC "C CNDTRS "C HIGH WIDE DEEP (5) OTPT (5) G 1 1# 8 3/4 27.00 20.13 16.00 310 2806 G 1-1/2 1# 6 3/4 30.00 20.13 16.00 370 5753 G 1-1/2 1# 6 3/4 39.25 26.13 20.00 480 7425 T 45 7 Volts: 480/277 Wye Phases: 3 Mounting: XFMR XFMR 2 FUTURE LTG CONTROL "LCP5A" TO PV ARRAY 7 PV INVERTER ISCA=7,979 5TH FLOOR ROOF Wires: 4 PANEL "L4A" 3 PANEL "L5A" XFMR XFMR ISCA=3,028 T XFMR T 45 XFMR 45 D 8 10 PC A100.4G PANEL "H4A" XFMR ISCA= 8,781 XFMR 277V 4#4, 1#10G 1"C. PANEL "H5A" 6 Load PANEL "HM1" PANEL "H1A" PANEL "H2A" PANEL "H3A" PANEL "H4A" ELEVATOR AIR HANDLING UNIT (AHU-1) AIR HANDLING UNIT (AHU-2) PANELBOARD PANEL "H5A" "H5A" (FUTURE LOAD) Type L; R; G; M; O L; R; G; O L; R; G; M L; R; G L;L;R;R;G;GM M M M L; R;GG; M LTG LTG CONTROL CONTROL "LCP4A" "LCP5A" TO LIGHTING17 ASI #15 LOADS (TYP.) TO LOW VOLTAGE SWITCH(ES) AS SHOWN ON PLANS ISCA=7,979 XFMR ISCA=3,071 T XFMR T 45 XFMR 45 SLAVE SLAVE PANEL PANEL PANEL "H3A" PANEL "H4A" XFMR TO LIGHTING LIGHTING TO LOADS LOADS (TYP.) (TYP.) ISCA= 9,759 XFMR 277V 277V 4#4, 1#10G 1"C. LTG LTG CONTROL CONTROL "LCP3A" "LCP4A" TO LOW VOLTAGE SWITCH(ES) AS SHOWN ON PLANS TO LOW VOLTAGE SWITCH(ES) AS SHOWN ON PLANS ~ PANEL "L4A" XFMR PC PC ~~ ~~ ~~ PANEL "L3A" 3 SPD ASI #15 Load Type L Lighting R Receptacle M Motor C Continuous G General K Kitchen E Existing O Other General Notes: 2 ~ 10 17 ISCA=3,116 8 8 1 NETWORK COMMUNICATION PER MANUFACTURER RECOMMENDATIONS (TYP.) ISCA= 8,781 3RD FLOOR 4TH FLOOR 3RD 4TH FLOOR PANEL "H3A" XFMR TO LIGHTING LIGHTING TO LOADS LOADS (TYP.) (TYP.) ISCA= 10,978 XFMR SLAVE SLAVE PANEL PANEL 277V 277V 4#4, 1#10G 1"C. LTG LTG CONTROL CONTROL "LCP2A" "LCP3A" ISCA= 9,759 TO LIGHTING LIGHTING TO LOADS LOADS (TYP.) (TYP.) ISCA= 13,151 MASTER PANEL ISCA= 10,978 ELEVATOR #1 ELEVATOR #1 AHU M XFMR 5 TVSS A100.4G 9 SPD 4 4#4, 1#10G 1"C. PANEL "HM1" ISCA= 1,891 XFMR 15 DM 10 ASI #15 ~ 17 AHU 2 1 M M M A100.4G XFMR A100.4G ISCA= 13,151 4 A100.4G MEC A100.4G VFD MASTER PANEL 2ND 3RD FLOOR MECHANICAL 2 TO LOW VOLTAGE PANELAS SWITCH(ES) SHOWN"H1A" ON PLANS XFMR AHU ELEVATOR #1 REFER TO MECHANICAL EQUIPMENT SCHEDULE ST FOR INFORMATION. CT COMP. 4 ISCA= 1,891 UTILITY METER M 5 SPD GFI 100A3P A100.4G LSIG 1000AF 6 AHU 2 M M VFD T 30 XFMR 17 10 2ND FLOOR 2 T 30 4. INTEGRAL DISCONNECTING MEANS FURNISHED WITH EQUIPMENT. 5. PROVIDE CONNECTION TO DUPLEX SUMP PUMP CONTROLLER. MAKE FINAL CONNECTIONS TO EQUIPMENT. COORDINATE EXACT REQUIREMENTS WITH THE MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN. 3 PANEL "L1A" XFMR A100.4G XFMR ISCA=1,845 Key LSI 100A3P A100.4G MEC MEC LSI 100A3P A100.4G LSI 100A3P A100.4G LSI 100A3P A100.4G LSI 100A3P LSI MEC MEC LSI MEC MEC LSI 100A3P A100.4G SPARE SPARE SPARE LSI 400A3P LSI 225A3P LSI 225A3P MAIN DISTRIBUTION CENTER "MDC" 1000 AMP BUS, 480/277V, 3∅, 4W 35,000 AIC MINIMUM ~ A7G CT COMP. MAIN ELECT. RM. GROUND BAR RM. GROUND BAR A7G A7G A7G GFI A7G LSIG 1000AF 100A3P A7G LSI LSI 100A3P MECA7G A7G SPARE (FUTURE PV) LSI 100A3P LSI 100A3P LSI 100A3P LSI 100A3P LSI MEC LSI MEC LSI 100A3P SPARE SPARE SPARE LSI 400A3P LSI 225A3P LSI 225A3P LSI 50A3P (3) SPACES N 1000AT UFER LIGHTNING BLDG. PROT. STEEL ~ 50A3P G ISCA=27,402ISCA=27,402 B SPARE (FUTURE PV) PV) (3) SPACES LSI N 1000AT ISCA=27,402 IT ROOM ELEC RM GROUND GROUND BARS BARS GROUND G COLD WATER RODS PIPE 1ST FLOOR # Item HP FLA AC AHU 1 1 AIR CONDITIONING UNIT AIR HANDLING UNIT 0 0 1A 88AA 0 AHU 2 AIR HANDLING UNIT 0 88AA 0 B B CP CU 1 2 1 1 0 0 0.5 0 CUH DWH 1 1 DWH 2 EF EF ELEV FCU FCU HWP HWP SP SP 1 2 1 1 2 1 2 1 2 BOILER BOILER CIRCULATION PUMP AIR COOLED CONDENSING UNIT CABINET UNIT HEATER DOMESTIC HOT WATER HEATER DOMESTIC HOT WATER HEATER EXHAUST FAN EXHAUST FAN ELEVATOR FAN COIL UNIT FAN COIL UNIT HOT WATER PUMP HOT WATER PUMP ELEVATOR SUMP PUMP SUMP PUMP Load 0A 0A 0A 15 A 0 VA 181000 VA 181000 VA 500 VA 500 VA 0 VA 0 VA 0 0 0A 0A 200 VA 500 VA 0 0A 3 0.25 0 0 0 5 5 5 0 0A 0A 0A 0A 0A 0A 0A 0A 0A 4 ISCA= 14,555 Eq Load (VA) Voltage Phases Feeders Wire Protec Feeder Feeder Protecti s s on Protection tion Ground Conduit Breaker Disconnect Fuse A7G 208 V 480 V 1 3 2#12 3#2/0 1#12G 3/4" 1#6G 1-1/2" FED 225 A FROM VFD CU-1 - 2 1, 3 253746 VA 181000 480 V 3 3#2/0 1#6G 1-1/2" 225 A VFD - 1, 3 500 VA 500 VA 1127 VA 3120 VA 120 V 120 V 120 V 208 V 1 1 1 1 2#12 2#12 2#12 2#12 #12G #12G #12G 1#12G 3/4” 3/4” 3/4” 3/4" 20 A 20 A 20 A 20 A S 30 A 20 A 200 VA 500 VA 120 V 120 V 1 1 2#12 2#12 1#12G 3/4" 1#12G 3/4" 20 A 20 A 4100 VA 4100 VA 277 V 1 2#10 1#10G 3/4" 30 A 0 VA 0 VA 20000 VA 18000 250 VA 200 VA 0 VA 0 VA 0 VA 12200 VA 480 V 120 V 480 V 120 V 120 V 480 V 480 V 480 V 480 V 3 1 3 1 1 3 3 3 3 3#12 2#12 3#4 2#12 2#12 3#12 3#12 3#12 3#12 #12G #12G 1#10G #12G #12G 1#12G 1#12G #12G #12G 15 A 20 A 60 A 20 A 20 A 20 A 20 A 15 A 20 A 3824 VA 667 VA 20000 VA 18000 250 VA 200 VA 6055 VA 6055 VA 6055 VA 12200 VA 3/4” 3/4” 1" 3/4” 3/4” 3/4" 3/4" 3/4” 3/4” A7G UFER LIGHTNING BLDG. PROT. STEEL A7G A7G A7G ELECTRICAL ONE-LINE DIAGRAM SCALE: 1/8" =RM 1'-0" IT ROOM ELEC COLD GROUND WATER RODS PIPE GROUND GROUND BARS BARS 1ST FLOOR A 6/13/2013 3:50:29 7/18/2013 9/20/2013 9/26/2013 10:03:12AM 6:55:24 8:37:44 PM AM D:\Revit Local Files\2013\E-UCCSAOB_Central_JHafer.rvt 1ST FLOOR 1 2 INTEGRAL - 30 A S 60 A S S VFD VFD 30 A 30 A 4 10 A 3 4 5 6 UNIVERSITY OF COLORADO COLORADO SPRINGS ISSUE: 06/17/13 60 A 15 A 20 A OWNER: 1420 AUSTIN BLUFFS PKWY COLORADO SPRINGS, CO 80918 3 3 6 07/19/13 11 09/20/13 17 09/27/13 5 BID PACKAGE 03 A7G Notes 208 VA 253746 VA 181000 MAIN ELECT. RM. GROUND BAR A7G COLORADO SPRINGS, CO 80918 MAIN DISTRIBUTION CENTER "MDC" 1000 AMP BUS, 480/277V, 3∅, 4W 1ST FLOOR 35,000 AIC MINIMUM A1000.4 A7G UCCS - ACADEMIC OFFICE BUILDING 3. VFD (VARIABLE FREQUENCY DRIVE) WITH LOCAL DISCONNECTING MEANS FURNISHED WITH EQUIPMENT. 4#4, 1#10G 1"C. XFMR PROJECT: 2. AIR CONDITIONING UNIT IS FED FROM THE ASSOCIATED CONDENSING UNIT LOCATED ON THE ROOF. ISCA=1,845 SPD PANEL "H1A" ISCA=23,115 1. SINGLE POINT CONNECTION. PROVIDE CONNECTION TO INDIVIDUAL VFDs FURNISHED WITH THE EQUIPMENT. COORDINATE EXACT CONNECTION REQUIREMENTS WITH THE MECHANICAL CONTRACTOR, EQUIPMENT SUPPLIER AND EQUIPMENT SHOP DRAWINGS PRIOR TO ROUGH-IN. VFD ISCA= 13,386 LSI DM 1 EQUIPMENT SCHEDULE NOTES: PANEL "L1A" ISCA=23,115 XFMR TO LOW VOLTAGE SWITCH(ES) AS SHOWN ON PLANS LTG CONTROL ISCA= "LCP1A" 14,555 MEC Connected Load 33832 VA 34155 39237 39301 146468 VA 166268 166628 568845 VA 421353 0 VA 66468 12180 9000 VA VA 0 VA 0 VA 5600 VA 213652 VA 250401 269613 213292 261411 VA 280594 224449 224870 250773 VA 270155 205535 205175 904 A 973 774 776 1013 944 AA 815 817 976 906 A 742 741 4 5 10 4 4 5 0 % A-B % B-C % C-A Demand Factor Demand Load Switchboard Totals Power Factor: 125% 42290 VA 42694 49046 49126 53% 78234 VA 88134 88314 Total Connected Load: 645062 111% 632282 VA 466603 763745 VA 821536 644638 0% 0 VA Total Connected Current: 776 919 A 988 775 100% 66468 12180 9000 VA VA 0% 0 VA Total Demand Load: 621823 767406 VA 825278 621563 Total Demand Current: 748 0% 0 VA 923 A 993 100% 5600 VA Breaker Accessories * = GFI ** = Shunt Trip 6 M 11 3 ASI #15 277V VFD ISCA=ISCA=TO LIGHTING 13,38613,386 LOADS (TYP.) MEC Note TO TO LOW LOW VOLTAGE VOLTAGE SWITCH(ES) AS AS SWITCH(ES) SHOWN SHOWN ON ON PLANS PLANS ~ XFMR LTG LTG CONTROL CONTROL "LCP1A" "LCP2A" ~~ ~~ ~~ XFMR 277V 277V 4#4, 1#10G 1"C. PANEL "H2A" ~~~ T XFMR T 15 XFMR 45 PANEL "HM1" C UTILITY METER SLAVE PANEL ASI #15 ISCA=3,162 REFER TO MECHANICAL ST EQUIPMENT SCHEDULE ISCA=1,379 FOR INFORMATION. PANEL "LM1" T 9 1 SPD ~ 10 C 13342 VA 11665 VA 11541 11721 18251 VA 18241 18180 17641 13707 VA 13881 13878 12799 11968 13046 17978 VA 18040 6667 VA 6000 84582 VA 60333 84582 VA 60333 19156 9960 VA VA 2 NETWORK COMMUNICATION TO LOW VOLTAGE PER MANUFACTURER SWITCH(ES) AS RECOMMENDATIONS (TYP.) SHOWN ON PLANS 2ND 3RD FLOOR 17 B 13049 VA 14448 VA 14419 14778 22568 VA 22627 22621 23161 13756 VA 13724 13698 14299 18460 17381 21760 VA 6667 VA 6000 84582 VA 60333 84582 VA 60333 19156 15535 VA ~~ PANEL "H2A" PC PC A100.4G ~ XFMR ISCA=3,116 T XFMR T 45 XFMR 45 1 SPD ~ PANEL "L3A" XFMR 10 ASI #15 ~~ ~~ ~~ 17 ISCA=3,162 8 8 A 13652 VA 11640 VA 11427 11068 20291 VA 20288 11643 VA 11703 11699 12418 13673 17344 VA 17342 6667 VA 6000 84582 VA 60333 84582 VA 60333 19156 15886 VA COB #09 4TH 5TH FLOOR 2ND FLOOR MCB Rating: 1000 A 2 SLAVE PANEL 4TH 5TH FLOOR XFMR Bus Rating: 1000 A ADD 03 ~~~ ISCA=3,071 XFMR A.I.C. Rating: 35,000 Mains Type: MCB Feed: SLAVE FUTURE PANEL PANEL "H5A" 1 SPD PANEL "L2A" P 303.607.0977 www.slaterpaull.com ~ 5TH FLOOR PANEL "LM1"3 ARCHITECTS NOTE 1331 Nineteenth Street Denver, CO. 80202 Location: ELEC 1S-4 Supply From: PV INVERTER 11 ISCA=1,379 BTUH Switchboard MDC COB #09 3 WEIGHT ROOF XFMR PANEL "L2A" 3 DIMENSIONS (5) Circuit Notes: PC ELECTRIC UTILITY COMPANY U.G. PRIMARY SERVICE. FUSE 3.) TO PV ARRAY PROVIDE SURGE PROTECTIVE DEVICE. INSTALL FUTURE IN THE ELECTRICAL ROOM ADJACENT TO THE PANELBOARD. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. PANEL "L5A" A1000.4 SWITCH GROUNDING (4) CONSULTANT: ISCA=3,028 NEW PAD MOUNTED UTILITY TRANSFORMER (LOCATED AT THE PARKING GARAGE, REFER TO SITE ELECTRICAL PLAN) CCT BRKR LOW VOLTAGE FEEDER (3) 2.) PROVIDE LOW VOLTAGE CONNECTION TO THE BUILDING AUTOMATION SYSTEM HEAD-END EQUIPMENT. VERIFY COMMUNICATION PROTOCOL REQUIREMENTS WITH THE MECHANICAL CONTRACTOR PRIOR TO PURCHASE. 17 ELECTRIC UTILITY COMPANY U.G. PRIMARY SERVICE. LV PROT (2) SCHEDULE IS BASED UPON TYPE XHHW-2 COMPACT ALUMINUM 600V CONDUCTOR (ALCAN STABILOY OR INTERIOR DAYLIGHT HARVESTING PHOTOCELL. REFER TO POWER PLANS, LIGHTING CONTROL SCHEDULES AND SPECIFICATIONS FOR ADDITIONAL INFORMATION. ASI #15 NEW PAD MOUNTED UTILITY NEW PAD MOUNTED TRANSFORMER UTILITY TRANSFORMER (LOCATEDAT ATTHE THEPARKING (LOCATED PARKING GARAGE, GARAGE, REFER TO SITE REFER TO SITE ELECTRICAL PLAN) ELECTRICAL PLAN) LV PROT (2) PRIMARY O.C. PROTECTION PER NEC 450. FUTURE 10 3 SLATERPAULL SCHEDULE LV FLA NOTES: HV PROT (1) 6 HV FLA ] 3 A7 G MEC 3 . FIELD LOCATE EXISTING UNDERGROUND PUBLIC AND OWNER UTILITIES OF ALL TRADES AND BUILDING GROUNDING/LIGHTNING PROTECTION SYSTEMS PRIOR TO ANY EXCAVATION. REPLACE OR REPAIR DAMAGED UTILITIES AND GROUNDING/LIGHTNING PROTECTION SYSTEMS TO ORIGINAL CONDITION. E PROVIDE (1) 2" SLEEVE THROUGH FLOOR FOR FUTURE FEEDER INDICATED. REFER TO FLOOR PLAN FOR PROPOSED SLEEVE LOCATION. COORDINATE PENETRATION WITH THE STRUCTURAL CONTRACTOR PRIOR TO ROUGH-IN. 1 TRANSFORMER ALUMINUM FEEDER SCHEDULE KEY ~ ~ ~ ~ ONE-LINE DIAGRAM NOTES: 5 4 3 2 ~ ~ ~ ~ 1 ISSUE FOR CONSTRUCTION BP03 - ADDENDUM 03 BP03 - COB 09 #09 BP03 - ASI 15 DRAWING INFORMATION: 11254.000 PROJECT NO: DRAWN BY: JAH CHECKED BY: JAH APPROVED BY: JAH SHEET TITLE: ELECTRICAL ONE-LINE DIAGRAM AND SCHEDULES E-101 SHEET OF