KEY NOTES:
1 . PANELBOARDS INDICATED ON ONE LINE DIAGRAMS DO NOT SHOW ALL BRANCH
CIRCUITS. REFER TO PANELBOARD SCHEDULE(S)
2 . CIRCUIT BREAKER TRIP FUNCTION:
L=LONG TIME
S=SHORT TIME
I=INSTANTANEOUS
G=GROUND FAULT
CONDUCTORS
[
4
4#
350 AL
A1000.4
A100.4 G
PROVIDE (3) 4" SLEEVES THROUGH FLOOR FOR FUTURE PHOTOVOLTAIC SYSTEM
FEEDER. REFER TO FLOOR PLAN FOR PROPOSED SLEEVE LOCATION. COORDINATE
PENETRATION WITH THE STRUCTURAL CONTRACTOR PRIOR TO ROUGH-IN.
2
4 . PROVIDE SEPARATE INSULATED GROUNDING CONDUCTOR IN ALL FEEDER, HOMERUN
AND BRANCH CIRCUITS.
5 . INSTALL CONDUIT CONCEALED IN FINISHED AREAS UNLESS OTHERWISE NOTED. PAINT
EXPOSED CONDUIT TO MATCH EXISTING FINISHES WITHIN THE SURROUNDING AREA.
6 . DO NOT ROUTE CONDUIT WITHIN STRUCTURAL OR TOPPING SLABS OF FLOORS UNLESS
SPECIFICALLY NOTED OTHERWISE AND WRITTEN APPROVAL IS OBTAINED FROM THE
STRUCTURAL ENGINEER.
3
AT THE CONTRACTOR'S OPTION, THIS PANELBOARD MAY BE PROVIDED AS A SINGLE
SECTION UNIT.
4
SINGLE POINT CONNECTION. COORDINATE WITH THE MECHANICAL CONTRACTOR
AND EQUIPMENT SUPPLIER FOR CONNECTION TO MULTIPLE VFD'S. VFD'S
FURNISHED WITH THE EQUIPMENT.
5
COORDINATE METER REQUIREMENTS WITH COLORADO SPRINGS UTILITIES PRIOR
TO ROUGH-IN.
6
6
PROVIDE (1)1"C. WITH PULL STRINGS.
7
7
EXTERIOR PHOTOCELL ON ROOF. PROVIDE LOW VOLTAGE CONNECTION TO THE
LIGHTING CONTROL SYSTEM AS INDICATED. REFER TO ROOF POWER PLAN,
LIGHTING CONTROL SCHEDULES AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
7 . FIRE SEAL ALL FIRE RATED WALL AND FLOOR PENETRATIONS. REFER TO
ARCHITECTURAL DRAWINGS FOR FIRE RATED WALLS.
8
8
8 . COORDINATE EXACT REQUIREMENTS AND LOCATIONS OF MECHANICAL EQUIPMENT
WITH MECHANICAL DRAWINGS AND MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN
AND ORDERING MATERIALS OR EQUIP
9
9
4#
KEY (6)
"C
,
1/0 AL
1#
6 AL
G
1#
250 AL
G
2
1
REFER TO MECHANICAL EQUIPMENT SCHEDULE.
REFER TO TRANSFORMER SCHEDULE.
XFMR
NOTE:
HV PROT (1)
CCT BRKR
SWITCH
HIGH VOLTAGE FEEDER (3)
480 V
208 V
T15
18.0
41.6
25 A 3 P
3#
10
,1#
10
G
3/4
50 A 3 P
4#
6
,1#
10
T30
36.1
83.3
45 A 3 P
3#
6
,1#
10
G
1
100 A 3 P
4#
1
,1#
8
T45
54.1
1.)
124.9
70 A 3 P
3#
4
,1#
8
G
1-1/4
150 A 3 P
4#
1/0
,1#
6
FUSE
CONDUCTORS
"C
CONDUCTORS
SECONDARY O.C. PROTECTION PER NEC 450.
ALL CONDUCTORS ARE COPPER. SEE PLANS FOR INCREASED CONDUCTOR SIZES DUE TO VOLTAGE DROP ETC.
ENGINEER APPROVED EQUIVALENT).
4.)
5.)
BONDING AND GROUNDING CONDUCTOR PER NEC 250.
DIMENSIONS, WEIGHTS & BTUH OUTPUT SHOWN ARE FOR REFERENCE ONLY. ACTUAL DIMENSIONS MAY VARY FROM MANUFACTURER TO MANUFACTURER.
6.)
CONDUIT 40% FILL RATIO BASED ON EMT.
PC
PC
"C
CNDTRS
"C
HIGH
WIDE
DEEP
(5)
OTPT (5)
G
1
1# 8
3/4
27.00
20.13
16.00
310
2806
G
1-1/2
1# 6
3/4
30.00
20.13
16.00
370
5753
G
1-1/2
1# 6
3/4
39.25
26.13
20.00
480
7425
T
45
7
Volts: 480/277 Wye
Phases: 3
Mounting:
XFMR
XFMR
2
FUTURE
LTG
CONTROL
"LCP5A"
TO PV
ARRAY
7
PV
INVERTER
ISCA=7,979
5TH FLOOR
ROOF
Wires: 4
PANEL
"L4A"
3
PANEL
"L5A"
XFMR
XFMR
ISCA=3,028
T
XFMR T
45 XFMR
45
D
8
10
PC
A100.4G
PANEL
"H4A"
XFMR
ISCA=
8,781
XFMR
277V
4#4, 1#10G
1"C.
PANEL
"H5A"
6
Load
PANEL "HM1"
PANEL "H1A"
PANEL "H2A"
PANEL "H3A"
PANEL "H4A"
ELEVATOR
AIR HANDLING UNIT (AHU-1)
AIR HANDLING UNIT (AHU-2)
PANELBOARD
PANEL
"H5A" "H5A" (FUTURE LOAD)
Type
L; R; G; M; O
L; R; G; O
L; R; G; M
L; R; G
L;L;R;R;G;GM
M
M
M
L; R;GG; M
LTG
LTG
CONTROL
CONTROL
"LCP4A"
"LCP5A"
TO LIGHTING17
ASI #15
LOADS (TYP.)
TO LOW VOLTAGE
SWITCH(ES) AS
SHOWN ON PLANS
ISCA=7,979
XFMR
ISCA=3,071
T
XFMR T
45 XFMR
45
SLAVE
SLAVE
PANEL
PANEL
PANEL
"H3A"
PANEL
"H4A"
XFMR
TO LIGHTING
LIGHTING
TO
LOADS
LOADS (TYP.)
(TYP.)
ISCA=
9,759
XFMR
277V
277V
4#4, 1#10G
1"C.
LTG
LTG
CONTROL
CONTROL
"LCP3A"
"LCP4A"
TO LOW VOLTAGE
SWITCH(ES) AS
SHOWN ON PLANS
TO LOW VOLTAGE
SWITCH(ES) AS
SHOWN ON PLANS
~
PANEL
"L4A"
XFMR
PC
PC
~~ ~~ ~~
PANEL
"L3A"
3
SPD
ASI #15
Load Type
L
Lighting
R
Receptacle
M
Motor
C
Continuous
G
General
K
Kitchen
E
Existing
O
Other
General Notes:
2
~
10
17
ISCA=3,116
8
8
1
NETWORK COMMUNICATION
PER MANUFACTURER
RECOMMENDATIONS (TYP.)
ISCA=
8,781
3RD
FLOOR
4TH FLOOR
3RD
4TH FLOOR
PANEL
"H3A"
XFMR
TO LIGHTING
LIGHTING
TO
LOADS
LOADS (TYP.)
(TYP.)
ISCA=
10,978
XFMR
SLAVE
SLAVE
PANEL
PANEL
277V
277V
4#4, 1#10G
1"C.
LTG
LTG
CONTROL
CONTROL
"LCP2A"
"LCP3A"
ISCA=
9,759
TO LIGHTING
LIGHTING
TO
LOADS
LOADS (TYP.)
(TYP.)
ISCA=
13,151
MASTER
PANEL
ISCA=
10,978
ELEVATOR
#1
ELEVATOR #1
AHU
M
XFMR
5
TVSS
A100.4G
9
SPD
4
4#4, 1#10G
1"C.
PANEL
"HM1"
ISCA=
1,891
XFMR
15
DM
10
ASI #15
~
17
AHU
2
1
M
M
M
A100.4G
XFMR
A100.4G
ISCA=
13,151
4
A100.4G
MEC
A100.4G
VFD
MASTER
PANEL
2ND
3RD FLOOR
MECHANICAL
2
TO LOW VOLTAGE
PANELAS
SWITCH(ES)
SHOWN"H1A"
ON PLANS
XFMR
AHU
ELEVATOR #1
REFER TO MECHANICAL
EQUIPMENT SCHEDULE ST
FOR INFORMATION.
CT COMP.
4
ISCA=
1,891
UTILITY
METER
M
5
SPD
GFI
100A3P
A100.4G
LSIG 1000AF
6
AHU
2
M
M
VFD
T
30
XFMR
17
10
2ND FLOOR
2
T
30
4. INTEGRAL DISCONNECTING MEANS FURNISHED WITH EQUIPMENT.
5. PROVIDE CONNECTION TO DUPLEX SUMP PUMP CONTROLLER. MAKE FINAL CONNECTIONS TO EQUIPMENT. COORDINATE EXACT REQUIREMENTS WITH THE MECHANICAL
CONTRACTOR PRIOR TO ROUGH-IN.
3
PANEL
"L1A"
XFMR
A100.4G
XFMR
ISCA=1,845
Key
LSI
100A3P
A100.4G
MEC
MEC
LSI
100A3P
A100.4G
LSI
100A3P
A100.4G
LSI
100A3P
A100.4G
LSI
100A3P
LSI
MEC
MEC
LSI
MEC
MEC
LSI
100A3P
A100.4G
SPARE
SPARE
SPARE
LSI
400A3P
LSI
225A3P
LSI
225A3P
MAIN DISTRIBUTION CENTER "MDC"
1000 AMP BUS, 480/277V, 3∅, 4W
35,000 AIC MINIMUM
~
A7G
CT COMP.
MAIN ELECT. RM. GROUND BAR
RM. GROUND
BAR
A7G
A7G
A7G
GFI
A7G
LSIG 1000AF
100A3P
A7G
LSI
LSI
100A3P
MECA7G
A7G
SPARE
(FUTURE PV)
LSI
100A3P
LSI
100A3P
LSI
100A3P
LSI
100A3P
LSI
MEC
LSI
MEC
LSI
100A3P
SPARE
SPARE
SPARE
LSI
400A3P
LSI
225A3P
LSI
225A3P
LSI
50A3P
(3) SPACES
N
1000AT
UFER LIGHTNING BLDG.
PROT. STEEL
~
50A3P
G
ISCA=27,402ISCA=27,402
B
SPARE
(FUTURE PV)
PV)
(3) SPACES
LSI
N
1000AT
ISCA=27,402
IT ROOM ELEC RM
GROUND GROUND
BARS
BARS
GROUND
G
COLD
WATER RODS
PIPE
1ST FLOOR
#
Item
HP
FLA
AC
AHU
1
1
AIR CONDITIONING UNIT
AIR HANDLING UNIT
0
0
1A
88AA
0
AHU
2
AIR HANDLING UNIT
0
88AA
0
B
B
CP
CU
1
2
1
1
0
0
0.5
0
CUH
DWH
1
1
DWH
2
EF
EF
ELEV
FCU
FCU
HWP
HWP
SP
SP
1
2
1
1
2
1
2
1
2
BOILER
BOILER
CIRCULATION PUMP
AIR COOLED CONDENSING
UNIT
CABINET UNIT HEATER
DOMESTIC HOT WATER
HEATER
DOMESTIC HOT WATER
HEATER
EXHAUST FAN
EXHAUST FAN
ELEVATOR
FAN COIL UNIT
FAN COIL UNIT
HOT WATER PUMP
HOT WATER PUMP
ELEVATOR SUMP PUMP
SUMP PUMP
Load
0A
0A
0A
15 A
0 VA
181000
VA
181000
VA
500 VA
500 VA
0 VA
0 VA
0
0
0A
0A
200 VA
500 VA
0
0A
3
0.25
0
0
0
5
5
5
0
0A
0A
0A
0A
0A
0A
0A
0A
0A
4
ISCA=
14,555
Eq Load (VA)
Voltage
Phases
Feeders
Wire
Protec
Feeder Feeder Protecti
s
s
on
Protection tion
Ground Conduit Breaker Disconnect Fuse
A7G
208 V
480 V
1
3
2#12
3#2/0
1#12G 3/4"
1#6G 1-1/2"
FED
225 A
FROM
VFD
CU-1
-
2
1, 3
253746 VA
181000
480 V
3
3#2/0
1#6G
1-1/2"
225 A
VFD
-
1, 3
500 VA
500 VA
1127 VA
3120 VA
120 V
120 V
120 V
208 V
1
1
1
1
2#12
2#12
2#12
2#12
#12G
#12G
#12G
1#12G
3/4”
3/4”
3/4”
3/4"
20 A
20 A
20 A
20 A
S
30 A
20 A
200 VA
500 VA
120 V
120 V
1
1
2#12
2#12
1#12G 3/4"
1#12G 3/4"
20 A
20 A
4100 VA 4100 VA
277 V
1
2#10
1#10G 3/4"
30 A
0 VA
0 VA
20000 VA
18000
250 VA
200 VA
0 VA
0 VA
0 VA
12200 VA
480 V
120 V
480 V
120 V
120 V
480 V
480 V
480 V
480 V
3
1
3
1
1
3
3
3
3
3#12
2#12
3#4
2#12
2#12
3#12
3#12
3#12
3#12
#12G
#12G
1#10G
#12G
#12G
1#12G
1#12G
#12G
#12G
15 A
20 A
60 A
20 A
20 A
20 A
20 A
15 A
20 A
3824 VA
667 VA
20000 VA
18000
250 VA
200 VA
6055 VA
6055 VA
6055 VA
12200 VA
3/4”
3/4”
1"
3/4”
3/4”
3/4"
3/4"
3/4”
3/4”
A7G
UFER LIGHTNING BLDG.
PROT. STEEL
A7G
A7G
A7G
ELECTRICAL ONE-LINE DIAGRAM
SCALE:
1/8" =RM
1'-0"
IT ROOM ELEC
COLD GROUND
WATER RODS
PIPE
GROUND GROUND
BARS
BARS
1ST FLOOR
A
6/13/2013 3:50:29
7/18/2013
9/20/2013
9/26/2013
10:03:12AM
6:55:24
8:37:44
PM
AM
D:\Revit Local Files\2013\E-UCCSAOB_Central_JHafer.rvt
1ST FLOOR
1
2
INTEGRAL -
30 A
S
60 A
S
S
VFD
VFD
30 A
30 A
4
10 A
3
4
5
6
UNIVERSITY OF
COLORADO COLORADO SPRINGS
ISSUE:
06/17/13
60 A
15 A
20 A
OWNER:
1420 AUSTIN BLUFFS PKWY
COLORADO SPRINGS, CO 80918
3
3
6 07/19/13
11 09/20/13
17 09/27/13
5
BID PACKAGE 03
A7G
Notes
208 VA
253746 VA
181000
MAIN ELECT. RM. GROUND BAR
A7G
COLORADO SPRINGS, CO 80918
MAIN DISTRIBUTION CENTER "MDC"
1000 AMP BUS, 480/277V, 3∅, 4W 1ST FLOOR
35,000 AIC MINIMUM
A1000.4
A7G
UCCS - ACADEMIC
OFFICE BUILDING
3. VFD (VARIABLE FREQUENCY DRIVE) WITH LOCAL DISCONNECTING MEANS FURNISHED WITH EQUIPMENT.
4#4, 1#10G
1"C.
XFMR
PROJECT:
2. AIR CONDITIONING UNIT IS FED FROM THE ASSOCIATED CONDENSING UNIT LOCATED ON THE ROOF.
ISCA=1,845
SPD
PANEL
"H1A"
ISCA=23,115
1. SINGLE POINT CONNECTION. PROVIDE CONNECTION TO INDIVIDUAL VFDs FURNISHED WITH THE EQUIPMENT. COORDINATE EXACT CONNECTION REQUIREMENTS WITH THE
MECHANICAL CONTRACTOR, EQUIPMENT SUPPLIER AND EQUIPMENT SHOP DRAWINGS PRIOR TO ROUGH-IN.
VFD
ISCA=
13,386
LSI
DM
1
EQUIPMENT SCHEDULE
NOTES:
PANEL
"L1A"
ISCA=23,115
XFMR
TO LOW VOLTAGE
SWITCH(ES) AS
SHOWN ON PLANS
LTG
CONTROL
ISCA= "LCP1A"
14,555
MEC
Connected Load
33832 VA
34155
39237
39301
146468 VA
166268
166628
568845 VA
421353
0 VA
66468
12180
9000 VA
VA
0 VA
0 VA
5600 VA
213652 VA
250401
269613
213292
261411 VA
280594
224449
224870
250773 VA
270155
205535
205175
904 A
973
774
776
1013
944 AA
815
817
976
906 A
742
741
4
5
10
4
4
5
0
% A-B
% B-C
% C-A
Demand Factor
Demand Load
Switchboard Totals
Power Factor:
125%
42290 VA
42694
49046
49126
53%
78234 VA
88134
88314
Total Connected Load: 645062
111%
632282 VA
466603
763745 VA
821536
644638
0%
0 VA
Total Connected Current: 776
919 A
988
775
100%
66468
12180
9000 VA
VA
0%
0 VA
Total Demand Load: 621823
767406 VA
825278
621563
Total Demand Current: 748
0%
0 VA
923 A
993
100%
5600 VA
Breaker Accessories
* = GFI
** = Shunt Trip
6
M
11
3
ASI #15
277V
VFD
ISCA=ISCA=TO LIGHTING
13,38613,386
LOADS (TYP.)
MEC
Note
TO
TO LOW
LOW VOLTAGE
VOLTAGE
SWITCH(ES) AS
AS
SWITCH(ES)
SHOWN
SHOWN ON
ON PLANS
PLANS
~
XFMR
LTG
LTG
CONTROL
CONTROL
"LCP1A"
"LCP2A"
~~ ~~ ~~
XFMR
277V
277V
4#4, 1#10G
1"C.
PANEL
"H2A"
~~~
T
XFMR T
15 XFMR
45
PANEL
"HM1"
C
UTILITY
METER
SLAVE
PANEL
ASI #15
ISCA=3,162
REFER TO MECHANICAL
ST
EQUIPMENT SCHEDULE
ISCA=1,379
FOR INFORMATION.
PANEL
"LM1"
T
9
1
SPD
~
10
C
13342 VA
11665 VA
11541
11721
18251 VA
18241
18180
17641
13707 VA
13881
13878
12799
11968
13046
17978 VA
18040
6667 VA
6000
84582 VA
60333
84582 VA
60333
19156
9960 VA
VA
2
NETWORK COMMUNICATION
TO LOW VOLTAGE
PER MANUFACTURER
SWITCH(ES) AS
RECOMMENDATIONS (TYP.)
SHOWN ON PLANS
2ND
3RD FLOOR
17
B
13049 VA
14448 VA
14419
14778
22568 VA
22627
22621
23161
13756 VA
13724
13698
14299
18460
17381
21760 VA
6667 VA
6000
84582 VA
60333
84582 VA
60333
19156
15535 VA
~~
PANEL
"H2A"
PC
PC
A100.4G
~
XFMR
ISCA=3,116
T
XFMR T
45 XFMR
45
1
SPD
~
PANEL
"L3A"
XFMR
10
ASI #15
~~ ~~ ~~
17
ISCA=3,162
8
8
A
13652 VA
11640 VA
11427
11068
20291 VA
20288
11643 VA
11703
11699
12418
13673
17344 VA
17342
6667 VA
6000
84582 VA
60333
84582 VA
60333
19156
15886 VA
COB #09
4TH
5TH FLOOR
2ND FLOOR
MCB Rating: 1000 A
2
SLAVE
PANEL
4TH
5TH FLOOR
XFMR
Bus Rating: 1000 A
ADD 03
~~~
ISCA=3,071
XFMR
A.I.C. Rating: 35,000
Mains Type: MCB
Feed:
SLAVE
FUTURE
PANEL
PANEL
"H5A"
1
SPD
PANEL
"L2A"
P 303.607.0977
www.slaterpaull.com
~
5TH FLOOR
PANEL
"LM1"3
ARCHITECTS
NOTE
1331 Nineteenth Street
Denver, CO. 80202
Location: ELEC 1S-4
Supply From:
PV
INVERTER
11
ISCA=1,379
BTUH
Switchboard MDC
COB #09
3
WEIGHT
ROOF
XFMR
PANEL
"L2A"
3
DIMENSIONS (5)
Circuit Notes:
PC
ELECTRIC UTILITY
COMPANY U.G.
PRIMARY SERVICE.
FUSE
3.)
TO PV
ARRAY
PROVIDE SURGE PROTECTIVE DEVICE. INSTALL
FUTURE IN THE ELECTRICAL ROOM
ADJACENT TO THE PANELBOARD. REFER TO SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
PANEL
"L5A"
A1000.4
SWITCH
GROUNDING (4)
CONSULTANT:
ISCA=3,028
NEW PAD MOUNTED
UTILITY TRANSFORMER
(LOCATED AT THE PARKING
GARAGE, REFER TO SITE
ELECTRICAL PLAN)
CCT BRKR
LOW VOLTAGE FEEDER (3)
2.)
PROVIDE LOW VOLTAGE CONNECTION TO THE BUILDING AUTOMATION SYSTEM
HEAD-END EQUIPMENT. VERIFY COMMUNICATION PROTOCOL REQUIREMENTS WITH
THE MECHANICAL CONTRACTOR PRIOR TO PURCHASE.
17
ELECTRIC UTILITY
COMPANY U.G.
PRIMARY SERVICE.
LV PROT (2)
SCHEDULE IS BASED UPON TYPE XHHW-2 COMPACT
ALUMINUM 600V CONDUCTOR (ALCAN STABILOY OR
INTERIOR DAYLIGHT HARVESTING PHOTOCELL. REFER TO POWER PLANS, LIGHTING
CONTROL SCHEDULES AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
ASI #15
NEW PAD MOUNTED
UTILITY
NEW PAD
MOUNTED
TRANSFORMER
UTILITY
TRANSFORMER
(LOCATEDAT
ATTHE
THEPARKING
(LOCATED
PARKING
GARAGE, GARAGE,
REFER TO SITE
REFER TO SITE
ELECTRICAL
PLAN)
ELECTRICAL PLAN)
LV PROT (2)
PRIMARY O.C. PROTECTION PER NEC 450.
FUTURE
10
3
SLATERPAULL
SCHEDULE
LV FLA
NOTES:
HV PROT (1)
6
HV FLA
]
3
A7 G
MEC
3 . FIELD LOCATE EXISTING UNDERGROUND PUBLIC AND OWNER UTILITIES OF ALL TRADES
AND BUILDING GROUNDING/LIGHTNING PROTECTION SYSTEMS PRIOR TO ANY
EXCAVATION. REPLACE OR REPAIR DAMAGED UTILITIES AND GROUNDING/LIGHTNING
PROTECTION SYSTEMS TO ORIGINAL CONDITION.
E
PROVIDE (1) 2" SLEEVE THROUGH FLOOR FOR FUTURE FEEDER INDICATED. REFER
TO FLOOR PLAN FOR PROPOSED SLEEVE LOCATION. COORDINATE PENETRATION
WITH THE STRUCTURAL CONTRACTOR PRIOR TO ROUGH-IN.
1
TRANSFORMER
ALUMINUM FEEDER SCHEDULE
KEY
~ ~ ~ ~
ONE-LINE DIAGRAM NOTES:
5
4
3
2
~ ~ ~ ~
1
ISSUE FOR CONSTRUCTION
BP03 - ADDENDUM 03
BP03 - COB 09
#09
BP03 - ASI 15
DRAWING INFORMATION:
11254.000
PROJECT NO:
DRAWN BY:
JAH
CHECKED BY:
JAH
APPROVED BY:
JAH
SHEET TITLE:
ELECTRICAL
ONE-LINE DIAGRAM
AND SCHEDULES
E-101
SHEET
OF